1. Introduction
The increasing integration of renewable power plants (RPPs), particularly wind power plants (WPPs) and photovoltaic power plants (PV systems), is significantly reshaping the topology and operational dynamics of modern power systems. In this evolving landscape, busbar protection, especially at the transmission level, remains a critical function for ensuring system reliability. Faults at the busbar can result in the disconnection of multiple transmission lines, leading to extensive outages and operational instability.
While several IEC 61850-based protection studies exist, none have combined real-time hardware-in-the-loop (HIL) validation with adaptive busbar differential logic on physical relay hardware at a transmission-level point of common coupling (PCC), which forms the unique focus of this work.
A key challenge in the protection of such systems lies in maintaining consistent reliability under various operating conditions. One of the primary challenges is current transformer (CT) saturation, which can cause maloperation of protection relays, either through false tripping or failure to detect internal faults accurately [
1,
2].
Various methods have been proposed to enhance the performance of busbar differential protection, especially for RPP-integrated power systems. Traditional high-impedance and low-impedance differential relays have shown limitations in handling CT saturation during external fault conditions. As a response, the use of digital and numerical relays based on the IEC 61850 communication standard [
3] has increased, due to their fast communication capabilities and precise fault discrimination [
4,
5].
For instance, the authors in [
6] proposed a backup subscription scheme (BSS) using IEC 61850-9-2 sampled values (SVs) [
7] to improve the dependability of the differential protection system. Their approach, validated through hardware-in-the-loop (HIL) testing, significantly enhances flexibility in digital substations. However, interoperability between multivendor IEC 61850 standard devices remains a notable concern. A recent study in [
8] demonstrated that protection maloperations can arise when devices from different vendors fail to communicate, emphasizing the significance of standardized and vendor-consistent system configurations.
HIL simulation has become an essential technique for testing protection systems under realistic and real-time conditions. The authors in [
9] used the HIL to assess the performance of volts-per-hertz protection for generator over-excitation, while the authors in [
10] developed a HIL-based testbed to evaluate low-voltage DC (LVDC) grid stability through damping impedance techniques.
Regarding RPP integration, a study by the references in [
11] benchmarked the fault-ride-through (FRT) performance of PV system inverters using power hardware-in-the-loop (PHIL), highlighting the importance of such simulations in ensuring transient stability in inverter-rich networks. Similarly, the study in [
12] investigated the effects of various smart inverter control modes on overcurrent protection, concluding that dynamic coordination strategies are essential for ensuring protection reliability in modern distributed energy systems.
In addition to these technical considerations, recent wind energy research has emphasized the evolving role of WPPs in providing essential grid services beyond energy production. As highlighted in [
13], wind power plants are now expected to deliver functionalities such as inertia emulation, frequency support, and reactive power compensation to stabilize system operation during faults and disturbances. These requirements impose additional constraints on protection systems, which must now coordinate with advanced control mechanisms embedded within wind turbines and their associated power electronics.
Several recent studies further support the adoption of advanced protection and testing methodologies. A technique using composite sequence currents for bus protection in inverter-based renewable systems was proposed in [
14], showing flexibility to CT saturation. The authors of [
15] applied HIL simulation for protection device testing, while [
16] developed a frequency-based digital busbar protection approach.
The ultra-high-speed transient energy busbar protection for inverter-based renewables was introduced in [
17], and multiple works in [
18,
19] explored HIL methods for protection and control studies. Review studies such as [
4,
5] emphasized on IEC 61850-based protection schemes and digital substation architectures, highlighting the significance of interoperability.
Other works focused on relay and communication modeling [
20,
21] and the bibliometric evaluation of HIL techniques [
22]. Interoperability and certification methods for IEC 61850 protection were critically reviewed in [
23] and a combined HIL platform for microgrid commissioning was presented in [
24].
Despite these advances, there remains a clear gap in presenting a complete and integrated protection framework that simultaneously combines IEC 61850 standard-based logic, standardized relay coordination schemes, renewable generation integration (including inverter-based resources), and real-time validation via HIL simulations. While existing literature offers isolated solutions targeting individual aspects, such as overcurrent protection [
19], interoperability [
25], or HIL validation [
18], an all-encompassing approach is largely absent. This study addresses that gap by designing and validating a real-time HIL monitoring and protection system for the PCC, using an SEL-487B relay and a wind power plant (WPP)-integrated IEEE 9-bus power system.
Unlike previous IEC 61850-based protection studies, which have typically addressed only isolated aspects, this work presents a fully integrated framework that combines several advanced features into a single system. For example, the study in [
6] proposed a backup subscription scheme using IEC 61850-9-2 sampled values to enhance differential protection dependability, but did not incorporate adaptive logic or hardware validation. The study in [
8] examined the interoperability challenges among multivendor IEC 61850 devices, yet they did not develop or validate a complete protection scheme. Another study in [
14] explored composite sequence currents for busbar protection in inverter-based systems, though only via simulation without real-time HIL implementation or adaptive relay settings. Similarly, in [
19], the HIL was used to test overcurrent protection under corrupted sampled value frames, but their work did not address busbar differential protection at the transmission level. In contrast, this study integrates a low-impedance IEC 61850 busbar differential protection scheme implemented on a physical SEL-487B relay, validated through real-time digital simulation on RTDS hardware, with an adaptive logic mechanism that switches between Group 1 and Group 2 relay settings in response to loading conditions. Furthermore, the framework operates at a transmission-level PCC within a large-scale wind power plant (LSWPP)-integrated IEEE 9-bus system. This systematic and hardware-based approach has not been previously reported and contributes a replicable and extensible foundation for deploying intelligent, standards-based protection in renewable-integrated modern power grids.
The contribution of this work is as follows:
Realistic transmission-level PCC-based study: Given the critical nature of busbar protection at the transmission level, this study uses a modern power grid model whose parameters are well-suited for protection analysis. This aligns with the requirements stated in the reference [
26], who noted that accurate system studies require comprehensive data on synchronous generators, high-voltage transformers, transmission lines, loads, and busbars. Most previous IEC 61850 standard-related protection studies have focused on distribution-level or small test networks [
19], making this work one of the few to evaluate the protection behavior at the transmission scale.
Initial load flow assessment: Prior to fault simulation and protection testing, load flow analysis was conducted to verify the stability of the power system network under initial operating conditions. This is a fundamental step in power system network validation.
Full documented configuration procedures: All configuration steps involved in implementing the IEC 61850 standard-based monitoring and protection system are systematically documented to facilitate replication and transparency.
Real-time HIL validation with the involvement of physical protection devices SEL-487B and SEL-751A: The proposed protection scheme was evaluated using Real-Time Digital Simulator (RTDS) hardware, enabling HIL testing with physical relay devices interfaced through giga-transceiver analog output (GTAO).
Adaptive relay setting logic: An automatic transition between Group 1 and Group 2 settings is implemented, allowing the relay to adjust protection sensitivity dynamically as load conditions increase, a feature not reported in previous IEC 61850-based protection studies [
5,
12].
Foundation for scalability and interoperability: The framework demonstrates how IEC 61850 standard-based busbar differential protection can be applied to renewable-integrated networks in a modular and scalable way, forming a foundation for future enhancements such as grid-forming inverter integration, cyber-resilience testing, and multivendor interoperability validation [
8].
The remainder of this paper is as follows:
Section 2 introduces the modern power grid system used in the study.
Section 3 details the configuration of the monitoring and protection system.
Section 4 describes the hardware-in-the-loop (HIL) simulation test setup.
Section 5 outlines the test scenarios and case studies.
Section 6 discusses the results, and
Section 7 outlines research directions and future work.
2. The Modern Power Grid System Used for the Study and Its Fundamental Simulations
The modern power grid used in this study was adapted from our most recent study in [
27]. It is shown in
Figure 1 and is a result of the modeling of an IEEE 9-bus power system modified and integrated with a large-scale wind power plant (LSWPP).
In the figure, WTGU denotes the wind turbine generator unit, each connected to collector buses (Collector1Bus, Collector2Bus, and Collector3Bus). The WPPHVTRF represents the wind power plant high-voltage transformer, with WPPHVTRF1, WPPHVTRF2, and WPPHVTRF3 stepping up voltages from 24 kV collector buses to 230 kV transmission-level buses. The Group1SEBus, Group2SEBus, and Group3SEBus indicate the secondary side buses of the respective high-voltage transformers. The lines connecting these buses are designated as LineGroup1, LineGroup2, and LineGroup3, which transfer power toward the WPPSEBus (wind power plant sending-end bus). The WPPREBus (wind power plant receiving-end bus) represents the point of common coupling bus. The WPPTransLine stands for the wind power plant transmission line, while PCCTerm refers to the point of common coupling terminal where the WPP integrates with the external electrical power grid.
This system comprises essential components of a high-voltage transmission network, such as synchronous generators, transformers, transmission lines, loads, and busbars, enabling a realistic simulation of power system dynamics under both normal and fault conditions. Although a particular wind turbine generator unit (WTGU) is also selected for monitoring, the point of common coupling (PCC) of the modern power grid still serves as the main point of focus for the proposed monitoring and protection system. In the modern power grid of discussion, the PCC is the LSWPP receiving-end busbar (WPPREBus).
The modern power grid described above operates in two conditions, under initial load demand and increased load demand. The logic used for the simulation of these conditions is shown in
Figure 2 [
27].
Load flow simulations were performed on the described system under initial and increased load demand conditions. The analysis focused specifically on the branch currents related to the protected busbar WPPREBus or simply PCC, and busbar voltages. The results of these simulations, recorded after the system reached a steady state, are presented in
Table 1,
Table 2,
Table 3 and
Table 4. Among them, the results in
Table 2 are the same as the ones we obtained in our recent study in reference [
27].
3. Monitoring and Protection System Design
3.1. Overview of the Proposed System
The monitoring and protection system used in this study is based on a low-impedance busbar current differential relaying system. This method was chosen for its advantages over other busbar current differential relaying systems. Reference [
28] can be visited for an example of a low-impedance busbar current differential relaying system, and reference [
29] for a detailed comparison of various types and their respective benefits and drawbacks.
The working principle of a differential protection system is as follows: if the differential current exceeds both the pick-up current and the product of the percentage slope (SLP) and the restraining current , the relay sends a TRIP signal (binary 1) to the circuit breaker (CB).
In summary, a trip signal is issued if
>
and
×
.
is the pick-up current threshold. The relay works with secondary currents from current transformers (CTs), which compare the expected values. CTs on parallel feeders must have identical turn ratios to ensure accurate computation of secondary currents [
30,
31].
Nowadays, digital/numerical relays are used in monitoring and protection systems. One advantage of digital relays is their ability to determine phase angles even under severe CT saturation accurately. Proper relay function depends on accurately distinguishing between internal and external faults.
In the event of a through fault, the relay can temporarily block differential protection operating elements to avoid false trips. However, this method can delay trips during actual internal faults. To address this, directional detection elements are used. These determine the direction of fault current flow and enhance the ability of the relay to respond correctly, even during CT saturation [
1,
2]. For further information on CT saturation, see references [
32].
Overall,
Figure 3 presents the development process flowchart for the study. The flowchart summarizes the systematic stages followed in this study, including: modeling the modern power grid with an integrated large-scale wind power plant (LSWPP), selecting and configuring instrument transformers, implementing low-impedance busbar differential protection on the SEL-487B relay, integrating IEC 61850 GOOSE communication, and validating the complete system through real-time hardware-in-the-loop (HIL) testing on RTDS hardware. These stages are detailed in
Section 2 (System Modeling),
Section 3 (Protection System Design and Relay Configuration),
Section 4 (HIL Setup and IEC 61850 Communication Integration),
Section 5 (System Testing and Evaluation), and
Section 6 (Results and Discussion).
3.2. Instrument Transformer Selection
Current transformers (CTs) were rated at 150% of the full-load current at the PCC (Bus2) to ensure reliable measurement and minimize CT saturation. As shown in
Table 3, the branch current in LineDLoad1 (0.4530 kA) was the largest and approximately equal to the sum of Line24, Line12, and WPPLine currents, making it the basis for CT sizing. Accordingly, an 800:5 CT (160:1 turns ratio, 0.41 Ω burden) was selected in line with IEEE recommendations, and identical ratios were applied across all CTs to maintain differential protection accuracy. For voltage measurement, standard CVT parameters for 230 kV systems were adopted from RTDS Technologies, with only minor editing of signal names for mapping.
3.3. Configuration of SEL-487B Relay
The SEL-487B Relay was configured to implement a low-impedance busbar differential protection system at the PCC. Current transformer (CT) and voltage transformer (VT) inputs were mapped per phase to three differential elements (DIFF_R, DIFF_Y, DIFF_B), each processing four feeder currents (ILine12, ILine24, IDLoad1, IWPPLine). Differential operation was defined by the pickup threshold O87P and two percentage restraint slopes: Slope 1 for internal faults and Slope 2 for external faults. To enhance security under CT saturation, a directional element with a designated reference feeder and the 50DSP threshold provided supervision.
Adaptive protection was achieved through automatic switching between Group 1 and Group 2 settings, where Group 1 applied under normal load conditions and Group 2 under increased load. This ensured high sensitivity under stressed conditions while maintaining stability during external faults. Detailed settings, terminal aliasing, and QuickSet screenshots are provided in
Appendix A.
Integration of the relay into the monitoring and protection framework followed the IEC 61850 standard, where Logical Nodes (LNs), GOOSE messaging, and communication mapping were applied to enable interoperability and real-time data exchange within the system.
Figure 4 [
31] illustrates the modified logic of the red-phase differential element, showing four current inputs, the filtered differential path, directional supervision, and fault detection logic, while
Table 5 summarizes the five conditions that must be satisfied for the instantaneous differential element (87RP) to assert, ensuring secure and dependable operation of the protection system.
The SEL-487B Relay was configured to implement a low-impedance busbar differential protection system at the PCC in accordance with the IEC 61850 standard. Current transformer (CT) and voltage transformer (VT) inputs were mapped per phase to three differential elements (DIFF_R, DIFF_Y, DIFF_B), each processing four feeder currents (ILine12, ILine24, IDLoad1, IWPPLine). Differential operation was defined by the pickup threshold O87P and two percentage restraint slopes: Slope 1 for internal faults and Slope 2 for external faults. To ensure security under CT saturation, a directional element with a designated reference feeder and the 50DSP threshold provided additional supervision.
Adaptive protection was implemented through automatic switching between Group 1 and Group 2 settings, where Group 1 applied under normal load conditions and Group 2 under increased load. This ensured high sensitivity while maintaining stability during stressed operating conditions. Detailed configuration parameters, terminal aliasing, and QuickSet screenshots are provided in
Appendix A for reproducibility, while only the essential configuration principles are summarized here.
3.4. Group 1 and Group 2 Switchover Logic Configuration
The adaptive protection framework automatically transitions from Group 1 to Group 2 settings when feeder currents increase under higher load demand, particularly when the wind power plant (WPP) contributes additional generation. This switchover is achieved by definite-time overcurrent elements configured to monitor key feeders.
If the measured current exceeds the set threshold of 0.55 A for any of the definite-time elements (50P10P, 50P11P, 50P12P), the corresponding relay wordbits (50P10RP, 50P11YP, 50P12BP) assert and, after the time delay, activate (50P10RT, 50P11YT, 50P12BT). Their activation triggers the Group 2 (SS2) settings, which remain in force until the relay front-panel pushbutton (PB5) is manually pressed to revert to Group 1 (SS1).
The implemented logic is illustrated in
Figure 5, showing the switchover configuration in AcSELerator QuickSet. Detailed parameters, aliasing, and screenshots are provided in
Appendix A for reproducibility.
4. Hardware-in-the-Loop Simulation Test Setup on Real-Time Simulation Computer-Aided Design 2.4
The proposed monitoring and protection system was validated in a hardware-in-the-loop (HIL) environment using the Real-Time Digital Simulator (RTDS) and RSCAD 2.4. The RTDS was interfaced with the SEL-487B busbar differential relay and SEL-751A feeder relay through GTAO analog output modules for CT and VT signals and GTFPI I/O channels for breaker control and status. This allowed device-level testing under realistic operating and fault scenarios without requiring a physical substation.
At the CSAEMS laboratory (CPUT), the testbench integrated simulated secondary signals with physical relays. Analog outputs from the RTDS represented CT and CVT signals of Bus2, while binary GOOSE messages coordinated protection actions. The setup enabled end-to-end evaluation of real-time monitoring, adaptive protection logic, and trip coordination.
Figure 6 shows the complete HIL setup, including the RTDS racks, GTAO/GTFPI modules, Omicron amplifiers, and SEL relays. This arrangement ensured scalable and accurate interfacing between simulation and hardware, replicating a transmission-level substation environment.
Additional CT/CVT parameter configurations, GTAO mappings, and monitoring signal settings are provided in
Appendix B.
Table 6 summarizes the selected electrical and mechanical signals from WTGU13 that were monitored via IEC 61850 logical nodes (MMXU) and published as GOOSE messages. The full IEC 61850 dataset mapping and logical node bindings used to publish WTGU13 signals are documented in
Appendix C. These included voltages, currents, active/reactive power, frequencies, and rotor speed, ensuring comprehensive visibility of wind turbine performance under varying loading conditions.
6. Results and Discussion
This section discusses the results from two hardware-in-the-loop (HIL) case studies: (1) real-time monitoring of selected signals through the IEC 61850 standard, and (2) protection system performance under nominal and increased load conditions.
6.1. Case Study 1: Real-Time Monitoring of Selected Signals
The first case study focused on validating the real-time monitoring framework implemented using the IEC 61850 standard. Electrical and mechanical variables from WTGU13, including voltages, currents, active power, frequency, and rotor speed (as listed in
Table 6), were published as GOOSE messages from the RTDS-simulated model to the physical relays and visualized through the IED interfaces. The results confirmed that these analog values were transmitted reliably and time-coherently, with no packet losses observed during the tests.
This case study demonstrated that the developed system can accurately stream and display real-time process measurements from a large-scale wind power plant model at a transmission-level PCC. It should also be noted that these same monitored signals (along with additional signals as needed) will be used in future research to implement a coordinated control framework that integrates monitoring, operation, and protection functions within the same IEC 61850-based platform.
6.2. Case Study 2: Protection Under Nominal and Increased Load Conditions
The second case study evaluated the performance of the protection system under both nominal and increased load demand conditions. At nominal load, the SEL-487B relay correctly restrained differential elements during normal operation and issued trips only when internal faults were applied. The measured operating and restraint currents were 0.32 PU and 4.38 PU, respectively, and the measured end-to-end fault clearance time was 606.667 ms from inception to breaker operation.
While field installations are typically expected to achieve full fault clearance within about 100 ms, the measured fault clearance times of 606.667 ms (initial load) and 706.667 ms (increased load) are acknowledged as the actual end-to-end operation times achieved by the developed system in the HIL environment.
Under increased load, the relay automatically switched from Group 1 to Group 2 settings based on the pre-defined load threshold. Under these conditions, the measured operating and restraint currents rose to 1.96 PU and 6.20 PU, respectively, while the relay maintained stability and selectivity. GOOSE-based breaker confirmation signals were received after the trip command. These results confirm the dependability, speed, and adaptability of the proposed protection system even under stressed loading conditions.
6.3. Communication Reliability and Real-Time Behavior
Throughout both case studies, the IEC 61850-based communication framework performed reliably. All analog and binary signals between the RTDS-simulated power grid and the physical SEL-487B and SEL-751A relays were exchanged using GOOSE messaging with no observed packet losses. This confirms the suitability of IEC 61850 standard peer-to-peer communication for time-critical monitoring and protection applications in renewable-integrated networks when implemented with proper LN mapping, dataset configuration, and Virtual Local Area Network (VLAN).
6.4. Comparative Contribution and Novelty
Most previous IEC 61850-based studies have concentrated primarily on protection functions and have treated monitoring either superficially or as offline data acquisition, often without real-time communication or hardware validation. For example, the study in [
6] developed a backup subscription scheme using IEC 61850-9-2 sampled values; however, it did not implement real-time monitoring or adaptive logic. Another study in [
8] focused on multivendor interoperability analysis, while the one in [
14] introduced a composite sequence current technique evaluated only in offline simulation. Moreover, in [
19], the HIL testing was also performed, but only for overcurrent protection, not for live process variable monitoring or busbar differential systems.
In addition, several review papers such as [
4,
5,
23] extensively discussed IEC 61850-based protection schemes, digital substation architectures, and interoperability and certification challenges, respectively. However, they only provided conceptual and architectural overviews and did not include practical implementations, real-time hardware-in-the-loop validation, or detailed configuration procedures. While these reviews are valuable in highlighting gaps and trends, they offer no quantitative performance metrics or reproducible system designs.
A further limitation observed across nearly all the reviewed studies is the lack of transparency and reproducibility in their configuration processes. None of them provided complete step-by-step configuration details of their IEC 61850-based systems, which makes it difficult for other researchers or practitioners to replicate their setups. In contrast, the present work includes fully documented configuration procedures, such as detailed terminal aliasing tables, instrument transformer ratio settings, differential and directional element logic diagrams, and complete IEC 61850 dataset bindings to ensure transparency and reproducibility. These configuration procedures are presented in
Appendix A,
Appendix B and
Appendix C. This level of detail has not been previously reported and represents a significant advancement over prior studies.
Additionally, most of the reviewed works used simplified test systems at the distribution level, whereas the present study was performed on a realistic transmission-level IEEE 9-bus system integrated with a large-scale wind power plant (LSWPP). This allowed evaluation of protection and monitoring behavior under conditions that are much closer to those found in actual high-voltage substations.
To clearly position the present work in relation to prior studies,
Table 9 has been expanded to include the additional studies cited in the introduction and literature review, and compares them across key aspects such as real-time monitoring, real-time HIL validation, adaptive logic, CT/VT selection based on IEEE/IEC standards, configuration transparency, type of system used, and reported trip times.
As reflected in
Table 9, most of the reviewed IEC 61850-based studies either concentrated on specific protection algorithms or on isolated aspects such as interoperability, communication modeling, or HIL-based testing, but none combined real-time monitoring of analog electrical and mechanical signals with protection validation on actual hardware, comprehensive configuration transparency, and a realistic transmission-level system model. Even the few studies that performed HIL testing, such as [
9,
10,
18,
19,
24], focused only on protection behavior and used simplified distribution-level systems without providing reproducible configuration procedures.
This clearly demonstrates that the present work is the first to integrate a real-time IEC 61850-based monitoring framework, adaptive busbar differential protection, IEEE/IEC standards-based CT/VT selection, full configuration transparency, and a transmission-level test system into a single hardware-validated framework within a renewable-integrated grid, addressing a long-standing gap in the literature.
6.5. Scalability and Interoperability Considerations
It is acknowledged that the current HIL setup is based on an IEEE 9-bus system integrated with a single large-scale wind power plant, which represents a simplified test environment. However, the proposed framework was intentionally designed using modular IEC 61850 logical node structures, GOOSE-based peer-to-peer communication, and standardized ICD/SCD configuration files. These features inherently support the addition of multiple busbar zones, feeder bays, and PCCs without altering the underlying logic. Moreover, the use of vendor-neutral IEC 61850 data models enables future extension to multivendor intelligent electronic devices (IEDs), which is essential for realistic utility-scale substations. These design attributes indicate that the proposed framework can be scaled to larger and more complex networks in future studies.
7. Conclusions and Future Work
Based on the outcomes of this study, several future research directions are planned to further enhance and extend the developed IEC 61850-based monitoring and protection framework for large-scale renewable-integrated power systems.
It is acknowledged that the current fault clearance times (606.667 ms and 706.667 ms) are longer than typical field values (~100 ms) due to additional processing and communication delays in the hardware-in-the-loop setup, and future work will aim to reduce these times through optimization of the test platform and relay logic.
7.1. Adaptive Logic Refinement
Future work will focus on enhancing the adaptive protection logic implemented in the SEL-487B relay. This will include refining the automatic transition between Group 1 and Group 2 settings based on real-time system loading conditions and introducing automatic reversion to Group 1 settings once load returns to normal. This refinement will be tested through staged scenarios involving load variations, feeder switching, and temporary islanding/reconnection events to confirm its stability and responsiveness under dynamic network conditions.
7.2. Integration of Grid-Forming Inverters
The proposed framework will be expanded to incorporate grid-forming inverter (GFM) models within the RTDS-simulated network. This will allow assessment of how GFMs contribute to fault ride-through capability, system inertia, and frequency support during disturbances in renewable-integrated systems. Evaluating the protection system’s behavior in the presence of GFMs will help establish its applicability to future grids with high inverter-based resource penetration.
7.3. Cybersecurity and Resilience Testing
The current HIL testbed will be extended to evaluate the resilience of IEC 61850-based systems against cyberattacks, in line with IEC 62351 requirements. This will involve injecting faulty or delayed GOOSE and sampled value (SV) messages, message dropouts, and denial-of-service conditions into the communication layer to simulate compromised network scenarios. These experiments will help develop and validate cybersecurity countermeasures and intrusion detection strategies for substation automation systems.
7.4. Development of a Coordinated Monitoring–Operation–Protection (MOP) Control Method
Building on Case Study 1, which demonstrated real-time monitoring of electrical and mechanical signals through IEC 61850 GOOSE messaging, future work will develop a coordinated control framework that integrates monitoring, operation, and protection (MOP) functions on the same platform. The currently monitored signals (and additional required measurements) will be used to design automated control logic for supervising system operating states, issuing control actions, and coordinating protection schemes. This will transform the present system from a protection-only configuration into a comprehensive intelligent substation control solution for renewable-integrated power grids.