Next Article in Journal
Evaluation of the Melting Gasification Process for Recovery of Energy and Resources from Automobile Shredder Residues
Next Article in Special Issue
Effectiveness of Large Soil Grain Sizes in Studying Impulse Characteristics of Soil
Previous Article in Journal
Energy Recovery from Waste—Closing the Municipal Loop
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Effect of Ground Electrodes on the Susceptibility to Damage of Customer Premises Equipment (CPE) under Impulse Conditions

by
Usman Muhammad
1,
Normiza Mohamad Nor
1,*,
Annuar Mohd Ramli
2 and
Nurul Nadia Ahmad
1
1
Faculty of Engineering, Multimedia University, Jalan Multimedia, Cyberjaya 63100, Malaysia
2
Fixed Infra Media Lab, Research & Innovation Development Division, TMRD Sdn. Bhd, TM Innovation Centre, Cyberjaya 63000, Malaysia
*
Author to whom correspondence should be addressed.
Energies 2022, 15(3), 1247; https://doi.org/10.3390/en15031247
Submission received: 27 December 2021 / Revised: 26 January 2022 / Accepted: 1 February 2022 / Published: 8 February 2022

Abstract

:
One of the requirements for the safe operation of customer premises equipment (CPE) is an adequate grounding system as a means to divert high fault currents to the ground. In this work we report on the results of an experimental study of the impulse characteristics at a charging voltage of 30 kV on the surge protective device connected to 16 earth electrodes and installed at two sites, giving various ground resistance at low voltages, RDC values. All of these grounding electrodes were installed and tested under the same charging voltage to determine the effectiveness of ground electrodes toward the damage of a modem at the premises. We observed that modems did not experience damage when the ground electrode of the distribution pole (DP) had an RDC below 30 Ω in general and below 46 Ω when ground electrodes installed in low resistivity soil were used. The impulse polarity did not affect the damage susceptibility of the CPE.

1. Introduction

A good grounding system is necessary to provide the path for a high magnitude of current to be discharged into the ground and to reduce the voltage rise in the vicinity of the grounding system subjected to high impulse. A good grounding system can be achieved by considering two major parameters: ground electrode and soil resistivity. As generally defined in many standards [1,2], a low ground resistance value RDC is required so that a high current can be effectively discharged to the ground, and the voltage rise can be reduced. In practice, however, it is sometimes challenging to obtain a low resistance value due to a limited availability of ground area, proximity to other facilities (substations, telecommunications poles, and buildings), high soil resistivity in some areas, and more usage of insulated cables, which can no longer be considered as part of grounding systems.
Using an EMTP, Hidaka et al. [3] demonstrated that the protection level for equipment of low voltage equipment with an RDC of 40 Ω (with the ground wire) is close to the performance of 30 Ω (without the ground wire). They further reasoned that 30 Ω is adequate for low voltage equipment, as regulated by the local company, but the ground wire can improve the performance to some extent. However, the study [3] was performed for a 6.6 kV distribution line and by the computational method.
Due to a limited study presence correlating the effectiveness of grounding systems with the performance of a telecommunication modem, and by experimental approach, this paper investigates the relationship of RDC with the voltage level of a modem that causes damage to telecommunication systems. Further, experimental work on the performance of the modem in a real application with various ground electrodes and its corresponding RDC has not been extensively presented before. Modems are normally tested and specified as in ITU-T K.21: Series K [4]; however, these standard methods of testing do not provide the condition in situ. Though it is recommended to have a low ground resistance value for the grounding facility, it can be challenging and difficult to achieve the required low resistance value. Furthermore, the suggested values proposed in the standard to be used as the grounding facility’s requirements, as a basis used in real engineering practice, (i.e., below 10 Ω) may not be realized in high resistivity soil. Commercial modems are designed and developed to pass the compliance tests performed in the laboratory. However, at real sites (customer premises), modems can be susceptible to factors, such as the various grounding at the DP and customer premises, resistive coupling [5], and effectiveness of the surge protective device.
This paper is a continuation of Ramli et al. [5]. In their studies, the test setup was carried out at a field site, where the source of lightning was from real events. Various magnitudes and responses of impulse conditions were seen, necessitating a longer period of study to ensure that adequate data were obtained for analysis. Furthermore, ground electrodes cannot easily be varied since the testing was carried out at the designated site of a telecommunication station where the areas were limited only to the specific site. For this reason, this paper attempted to determine the effective RDC value that was suitable and considered acceptable to be used along with the modem. This study would be useful to manufacturers with regards to enhancing the withstand levels of the modem and establishing whether there is a need to improve the grounding systems at the distribution box (DP) pole and at the customer’s premises. This paper focuses on the effect of the ground electrodes at the DP, where the effective RDC values from this study can be applied as a basis of grounding systems for modems. By having various ground electrodes at the DP, the susceptibility of the modem to various ground resistance values RDC to the transient can be determined. Impulse tests were carried out on various ground electrodes that were installed at two sites and connected to the modem, where the ground resistance value RDC that will not cause damage to the modem was determined. It was revealed that a modem was susceptible to damage by the ground electrodes at an RDC value of above 30 Ω in general and above 46 Ω for the ground electrodes installed in low resistivity soil.
Impulse polarity has been known to cause different performances of grounding systems [6,7], and many pieces of electrical equipment [8,9] with higher negative impulse voltage levels have caused a breakdown of the soil. Due to the complexities of the electric field distribution, physical shapes of electrical equipment, as well as various grain sizes, soil density, inhomogeneity of soil resistivity, and soil composition, the impulse polarity effect may not be that observable in some studies [6,7], a fact which leads to inconsistent results from one study to another. Due to differences in the findings of impulse polarity effects in several studies, it is important to determine the voltage level that causes damage to the modems when subjected to both impulse polarities. Ultimately, in this paper, impulse polarity was found to have no effect on the resistance of CPE toward damage. This paper contributes to the proposed ground resistance value that is suitable to be used at the DP, which will not cause damage to the CPE.

2. Test Arrangement

2.1. Impulse Test Equipment

Figure 1 shows the test setup used, where a combination impulse generator that can generate 1.2/50 μs from the magnitudes of 30 kV to 300 kV. A current rating of 10 kA was used, which was injected into the distribution pole (DP) box. The cable that entered the DP box was the paired cable, and the one that went out from the box was the drop wire; these cables were based on ANSI/TIA/EIA 568-B [10]. Inside the DP box, a gas surge arrester was used to divert the high current to the ground during overvoltages; the gas surge arrester was connected to several ground electrodes, defined as ground electrodes for the DP. The details of its configurations and ground resistance RDC values are listed in Section 2.2. A voltage divider with a ratio of 3890:1 and a current transformer 1 of 0.01 V/A were used for the measurement of the applied voltage and current of the ground electrode. The signals of voltage and current were obtained with a digital storage oscilloscope (DSO).
From the DP, via drop wires, the DPwas connected to the modem where the voltage and current of the modem were measured with divider, HV2 with a ratio of 1000:1 and a current transformer with 0.1 V/A sensitivity, where both measurements were captured by the DSO. In order to replicate the condition and connection of the modem at the premises, a diesel generator was used to set the modem to ‘ON’ mode, and the neutral part of the power adapter was connected to the ground electrode, which in this case was a single rod electrode. The power adapter used for the modem in this work was the earth pin made of plastic to ensure any high voltage or current would be discharged to the ground electrode of the power adapter via a neutral cable, which was a typical TT ground systems used in Malaysia, as outlined in [11].
Current transformer 3 measured the current that flowed to the ground through the utility’s ground installation. Figure 1 shows the test setup used in the study. Because we expected various modems to have different susceptibility levels toward lightning, one type/brand of modem was used throughout the tests, and the modem was replaced with a new one after every test was carried out. The lowest charging voltage that was capable of generating this impulse generator was 30 kV injected into the paired cables before the DP. It should be noted that there was no direct connection from the ground of one equipment piece to another (i.e., the ground for the DP was not connected to the ground of the power adapter and remote earth).

2.2. Testing Sites

Ground electrodes were installed at two different sites. Wenner method was applied to determine soil resistivity, and CDEGS was used to interpret the soil into 2-layer soil models. Table 1 summarizes the soil resistivity profiles for these two sites, in which site 2 had lower soil resistivity than site 3. Site 2 was split into 2a and 2b where two groups of electrodes were placed 50 m apart from each other.

2.3. Ground Electrodes

Sixteen ground electrodes under tests were used and installed at sites 1, 2a, and 2b, where these ground electrodes were labelled DP earth. Table 2 summarizes the ground electrodes used, in which 6 of these configurations were similar to that presented in [5], with the rod electrode configuration being as follows: (a) at 1.5 m length, with 16 mm diameter rod; (b) the rod electrode (a) connected by copper plate, of 2 cm width, 0.2 mm thickness, and 3 m length; and (c) was the rod electrode (b), connected to another rod electrode with 3 m copper plate. Configurations (d), (e), and (f), consisted of a grounding device with spike rods (GDSR), with dimensions shown in Table 2 in configuration (d). Configuration (e) consisted of configuration (d) connected to a single rod electrode (a), and configuration (f) with a GDSR, connected to two rod electrodes, with 3 m copper plate from one rod to another. All of these electrodes were installed 30 cm below the ground’s surface. At site 2, four other electrodes were used, placed 50 m away from the six configurations installed earlier, with two electrodes in similar configuration to (a) and (d), while the other two configurations (g) consisted of configuration (a) connected to 2 m × 2 m ground electrode, and configuration (h) consisted of configuration (d) connected to the 2 m × 2 m ground electrode. The same copper plate, with the width of 2 cm, thickness of 0.2 mm, and length of 3 m was used in the test to provide connection to the mesh.
The Fall-of-Potential (FoP) method was performed to determine its RDC values, which are also presented in Table 2. As seen and expected, the larger the size of the ground electrodes (configurations (c) and (f)), the lower the RDC values were. Though the soil resistivity of the upper layer for site 2 was lower, high RDC values were seen for ground electrodes installed at site 2a, in comparison to site 1, with the same configurations. This could be due to a shallower depth of site 2, below 2 m, where the electrodes may also be influenced by the higher soil resistivity of the lower layer at site 2. On the other hand, the electrodes installed at site 1 were only in contact with and influenced by the upper layer of soil resistivity, due to a higher depth of the upper layer of more than 10 m. We also noticed that that the difference in RDC values became smaller in electrodes with low RDC values, i.e., the difference in RDC values of configurations (a) and (d) installed at site 2b was more than 30%, while the difference in RDC values between configurations (g) and (h) was less than 15%. This finding was similar to that published in several standards [1,9]; the lower the ground resistance RDC value, the less pronounced the reduction in RDC values expected to be present. Another ground electrode for the neutral pin of the power adapter that was connected to a single rod electrode had RDC values that were measured as 625 Ω for site 1 and 913 Ω for sites 2a and 2b. In the case of a high current that may occur during the test, the ground terminal of the impulse generator was connected to 20 m × 30 m grid, having an RDC of 8 Ω to provide the path for any high current that may have occurred during the tests.

3. Test Results

3.1. Measurements from Voltage Divider 1 and Current Transformer 1

The measurement from the voltage divider 1 was taken to represent the applied voltage, while the current transformer 1 was the current that flowed to the DP’s ground. Figure 2 shows the voltage applied to the DP. As stated in Section 2.1, the voltage applied to the gas surge arrester, while the current trace of Figure 2 was measured as the current that flowed to the ground at the DP, indicated the DP earth of various configurations in Figure 1. Similar traces were seen for other ground electrode configurations and impulse polarity, except for some changes in the magnitudes of voltage and current, depending on the ground electrode’s performance. The Figure shows fast rise times of voltage and current traces, and the current signal follows the voltage signal on both front and decay times, indicating a predominantly resistive behavior of the ground electrode. Throughout the course of the test, it was difficult to achieve the desired charging voltage of 30 kV when the tests were performed on configurations (b) and (c) installed at site 1, and configuration (b) installed at site 2, under negative impulse polarity, despite the fact that several attempts were made. When charging voltage levels were increased under negative impulse polarity on these configurations, higher than 30 kV, triggering in the impulse generator was achieved. It is thought that the non-achieved charging voltage at 30 kV, for negative impulse polarity could be due to a higher voltage to cause a breakdown in the spark gap of the impulse generator under negative impulse polarity, which was a typical observation in the breakdown of the air gap, whereby a higher voltage was needed to cause a breakdown for negative rather than positive impulse polarity, as described in [8]. For other sites, the triggering was achieved at 30 kV under negative impulse polarity, which could be due to probabilistic characteristics of the air breakdown of the spark gap, especially the tests carried out in situ, where uncontrollable atmospheric pressure and surrounding conditions could happen.
From the voltage and current plots, impulse impedance values were measured by dividing the peak voltage by the peak current, V p e a k / I p e a k . Table 3 shows the impulse impedance Zimp values in comparison to their corresponding RDC for each ground electrode and for both impulse polarities. The Table illustrates that the Zimp values are always lower than that of the corresponding RDC values for both impulse polarities. The percentage difference between the RDC and Zimp values was measured by taking the difference between RDC and Zimp and dividing it by RDC, and the resultant was multiplied by a hundred percent. We observed that generally the higher the RDC, the higher the percentage difference was between RDC and Zimp. This finding is similar to that found in several publications [6,7], Refs.[12,13] whereby the degree of reduction is dependent on the RDC values. This is thought to be due to the dependency of the electric field E on the soil resistivity ρ, and the current density J, where J is in general a division of current I to the cross-sectional area A, as defined in Equation (1). As generally known, the non-linearity in impulse impedance, where a reduction in RDC to impulse impedance Zimpulse would occur if the electric field E were higher than the critical electric field Ec. For a high RDC, the ground electrodes may have been installed in high ρ, have a low A, or have both conditions, which would cause a rise in the electric field value E, exceeding the Ec. Due to this, a higher rate of non-linearity, which causes a higher percentage of reduction in impulse impedance from RDC, would be exhibited for ground electrodes with a high RDC. Another reason could be due to larger air voids for soil in high soil resistivity in comparison to low soil resistivity where the air voids may have filled up with water, and the soil is more compacted. Hence, more discharges might have occurred in high soil resistivity (high RDC) in comparison to low soil resistivity (low RDC), causing a significant reduction in impulse impedance from its RDC in high soil resistivity (high RDC).
In this study, it was established that the percentage difference between Zimp and RDC was not affected by the impulse polarity
E = ρ J

3.2. Measurements from Voltage Divider 2 and Current Transformers 2 and 3

In this study, the voltage divider 2 was used to measure the voltage applied on the modem, while the current transformer 2 was applied to measure the current that flowed through the modem, as shown in Figure 3a,b, respectively, for voltage and current traces for configuration (h), installed at site 2b under positive impulse polarity. It can be seen from both Figures that the traces had fast rise times and were found to be rather distorted. These traces were for the condition of no damage to the modem, i.e., the modems were found to be in good working condition after the tests were carried out. On the other hand, higher voltage and current traces were observed for the case of damage to the modems, shown in Figure 4a,b for voltage and current traces, respectively. As can be seen in the Figure, a collapse of voltage was seen in Figure 4a with oscillations, which were followed by a slight increase in the current magnitudes, indicated in the corresponding Figure 5a. A sudden voltage drop followed by an increase in current is a typical indication of equipment breakdown when high voltage tests are carried out on it, as discussed in [9]. Oscillations in the voltage trace could be due to harmonics that may be present due to pre-discharges within the test circuit in the modem.
Despite the fact that new modems were used for every test, it was noted that voltage and current traces produced from the voltage divider and current transformer were of many shapes; they were found to be different not only in various ground electrodes, but also in both impulse polarities for the same ground electrodes. This could be due to many components in the modems that affected the way that the currents and voltage went through them, and the damage may have been caused by the failure that occurred in different components from one test to another.
Current transformer 3 measured the current flows through the power adapter, where the typical current trace was shown in Figure 5a,b, respectively, for the case of no damage and damage to the modems. The current traces were, however, found to be different in shape and magnitude for different configurations and impulse polarity; some had current traces that flowed to the ground of the modem that was found to be zero. Table 4 summarises the voltage and current magnitudes of the modem and the condition of the modem post-tests. In correlating the RDC values of the ground electrode with the damage to the modem, it can be seen that the damage to the modem occurred in the ground electrode with an RDC value below 30 Ω in high resistivity soil (site 2), while a higher RDC value was seen in low resistivity soil (site 2a), and no damage was seen for the ground electrode with an RDC value below 46 Ω.
We also noticed no damage to the modem if any of the three conditions were fulfilled: (i) voltage at the modem was below 15 kV, and the current magnitude was below 35 A; (ii) voltage at the modem was higher than15 kV (i.e., configuration (f) installed at site 1), but the current was below 5 A; and (iii) higher current magnitudes, more than 35 A (i.e., configuration (f) installed at site 2b), the voltage at the modem must be low enough, no more than 2 kV. Other than these three conditions, damage to the modems was present. We also detected no observable factor in terms of impulse polarity. Despite the fact that only one modem was tested for each test, and the damage to the modem could be probabilistic, it was still clear that more modems experienced damage to the ground electrodes installed at sites 2a,b, which had higher RDC values than that in site 1. Higher magnitudes of current were noticed flowing through the modem, reaching hundreds of amperes in some modems. High current magnitudes were also seen going through the power adapter, which can pose a danger to the modem users. This shows the importance of considering ground electrodes with low RDC values at the distribution pole, at the customer’s premises, or utility to avoid any modem damage on site.

4. Conclusions

An investigation of the damage to a modem with a different RDC was conducted at a charging voltage of 30 kV. There was no specific trend found on the dependency of the damage to the modem in terms of impulse polarity. This is thought to be due to the low voltage level used, which was only 30 kV and made the impulse polarity effect not that observable. When impulse tests with a voltage level of 30 kV were carried out on 16 ground electrodes connected to the distribution poles, modems, and adapters, we noticed that no damage occurred on the modem in the event of any of these three observations: (i) voltage at the modem was less than 15 kV, and the current that flowed through it was less than 35 A; (ii) voltage on the modem was higher than 15 kV, but the current was below 5 A; and (iii) for the case of a high current at the modem, the voltage had to be low enough, below 2 kV. We also observed that the current that flowed through the power adapter could reach more than 20 A, which in real application and practice, can cause tripping in the premises and pose a danger to the users. We expected it to be difficult to consider these three conditions for damage to the modems and safety considerations for the users, since testing and taking high voltage measurements are not common. For this reason, the basis of the adequacy of the grounding system at the premises is evident in this paper. In order to avoid damage to the modems and provide safety to current-sensitive equipment at the premises, it is important to consider having the grounding systems at the DP below 30 Ω in general and lower than 46 Ω if the ground electrode is installed and in contact with soil with a low resistivity value below 100 Ωm. This study is anticipated to raise awareness to users and telecommunication companies and even more so toward the design innovation of modem susceptibility, with the grounding systems at the DP in mind and at the customers’ premises. High magnitudes of current were observed at the modem, and the power adapter provided valuable information to the users and was useful in improving the ground resistance value and avoiding contact with modems during severe weather conditions. Furthermore, this study presents an integral suggestion that surge protective devices should be used alongside modems and other current-sensitive devices at the premises in order to avoid functional and structural damage to the CPE.

Author Contributions

Conceptualization, N.M.N. and A.M.R.; methodology, N.M.N. and A.M.R.; validation, N.M.N. and A.M.R.; formal analysis, N.M.N.; investigation, N.M.N. and A.M.R.; resources, N.N.A.; data curation, U.M.; writing—original draft preparation, U.M.; writing—review and editing, N.M.N.; visualization, N.M.N.; supervision, N.M.N. and N.N.A.; project administration N.M.N. and N.N.A.; funding acquisition, N.M.N. and N.N.A. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by TELEKOM MALAYSIA RESEARCH AND DEVELOPMENT (TMR&D) with the grant numbers MMUE190085 and MMUE210072 and the MINISTRY OF HIGHER EDUCATION (MOHE) on the Fundamental Research Grant Scheme (FRGS) with the grant number FRGS/1/2021/TK0/MMU/02/8.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. IEEE. IEEE Guide for Safety in AC Substation Grounding; Std 80-2013; IEEE: Piscataway, NJ, USA, 2013. [Google Scholar]
  2. International Telecommunication Union (ITU) Standard. SERIES K: Protection of Customer Premises from Overvoltages; K. 66; ITU-T: Geneva, Switzerland, 2019. [Google Scholar]
  3. Hidaka, T.; Ishimoto, K.; Asakawa, A.; Shiota, K. Relationship between Grounding Resistance Connected to Surge Arresters and Lightning Surge Behavior Observed in Low-Voltage Equipment. In Proceedings of the International Symposium on Lightning Protection (XII SIPDA), Belo Horizonte, Brazil, 7–11 October 2013. [Google Scholar]
  4. ITU-T. Series K: Protection Against Interference, Resistibility of Telecommunication Equipment Installed in Customer Premises to Overvoltages and Overcurrents; K.21; ITU-T: Geneva, Switzerland, 2019. [Google Scholar]
  5. Ramli, A.; Jamlus, N.; Ibrahim, A.; Amiruddin, F. Resistive Coupling Effect to Customer Premises Equipment (CPE) due to Non-Equipotential Earthing System. In Proceedings of the IEEE International Conference on High Voltage Engineering and Application (ICHVE), Athens, Greece, 10–13 September 2018. [Google Scholar]
  6. Abdul Ali, A.; Ahmad, N.; Mohamad Nor, N.; Reffin, M.; Syed Abdullah, S. Investigations on the Performance of a New Grounding Device with Spike Rods under High Magnitude Current Conditions. Energies 2019, 12, 1138. [Google Scholar] [CrossRef] [Green Version]
  7. Abdul Ali, A.; Ahmad, N.; Mohamad Nor, N. Effect of Impulse Polarity on a New Grounding Device with Spike Rods (GDSR). Energies 2020, 13, 4672. [Google Scholar] [CrossRef]
  8. Lundgaard, L.; Linhjell, D.; Berg, G. Propagation of Positive and Negative Streamers in Oil with and without Pressboard Interfaces. IEEE Trans. Dielectr. Electr. Insul. 1998, 5, 388–395. [Google Scholar] [CrossRef]
  9. Kuffel, E.; Zaengl, W.S.; Kuffel, J. High Voltage Engineering: Fundamentals; Butterworth-Heinemann: New Delhi, India, 2000. [Google Scholar]
  10. ANSI/TIA/EIA 568-B: Commercial Building Telecommunications Cabling Standard; Cablingdb: Hochiminh City, Vietnam, 2015.
  11. BS7430-2011: Code of Practice for Protective Earthing of Electrical Installations; British Standards Institution: London, UK, 2011.
  12. Sekioka, S. Frequency and Current-Dependent Grounding Resistance Model for Lightning Surge Analysis. IEEE Trans. Electromagn. Compat. 2018, 61, 419–425. [Google Scholar] [CrossRef]
  13. Harid, N.; Griffiths, H.; Mousa, S.; Clark, D.; Robson, S.; Haddad, A. On the Analysis of Impulse Test Results on Grounding Systems. IEEE Trans. Ind. Appl. 2015, 51, 5324–5334. [Google Scholar] [CrossRef]
Figure 1. Test arrangement used in the study.
Figure 1. Test arrangement used in the study.
Energies 15 01247 g001
Figure 2. Voltage and current traces, measured with voltage divider 1 and current transformer 1, respectively, for configuration (f) installed at site 1.
Figure 2. Voltage and current traces, measured with voltage divider 1 and current transformer 1, respectively, for configuration (f) installed at site 1.
Energies 15 01247 g002
Figure 3. Measured traces on the modem for the case of no damage to the modem for configuration (h) installed at site 2b (a) Voltage trace measured with voltage probe 2 (x scale is 10 μs/div, and y scale is 5 kV/div); (b) Current flows through the modem, measured with current transformer (CT) 2 (x scale is 10 μs/div, and y scale is 5 kV/div, and the voltage magnitude is multiplied by 10, since the CT used had a sensitivity of 0.1 V/A).
Figure 3. Measured traces on the modem for the case of no damage to the modem for configuration (h) installed at site 2b (a) Voltage trace measured with voltage probe 2 (x scale is 10 μs/div, and y scale is 5 kV/div); (b) Current flows through the modem, measured with current transformer (CT) 2 (x scale is 10 μs/div, and y scale is 5 kV/div, and the voltage magnitude is multiplied by 10, since the CT used had a sensitivity of 0.1 V/A).
Energies 15 01247 g003
Figure 4. Measured traces on the modem for the case of damage to the modem for configuration (d), installed at site 2b (a) Voltage trace measured with voltage divider 2 (x scale is 10 μs/div, and y scale is 5 kV/div); (b) Current flows through the modem, measured with current transformer (CT) 2 (x scale is 10 μs/div, and y scale is 5 kV/div, and the voltage magnitude is multiplied by 10, since the CT used had a sensitivity of 0.1 V/A).
Figure 4. Measured traces on the modem for the case of damage to the modem for configuration (d), installed at site 2b (a) Voltage trace measured with voltage divider 2 (x scale is 10 μs/div, and y scale is 5 kV/div); (b) Current flows through the modem, measured with current transformer (CT) 2 (x scale is 10 μs/div, and y scale is 5 kV/div, and the voltage magnitude is multiplied by 10, since the CT used had a sensitivity of 0.1 V/A).
Energies 15 01247 g004
Figure 5. Current flows through the power adapter, measured with current transformer (CT) 3 (a) Configuration (b) installed at site 1, for the case of no damage to the modem; (b) Configuration (a) installed at site 2, for the case of damage to the modem.
Figure 5. Current flows through the power adapter, measured with current transformer (CT) 3 (a) Configuration (b) installed at site 1, for the case of no damage to the modem; (b) Configuration (a) installed at site 2, for the case of damage to the modem.
Energies 15 01247 g005
Table 1. Soil resistivity profiles of testing sites.
Table 1. Soil resistivity profiles of testing sites.
SiteUpper Layer Soil ResistivityLower Layer Soil ResistivityHeight of Upper Layer (m)Height of Lower Layer (m)
184.9689212.54Inf
2a and 2b78.41126.361.84Inf
Table 2. Configurations of ground electrodes and their corresponding RDC values.
Table 2. Configurations of ground electrodes and their corresponding RDC values.
ConfigurationRDC Values (Ω)
Site 1Site 2aSite 2b
Energies 15 01247 i001
(a) Single rod electrode
46.0150.8103.1
Energies 15 01247 i002
(b) 2-rod electrode
30.978.7
Energies 15 01247 i003
(c) 3-rod electrode
14.342.2
Energies 15 01247 i004
(d) Grounding devices with spike rods (GDSR)
31.488.569.1
Energies 15 01247 i005
(e) GDSR with single rod electrode
19.249.8
Energies 15 01247 i006
(f) GDSR with 2-rod electrodes
14.234.6
Energies 15 01247 i007
(g) 2 m × 2 m electrode with single rod electrode
39.7
Energies 15 01247 i008
(h) 2 m × 2 m electrode with GDSR
34.2
Table 3. RDC, Zimp, and percentage difference between RDC and Zimp.
Table 3. RDC, Zimp, and percentage difference between RDC and Zimp.
Conf.RDC (Ω)Impulse Impedance Values (Ω)Percentage Difference Between RDC
and Zimpulse (%)
Site 1Site 2aSite 2bSite 1Site 2aSite 2bSite 1Site 2aSite 2b
++++++
(a)46150.8103.113.513.424.625.438.570.6570.8783.6983.1662.66
(b)30.978.7 8.2*16.9* 73.46*78.53*
(c)14.342.2 5.7*11.111.5 60.14*73.772.75
(d)31.488.569.112.212.822.119.620.8261.1559.2475.0377.8569.9
(e)19.249.8 8.88.115.314.4 54.1757.8169.2871.08
(f)14.234.6 6.36.410.810.6 55.6354.9368.7969.36
(g) 39.7 12.97 67.33
(h) 34.2 15.2 55.56
* Charging voltage at 30 kV is not achieved. Energies 15 01247 i009 No damage to the modem is observed.
Table 4. Voltage and current magnitudes and the condition of the modem for various ground electrodes.
Table 4. Voltage and current magnitudes and the condition of the modem for various ground electrodes.
Site/ Conf./RDC Values Impulse PolarityVoltage on the Modem, V2 (kV)Current through the Modem, CT2 (A)Condition of the Modem after the TestsCurrent on the Power Adapter, CT3 (A)Condition Fulfilment
Site 1 (a), 46 ΩPositive828Working26.4Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
Negative−8−33.6Working−34.4Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
Site 1 (b), 30.9 Ω Positive14.820Working22.4Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A
NegativeNo triggering achieved at 30 kV
Site 1 (c), 14.3 ΩPositive1320Working0Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
NegativeNo triggering achieved at 30 kV
Site 1 (d), 31.4 ΩPositive460Damaged24.4Not fulfilling any of the three conditions
Negative−16.4−62.4Damaged−28.4Not fulfilling any of the three conditions
Site 1 (e), 19.2 ΩPositive13.21.6Working0Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
Negative−13.2−23.2Working−25.2Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
Site 1 (f), 14.2 ΩPositive121.6Working0Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
Negative−16−3.6Working0(ii) voltage on the modem is higher than15 kV, but the current is below 5 A.
Site 2a (a), 150.8 Ω Positive6.2244Damaged30Not fulfilling any of the three conditions
Negative−7.2−236Damaged−38Not fulfilling any of the three conditions
Site 2a (b), 78.7 ΩPositive153640Damaged0Not fulfilling any of the three conditions
NegativeNo triggering achieved at 30 kV
Site 2a (c), 42.2 ΩPositive1223Working23Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
Negative−14.4−22.4Working0Fulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
Site 2a (d), 88.5 ΩPositive5200Damaged25Not fulfilling any of the three conditions
Negative−16−40Damaged−42Not fulfilling any of the three conditions
Site 2a (e), 49.8 ΩPositive14220Damaged28Not fulfilling any of the three conditions
Negative−14−308Damaged−28Not fulfilling any of the three conditions
Site 2a (f), 34.6 ΩPositive580Damaged20Not fulfilling any of the three conditions
Negative−2−126.4Working−26Fulfilling condition (iii) higher current magnitudes, more than 35 A, but the voltage at the modem is not more than 2 kV
Site 2b (a), 103.1 ΩPositive17.20DamagedNot measuredNot fulfilling any of the three conditions
Site 2b (d), 69.1 ΩPositive17.30DamagedNot measuredNot fulfilling any of the three conditions
Site 2b (g), 39.7 ΩPositive16.70DamagedNot measuredNot fulfilling any of the three conditions
Site 2b (h), 34.2 ΩPositive14.30WorkingNot measuredFulfilling condition (i) voltage at the modem is below 15 kV, and the current magnitudes is below 35 A.
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Muhammad, U.; Mohamad Nor, N.; Ramli, A.M.; Ahmad, N.N. Effect of Ground Electrodes on the Susceptibility to Damage of Customer Premises Equipment (CPE) under Impulse Conditions. Energies 2022, 15, 1247. https://doi.org/10.3390/en15031247

AMA Style

Muhammad U, Mohamad Nor N, Ramli AM, Ahmad NN. Effect of Ground Electrodes on the Susceptibility to Damage of Customer Premises Equipment (CPE) under Impulse Conditions. Energies. 2022; 15(3):1247. https://doi.org/10.3390/en15031247

Chicago/Turabian Style

Muhammad, Usman, Normiza Mohamad Nor, Annuar Mohd Ramli, and Nurul Nadia Ahmad. 2022. "Effect of Ground Electrodes on the Susceptibility to Damage of Customer Premises Equipment (CPE) under Impulse Conditions" Energies 15, no. 3: 1247. https://doi.org/10.3390/en15031247

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop