Next Article in Journal
CO2-ECBM from a Full-Chain Perspective: Mechanism Elucidation, Demonstration Practices, and Future Outlook
Previous Article in Journal
Charging Incentive Design with Minimum Price Guarantee for Battery Energy Storage Systems to Mitigate Grid Congestion
Previous Article in Special Issue
Toward Zero-Emission Buildings in Italy: A Holistic Approach to Identify Actions Under Current and Future Climates
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Decision Support Tool to Assess the Energy Renovation Performance Through a Timber-Based Solution for Concrete-Framed Buildings

1
Department of Electrical Electronic and Computer Engineering (DIEEI), University of Catania, Via S. Sofia 64, 95123 Catania, Italy
2
Area Sistemi Informativi di Ateneo, Università di Palermo, Viale delle Scienze Ed.11, 90128 Palermo, Italy
3
Engineering Ingegneria Informatica Spa, Viale Regione Siciliana 7275, 90146 Palermo, Italy
4
Department of Civil Engineering and Architecture (DICAr), University of Catania, Via S. Sofia 64, 95123 Catania, Italy
*
Author to whom correspondence should be addressed.
Energies 2025, 18(11), 2839; https://doi.org/10.3390/en18112839
Submission received: 29 April 2025 / Revised: 22 May 2025 / Accepted: 27 May 2025 / Published: 29 May 2025
(This article belongs to the Special Issue Performance Analysis of Building Energy Efficiency)

Abstract

:
The present paper describes a novel and user-friendly Decision Support System (e-DSS) designed to assist technicians in the preliminary design stage of a building renovation process based on the solutions developed in the innovation project e-SAFE, funded by the EU under the H2020 program. The e-DSS is engineered to rapidly assess key performance indicators, including energy performance before and after renovation, reduction in CO2 emission for space heating, space cooling, and DHW preparation, seismic upgrade feasibility, expected costs, and payback time. To demonstrate its capabilities, the e-DSS was applied to an existing public housing building in Catania, southern Italy. The predicted thermal energy needs for space heating and cooling were compared to the results from detailed simulations using a professional-grade software tool, for both as-built condition and a proposed renovation generated by the e-DSS itself. The discrepancies identified through this comparison will inform the refinement of the e-DSS algorithms to increase their accuracy and reliability. More generally, this paper recommends suitable algorithms that can be effectively employed in the development of simplified decision-making tools specifically tailored for building professionals operating in the early phase of building renovation projects.

1. Introduction

The innovation project e-SAFE, funded by the EU under the H2020 program, is developing a new deep renovation system for non-historical buildings with reinforced concrete (RC) structural frames, which combines energy efficiency with a series of further advantages including improved seismic resistance, affordability, and improved architectural image, as well as reduced implementation time, costs, and occupant disruption [1].
The retrofit approach proposed in e-SAFE consists of cladding the building envelope with a new prefabricated timber-based shell acting as a seismic-resistant and energy-efficient skin. Seismic improvement relies on the use of structural panels made of Cross-Laminated Timber (CLT), called e-CLT, applied to the outer blind walls; these are connected to the RC beams through innovative seismic energy dissipation dampers [2]. The e-CLT panels are combined with non-structural panels (called e-PANELs) that may also include new high-performing windows to replace the existing ones. Both panels are conceived to be prefabricated offsite and to be installed from the outside of the building through mobile lifting equipment (cranes, lifting platforms, etc.), thus avoiding the disruption of traditional scaffolding and occupant relocation. The distribution of e-CLTs and e-PANELs also depends on the seismicity of the specific area, the seismic vulnerability of the building, and the expected level of seismic upgrading. e-PANELs are also the envelope solution adopted in case the seismic upgrading relies on a metal exoskeleton, called e-EXOS [3].
Since the topic of combined energy and seismic upgrading of buildings has become increasingly important, there has also been a growing interest in the development of Decision Support Systems (DSSs) to inform and guide the decision process of various building retrofit interventions. For this reason, among the other outputs of the project, e-SAFE researchers also developed a Decision Support System (called e-DSS) to assist in the preliminary design stage of renovation projects based on the proposed solutions while also helping to evaluate energy, environmental, and cost performance and seismic upgrade feasibility.
There are already some tools available to support design choices for separate energy retrofit or seismic retrofit projects, with rather easy-to-use interfaces for designers and practitioners and a clear overview of the results for the final client. As an example, some authors [4,5] analyzed and grouped the most common decision-making methods and found that multi-criteria approaches are widely used in DSSs within the construction sector. In addition, some companies and universities have already started developing decision support tools themselves, within the framework of various research projects dealing with large-scale building renovation. One such tool is GET.one.app, developed within the H2020 project Pro-GET-onE (PROactive synergy of inteGrated Efficient Technologies on buildings Envelopes) [6], which proposes a renovation strategy based on pre-assembled components. GET.one.app is a facade design tool that allows users to choose between three possible solutions: maintaining existing balconies, converting them into solar greenhouses, or adding an extra room. Additionally, the tool enables the customization of materials, colors, finishes, and shading solutions, allowing the end user to visualize modifications directly on a 3D model via an online interface. However, to ensure full accessibility to users, 3D management must start with a BIM model, which means that the preliminary design process cannot be completed in just a few simple steps. Indeed, it requires more time and expertise with the BIM environment.
The same issue with BIM usage is observed with six other tools developed within the BIM4EEB project [7,8]. Here, the design process requires an initial scan of the building, which is then uploaded into a BIM system that speeds up the scan-to-BIM process by using Augmented Reality (AR) and a sensor stick. Additional tools integrate the necessary energy data for the actual design phase; in particular, “BIMeaser” facilitates the simulation and comparison between different design options, and “Auteras” and “BIMcpd” optimize the HVAC system design as part of the building automation control system. Finally, “BIMplanner” and “BIM4Occupants” assist in the construction and building operation phases. This approach guarantees high accuracy but does not allow for a quick preliminary assessment of potential energy improvements and renovation/operational costs.
A similar approach is found in the tool developed by the RenoZEB project [9], which facilitates building retrofitting to achieve the nearly Zero-Energy Building (nZEB) standard. This tool also relies on a BIM interface and enables post-retrofit monitoring. It allows users to compare different energy renovation scenarios and simulating the impact of solutions such as thermal insulation, window replacement, efficient HVAC systems, and integrated photovoltaic panels. While these tools provide a high level of detail, they compromise speed in identifying potential efficiency improvements and overall building system performance. Furthermore, neither of them includes reasoning on possible solutions for seismic retrofit as the e-DSS does. Additionally, unlike the e-DSS, they do not focus on a specific retrofitting methodology but rather offer a broad range of possible choices.
Other tools, such as PARADIS [10], work as plug-ins for BIM software tools like Revit. In this case, the process starts from the drawing of the model, from which geometric data are extracted. The tool then generates possible renovation scenarios from the interventions that the user previously set on individual building components (opaque and transparent envelope, mechanical systems), which are then evaluated against key performance indicators (KPIs). This tool provides high flexibility and facilitates decision-making among multiple design options, but it relies on a BIM environment and does not carry out any analysis of the seismic aspect.
On the other hand, some tools start by analyzing the existing building performance. For instance, EnPROVE [11,12] collects building data through a wireless sensor network, monitoring energy consumption, temperature, and humidity. It eventually creates an Energy Consumption Model (ECM) based on the collected data and simulates the impact of different technologies. Finally, multi-criteria analysis allows for the comparison of various retrofitting strategies to select the most appropriate one but without evaluating the feasibility of any possible seismic retrofit actions.
The Refurbishment Assessment Tool (RAT) is an interactive tool developed within the RECO2ST project [13], and it utilizes the HULC software (i.e., the building energy simulation program used in Spain for implementing the Energy Performance of Buildings Directive) to create a digital model of the building by incorporating climatic data, envelope components, and geometric data, as well as ventilation and external obstructions (e.g., neighboring buildings). The tool performs dynamic hourly simulations over an entire year, identifying major deficiencies in the building, e.g., particularly high U-values of the opaque and transparent envelope components. Based on these deficiencies and the predefined retrofit options, the tool generates various retrofit combinations, discarding the least efficient ones through an iterative process. Then, an optimal set of solutions is compared with regulatory constraints (in this case, the Spanish legislation). This tool also focuses on energy retrofit only and does not deal with the seismic aspects.
Finally, some tools are more focused on the urban scale, such as CLARITY [14], which assists urban planners, engineers, and policymakers in integrating climate adaptation strategies into infrastructure and building planning.
In this framework, the e-DSS developed within the e-SAFE project adopts a peculiar approach that is coherent with its scopes. Indeed, this tool should be used by technicians when they are asked to quickly assess the feasibility of an e-SAFE-based building renovation in order to identify the most suitable options and the expected benefits. Accordingly, the tool is simple to use and allows for quick tabular input data; through a series of questions, it notifies the user whether any seismic renovation solutions are applicable and calculates a series of key performance indicators (KPIs), including energy needs, non-renewable energy use, cost savings, time, and cost for the renovation works. Several parameters included in the calculations are taken from a database prepared by e-SAFE experts, available for three different European countries (Italy, Greece, and Romania).
The present paper only deals with energy issues and only considers those data and KPIs regarding the building envelope; the simulation of the thermal systems will be addressed by a future separate paper. With the aim of demonstrating the capabilities of the tool, the e-DSS is here used to assess one existing building belonging to the local public housing institute in Catania, southern Italy. The main resulting KPIs are then compared against those obtained through detailed simulations with a certified commercial software tool used in Italy by professionals, both for the current building status and for its possible renovated configuration. This allows for identifying possible improvements to some algorithms within the e-DSS while also estimating the change in both the space heating and space cooling energy demand introduced by the e-SAFE renovation.

2. Materials and Methods

In the first part, this section presents the approach implemented in the e-DSS to manage the data input regarding the building geometry, the envelope components, and the weather data used for energy calculations. Then, Section 2.4 describes the equations used to calculate the energy needs for space heating and cooling. Finally, Section 2.5 shows how the e-DSS supports the evaluation of a renovation project and assists the user in assessing its energy performance.

2.1. Building Geometry

Coherently with the scope of having a tool that can be easily used during a preliminary design and evaluation stage, the introduction of the geometrical data is managed in a simplified way whilst still being able to reliably calculate the heat transfer area, the heated volume, and the heated floor area.
The main simplification consists of describing the building as a polygon with no more than eight sides, each identified through a subscript “i” associated with a different orientation (north = 1, northeast = 2, east = 3, southeast = 4, south = 5, southwest = 6, west = 7, northwest = 8). The user must introduce the length of the facade for each possible orientation (Lengthi), the building height above the ground (Htot), the total number of floors above the ground (nfloors), and the number of heated floors (nheat). With these data, the e-DSS can already calculate the overall heated area of each facade (Sheat_i):
S h e a t _ i = n h e a t n f l o o r s · L e n g t h i · H t o t
However, if there are other buildings adjacent to a certain facade, even if partially, the e-DSS assesses the heated area in contact with those adjacent buildings (Sadj_i):
S a d j _ i = n a d j _ f l o o r s _ i n h e a t · S h e a t _ i
Here, nadj_floors_i is the number of heated floors that are in contact with an adjacent building on that facade, which is provided by the user for each orientation (nadj_floors_i = 0 if there are no adjacent buildings on that orientation).
Then, it is necessary to separate the opaque surface area from the glazed surface area: to this aim, the user must specify the total window surface area (Sw_i) for each orientation, while the overall window surface area in the entire building is calculated as follows:
S w = i = 1 8 S w _ i
Now, the “effective” heated vertical surface area in contact with the outdoors for each orientation (Seff_i) is calculated through Equation (4), while the only opaque portion is defined with Equation (5):
S e f f _ i = S h e a t _ i S A d j _ i
S e f f _ o p _ i = S e f f _ i S w _ i S b o x _ i
In Equation (5), the surface area of the shutter boxes, if any, is roughly evaluated as 15% of the window’s surface, as in Equation (6); here, BOX is a Boolean variable introduced by the user (BOX = 1 if the building is provided with roller shutters; otherwise, BOX = 0).
S b o x _ i = B O X · 0.15 · S w _ i
Finally, the e-DSS needs to know the ground floor surface area (Sfloor) and the roof surface area (Sroof). The first one is directly provided by the user as an input (it corresponds to the area of the base polygon); as far as the roof is concerned, it is calculated by the e-DSS by multiplying the ground floor area by a correction factor (froof):
S r o o f = f r o o f · S f l o o r
The correction factor depends on the type of roof selected by the user, making a choice between a flat surface (external roof or non-heated attic) and pitched surface (with a heated volume below), through a drop-down menu (see Table 1). In the case of pitched surface, two slopes can be selected (low angle = around 20°, high angle > 30°).
The choice of a suitable boundary condition for both the roof and the ground floor introduces a further correction factor (btr_U) needed in the calculation of the heat transfer rate, as specified in Section 2.4. The various values are reported in Table 1 [15]. Finally, for all vertical surfaces attached to adjacent buildings, it is btr_U_adj = 0.
As a final piece of information about the geometry of the building, the user has to manually add the heated net floor area (Snet), the heated net volume (Vnet) and the heated gross volume (Vg). In this stage, some checks are performed by the tool to avoid inappropriate input, eventually showing a warning:
  • The heated gross volume cannot exceed the product of the ground surface area times the building height.
  • Th ratio of the building height to the number of floors must be between 2.5 m and 5 m.
  • The heated net volume must be within 60% to 90% of the heated gross volume.
Finally, the e-DSS calculates the compactness ratio (S/V), as per Equation (8):
S / V = S d _ t o t / V g
Here, Vg is the gross heated volume of the building and Sd_tot is the overall heated envelope surface, given by Equation (9):
S d _ t o t = S f l o o r + S r o o f + i = 1 8 S h e a t _ i

2.2. Features of the Building Envelope Components

To describe the thermal performance of the building envelope components, it is necessary to insert their thermal transmittance (U-value). To this aim, the e-DSS already contains a predefined list of common opaque components with their corresponding U-value; the list is available through a drop-down menu, but the user can also decide to manually insert a different U-value if, for instance, this is already known from previous analyses. The list of the opaque structures implemented in the e-DSS is reported in Appendix A (Table A1). The corresponding U-values are different for Italy, Greece, and Romania; these values have been defined through preliminary research conducted by local e-SAFE partners, who analyzed the most common assemblies and building materials used in the three countries until the end of the XX century.
The e-DSS follows a similar approach to define the U-values of the windows (Uw) by combining the features of both the glazed surface and the opaque frame (see Table A2 in Appendix A). By default, the frame occupies 30% of the window surface (frame factor F F = 0.3), which approximates the real features of many commercial windows. The thermal transmittance of the shutter boxes, if any, is set by default as Ubox = 4 W/(m2∙K).
The presence of roller shutters also implies calculating the thermal transmittance of the windows when the shutters are closed (Uws). The latter is determined according to UNI/TS 11300-1:2014 [15] by referring to a shutter with average air permeability:
U w s = U w 1 + 0.55 · R s h + 0.11 1
In Equation (10), Rsh is the additional thermal resistance of the closed shutter, whose possible values are Rsh = 0 m2∙K/W (metal shutter), Rsh = 0.15 m2∙K/W (wood or insulated plastic shutter) or Rsh = 0.1 m2∙K/W (other types of shutters). Finally, UNI/TS 11300-1:2014 determines the corrected window U-value (Uw_corr) considering that the shutters are closed during 60% of the day, as per Equation (11). Of course, if no roller shutter is selected, Uw_corr = Uw.
U w _ c o r r = 0.6 · U w s + 0.4 · U w
Moreover, to account for movable shading devices (e.g., blinds and curtains), the user can select an item from a drop-down menu, which implies a suitable shading factor:
  • Inner light curtain: fshade = 0.80;
  • Outer light curtain: fshade = 0.70;
  • Other type of shading (inner side): fshade = 0.55;
  • Other type of shading (outer side): fshade = 0.35.
The e-DSS also considers the color of the external finish for the vertical walls and the roof. The color determines the solar absorption coefficients, which are, respectively, identified as α v and α h o r ; three possibilities are available (light = 0.3, medium = 0.6, and dark = 0.9), as suggested by UNI/TS 11300-1:2014 [15].
Finally, the user can specify whether a facade has balconies. Consequently, a projection factor (Fsh_i_j) is attributed to the windows and the walls located in that facade. The value of the projection factor changes each month (“j”) coherently with the average sun height; the default values are taken from UNI/TS 11300-1:2014 and refer to an obstruction angle of 30° (typical of balconies) and latitude 42°00′ N (average recurring latitude in Italy, Greece, and Romania). If a facade has no balconies, Fsh_i_j = 1 applies in all months.

2.3. Weather Data

The weather data necessary for the energy assessment of the building, according to the quasi-steady-state method adopted in the e-DSS and described in detail in the next section, are the monthly average of the dry-bulb air temperature (°C) and daily global solar irradiation (MJ/m2). Accordingly, the e-DSS tool automatically connects to the freeware online service PVGIS [16] and downloads the latest available year of data in the PVGIS-SARAH3 database for the location specified by the user through the latitude and the longitude. This database collects re-analysis data from satellite observations for Europe, Asia, Africa, and South America with a spatial resolution of about 5 km.
The data are downloaded in hourly format for one year and then directly averaged by the number of hours in the months in the case of air temperature, while for solar irradiation values, the hourly values (Wh/m2) are first summed up, then averaged by the number of days in the month, and eventually converted into MJ/m2. This operation is performed for a horizontal surface (slope angle of 0°) and for eight vertical surfaces (slope angle of 90°), with azimuth angles changing by 45° step starting from south (0°).

2.4. Energy Calculations

The proposed approach to calculate the thermal energy needs for space heating and cooling is inspired by the quasi-steady-state method introduced by Italian national standard UNI/TS 11300-1:2014 and is today adopted by all commercial tools for building energy certification [15]. However, the attribution of some parameters has been simplified to make input data user-friendly, coherently with the scopes of the tool.
Equations (12) and (13) show the monthly thermal energy balances used to calculate the final thermal energy demand for space heating (QH) and space cooling (QC) under the hypothesis of continuous operation in standard conditions:
Q H _ j = Q H _ l o s s _ j η H _ g n _ j · Q H _ g a i n _ j · H d a y s _ j
Q C _ j = Q C _ g a i n _ j η C _ l s _ j · Q C _ l o s s _ j · C d a y s _ j
Here, the subscript “j” refers to each month (j = 1 ÷ 12). The duration in days of the months included in the heating season ( H d a y s _ j ) and in the cooling season ( C d a y s _ j ), as well as the relations to calculate the utilization factors η H _ g n _ j and η C _ l s _ j , will be introduced in Section 2.4.4. From now on, this section will detail only the equations relating to the space heating needs. However, they are also applicable in the cooling season, apart from some slight differences that will be duly underlined.
In Equation (12) and Equation (13), the daily heat losses and heat gains are calculated as per Equation (14) and Equation (15), respectively. The single terms are commented on hereafter.
Q H _ l o s s _ j = Q H _ t r _ j + Q H _ v e _ j Q H _ s o l _ o p _ j
Q H _ g a i n _ j = Q H _ e n d _ j + Q H _ s o l _ w _ j

2.4.1. Transmission Heat Losses

For each month “j” included in the heating period, the daily thermal energy transmitted through the building envelope is:
Q H _ t r _ j = 24 · H t r · θ H E A T θ e _ j + 11 · r _ t o t / 1000
Here, θ e _ j is the monthly mean outdoor air temperature, determined as explained in Section 2.3, while θ H E A T is the indoor temperature setpoint, set by the user through a specific drop-down menu (this is expressed as θ C O O L in the cooling season). The total radiant heat exchange with the sky is determined as per Equation (17):
r _ t o t = R O O F · r r o o f + 0.5 · i = 1 8 r _ i
Here, ROOF is a Boolean variable (ROOF = 1 if the type of boundary condition selected for the roof corresponds to “Outdoors”; otherwise, ROOF = 0). Moreover, given the thermal resistance associated with the outside surface heat transfer ( R s e _ h o = R s e _ v = 0.04 m2∙K/W) [17], one can calculate the following [18]:
r _ r o o f = R s e _ h o · 4.14 · S r o o f · U r o o f
r _ i = R s e _ v · 4.14 · ( S e f f _ o p _ i · U w a l l + S b o x _ i · U b o x + S w _ i · U w _ c o r r )
Back to Equation (16), the transmission heat loss coefficient (Htr, in W/K) is:
H t r = H t r _ f l o o r + H t r _ r o o f + i = 1 8 H t r _ i
As far as the vertical surfaces are concerned, the e-DSS the following calculates for each orientation:
H t r _ i = c t h · S e f f _ o p _ i · U w a l l + S w _ i · U w _ c o r r + S b o x _ i · U b o x + S a d j _ i · U w a l l · b t r _ U _ a d j
Here, the correction coefficient (cth) considers—in a simplified way—the role of the thermal bridges. Several cases may occur, according to the presence of balconies:
  • If there are no balconies: cth = 1.1;
  • If the balconies are just on one facade: cth = 1.2;
  • If the balconies are on two facades: cth = 1.3;
  • If the balconies are on three facades: cth = 1.35;
  • If the balconies are on four or more facades: cth = 1.4.
Similarly, the e-DSS calculates the transmission heat loss coefficient in relation to the floor and the roof according to Equation (22) and Equation (23), respectively:
H t r _ f l o o r = c t h · S f l o o r · U f l o o r · b t r _ U _ f l o o r
H t r _ r o o f = c t h · S r o o f · U r o o f · b t r _ U _ r o o f
In these equations, the correction coefficient is by default cth = 1.1 because the thermal bridges occurring in horizontal envelope surfaces are usually not as impactive as in vertical walls with balconies. Finally, the e-DSS determines the transmission heat loss coefficient per unit heated envelope surface, recalled in several national regulations:
H T = H t r / S d _ t o t

2.4.2. Ventilation Heat Losses

The daily heat transfer by ventilation is calculated as per Equation (25), where the ventilation heat loss coefficient (Hve, in W/K) is derived from Equation (26) [15]:
Q H _ v e _ j = 24 · H v e · θ H E A T θ e _ j / 1000
H v e = 0.34 · V n e t · A C H · R E S + 1 R E S · 3.6 · L p s · f v e · P s q m · S n e t · C 2 · ( 1 R E C )
In Equation (26), Vnet is the net volume of the heated zones, and Snet is the overall net floor surface of the building. Both values are assigned during the definition of the building geometry. Furthermore, the air exchange rate is assigned as a function of the intended building use: in residential buildings, ACH = 0.3 h−1, while in other type of buildings, one has to know the nominal ventilation rate per person in L/s (Lps), the occupancy rate in people/m2 (Psqm), and the correction factor (fve) that accounts for the possibility that mechanical ventilation is not exploited all day long. Their values are reported in Appendix A (Table A3) [15]. The coefficient C2 depends on the altitude of the location (see Table 2). RES is a Boolean variable: RES = 1 if the predominant building use is “Residential”, while RES = 0 in all other cases. Finally, REC is the efficiency of the heat recovery unit in the case of a controlled mechanical ventilation system (REC = 0 if no heat recovery unit is provided, and REC = 0.8 by default if the user does not know the exact value).

2.4.3. Solar Gains Through Windows and Opaque Components

The mean daily value of the solar gains through windows ( Q H _ s o l _ w _ j , in kWh/day) is determined as:
Q H _ s o l _ w _ j = f s h a d e · g f a c t o r · i = 1 8 I s o l _ i _ j · S w _ i · F s h _ i _ j · 1 F F / 3.6
In Equation (27), g f a c t o r is the solar transmission factor of the glazed surface, automatically attributed according to the glazing type (Table A2), and I s o l _ i _ j is the monthly mean of the daily global solar irradiation (MJ/m2) for the “i-th” orientation and the “j-th” month.
The mean daily value of the solar gains absorbed by the opaque envelope components ( Q H _ s o l _ o p _ j , in kWh/day) is determined as:
Q H _ s o l _ o p _ j = i = 1 8 I s o l _ i _ j · ( S e f f _ o p _ i · U w a l l + S b o x _ i · U b o x · R s e _ v · α v ) + + R O O F · I s o l _ h o r _ j · S r o o f · U r o o f · R s e _ h o · α h o / 3.6
Here, I s o l _ h o r _ j is the monthly average of the daily global solar irradiation on the horizontal plane (MJ/m2) for the j-th month.

2.4.4. Endogenous Heat and Utilization Factors

The endogenous heat is determined as:
Q H _ e n d _ j = ( 24 · θ E N D · S n e t ) / 1000
Here, θ E N D is the average thermal power released by endogenous heat sources (people, electric appliance, artificial lighting) per unit net surface, whose values depend on the intended building use (Table A4).
Moreover, the first step to calculate the utilization factors η H _ g n _ j and η C _ l s _ j consists of evaluating the time constant (tau) of the building, measured in hours:
t a u = ( S d t o t · C m e a n / 3600 ) / [ ( H t r + H v e ) / 1000 ]
In Equation (30), Cmean is the mean thermal capacity per unit surface of opaque heated envelope. This parameter is attributed based on the type of wall selected by the user (see Table A1), and its value is either 135 kJ/(m2∙K) in the case of heavy structures (concrete walls, tuff, solid bricks) or 120 kJ/(m2∙K) otherwise [15].
Once the time constant is known, the gains utilization factor in the heating season is determined for each j-th month as:
η H _ G N _ j = m i n   1 γ H _ j a H 1 γ H _ j ( a H + 1 ) ; 1
where:
a H = 1 + t a u 15                                 γ H _ j = m a x Q H _ g a i n _ j / Q H _ l o s s _ j ; 0
Finally, the duration of the heating season corresponds to all those months in which the condition in Equation (33) holds. If the condition is true, Hdays in Equation (12) is the number of the days in that month; otherwise, Hdays = 0.
γ H _ j < ( a H + 1 ) / a H   A N D   γ H _ j 0  
Similarly, in the cooling season, the utilization factor for the heat losses is:
  η C _ l s _ j = m i n 1 γ C _ j a C 1 γ C _ j ( a C 1 ) ; 1           w i t h             γ C _ j > 0
where:
a C = max 8.1 + t a u 17 13 ·   S w S n e t   ; 0                         γ C _ j = Q C _ g a i n _ j / Q C _ l o s s _ j
The duration of the cooling season corresponds to those months in which the condition in Equation (36) holds. If the condition is true, Cdays in Equation (13) is the number of the days in that month; otherwise, Cdays = 0.
γ C _ j 1 < ( a C + 1 ) / a C

2.5. Renovation Stage

The e-DSS does not aim at calculating or certifying the seismic improvement provided by the possible renovation solutions, since this outcome would need the use of specific tools for a dynamic structural analysis. However, the e-DSS assists the technician in the preliminary decision-making process towards the most suitable e-SAFE solution for energy-and-seismic improvement, considering the height and shape of the building, the current state of conservation of the RC structures, and the seismic zone.
Thus, the user can initially select if he/she wants to go for an energy-and-seismic renovation. In this case, the e-DSS poses a series of questions, such as:
  • Level of degradation of the existing structures (no degradation, just slightly degraded, degraded but they can be easily recovered, too degraded);
  • Percentage of perimeter occupied by balconies in a typical floor;
  • Number of facades attached to other buildings;
  • Number of floors;
  • Presence of constraints that prevent altering the appearance of the building (e.g., local regulations, cultural heritage restrictions);
  • Availability of sufficient space for crane operations around the building.
The seismicity of the city where the building is located depends on the Peak Ground Acceleration (PGA), automatically retrieved through the EFEHR web service [19].
Based on the above data, the e-DSS attributes a score to the building and determines the most suitable combined energy-and-seismic renovation solution (e-CLT or e-EXOS). In some cases, the e-DSS might exclude one or even both solutions, which happens, for instance, if the number of floors is above twelve or when local regulations forbid altering the facade. Further details are available in the relevant e-SAFE project’s deliverable [20].
After this preliminary decision stage, if the user chooses either a simple energy renovation (no seismic improvement) or a combined energy-and-seismic renovation relying on e-EXOS, the tool considers e-PANEL as the only candidate solution to improve the envelope’s energy performance. A typical cross-section of an e-PANEL applied to an existing wall is depicted in Figure 1. Here, the non-insulated wooden frame covers approximately 30% of the total e-PANEL surface, based on a series of detailed design experiences conducted so far.
Accordingly, the e-DSS calculates the mean U-value of the wall renovated through the e-PANEL (Uwall_new) as follows:
U w a l l _ n e w = 0.7 U P A N E L + 0.3 U f r a m e
where:
U P A N E L = 1 U w a l l + 0.01 λ w o o d + δ i n s λ i n s + 0.0125 λ f i b + R G A P + δ c l a d λ c l a d 1
U f r a m e = 1 U w a l l + δ i n s   + 0.01 λ w o o d + 0.0125 λ f i b + R G A P + δ c l a d λ c l a d 1
The above equations rely on the following positions:
  • The wooden frame has the same thickness as the insulation layer.
  • The wooden frame and the wooden board behind the insulation have default thermal conductivity λwood = 0.13 W/(m∙K).
  • The thermal resistance of the scarcely ventilated air gap behind the cladding is RGAP = 0.09 m2∙K/W [17].
  • The fiber cement board has default thermal conductivity λfib = 0.32 W/(m∙K).
  • The thermal resistance of the metal brackets and the water-proof membrane, necessary to reduce the risk of moisture accumulation, is negligible [21].
  • The type of cladding can be selected from a drop-down menu (Appendix A, Table A5), which automatically sets δclad and λclad.
Now, when the user decides to simulate a renovation scenario relying on the e-PANEL, the main step consists of setting the insulation type and thickness. The type of material can be chosen from a drop-down menu including the options available in Appendix A (Table A5), each associated with a design conductivity value [22]. Moreover, the user must set the insulation thickness (δins) wisely, because in the case of energy renovation, many European countries require that a threshold U-value is not overcome (Table 3).
To this aim, the e-DSS automatically calculates the minimum thickness needed to comply with this legal requirement, knowing the country where the building is and the climatic zone, if relevant. Indeed, the e-DSS operates a “while” loop, where the insulation thickness is increased by 2 cm steps and Equations (37)–(39) are solved until the resulting Uwall_new becomes lower than the relevant threshold. Then, the e-DSS notifies the result, and the user can either confirm it or choose an even higher insulation thickness; in the second case, the e-DSS calculates the final Uwall_new again and assigns it to all walls in the building to calculate the new energy performance.
Then, the user might also want to include a roof renovation. In this case, the e-DSS allows for selecting the desired insulation (drop-down menu in Table A5) and its thickness (δins_roof), so that it can calculate the new thermal transmittance (Uroof_new) assigned to the roof surface in place of Uroof:
U r o o f _ n e w = 1 U r o o f + δ i n s _ r o o f l a m b d a i n s _ r + 0.1 1
Here, the additional thermal resistance R = 0.1 m2∙K/W accounts for both the new tiles and the lightweight cement screed layer between the insulation and the tiles, with an overall thickness of around 5 cm and an average thermal conductivity around 0.5 W/(m∙K). In this stage, the user can also select the type of tiles and the presence of a weather-protection membrane; however, this choice does not affect energy performance.
As far as thermal bridges are concerned, the correction coefficient (cth) used in Equation (21) assumes different values compared to the pre-renovation stage, since thermal bridges are partially corrected by the outer thermal insulation:
  • If there are no balconies: cth = 1.1;
  • If the balconies are just on one facade: cth = 1.125;
  • If the balconies are on two facades: cth = 1.15;
  • If the balconies are on three facades: cth = 1.175;
  • If the balconies are on four or more facades: cth = 1.2.
Coming to the glazed components, the proposed renovation solution implies that they are replaced by new high-performing windows mounted in a suitably shaped e-PANEL. The glazing type is set by default as low-e double glazing, but the user can select the type of frame; consequently, the e-DSS sets the new U-value (Uw_new) according to Table A2. The user can also choose to manually insert the new U-value if it is known from technical datasheets; in any case, gfactor_new = 0.67 is used by default.
The new windows also include outer shading devices, whose shading factor is set by default to fshade = 0.35. Furthermore, the new windows are not provided with shutter boxes; so, if the existing windows had shutter boxes, in the renovation stage, the e-DSS would set SBOX = 0 in Equations (21) and (28), and the window surface would be increased by 15%.

3. Case Study

3.1. Building Geometry and Features

The building taken as a case study is situated in Catania (southern Italy), its construction dates to the 1960s, and it is part of the local public residential stock. It consists of five floors with two flats per floor, with an RC structural frame and cavity walls with two layers of lightweight concrete blocks. The roof is flat and uninsulated, while a floor slab separates the ground floor from an inaccessible, hollow basement that prevents rising damp. Balconies are present on the two main fronts, facing south and north; most of the glazed surface lies on these fronts, while only few small windows are in the east and west fronts. Almost all windows have double glazing and metal frames with no thermal break, roller shutters, and uninsulated boxes, while only a few windows have single clear glasses. Finally, there are no adjacent buildings (nadj_floors = 0). Figure 2 shows the typical plan of the building, including an internal condominium staircase, and a picture of the main facade. Table 4 contains all the input data used in the e-DSS, retrieved both from the available design documents (plans, fronts) and through on-site surveys. The length of the facades was taken by assuming a slightly simplified shape, i.e., by excluding the projection of the stairwell.
In the renovation stage, the e-PANEL will have δins = 8 cm, leading to Uwall_new = 0.36 W∙m−2∙K−1, below the maximum value set by law in Zone B (Table 3). The roof will be insulated by 10 cm of wood fiber, with a resulting Uroof_new = 0.30 W∙m−2∙K−1. New windows have a timber frame and low-e double glazing, with Uw_new = 2.3 W∙m−2∙K−1.

3.2. Simulation with a Commercial Tool

The case study was simulated not only with the e-DSS but also with Blumatica Energy [24], a commercial certified tool widely used by professionals in Italy for building energy certification, thus allowing for comparing the results from both tools and assessing the reliability of the e-DSS. Table A6 and Table A7 in Appendix A describe the wall and roof assemblies used in the simulation with Blumatica Energy. It is worth mentioning that Blumatica Energy also performs a detailed analysis of all thermal bridges, based on their geometry and the materials included in the opaque components.
One key aspect is that the two tools use different weather data to calculate the building’s energy needs. Indeed, Blumatica Energy adopts the official weather data available in the Italian standard UNI 10349-1:2016 [25], while the e-DSS follows the approach already described in Section 2.3. The reason for this choice is that the e-DSS should in principle be used in every location worldwide, and using official weather databases for many different countries would mean a huge preliminary implementation work. Table 5 and Figure 3 compare the main data taken from the two different sources for the city of Catania, using 2023 as the reference year for PVGIS. The year 2023 was selected to represent the PVGIS climatic data, as it was identified as one of the most representative years based on an analysis of the last 15 years available in the software (from 2009 to 2023). The relevance of the selected year is demonstrated in Figure 4, where it can be observed that, for most months, 2023 closely aligned with the median values both in terms of temperature and solar irradiance. The biggest differences in the mean air temperatures occurred in July and September, and in both cases, PVGIS provides higher values than UNI 10349-1:2016 (by 3.8 °C and 1.9 °C, respectively). In the heating season, March is the month showing the highest discrepancy, with PVGIS providing a higher mean temperature by 1.6 °C. The discrepancy between the mean daily global irradiation is usually below 10%, except for the north facade (PVGIS systematically underestimates this by around 50%) and the south facade in the winter (PVGIS overestimates this by around 70%).

4. Results and Discussion

4.1. Comparison Between e-DSS and Blumatica Energy

To investigate the reliability of the e-DSS in estimating heat losses and heat gains during both the heating and cooling seasons, this section compares the outcomes from the two software tools. It is important to note that this comparison should not be considered a ‘validation’ process due to the different weather datasets employed by each tool, as outlined in Section 3.2.
As a first result, Table 6 proves that the e-DSS calculated the main geometric outputs—overall heated envelope surface and compactness ratio—with good accuracy, despite its simplified approach. The transmission heat loss coefficient was slightly underestimated both before and after renovation; however, in both cases, the discrepancy was below 5%. This result is very satisfying if one considers the simplified approach to assess thermal bridges, based on correction coefficients that depend on the number of facades with balconies.
Then, Figure 5 and Figure 6 and Table 7 provide the details of the terms that concur in the calculation of space heating and cooling demand, both before and after renovation.
Starting from the heating demand (Figure 5), in the current building configuration (before renovation), the main discrepancy concerns the solar gains; indeed, the e-DSS overestimated them by 45%, which is coherent with the difference in the mean global irradiation values reported in winter by the two weather datasets for the south orientation (Figure 3), i.e., the orientation with the greatest glazed surface. Instead, internal gains were just slightly underestimated (−4%) compared with Blumatica Energy. Heat losses by ventilation showed very good accordance (−1.6%), whereas the e-DSS underestimated heat losses by transmission by 6.8%; this is coherent with the difference in the transmission heat loss coefficients observed in Table 6 but also stems from the mean monthly outdoor air temperatures in the winter months (Table 5) that were—on average—higher in the e-DSS than in Blumatica Energy, thus providing a lower temperature drop between indoors and outdoors. Overall, the space heating demand calculated by the e-DSS underestimated the result provided by Blumatica Energy by 19.8%.
Still looking at the heating demand (Figure 5), the previously outlined differences became less important in the building after renovation because the low U-values and the presence of effective movable shading devices reduced the effects of the different weather data. Thus, in this case, the e-DSS overestimated the heating demand by 10.5%, with the solar gains being underestimated by just 5%. The calculation of internal gains and heat losses by ventilation maintained very good reliability.
The calculation of the cooling demand (Figure 6) presents different outcomes that can be partially justified by the different weather data. Indeed, the monthly mean outdoor air temperature values retrieved from PVGIS are constantly higher than the corresponding data used by Blumatica Energy and—in July and August—also above the indoor set-point temperature (26 °C). For this reason, in the e-DSS, heat losses by ventilation and transmission turned into heat gains, thus contributing to increasing the cooling demand, while Blumatica considered these terms as heat losses that reduced the cooling demand. Furthermore, there is a difference in the mean global irradiation values reported in the summer by the two weather datasets for the south orientation, which is, however, not as high as in the winter (Figure 3), which makes the calculation of solar gains before renovation not too deceiving (+11.0%). Internal gains were affected by a very low discrepancy (−3.9%). Overall, the cooling demand before renovation was overestimated by 26.9%.
When looking at the cooling demand in the renovation stage (Figure 6), the most important and somehow surprising difference lies in the solar gains, which were strongly underestimated by the e-DSS (−41.7%). This difference was partially compensated for by the underestimation in the heat losses, providing an overall discrepancy as high as −14.8% (Table 7). The reason for this result will be discussed in Section 4.3.
It is also worth mentioning that a sensitivity analysis of the key input parameters was performed during the debug phase as a standard quality assessment procedure, which provided consistent results.
Finally, one can observe that, according to Blumatica Energy, the proposed e-SAFE renovation cut the heating demand by 69% (from 41.0 MWh to 12.7 MWh), while the e-DSS suggested a reduction by 57% (from 32.9 MWh to 14.0 MWh). On the other hand, the cooling demand decreased by 11.2% in Blumatica Energy (from 23.2 MWh to 20.6 MWh), while the e-DSS emphasized this reduction to 40.4% (from 29.4 MWh to 17.5 MWh).

4.2. The Role of the Different Weather Datasets

As already discussed, one of the reasons that justify the different outcomes between Blumatica Energy and the e-DSS is the use of different weather datasets. In order to remove the effect of weather data, a further test was conducted by forcing the data retrieved from UNI 10349-1:2016 (and used by Blumatica Energy) into the e-DSS.
In this case, the accordance between the heating needs in the current building configuration was highly improved; heat losses now differed by only 0.6%, while heat gains were still overestimated but only by 4.5%. Consequently, the heating demand calculated by the e-DSS was only 0.8% below the value obtained from Blumatica Energy. Similarly, in the cooling season, both heat gains and heat losses were slightly overestimated by the e-DSS, with an overall 2.5% difference in the cooling needs. However, and quite surprisingly, worse outcomes emerged in the simulation of the building after renovation; actually, in both seasons, the solar gains through the windows were strongly underestimated, leading to higher heating demand (+35.9%) and lower cooling demand (−36.7%) than in Blumatica Energy. The reason behind this outcome is discussed in Section 4.3.

4.3. Discussion and Possible Improvements of the e-DSS

As outlined in the previous sections, the first important issue in the e-DSS is the choice of the weather data used to calculate the thermal energy demand. While Blumatica Energy adopts the official weather data available in the Italian standard UNI 10349-1:2016 [25], the e-DSS retrieves data from the online service PVGIS so that they can be available for every location worldwide. Moreover, the UNI data represent a long-term average, while PVGIS data correspond to a specific year (2023 in this case). This does not allow for direct comparison between the two tools but cannot be regarded as an error in the e-DSS; indeed, the main reason for using this tool is a quick and preliminary evaluation of the benefits ensured by e-SAFE renovation, which is still feasible. A more robust approach would require downloading and averaging several years of weather data from PVGIS, which is feasible but would made the tool cumbersome and slow down the simulations.
Another limitation of the e-DSS is that it does not allow for describing the presence of different types of windows, roller shutters, and movable shading devices. Moreover, the attribution of the projection factors in Table A4 is only associated with the presence of balconies and can assume a single value for each facade; instead, a real building can present other types of obstructions (vertical fins, opposite buildings), and the balconies in a certain facade can provide different shading patterns to the various windows. The error introduced by this limitation in the e-DSS depends on the specific building, but in principle, this is likely to bring about an underestimation of the shading effect, especially in the summer.
Two further main simplifications were identified that justify the discrepancies between the results from the e-DSS and Blumatica Energy, and both regard the calculation of the solar gains through the glazed components.
The first simplification consists of neglecting the “exposure factor” (Fw) introduced by UNI/TS 11300-1:2014; this multiplies the solar transmission factor (gfactor) to account for the incidence angle of the solar radiation against the glazed surface and depends on the orientation, the type of glazing, and the month. For instance, the “exposure factor” for a south-oriented double glazing ranges between 0.90 and 0.98 in the winter months, but it becomes 0.77 to 0.80 in the summer months. Instead, an east-oriented double glazing has Fw = 0.86 to 0.90 in the winter and Fw = 0.915 in the summer. Neglecting this term in the e-DSS obviously implies overestimating the solar gains.
The second simplification consists of using a constant shading factor (fshade), which means assuming that the movable shading devices are always closed. In fact, UNI/TS 11300-1:2014 corrects this factor to consider that the shading device is closed over a certain percentage of time (twith), while in the remaining time (1 − twith), the shading device is open because the solar irradiance values are low:
f s h a d e _ c o o r = t w i t h · f s h a d e + 1 t w i t h
Default values are available for twith, according to the orientation and the month. For instance, a south-oriented shading device has twith = 0.56 to 0.82 in the summer and twith = 0.81 to 0.86 in the winter. North-facing shading devices always have twith = 0, meaning that they are always open. Now, let us apply Equation (41) in July to a south-facing window (twith = 0.62) both before renovation (fshade = 0.8) and after renovation (fshade = 0.35):
Before   renovation :   f s h a d e _ c o o r = 0.62 · 0.8 + 1 0.62 = 0.876
After   renovation :   f s h a d e _ c o o r = 0.62 · 0.35 + 1 0.62 = 0.597
From this example, it is possible to understand that the error caused by using a constant shading factor in the e-DSS amounts to around 10% before renovation (fshade = 0.8 in the e-DSS and fshade_corr = 0.876 in Blumatica Energy), but it exceeds 60% after renovation (fshade = 0.35 in the e-DSS and fshade_corr = 0.597 in Blumatica Energy). In both cases, the error leads to underestimating the solar gains in the e-DSS but to an unacceptable degree for the renovated building. This fully justifies the results presented in Section 4.2 and suggests that the two main simplifications discussed above should be avoided to provide a more reliable and realistic tool.
Finally, it is worth mentioning that the e-DSS has been tested by many technicians (mainly engineers and architects working either in construction companies or as freelance designers) during a series of dissemination and training activities conducted between 2022 and 2025 in Italy and Greece in the framework of the e-SAFE project. Around 40 participants were involved in the four events organized so far, and they were asked to simulate a residential building with the e-DSS, while also proposing and evaluating possible renovation solutions. The only data they were provided with were plans, perspective drawings and some information about wall assemblies, roofs, window types, and existing thermal systems.
During the final open discussion, almost all the participants expressed their satisfaction with the tool, highlighting its user-friendliness. In their opinion, no specific training is needed to use it, but on the contrary, its streamlined data input allow professionals to easily and quickly address a preliminary design stage. The technicians also provided suggestions for further improving the tool; the main recurrent suggestion regarded the possibility of implementing an algorithm to size the heat generators in the design stage, based on the building’s heat load, which is now left to user experience.

5. Conclusions

The findings presented herein suggest that the e-DSS can be used as a valuable and user-friendly tool for preliminary energy performance assessment of non-historical buildings with RC structural frames, before and after an e-SAFE renovation. Its primary function is to guide users in the decision-making process, thus helping in the choice of the most suitable energy-and-seismic renovation solution based on the features of the building. Its user-friendliness has been recognized by a pool of technicians (engineers, architects) involved in a series of training activities in Italy and Greece in the framework of the e-SAFE project. Apart from expressing their satisfaction, the technicians also provided suggestions for further improving the tool.
The e-DSS also highlights potential energy, cost, and environmental benefits. However, it is important to acknowledge that the e-DSS is neither intended for highly precise energy calculations nor for energy performance certification. The use of real weather data available from the freely accessible PVGIS service, while making the tool versatile and globally applicable, prevents direct comparison with other tools employing typical weather years. Nevertheless, it ensures a robust internal comparison between the pre- and post-renovation scenarios within the e-DSS framework. To further enhance its accuracy, future code improvements are necessary, particularly concerning the implementation of correction factors to simulate the operation of movable shading devices and the angle of incidence for solar radiation. Conversely, other simplifications within the code, such as those related to heat losses through thermal bridges and the projection factors for windows on balconied facades, introduce deviations that are deemed acceptable for preliminary assessments.
This initial study focused only on KPIs related to the energy performance of the building envelope. The simulation of thermal systems will be addressed in subsequent research. Moreover, the case study is a residential building located in a warm region of southern Italy. Future work should validate the e-DSS’s robustness across diverse climatic regions, potentially heating-dominated, and for other building typologies beyond residential applications. So far, the tool can be used only in Italy, Greece, and Romania, because for these countries, it includes a suitable database of materials, costs, and regulations.

Author Contributions

Conceptualization, G.E. and V.C.; methodology, G.E. and V.C., data curation, G.E. and M.T.; formal analysis, G.E. and G.M; visualization, G.E. and M.T.; software, M.T., M.L. and D.A.; validation, G.E., M.T. and M.L; writing—original draft preparation, G.E. and M.T.; writing—review and editing, V.C. and G.M.; resources, G.M. and D.A. All authors have read and agreed to the published version of the manuscript.

Funding

This research was carried out in the framework of the e-SAFE project (“Energy and seismic affordable renovation solutions”), which has received funding from the European Union’s Horizon 2020 Research and Innovation program under grant agreement no. 893135. Neither the Executive Agency for Small-and-Medium-sized Enterprises (EASME) nor the European Commission is in any way responsible for any use that may be made of the information it contains.

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

VariableDescriptionUnits
ACHAir exchangeh−1
aHEmpirical coefficient depending on building inertia -
BOXBoolean variable to define whether box is closed or open-
btr_U_ADJCorrection factor depending on the adjacent building-
btr_U_floorCorrection factor depending on the boundary condition (floor)-
btr_U_roofCorrection factor depending on the boundary condition (roof)-
C2Correction coefficient altitude of the location-
Cdays_jDays of the months included in the cooling seasonday
CmeanMean therm. cap. per unit surface of opaque heated envelopekJ∙m−2∙K−1
cthCorrection coefficient of the thermal bridges-
FFFrame factor-
froofCorrection factor to be applied to Sroof-
FSh_i_jProjection factor for each month and exposition-
fshadeCorrection factor for mobile devices-
fshade_coorCorrection factor corrected for mobile devices-
fveCorrection factor for mechanical ventilation is not exploited all day long-
FwExposure factor-
gfactorSolar transmission factor of the glazed surface-
gfactor_newSolar transmission factor of the renovated glazed surface-
H’TTransmission heat loss coeff. per unit heated envelope surfaceW∙K−1
Hdays_jDays of the months included in the heating seasonday
HtotBuilding height above the groundm
HtrTransmission heat loss coefficientW∙K−1
Htr_floorTransmission heat loss coefficient from the floorW∙K−1
Htr_iTransmission heat loss coefficient from each orientationW∙K−1
Htr_roofTransmission heat loss coefficient from the roofW∙K−1
HveVentilation heat loss coefficientW∙K−1
Isol_i_jMonthly mean of the daily global solar irradiationMJ∙m−2
LenghtiLength of the facade for each possible orientationm
LpsNominal ventilation rate per personL∙s−1∙person−1
nadj_floors_iNumber of heated floors in contact with an adjacent building-
nfloorsTotal number of floors above the ground-
nheatNumber of heated floors-
PsqmOccupancy ratepeople∙m−2
QC_gain_jHeat gains in the space cooling seasonkWh
QC_jOverall space cooling demandkWh
QC_loss_jHeat losses in the space cooling seasonkWh
QH_end_jEndogenous heat fluxkWh
QH_gain_jHeat gains in the space heating seasonkWh
QH_jOverall space heating demandkWh
QH_loss_jHeat losses in the space heating seasonkWh
QH_sol_op_jSolar gains on opaque surfaceskWh
QH_sol_w_jSolar gains on glazed surfaceskWh
QH_tr_jEnergy demand for transmission kWh
QH_ve_jEnergy demand for ventilationkWh
RECEfficiency of the heat recovery unit -
RESBoolean variable about the predominant building use-
RGAPThermal resistance of the scarcely ventilated air gapm2∙K∙W−1
ROOFBoolean variable to define boundary condition of the roof-
Rse_hoThermal resistance associated with horizontal surface heat transferm2∙K∙W−1
Rse_hoThermal resistance associated with vertical surface heat transferm2∙K∙W−1
RshAdditional thermal resistance of the closed shutterm2∙K∙W−1
S/VCompactness ratiom−1
SAdj_iHeated area in contact with adjacent buildingsm2
Sbox_iSurface area of the shutter boxesm2
Sd_totOverall heated envelope surfacem2
Seff_iHeated vert. surface in contact with the outdoors for each orientationm2
Seff_op_iOpaque portion of Seff_im2
SfloorGround floor surface aream2
Sheat_iOverall heated area of each facadem2
SnetHeated net floor aream2
SroofRoof surface aream2
Sw_iOverall glazed surface area for each orientationm2
tauTime constantS
twithPercentage of time with the shading device closed-
UboxU-values of the shutter boxesW∙m−2∙K−1
UPANELU-values of the wall renovated with e-PANELW∙m−2∙K−1
UroofU-values of the roofW∙m−2∙K−1
Uroof_newU-values of the renovated roof W∙m−2∙K−1
UwU-values of the windows (with shutters open)W∙m−2∙K−1
Uw_corrCorrected window U-valueW∙m−2∙K−1
Uw_newU-values of the renovated windowsW∙m−2∙K−1
UwallU-values of the wallsW∙m−2∙K−1
Uwall_newU-values of the renovated wall W∙m−2∙K−1
UwsU-values of the windows when the shutters are closedW∙m−2∙K−1
VgHeated gross volumem3
VnetHeated net volumem3
αhorSolar absorption coefficients—horizontal surface-
αvSolar absorption coefficients—vertical surface-
γC_jLosses-to-gains ratio in the cooling season-
γH_jGains-to-losses ratio in the cooling season-
δcladCladding thicknessmm
δinsInsulation thicknessmm
δins_roofRoof insulation thicknessmm
ηC_ls_jUtilization factors in the cooling season-
ηH_gn_jUtilization factors in the heating season-
θCOOLIndoor temperature setpoint in cooling mode°C
θe_jMonthly mean outdoor air temperature°C
θENDAverage thermal power released by endogenous heat sourcesW∙m−2
θHEATIndoor temperature setpoint in heating mode°C
λcladThermal conductivity of the claddingW∙m−1∙K−1
λfibThermal conductivity of the fiber cement boardW∙m−1∙K−1
λinsThermal conductivity of the insulationW∙m−1∙K−1
λwoodThermal conductivity of the wooden frame and boardW∙m−1∙K−1
ør_iRadiant heat exchange with the sky through each orientation kWh
ør_roofRadiant heat exchange with the sky through the roofkWh
ør_totTotal radiant heat exchange with the skykWh

Appendix A

Table A1. Predefined U-values for the opaque envelope components (all values are in W∙m−2∙K−1). The values are derived from preliminary research regarding building traditions in the three countries.
Table A1. Predefined U-values for the opaque envelope components (all values are in W∙m−2∙K−1). The values are derived from preliminary research regarding building traditions in the three countries.
DescriptionItalyGreeceRomania
Wall Solid brick wall1.55-1.80
(Uwall)Perforated bricks, tuff1.352.201.32
Uninsulated hollow bricks with air cavity1.101.60-
Hollow bricks with partially insulated air cavity0.800.850.92
Prefabricated concrete walls2.803.40-
Floor Uninsulated concrete slab1.65 *2.752.85
(Ufloor)Uninsulated hollow-core concrete floor1.251.201.15
Insulated concrete slab1.000.95-
Insulated hollow-core concrete floor0.800.900.80
RoofFlat uninsulated hollow-core concrete roof1.50-1.15
(Uroof)Pitched uninsulated hollow-core concrete roof1.80--
Pitched uninsulated roof with wooden structure1.803.20-
Uninsulated concrete slab-3.053.10
Generic partially insulated roof0.800.950.80
* In Italy, there is a significantly lower U-value because of the use of lightened concrete.
Table A2. Predefined U-values and solar transmission factors for the windows, as a function of the glazing type and the frame material (the same values are used in Italy, Greece, and Romania). The values are extracted from UNI/TS 11300-1:2014 [15].
Table A2. Predefined U-values and solar transmission factors for the windows, as a function of the glazing type and the frame material (the same values are used in Italy, Greece, and Romania). The values are extracted from UNI/TS 11300-1:2014 [15].
GlazingFrame U-Value
Single glazingWood4.9 W/(m2∙K)
(g-value = 0.85)Metal6.0 W/(m2∙K)
Metal with thermal break5.1 W/(m2∙K)
PVC5.0 W/(m2∙K)
Wood and metal5.2 W/(m2∙K)
Double glazing Wood2.8 W/(m2∙K)
(g-value = 0.75)Metal3.7 W/(m2∙K)
Metal with thermal break3.0 W/(m2∙K)
PVC2.9 W/(m2∙K)
Wood and metal3.1 W/(m2∙K)
Low-e double glazingWood1.5 W/(m2∙K)
(g-value = 0.67)Metal with thermal break1.7 W/(m2∙K)
PVC1.3 W/(m2∙K)
Wood and metal1.7 W/(m2∙K)
Low-e triple glazingWood1.0 W/(m2∙K)
(g-value = 0.50)Metal with thermal break1.1 W/(m2∙K)
PVC1.0 W/(m2∙K)
Wood and metal1.1 W/(m2∙K)
Table A3. Standard values for endogenous heat (θEND), occupancy rate (Psqm), and ventilation parameters, according to the predominant building use.
Table A3. Standard values for endogenous heat (θEND), occupancy rate (Psqm), and ventilation parameters, according to the predominant building use.
Predominant Building Use θENDPsqmLpsfve
(W∙m−2)(people∙m−2)(L∙s−1∙person−1)(-)
Residential4.50.05--
Library8.00.306.00.51
Hotel6.00.0511.00.26
Offices6.00.0611.00.59
Hospital8.00.0811.01.00
Cinema/theater8.01.005.50.51
Museum/church8.00.306.01.00
Restaurant 10.00.6010.00.47
Commercial building8.00.209.00.51
Swimming pool 10.00.302.50.34
Gym 5.00.206.00.18
School4.00.455.00.47
Industrial building6.0---
Table A4. Values of the projection factor (Fsh_i_j) associated with the balconies, according to the orientation of the facade.
Table A4. Values of the projection factor (Fsh_i_j) associated with the balconies, according to the orientation of the facade.
Month North (i = 1)Northeast (i = 2)Southeast (i = 4)
East (i = 3), West (i = 7)South (i = 5)
Northwest (i = 8)Southwest (i = 6)
January(j = 1)0.800.870.88
February(j = 2)0.800.840.84
March(j = 3)0.800.820.78
April(j = 4)0.800.800.70
May(j = 5)0.830.790.65
June(j = 6)0.820.770.63
July(j = 7)0.830.780.61
August(j = 8)0.810.780.66
September(j = 9)0.800.820.74
October(j = 10)0.800.840.82
November(j = 11)0.800.860.87
December(j = 12)0.800.870.89
Table A5. Default features for insulating and cladding materials used in the renovation stage.
Table A5. Default features for insulating and cladding materials used in the renovation stage.
Insulating Materialλ (W∙m−1∙K−1)Cladding Materialλ (W∙m−1∙K−1)δ (mm)
Wooden fiber0.04Fiber cement (with plaster)0.3215
Cellular glass0.055Fiber cement (without plaster)0.3215
Hemp fiber0.038Pre-painted aluminum2002
Cellulose fiber0.037Wooden slats0.1320
Sheep wool0.035WPC slats0.1320
Rock wool0.036Clay slats0.415
EPS0.037Porcelain stoneware1.015
XPS0.035Ceramic/clay1.015
Cork0.039
Table A6. Thermal features of external walls (from the inner to the outer side)—U = 1.00 W/(m2K).
Table A6. Thermal features of external walls (from the inner to the outer side)—U = 1.00 W/(m2K).
Materials (m)λ (W∙m−1∙K−1)Cp (J∙kg−1∙K−1)ρ (kg∙m−3)R (m2∙K∙W−1)
Surface thermal resistance ----0.13
Gypsum plaster0.020.57100013000.035
Hollow concrete blocks0.080.2910008450.276
Non-ventilated air gap0.090.5010001.20.180
Cement mortar0.011.40100020000.007
Hollow concrete blocks0.120.3910006670.307
Lime and cement plaster0.030.9084018000.033
Surface thermal resistance ----0.04
Table A7. Thermal features of the roof (from the top to the bottom side)—U = 1.30 W/(m2K).
Table A7. Thermal features of the roof (from the top to the bottom side)—U = 1.30 W/(m2K).
Materials (m)λ (W∙m−1∙K−1)Cp (J∙kg−1∙K−1)ρ (kg∙m−3)R (m2∙K∙W−1)
Surface thermal resistance----0.170
Exterior floor tiles0.020.57100013000.035
Cement mortar0.200.6484011320.310
Cement screed0.140.58100014000.241
Cement mortar0.021.40100020000.014
Concrete and clay blocks0.020.70100015000.029
Indoor plaster----0.040
Surface thermal resistance----0.170

References

  1. Available online: https://esafe-buildings.eu/en/ (accessed on 20 March 2025).
  2. Aloisio, A.; Boggian, F.; Tomasi, R. Design of a novel seismic retrofitting system for RC structures based on asymmetric friction connections and CLT panels. Eng. Struct. 2022, 254, 113807. [Google Scholar] [CrossRef]
  3. Evola, G.; Costanzo, V.; Urso, A.; Tardo, C.; Margani, G. Energy performance of a prefabricated timber-based retrofit solution applied to a pilot building in Southern Europe. Build. Environ. 2022, 222, 109442. [Google Scholar] [CrossRef]
  4. Nielsen, A.N.; Jensen, R.L.; Larsen, T.S.; Nissen, S.B. Early-stage decision support for sustainable building renovation—A review. Build. Environ. 2016, 103, 165–181. [Google Scholar] [CrossRef]
  5. Marcher, C.; Giusti, A.; Matt, D.T. Decision support in building construction: A systematic review of methods and application areas. Buildings 2020, 10, 170. [Google Scholar] [CrossRef]
  6. Ferrante, A.; Mochi, G.; Predari, G.; Badini, L.; Fotopoulou, A.; Gulli, R.; Semprini, G. A European Project for Safer and Energy Efficient Buildings: Pro-GET-One (Proactive Synergy of inteGrated Efficient Technologies on Buildings’ Envelopes). Sustainability 2018, 10, 812. [Google Scholar] [CrossRef]
  7. Daniotti, B.; Masera, G.; Bolognesi, C.M.; Spagnolo, S.L.; Pavan, A.; Iannaccone, G.; Signorini, M.; Ciuffreda, S.; Mirarchi, C.; Lucky, M.; et al. Workshop BIM4EEB A BIM-Based Toolkit for Efficient rEnovation in Buildings. Proceedings 2021, 65, 17. [Google Scholar] [CrossRef]
  8. Daniotti, B.; Spagnolo, S.L.; Pavan, A.; Bolognesi, C.M. Innovative Tools and Methods Using BIM for an Efficient Renovation in Buildings, 1st ed.; Springer Briefs: Milan, Italy, 2022. [Google Scholar] [CrossRef]
  9. Vavallo, M.; Arnesano, M.; Revel, G.M.; Mediavilla, A.; Sistiaga, A.F.; Pracucci, A.; Magnani, S.; Casadei, O. Accelerating Energy Renovation Solution for Zero Energy Buildings and Neighbourhoods—The Experience of the RenoZEB Project. Proceedings 2019, 20, 1. [Google Scholar] [CrossRef]
  10. Kamari, A.; Kirkegaard, P.H.; Schultz, C.P.L. PARADIS—A process integrating tool for rapid generation and evaluation of holistic renovation scenarios. J. Build. Eng. 2021, 34, 101944. [Google Scholar] [CrossRef]
  11. Neves-Silva, R.; Ruzzelli, A.; Fuhrmann, P.; Bourdeau, M.; Pérez, J.; Michaelis, E. Energy consumption prediction from usage data for decision support on investments: The EnPROVE approach. IFAC Proc. Vol. 2010, 43, 48–52. [Google Scholar] [CrossRef]
  12. Neves-Silva, R.; Camarinha-Matos, L.M. Simulation-Based Decision Support System for Energy Efficiency in Buildings Retrofitting. Sustainability 2022, 14, 12216. [Google Scholar] [CrossRef]
  13. Sánchez de la Flor, F.J.S.; Rodriguez Jara, E.A.; Pardo, A.R.; Salmeron Lissen, J.M.; Kolokotroni, M. Energy-Efficient Envelope Design for Apartment Blocks—Case Study of A Residential Building in Spain. Appl. Sci. 2021, 11, 433. [Google Scholar] [CrossRef]
  14. Havlik, D.; Fabris, J.; Geyer-Scholz, A.; Torres, L.; Cubillo, J. D6.7 CLARITY Guideline v2 2021. Available online: https://clarity-h2020.eu/content/downloads.html (accessed on 12 March 2025).
  15. UNI/TS 11300-1:2014; Prestazioni Energetiche degli Edifice—Parte 1: Determinazione del Fabbisogno di Energia Termica dell’Edificio per la Climatizzazione Estiva ed Invernale. Ente Nazionale di Normazione: Milan, Italy, 2014. (In Italian)
  16. Photovoltaic Geographical Information System, PVGIS. Available online: https://re.jrc.ec.europa.eu/pvg_tools/en/ (accessed on 22 March 2025).
  17. EN ISO 6946:2017; Building Components and Building Elements—Thermal Resistance and Thermal Transmittance—Calculation Methods. European Committee for Standardization: Brussels, Belgium, 2017.
  18. EN ISO 52016-1:2017; Energy Performance of Buildings—Energy Needs for Heating and Cooling, Internal Temperatures and Sensible and Latent Heat Loads—Part 1: Calculation Procedures. European Committee for Standardization: Brussels, Belgium, 2017.
  19. The Earthquake Hazard Map of Europe. Available online: http://www.efehr.org/earthquake-hazard/hazard-map/ (accessed on 17 May 2025).
  20. Lazzaro, M.; Evola, G. Deliverable D4.2—Decision Support System (e-DSS)—Renovation Space Representational Model (2.0); Zenodo; EU Open Research Repository: Brussel, Belgium; e-SAFE—Energy and Seismic Affordable Renovation Solution: Catania, Italy, 2021. [Google Scholar] [CrossRef]
  21. Urso, A.; Costanzo, V.; Nocera, F.; Evola, G. Moisture-Related Risks in Wood-Based Retrofit Solutions in a Mediterranean Climate: Design Recommendations. Sustainability 2022, 14, 14706. [Google Scholar] [CrossRef]
  22. UNI 10351:2021; Materiali da Costruzione—Proprietà Termoigrometriche—Procedura per la Scelta dei Valori di Progetto. Ente Nazionale di Normazione: Rome, Italy, 2021.
  23. Evola, G.; Costanzo, V.; Marletta, L. Hygrothermal and Acoustic Performance of Two Innovative Envelope Renovation Solutions Developed in the e-SAFE Project. Energies 2021, 14, 4006. [Google Scholar] [CrossRef]
  24. Available online: https://www.blumatica.it/software-certificazione-energetica-degli-edifici-ape-ed-aqe/ (accessed on 21 March 2025).
  25. UNI TS 10349-1:2016; Riscaldamento e Raffrescamento degli Edifice—Dati Climatici—Parte 1: Medie Mensili per la Valutazione della Prestazione Termo-Energetica dell’Edificio e Metodi per Ripartire l’Irradianza Solare nella Frazione Diretta e Diffusa e per Calcolare l’Irradianza Solare su di una Superficie Inclinata. Ente Nazionale di Normazione: Milan, Italy, 2016. (In Italian)
Figure 1. Cross-section of the e-PANEL applied to an existing wall.
Figure 1. Cross-section of the e-PANEL applied to an existing wall.
Energies 18 02839 g001
Figure 2. Typical floor plan of the investigated building and main facade (north).
Figure 2. Typical floor plan of the investigated building and main facade (north).
Energies 18 02839 g002
Figure 3. Mean daily global irradiation in Catania, calculated over the summer months (June to September) and the winter months (December to March).
Figure 3. Mean daily global irradiation in Catania, calculated over the summer months (June to September) and the winter months (December to March).
Energies 18 02839 g003
Figure 4. Monthly solar irradiation (top) and temperature (bottom) in Catania: comparison between 2023 and 15-year historical data (2009–2023) from PVGIS.
Figure 4. Monthly solar irradiation (top) and temperature (bottom) in Catania: comparison between 2023 and 15-year historical data (2009–2023) from PVGIS.
Energies 18 02839 g004aEnergies 18 02839 g004b
Figure 5. Heating energy demand before and after energy renovation: comparison between the results provided by Blumatica and the e-DSS, with the various terms affecting the energy balance.
Figure 5. Heating energy demand before and after energy renovation: comparison between the results provided by Blumatica and the e-DSS, with the various terms affecting the energy balance.
Energies 18 02839 g005
Figure 6. Cooling energy demand before and after energy renovation: comparison between the results provided by Blumatica and the e-DSS, with the various terms affecting the energy balance.
Figure 6. Cooling energy demand before and after energy renovation: comparison between the results provided by Blumatica and the e-DSS, with the various terms affecting the energy balance.
Energies 18 02839 g006
Table 1. Drop-down menu for the boundary conditions of floors and roofs [15].
Table 1. Drop-down menu for the boundary conditions of floors and roofs [15].
Boundary Condition b t r _ U f r o o f
Floor of the first heated levelBasement with no windows0.5-
Basement with windows0.8-
Ground0.45-
Outdoors1-
Roof of the last heated levelOutdoors (flat roof)11
Outdoors (pitched roof—low angle)11.05
Outdoors (pitched roof—high angle)11.15
Ventilated non-heated attic 11
Uninsulated non-heated attic0.91
Insulated non-heated attic0.71
Table 2. Values for the correction coefficient C2 [15].
Table 2. Values for the correction coefficient C2 [15].
Altitude (H)C2
H < 500 m1.00
500 m < H < 1000 m1.06
1000 m < H < 1500 m1.12
1500 m < H < 2000 m1.18
2000 m < H < 2500 m1.25
Table 3. Maximum U-values allowed for the vertical walls in case of building renovation (all values are in W∙m−2∙K−1) [23].
Table 3. Maximum U-values allowed for the vertical walls in case of building renovation (all values are in W∙m−2∙K−1) [23].
Climatic ZoneItalyGreeceRomania *
Zone A0.400.60-
Zone B0.400.50-
Zone C0.360.45-
Zone D0.320.40-
Zone E0.28--
Zone F0.26--
* In Romania, the recommended U-value for walls in the case of building renovation is U = 0.33 W∙m−2∙K−1, independently on the climatic zone.
Table 4. Building features used as input in the e-DSS.
Table 4. Building features used as input in the e-DSS.
ParameterValue
Year of construction1964
CoordinatesLat = 37.49°, long = 15.08°
AltitudeH = 7 m
Climatic zoneB
Number of dwellings10
Winter indoor set-point temperature θHEAT = 20 °C
Summer indoor set-point temperatureθCOOL = 26 °C
Number of floorsnfloors = 5
Number of heated floorsnheat = 5
Building heightHtot = 16.9 m
Gross surface of the ground floorSfloor = 231 m2
Heated net floor areaSnet = 940 m2
Window surface (N-E-S-W)Sw = 58.9 m2–11.7 m2–83.5 m2–11.7 m2
Overall net heated volumeVnet = 2630 m3
Overall gross heated volumeVg = 3454 m3
Color of the external finishMedium
U-value of the walls Uwall = 1.00 W∙m−2∙K−1
U-value of the windowsUw = 3.00 W∙m−2∙K−1
Existing roller shuttersWood or plastic
Shading devicesInner light curtains (fshade = 0.80)
Presence of balconiesNorth and south facades
U-value of the roofUroof = 1.30 W∙m−2∙K−1
Roof boundary conditionOutdoors (flat roof)
U-value of the floor slabUfloor = 0.64 W∙m−2∙K−1
Boundary condition for the floor slabBasement with no windows
Table 5. Monthly mean dry-bulb air temperature in Catania: comparison between UNI 10349-1:2016 (used by Blumatica) and PVGIS (used by the e-DSS).
Table 5. Monthly mean dry-bulb air temperature in Catania: comparison between UNI 10349-1:2016 (used by Blumatica) and PVGIS (used by the e-DSS).
MonthUNI 10349-1PVGIS (2023)Difference
January (heating season)11.9 °C11.0 °C−0.9 °C
February (heating season)10.4 °C10.5 °C+0.1 °C
March (heating season)11.8 °C13.4 °C+1.6 °C
April15.4 °C15.1 °C−0.3 °C
May18.8 °C18.0 °C−0.8 °C
June (cooling season)23.4 °C23.5 °C+0.1 °C
July (cooling season)25.8 °C29.6 °C+3.8 °C
August (cooling season)26.5 °C27.5 °C+1.0 °C
September (cooling season)22.9 °C24.8 °C+1.9 °C
October19.8 °C22.6 °C+2.8 °C
November15.1 °C17.2 °C+2.1 °C
December (heating season)12.3 °C12.9 °C+0.6 °C
Table 6. Comparison of some geometry-based parameters calculated in Blumatica and the e-DSS.
Table 6. Comparison of some geometry-based parameters calculated in Blumatica and the e-DSS.
ParameterUnitBlumaticae-DSSDifference
Overall heated envelope surface (Sd_tot)m21670.11638.6−1.9%
Gross dispersing volumem33501.03457.0−1.3%
Compactness ratio (S/V)m−10.4770.474−0.6%
Frame factor (FF)-0.720.7−2.8%
Transmission heat loss coefficient (H′T)
        Before renovationW∙m−2∙K−11.441.39−3.5%
        After renovationW∙m−2∙K−10.630.60−4.7%
Table 7. Heat gains and heat losses: comparison between the two tools in both seasons.
Table 7. Heat gains and heat losses: comparison between the two tools in both seasons.
Heating Demand (Winter)
ParameterBEFORE e-SAFE RenovationAFTER e-SAFE Renovation
Blumaticae-DSSΔBlumaticae-DSSΔ
QH41.0 MWh32.9 MWh−19.8%12.7 MWh14.0 MWh+10.5%
    QH_loss63.8 MWh59.8 MWh−6.3%31.6 MWh32.3 MWh+2.2%
    QH_gain24.2 MWh29.1 MWh+20.2%20.6 MWh19.8 MWh−3.9%
    ηH_gn0.9420.925−1.8%0.9170.922+0.5%
Cooling Demand (Summer)
ParameterBEFORE e-SAFE RenovationAFTER e-SAFE Renovation
Blumaticae-DSSΔBlumaticae-DSSΔ
QC23.2 MWh29.4 MWh+26.9%20.6 MWh17.5 MWh−14.8%
    QC_gain25.6 MWh26.5 MWh+3.5%23.7 MWh18.7 MWh−21.1%
    QC_loss2.4 MWh−2.9 MWh−218.4%3.1 MWh1.1 MWh−65.1%
    ηC_ls0.9910.996+0.1%0.9950.996-
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Evola, G.; Torrisi, M.; Costanzo, V.; Lazzaro, M.; Arnone, D.; Margani, G. A Decision Support Tool to Assess the Energy Renovation Performance Through a Timber-Based Solution for Concrete-Framed Buildings. Energies 2025, 18, 2839. https://doi.org/10.3390/en18112839

AMA Style

Evola G, Torrisi M, Costanzo V, Lazzaro M, Arnone D, Margani G. A Decision Support Tool to Assess the Energy Renovation Performance Through a Timber-Based Solution for Concrete-Framed Buildings. Energies. 2025; 18(11):2839. https://doi.org/10.3390/en18112839

Chicago/Turabian Style

Evola, Gianpiero, Michele Torrisi, Vincenzo Costanzo, Marilena Lazzaro, Diego Arnone, and Giuseppe Margani. 2025. "A Decision Support Tool to Assess the Energy Renovation Performance Through a Timber-Based Solution for Concrete-Framed Buildings" Energies 18, no. 11: 2839. https://doi.org/10.3390/en18112839

APA Style

Evola, G., Torrisi, M., Costanzo, V., Lazzaro, M., Arnone, D., & Margani, G. (2025). A Decision Support Tool to Assess the Energy Renovation Performance Through a Timber-Based Solution for Concrete-Framed Buildings. Energies, 18(11), 2839. https://doi.org/10.3390/en18112839

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop