PV Systems Control Using Fuzzy Logic Controller Employing Dynamic Safety Margin under Normal and Partial Shading Conditions

1
Department of Electrical Engineering, The School of Industrial, Aerospace and Audiovisual Engineering of Terrassa (ESEIAAT), Polytechnic University of Catalonia, 08222 Barcelona, Spain
2
Electrical and Control Engineering Department, College of Engineering & Technology, Arab Academy for Science, Technology and Maritime Transport (AASTMT), Alexandria 1029, Egypt
3
Key Laboratory of More Electric Aircraft Technology of Zhejiang Province, University of Nottingham, Ningbo 315100, China
*
Author to whom correspondence should be addressed.
Energies 2021, 14(4), 841; https://doi.org/10.3390/en14040841
Submission received: 28 October 2020 / Revised: 14 January 2021 / Accepted: 15 January 2021 / Published: 5 February 2021
(This article belongs to the Section A1: Smart Grids and Microgrids)

Abstract

:
Because of the unpredictable activity of solar energy sources, photovoltaic (PV) maximum power point tracking (MPPT) is essential to guarantee the continuous operation of electrical energy generation at optimal power levels. Several works have extensively examined the generation of the maximum power from the PV systems under normal and shading conditions. The fuzzy logic control (FLC) method is one of the effective MPPT techniques, but it needs to be adapted to work in partial shading conditions. The current paper presents the FLC-based on dynamic safety margin (DSM) as an MPPT technique for a PV system to overcome the limitations of FLC in shading conditions. The DSM is a performance index that measures the system state deviation from the normal situation. As a performance index, DSM is used to adapt the FLC controller output to rapidly reach the global maxima of the PV system. The ability of the proposed algorithm and its performance are evaluated using simulation and practical implementation results for single phase grid-connected PV system under normal and partial shading operating conditions.

1. Introduction

The main two factors motivating energy demand are the population and financial growth. The growing demand for energy and the environmental impact of fossil fuels has increased the need for clean and renewable energy sources. In the last decade, solar energy technologies have become less expensive and more efficient. Moreover, it is a more environmentally friendly energy source than traditional ones like fossil fuels, coal, and nuclear energy. Therefore, the share of photovoltaic (PV) systems among other renewable energy sources has increased. The PV system can be connected directly as a stand-alone system to the load or indirectly as a grid-connected PV system via the electric grid. The grid-connected system is preferable in the presence of multiple sources of electric energy [1,2]. Since the PV system’s output power depends primarily on environmental conditions, in particular irradiation and temperature, the PV system requires a maximum power point tracking (MPPT) controller to maintain the service at the global maxima [3,4], such that the maximum output power can always be delivered by the PV system.
During normal weather conditions, the PV system has only one global maximum, which the MPPT controller tries to follow, whereas the PV system in partial shading has multi-maximum points, local and global peaks. Hence, if the MPPT controller is not sufficiently resilient, the MPPT may struggle to locate the real maximum point and be stuck at a local maximum [5]. In this circumstance, the PV system’s output power would be significantly decreased. This can take place due to a passing cloud, obstructions caused by tall buildings, trees, poles, towers, etc., or even damage to one or more modules in the PV array [6,7]. A shunt-connected bypass diode is used to protect the module from hot-spot damage when a section of the PV module is shaded. However, by using this diode, the output power is decreased greatly, since the power produced from the shaded module is quite unusable. Furthermore, conduction losses occur as the current passes through the bypass diode which can contribute to a further deterioration in device performance [8,9].
Different MPPT techniques and algorithms of PV under partial shading conditions are scattered throughout the literature. They can be classified into new MPPT optimization algorithms, hybrid algorithms, modeling techniques, and converter topologies [10]. The proposed work belongs to the MPPT algorithm type rather than the modeling and converter topologies. Various MPPT algorithms are implemented in the literature. Some of these algorithms employ artificial intelligence (AI) methods such as fuzzy logic controller (FLC) [11,12], artificial neural networks, and neuro-fuzzy algorithms [13]. Most of them depend on a power-voltage (P-V) scan of the PV and store the state at each observed shading condition. Other methods such as partial swarm optimization (PSO) [14,15], Harris hawk optimization [16], bat algorithm [17], or implementing soft computing optimization techniques [10,18] have been proposed before. The main limitations of these techniques are their computational complexity, initial condition dependency, cost, and slow tracking. They may also cause voltage and MPP oscillations.
The MPPT controller based on FLC is a successful and robust algorithm to work with different weather conditions [11,12], mainly for its fast response under rapid changes, which makes it a good tool to avoid the conventional MPPT problems such as oscillations around the MPP. However, MPPT controllers based on FLC sometimes fail to track the global maxima under shaded conditions. Thus, modified FLC algorithms have been presented in the literature. An integration of FLC with differential flatness control is introduced in [19] and compared with PSO. An adaptive neuro-fuzzy system-based MPPT is implemented in [13]. Both techniques depend on P-V scan methods and require more time to attain a stable maximum operating point. A type-2 FLC-based MPPT under partial shading is suggested in [20]. In this technique, the fuzzy membership function is asymmetrical, and each membership has lower and upper boundaries to overcome the uncertainties of generated power due to the shading. The main difficulty of this technique is how to deduce the type-2 membership function. Moreover, most of these techniques are complex with a high computational burden. In addition, they apply a P-V scan technique which interrupts the delivered power during the scanning and affects the grid stability.
The adaptation of FLC for MPPT is also addressed in [21] by adjusting the FLC output based on the deviation of the PV voltage and nominal open circuit voltage, VOC. This technique is simple and robust, but it fails in some situations to work effectively under partial shading. Hence, the main target of this paper is to design and implement an adaptive FLC technique based on other criteria to work probably in partial shading conditions and overcome the limitation of other FLC-based MPPT.
An adaptive FLC based on a performance index called the dynamic safety margin (DSM) is proposed. The DSM based controller has the advantage to sustain a specified safety margin during transient and disturbance behaviors [22,23]. Moreover, it can greatly aid the performance recovery in some situations of operational deviation. The safety region of the PV is chosen to contain all the possible maximum operating points at different weather conditions without shading. This means that once the safe operation region has been determined, the monitoring operating point with respect to the safe region indicates the abnormal behavior either due to shading or malfunction. The deviation of the operating points from the safe operation region is used as a performance index to evaluate how far the operation mode from the normal behavior is and to adapt the MPPT controller to track the global maximum. Therefore, the contributions of this article are summarized as: (1) determine the safe operating region of the PV system and calculate DSM; (2) design an adaptive FLC based on DSM as a robust MPPT controller to overcome the shading conditions of a grid-connected PV system, and (3) implement the proposed technique on a single-phase multi-stage grid-connected system as a case study.
The partial shading effect on the PV model will be illustrated in Section 2. The proposed MPPT technique is explained in Section 3 and the case study description and configuration are illustrated in Section 4. The analysis of the simulation results and the experimental verification of the proposed system are carried out in Section 5 and Section 6, respectively. The conclusions are presented in Section 7.

2. Partial Shading Mode

Two groups of PV cells linked in series within a module could model a partially shaded module. Different levels of irradiance are received by each group. The module consists of r series-connected cells, in which s shaded cells receive irradiance G1, and (r − s) shaded cells receiving irradiance G2. The PV parameters can be represented as (1)–(4) [8,9]:
I ph 1 = I ph G 1
I ph 2 = I ph G 2
N s 1 = s
N s 2 = r s
where the subscripts 1 and 2 refer to the cells receiving irradiance of G1 and G2 respectively, Iph is the solar-generated current. Considering the existence of a single bypass diode for each PV module, the output current and voltage at the array terminal can be obtained by solving the following Equations (5) and (6):
I PV = I Ph G 1 I o 1 exp q V PVm 1 + I PV   R s N s 1 AK T k 1 V PVm 1 + I PV   R s   N s 1 R P N s 1 I PV > I Ph 1 I Ph G 2 I o 1 exp q V PVm 2 + I PV   R s N s 2 AK T k 1 V PVm 2 + I PV   R s   N s 2 R P N s 2 I PV > I Ph 2
V PV = V PV 1 I PV > I Ph 1 V PV 2 + V PV 1 I PV < I Ph 2
where A is the diode ideality factor, G is the operating irradiance level (W/m2), K is the Boltzmann constant, Gr is the nominal irradiance level (W/m2), Ns is the number of series-connected cells, Tk is the operating temperature (K), VPV is the output voltage, Io1 is the diode saturation current, VPVm is the PV module output voltage, IPV is the PV output current and Rs is the series-connected resistance. During partial shading, a segment of the PV cells, which obtains uniform irradiance, still perform at the optimum efficiency. Although the current flow is naturally constant through each cell in a series configuration, the shaded cells need to perform with a reverse bias voltage to provide a current such as the illumined cells. However, the resulting polarity of the reverse power contributes to power consumption and the decrease in the maximum output power of the partially shaded PV module.
It is important to realize that the features of a bypass diode array vary from the one without such diodes, as the bypass diodes provide an alternate current path during the shaded mode. The cells of a module no longer carry the same current. Therefore, different maxima are established by the P-V curve. It is a crucial issue to present multiple maximum points in the PV characteristics, and most conventional MPPT algorithms may not differentiate between local and global maximum points. Figure 1 outlines the circuit diagram of a PV array consisting of two modules with series connected bypass diodes.
The simulation results of the two series modules of KC200GT type (KYOCERA, Kyoto, Japan) at normal and shading conditions are shown in Figure 2. The PV module parameters at nominal conditions (1000 W/m2 and 25 °C) are: PV power is 200 W, PV voltage is 26.3 V, and PV current is 7.8 A. Furthermore, module 1 has nominal irradiation (1000 W/m2) while the second module has shading, and its irradiation is 800 W/m2. The system has two maxima operating points. Thus, the MPPT algorithm must operate the PV at the global peak. More investigation on different modules and shading conditions will be illustrated in Section 3.

3. The Proposed MPPT Algorithm

Different algorithms have been used to overcome the partial shading problem of the PV systems as discussed in the Introduction. Most of these techniques are complex with a high computational burden and have a bad impact on the grid stability due to the power interruption during P-V scanning. To overcome the problem of partial shading, a new MPPT algorithm based on FLC that can boost the output power when partial shading occurs is proposed. The proposed MPPT technique has been designed to adapt the FLC based on DSM, so the classical fuzzy MPPT and DSM are presented in detail in the following Section 3.1 and Section 3.2. The FLC employing DSM is illustrated in Section 3.3.

3.1. Fuzzy Logic Controller (FLC)

The fuzzy controller is one of the AI methods that is widely used in industrial applications. Using FLC as an MPPT controller provides multiple merits of enhanced efficiency, reliability, and simple design [24,25]. Figure 3 shows the general structure of FLC for MPPT application, which has two inputs and one output. The two FLC input variables are the error E and change of error CE at sampled times j defined by (7)–(9):
P PV = V PV   I PV
E j = P PV j P PV j 1 V PV j V PV j 1
C E j = E j E j 1
where PPV, IPV, VPV are the PV power, current, and voltage, respectively, at instant j. Figure 4 shows the variables’ membership functions. In the literature, some authors prefer to implement the FLC using five linguistic variables [26,27] or seven linguistic variables [28,29]. The difference between them is not significant, so in this paper, the implementation of the FLC will be made using five linguistic variables as in [2,21,30,31,32].
The overall configuration of the classical MPPT based on FLC for a given PV system is explained and implemented as a standalone system in [21] or grid-connected in [2,30,31,32]. The configuration of FLC is suitable for different PV system applications either power generation as in [2,21] or power quality improvement as in [32]. Therefore, normalized FLC membership functions are preferred [33], as illustrated in Figure 4, to generalize the FLC structure and parameters for different PV system power rating and applications. The general rule base structure of FLC is shown in Table 1 [2]. Hence, the general FLC of a normalized FLC membership functions as in Figure 4 and the fuzzy inference rule base in Table 1 can be implemented for the different PV systems. The FLC parameters are addressed, in more detail, in [30,34], such as the number and types of membership functions, rule base, fuzzification, etc.
To avoid the FLC redesign for different PV system configurations and ratings, a general FLC structure for MPPT will be employed with normalized membership functions and a fixed rule base. It is only required to determine the input and output scale factor of the FLC according to the PV system rating.

3.2. Dynamic Safety Margin (DSM) for PV

In general, the design objective of control systems is to achieve a specified constrained output. The DSM is a performance index whose independent variable is the distance from a predefined safety boundary. The idea of the DSM is introduced in [22,23]. Let x be the state space in ℜn, and Φx be subspace that defines the safe operation region for some system state variables x ∈ ℜm. Φ can be specified by a set of inequalities, Φ = {x|φi(x) ≤ 0, i =1, …, q}, where φi: ℜm→ℜ. φi (x) > 0 is the unsafe operation as shown in Figure 5, and ∂Φ = {x|φi(x) = 0, i =1, …, q} ⊂ Φ is the boundary of the safe region, where variable q is the number of defined inequalities and m is the number of state variables relevant to safety. Notice that mn, where n is the dimension of the state-space. The system trajectory starts from the initial condition, x0, to the operating point xs crossing the state space with varying distance to the safety boundary as shown in Figure 5. In this subspace of state variables, DSM is defined as the instantaneous shortest distance, δ(t), between the current state vector, x, and ∂Φ. Therefore, the DSM can be obtained by solving the following quadratic programming optimization problem:
min x p x x p 2 2
subject to x p Φ and the DSM is:
δ = s t · x x p o 2
where xpo is the solution of the previous optimization problem and:
s t = + 1 ,   if   x   into   the   region   of   safe   operation 1 ,   if   x   out   of   the   region   of   safe   operation  
As a result, in the case of the PV system, the state variable relevant to the safety boundary is chosen to be PV voltage and power, x = [VPV PPV]T, and the safe operation region, Φ, is selected to be the subspace that includes the state corresponding to the maximum power points for all possible circumstances of weather conditions, temperature and irradiation. If the PV operating point, which corresponds to a certain PV power, is beyond Φ, the extracted power from the PV system will not reach the maximum power leading to a lower performance of the PV system.
The safe region of a PV module can be determined by one of the following methods: (1) offline, based on the power and voltage (P-V) manufacture characteristic of the module. However, it requires to have accurate data about the PV modules and their connection; (2) online, by recording the maximum power point that has been obtained by FLC without shading conditions. This method does not require prior accurate data about the modules type or connection, but it may take a long time to record the boundary of the safe region; (3) by integrating both methods, offline and online. In the case of offline technique, the boundary of Φ is determined by grouping all the possible maximum power at different irradiation and temperature. To illustrate the idea, consider a real PV module of KYOCERA KC200GT type of 200 W rated power and 30 V open circuit voltage. By analysing the P-V characteristic, the safe region will be an elliptic shape, convex set, as shown in Figure 6.
In the case of a multi-module PV system, the safe region will be determined by combining the characteristics of modules based on the series and parallel connection. In the case of series connection, the total safe region, Φs, of ns modules connected in series is determined by:
Φs = {xs| xs = ns x, xΦ}
where Φ is the safe region of a single module, x = [VPV PPV]T is the state vector of a single PV module, and xs ∈ R2, xs = [Vs Ps]T is the state variable of new string voltage and power.
In the case of parallel connection, the total safe region, Φp, of np modules connected in parallel is determined by:
Φp = {xp| xp = Ap x, xΦ}
where A p = 1 0 0 n p , xp ∈ R2, xs = [Vp Pp]T is the state variable of the new parallel combination voltage and power.
The most appropriate technique to determine the safe region of a single module is the third one by integrating the offline and online methods to gain the advantages of both. Therefore, it is necessary to determine the basic safe region offline to start the algorithm and this region will be adapted based on real online observation.
In this study, KYOCERA KC200GT PV modules will be used to simulate and test the MPPT algorithm. Without loss of generality, this safe operation region can be approximately specified by a set of linear inequalities constraints as a polytope, as shown in Figure 6, in the form of Φ = {x|φi(x) ≤ 0, i = 1, …, 4}, where:
Φ i x = a i T x c i 0 ,   i = 1 4 ,
where aiT ∈ ℜ2 and ci ℜ are constant, φi(·) = 0 is a subspace of state vector boundary, ∂Φ. These constraints can be combined in a matrix form as follow:
A   x c
where:
A = a 1 T a 2 T a q T , c = c 1 c 2 c q
For the given KYOCERA KC200GT PV module type, the corresponding parameters of (15) are determined for the characteristic shown in Figure 6 such as:
A = 90 1 37.5 1 90 1 37.5 1 ,   c = 2450 865 2195 737.5
The boundary of the safe region is ∂Φ(xp) = {xp|A xp = c}. Since the boundary has four linear segments represented by the matrix equation, then:
A   x p = c
The minimum distances between the current state x and a boundary segment number i (δi(t)) are given by [23]:
δ i t = c i a i T   x t a i 2   0 ,   i f   φ i x < 0 <   0 ,   i f   φ i x > 0
All boundaries distance vector for d(t) = [δ1(t), δ2(t), …, δq(t)] T can be calculated using:
d t = D ia c A x t = d c D a x t
where D a = 1 a 1 2 2 0 0 1 a q 2 2 is a diagonal matrix, dc = Da c, D a = D ia A , d(.) ∈ ℜq, c ∈ ℜq, dc ∈ ℜq, Da ∈ ℜq×n, and Dia ∈ ℜq×q.
Since Φ is convex and the boundary constraints are linear, the safe region is a polytope, and the DSM, δ(.), is the minimum element in d(.) [23], such as:
δ t = min 1 i q δ i t
Therefore, the determination of the safe region, Φ, of a PV system and the DSM can be summarized in the following steps:
(1)
Determine the safe region of a single PV module offline from the datasheet of the PV manufacture as illustrated in Figure 6.
(2)
Determine its boundary as in the form of Equations (14)–(17).
(3)
Determine the overall safe region of all modules based on their parallel and series connections using (12) and (13).
(4)
Compute the online DSM by solving the optimization problem (10) subject to constraints (17). The solution of problem (10) with constraints (17) can be obtained by applying Equations (18) and (20).
(5)
Record the observed maximum point at normal conditions and update the safe region boundary of step 3 if necessary, to overcome the approximation in steps 1 and 2.

3.3. FLC Employing DSM

Adapting FLC can be implemented by regulating the fuzzy output based on a certain criterion. This idea is addressed in [21] by enhancing the FLC output based on the deviation of the PV voltage and PV open circuit voltage but it fails to work probably in partial shading conditions. Therefore, an adaptation criterion based on DSM is proposed. The general configuration of the PV system consists mainly of (1) PV modules, (2) converter subsystem, either DC-DC or DC-AC, based on the application, and (3) direct load and/or grid connection based on the PV mode, standalone or grid connected as shown in Figure 7. The main function of the MPPT controller is to determine the gate signal of the PV converter. Accordingly, the value of the DSM can be used to regulate the FLC output as shown in Figure 7 to obtain the suitable gating signal duty cycle of the PV converter subsystem. The adaptation of FLC based on DSM is carried out according to the following steps:
(1)
The measured voltage and current of the PV are manipulated as explained in Section 3.1 to obtain the FLC output.
(2)
The current state of the PV, x = [VPV PPV]T, is used to calculate the instantaneous value of the DSM, δ(.), based on the defined safe region, Φ, of the PV as explained in Section 3.2 and illustrated in Figure 6.
(3)
If the PV state, x = [VPV PPV]TΦ, then the system is normal, and standalone FLC is sufficient to track the global MPP. Otherwise, an abnormal situation has occurred either shading, malfunction, or fault.
(4)
The regulating criterion is considered so that if the PV state, x = [VPV PPV]TΦ, then the output of FLC is scaled depending on the value of δ(.) as indicated in the flow chart in Figure 8 according to the following equation:
D u t y = D u t y F L C [ 1 + S g t δ t ]
and:
s g t = 0 ,   if   x   within   the   safe   operation   region k ,   if   x   out   of   the   safe   operation   region  
where Duty is the duty cycle of the PWM to control the converter of the PV, k ∈ [0, 1] is the adaptation gain and δ(t) is the instantaneous DSM. In the case of partial shading, the operating point traverses to the unsafe mode. Then DSM will enhance the FLC to move to another maximum point located in Φ or near to it.
(5)
During the adaptation, maximum operating points are recorded, and the DSM based FLC will adjust the converter to operate at the global maximum point.

4. Case Study

To illustrate the implementation of the proposed FLC based on DSM, a single-phase grid connected PV system is used as a case study. It has been compared with previous work in [2,30,31]. The advantages and limitations of the case study configuration are addressed in [2]. The case study employing the MPPT controller based on DSM is illustrated in Figure 9. It includes a PV array with a flyback converter followed by a current-controlled voltage source inverter. The flyback converter has been chosen for several reasons. For instance, the voltage is converted down to a value determined by the turns’ ratio during the off phase. This allows to choose a diode with smaller capacitances and therefore higher switching speed, a MOSFET with a much lower ON resistance can be used. Consequently, the power losses could be reduced leading to higher efficiency. Also, it has a wide input voltage range and provides isolation between the grid and PV due to the presence of a high-frequency transformer [35]. Moreover, no need to use a bulky transformer after the inverter to step up the voltage to the grid voltage. Besides, it does not have many components, thus it is inexpensive compared to other topologies and provides DC-DC at one stage instead of using multiple stages. However, it has a higher ripple current and higher input and output capacitance. Also, its efficiency is typically between 75% to 80% [36].
The voltage source inverter feeds current into the single-phase grid and local single-phase loads. The VrefDC, VDCLink, VGrid, VAB, and iac are DC-link reference voltage, DC link voltage, grid voltage, inverter voltage, and grid current respectively [37]. From the sensed VPV and current IPV at the subsystem block, the E and CE are deduced as shown in Figure 9. Then, the deduced E and CE are manipulated by the FLC to produce the PWM of the flyback converter [38,39]. FLC works efficiently under normal conditions of the PV system in terms of fast performance and accurate MPPT without oscillation as seen in [21,31]. However, for the partial shading situation, the power is decreased due to the trapping of the local MPP instead of the global one which will be illustrated in Section 5.

5. Simulation Results

The simulation of the proposed technique has been carried out using the MATLAB/SIMULINK environment for the PV KYOCERA KC200GT module in different situations. The simulation results are presented to investigate the effectiveness of the proposed model and control algorithms of the single-phase grid-connected PV system. The PV power curves for a different number of modules at normal weather of 25 °C and 1000 W/m2, and partial shading conditions are shown in Figure 10. The proposed technique will be applied for the given case study based on the criteria in Section 3.

5.1. FLC Configuration

A normalized FLC is utilized as explained in Section 3.1 with two inputs, E and CE, and one output, duty cycle, as shown in Figure 11. The input scale factors, Ke and Kce will be changed based on the number of modules connected in series, such that Ke = ko/n and Kce = kco/n, where n is the number of modules, and ko and kco are the nominal scales for a single module and both are equal to 1. E and CE are computed from (8) and (9), while the number of membership functions and the rule base were illustrated in Figure 4 and Table 1, respectively.

5.2. DSM Computation

The safe region, Φ, of each module, is deduced based on the datasheet of the module as explained in Section 3.2 with the same parameters of Figure 6. For two or more modules connected in series, the overall safe region will be obtained by (12). Then the parameters of (15) will be (22) for two modules, (23) for three modules, and (24) for four modules:
A = 90 1 37.5 1 90 1 37.5 1 ,   c = 4900 1730 4390 1475
A = 90 1 37.5 1 90 1 37.5 1 ,   c = 7350 2595 6585 2212.5
A = 90 1 37.5 1 90 1 37.5 1 ,   c = 9800 3460 8780 2950
Then by measuring the PV system state, x = [VPV PPV]T, the online DSM can be computed by solving the optimization problem (10) subject to constraints (17) with the parameters (22), (23), or (24), based on the number of modules. The solution of problem (10) with constraints (17) can be obtained by applying (18) and (20). The observed maximum point under normal condition is recorded to update the safe region boundary (22), (23), and (24) if necessary, to overcome the approximation of the computed region of a single module.

5.3. MPPT Algorithm Results

The DSM based FLC algorithm described in Section 3.3 is implemented in the case study for different module configurations. Figure 12 shows the PV power for a different number of modules operating at normal conditions, while Figure 13 illustrates the PV power for the DSM based FLC at partial shading situations. The results in Figure 12 are similar for both controllers at normal operations. By comparing the global maximum in Figure 10 with the results in Figure 13 during partial shading conditions, the output power is the global maximum. For example, in the case of 4 modules, there are 4 peaks and the global one is about 450 W that has been obtained by the DSM based FLC, while the FLC has detected the first peak of 200 W. So, there is a considerable difference in the total output power for the FLC based on DSM compared to the normal FLC in the case of multiple modules.
Figure 14 shows the output PV voltage for DSM based FLC and standalone FLC for multiple PV modules at partial shading conditions. The output voltage of the FLC controller stands still at the local maxima, 25 V and 200 W, which is the first maxima point. On the other hand, the DSM based FLC output voltage always catches the global maxima point. For example, in the four modules case, the voltage is 115 V, and the power is 450 W, which reflects the success of the proposed algorithm. The simulation results for different PV module configurations under shading conditions are summarized in Table 2.

6. Practical Case Study

To verify the proposed technique, a laboratory PV system is prepared as illustrated in Figure 15. The control algorithms described in Section 3 are implemented on a 32-bit, floating-point, digital signal processor (DSP) type TMS320F28335 (TEXAS INSTRUMENTS, Dallas, TX, USA). The selected PV module is an 80 W NT-80 (E1) (SHARP, Osaka, Japan). The transformer of the flyback converter is an MYRRA-74070 ETD 44 120–160 W (MYRRA, Paris, France) and the flyback switching frequency is 50 kHz. Besides, the DC link capacitor is 470 µF, 250 V, while the current and voltage sensors are LA 100-P (LEM, Geneva, Switzerland) and LV 25-P (LEM, Geneva, Switzerland), respectively. The inverter is a grid micro-inverter type of 600 W (INSUPRA, Katy, TX, USA). The data are recorded using a TDS2024 200 MHz two Channels Digital Real-Time Oscilloscope (Tektronix, Beaverton, Orleans, LA, USA). The measured PV power curve and the simulated PV curve of the PV module are shown in Figure 16 with a maximum power of 80 W at temperature and irradiation of 28 °C and 700 W/m2, respectively. In the beginning, the practical PV curve from the datasheet has been addressed to determine the safety region, Φ, as in Section 3.2.
After that, the test rig has been connected as illustrated in Figure 15, where the input signals, measured, are the actual PV voltage, DC bus voltage, and currents. The designed Simulink program has been coded and downloaded into the DSP. The DSP and PC are configured in a hierarchical two-level control structure; DSP as individual control, which is directly connected to the field, and PC as a supervisory controller. Both DSP and PC are connected through USP communication. Then the proposed algorithm is applied based on the current measurement to produce the suitable duty cycle of the flyback converter to change the operating point of voltage.
The classical FLC and DSM based FLC have been tested in normal and partial shaded modes, the results have been illustrated and compared. Figure 17 shows the Vmpp signal measured by the DSP at the normal operation for DSM based FLC method. The result shows the system’s ability to obtain an accurate maximum power from the PV module. Figure 18 shows the simulation results of a single module voltage of 17.8 V. It is almost the same voltage that has been obtained from the PV curve around 80 W in Figure 16. Figure 19 shows the PV curve at normal and partial shading conditions for the practical system, while Figure 20 and Figure 21 show the extracted power from the PV module under partial shading conditions employing FLC with DSM and standalone FLC, respectively. In the case of FLC, the power was nearly 36 W, which represents the local peak in Figure 19 or the first peak. While for the DSM based FLC, the power was approximately the same as the global peak of 80 W in Figure 19.
By reviewing the simulation and practical results, it is clear that DSM based FLC is robust, fast, and can track the global maximum in the shading conditions. Moreover, it has less computational effort in comparison with other techniques that have been introduced in the introduction and Section 3. Finally, it does not require to make P-V scan of the PV system, which has a great impact on the grid stability.

7. Conclusions

A robust and fast MPPT technique is necessary for a PV system to generate the maximum allowable power in case of environmental conditions and load variations. The MPPT based on FLC is robust, fast, and easy to be implemented but it fails sometimes to track the global maxima under partial shading conditions. Therefore, it is necessary to adapt the FLC based on a certain performance criterion to be able to work properly during partial shading conditions. Then, an MPPT technique based on FLC employing DSM as a performance index is proposed for normal and partial shaded modes. The DSM is used to evaluate the PV system operation either at normal or abnormal conditions; abnormal covers either shading or malfunction operation. To determine the DSM, a safe operation region, normal operation mode, of the PV system must be determined. The DSM indicates the current PV state from the safety boundary for adapting the normalized FLC. The determination of the safety boundary of the PV system has been investigated and the relation between the safety region of the single PV module and the combination of different modules has been addressed. Additionally, the proposed DSM based FLC algorithm has been tested and compared with the classical FLC for a single-phase grid connected PV system as a case study. To guarantee the effectiveness of the proposed technique, a string of different series connections up to four PV modules have been employed. The simulation results ensure the proposed MPPT technique’s ability to detect the peak and operate the PV system on the global maximum point, while classical fuzzy MPPT fails to get the global maxima in the case of partial shading. To validate the proposed method, it has been successfully implemented for a practical PV system and results demonstrate the fruitful operation of the proposed algorithm. Since the technique does not need to apply P-V scan, it has a good impact on the grid stability with a fast response. The key issue of the proposed approach is the determination of the safe operating region. Consequently, a safe region must be specified offline before implementing the proposed technique based on the manufacturing data, then it is updated or identified online based on the historical data.

Author Contributions

Conceptualization, M.B. and M.A.; methodology, M.B. and M.A.; software, M.B.; validation M.B. and M.A.; formal analysis, M.B., A.A. and M.A.; Supervision, M.A. and M.G.; Writing—original draft preparation, M.B. and A.A.; Writing—review & editing, M.B., A.A., M.A. and M.G. All authors have read and agreed to the published version of the manuscript.

Funding

This work was partly supported by the Natural Science Foundation of China through the project with code 51850410515. Also, the experimental setup was co-funded by AASTMT.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Han, J.; Yan, L.; Li, Z. A Multi-Timescale Two-Stage Robust Grid-Friendly Dispatch Model for Microgrid Operation. IEEE Access 2020, 8, 74267–74279. [Google Scholar] [CrossRef]
  2. Bakkar, M.; El-Geliel, M.A.; Zied, M.A. Control of photovoltaic grid connected using different control strategies. In Proceedings of the 22nd Mediterranean Conference on Control and Automation, Palermo, Italy, 16–19 June 2014; pp. 710–715. [Google Scholar]
  3. Aquib, M.; Jain, S.; Agarwal, V. A Time-Based Global Maximum Power Point Tracking Technique for PV System. IEEE Trans. Power Electron. 2020, 35, 393–402. [Google Scholar] [CrossRef]
  4. Brito, M.A.G.d.; Galotto, L.; Sampaio, L.P.; Melo, G.d.A.e.; Canesin, C.A. Evaluation of the Main MPPT Techniques for Photovoltaic Applications. IEEE Trans. Electron. 2013, 60, 1156–1167. [Google Scholar] [CrossRef]
  5. Li, W.; Zhang, G.; Pan, T.; Zhang, Z.; Geng, Y.; Wang, J. A Lipschitz Optimization-Based MPPT Algorithm for Photovoltaic System Under Partial Shading Condition. IEEE Access 2019, 7, 126323–126333. [Google Scholar] [CrossRef]
  6. Hussan, R.; Sarwar, A. Maximum Power Point Tracking Techniques under Partial Shading Condition—A Review. In Proceedings of the 2018 2nd IEEE International Conference on Power Electronics, Intelligent Control and Energy Systems (ICPEICES), New Delhi, India, 22–24 October 2018; pp. 293–298. [Google Scholar]
  7. Ali, A.; Almutairi, K.; Sanjeevikumar, P.; Tirth, V.; Algarni, S.; Irshad, K.; Islam, S.; Zahir, H.; Shafiullah; Malik, M.Z. Investigation of MPPT Techniques Under Uniform and Non-Uniform Solar Irradiation Condition–A Retrospection. IEEE Access 2020, 8, 127368–127392. [Google Scholar] [CrossRef]
  8. Ramli, M.Z.; Salam, Z. Analysis and experimental validation of partial shading mitigation in photovoltaic system using integrated dc–dc converter with maximum power point tracker. IET Renew. Power Gener. 2019, 13, 2356–2366. [Google Scholar] [CrossRef]
  9. Mahmoudian, S.M.M.S.; Rahmani, R.; Yusof, R.; Renani, E.T. Analytical modeling of partially shaded photovoltaic systems. Energies 2013, 6, 128–144. [Google Scholar] [CrossRef] [Green Version]
  10. Mohapatra, A.; Nayaka, B.; Das, P.; Mohanty, K.B. A review on MPPT techniques of PV system under partial shading condition. Renew. Sustain. Energy Rev. 2017, 80, 854–867. [Google Scholar] [CrossRef]
  11. Kebir, G.; Larbes, C.; Ilinca, A.; Obeidi, T.; Kebir, S.T. Study of the Intelligent Behavior of a Maximum Photovoltaic Energy Tracking Fuzzy Controller. Energies 2018, 11, 3263. [Google Scholar] [CrossRef] [Green Version]
  12. Wang, Y.; Yang, Y.; Fang, G.; Wen, B.Z.H.; Tang, H.; Fu, L.; Chen, X. An Advanced Maximum Power Point Tracking Method for Photovoltaic Systems by Using Variable Universe Fuzzy Logic Control Considering Temperature Variability. Electronics 2018, 7, 355. [Google Scholar] [CrossRef] [Green Version]
  13. Bouselhama, L.; Hajjia, M.; Hajji, B.; Boualia, H. A new MPPT-based ANN for photovoltaic system under partial shading conditions. Energy Procedia 2017, 111, 924–933. [Google Scholar] [CrossRef]
  14. Rudra Sankar Pal, V. Mukherjee Metaheuristic based comparative MPPT methods for photovoltaic technology under partial shading condition. Energy 2020, 212, 118592. [Google Scholar]
  15. Zhao, Z.; Cheng, R.; Yan, B.; Zhang, J.; Zhang, Z.; Zhang, M.; Lai, L.L. A dynamic particles MPPT method for photovoltaic systems under partial shading conditions. Energy Convers. Manag. 2020, 220, 113070. [Google Scholar] [CrossRef]
  16. Mansoor, M.; Mirza, A.F.; Ling, Q. Harris hawk optimization-based MPPT control for PV systems under partial shading conditions. J. Clean. Prod. 2020, 274, 122857. [Google Scholar] [CrossRef]
  17. Seyedmahmoudian, M.; Soon, T.K.; Jamei, E.; Thirunavukkarasu, G.S.; Horan, B.; Mekhilef, S.; Stojcevski, A. Maximum Power Point Tracking for Photovoltaic Systems under Partial Shading Conditions Using Bat Algorithm. Sustainability 2018, 10, 1347. [Google Scholar] [CrossRef] [Green Version]
  18. Gosumbonggot, J.; Fujita, G. Partial Shading Detection and Global Maximum Power Point Tracking Algorithm for Photovoltaic with the Variation of Irradiation and Temperature. Energies 2019, 12, 202. [Google Scholar] [CrossRef] [Green Version]
  19. Zou, Y.; Yan, F.; Wang, X.; Zhang, J. An efficient fuzzy logic control algorithm for photovoltaic maximum power point tracking under partial shading condition. J. Frankl. Inst. 2020, 357, 3135–3149. [Google Scholar] [CrossRef]
  20. Verma, P.; Garg, R.; Mahajan, P. symmetrical interval type-2 fuzzy logic control based MPPT tuning for PV system under partial shading condition. ISA Trans. 2020, 100, 251–263. [Google Scholar] [CrossRef]
  21. Hassan, H.; Geliel, M.A.; Abu-Zeid, M. A proposed fuzzy controller for MPPT of a photovoltaic system. In Proceedings of the 2014 IEEE Conference on Energy Conversion (CENCON), Johar Bahru, Malaysia, 13–14 October 2014; pp. 164–169. [Google Scholar]
  22. Abdel-Geliel, M.; Badredden, E.; Gambier, A. Application of Dynamic Safety Margin in robust fault detection and fault tolerant control. In Proceedings of the 2006 IEEE Conference on Computer Aided Control System Design, 2006 IEEE International Conference on Control Applications, 2006 IEEE International Symposium on Intelligent Control, Munich, Germany, 4–6 October 2006; pp. 337–342. [Google Scholar]
  23. Abdel-Geliel, M. Fault Diagnosis and Performance Recovery Based on Dynamic Safety Margin. Ph.D. Dissertation, Mannheim University, Mannheim, Germany, 2006. [Google Scholar]
  24. Ibrahim, M.I.H.E.A. Comparison Between Fuzzy and P&O Control for MPPT for Photovoltaic System Using Boost Converter. J. Energy Technol. Policy 2012, 2, 2224–3232. [Google Scholar]
  25. Panda, M.K.P.A.; Srivastava, S.P. Fuzzy Intelligent Controller for The Maximum Power Point Tracking of a Photovoltaic Module at Varying Atmospheric Conditions. J. Energy Technol. Policy 2011, 1, 18–27. [Google Scholar]
  26. Aherkar, A.; Deshpande, A. Fuzzy maximum power point tracking algorithm for photovoltaic system. In Proceedings of the 2017 2nd IEEE International Conference on Recent Trends in Electronics, Information & Communication Technology (RTEICT), Bangalore, India, 19–20 May 2017; pp. 1564–1567. [Google Scholar]
  27. Cardozo, D.O.; Pardo, M.; Algarín, C.R. Fuzzy Logic Controller for Maximum Power Point Tracking Based on Voltage Error Measurement in Isolated Photovoltaic Systems. In Proceedings of the 2018 IEEE ANDESCON, Santiago de Cali, Colombia, 22–24 August 2018; pp. 1–6. [Google Scholar]
  28. Chudamani, N.S.R.; Chudamani, R. Single-stage grid interactive PV system using novel fuzzy logic based MPPT with active and reactive power control. In Proceedings of the 2012 7th IEEE Conference on Industrial Electronics and Applications (ICIEA), Singapore, 18–20 July 2012; pp. 1667–1672. [Google Scholar]
  29. Vadim, C.; Ilie, N. Photovoltaic system modeling with fuzzy logic based incrimental conductance tracking algorithm. In Proceedings of the 2017 International Conference on Modern Power Systems (MPS), Cluj-Napoca, Romania, 6–9 June 2017; pp. 1–7. [Google Scholar]
  30. Bakkar, M.A.M. Module Integrated Converter for Photovoltaic Applications with Different Control Strategies. presented at the 16th International Middle East Power Systems Conference (MEPCON), Cairo, Egypt, 23–25 December 2014. [Google Scholar]
  31. Bakkar, M.A.M.; Abozeed, M. Photovoltaic Maximum Power Point Grid Connected based on Power Conditioning Technique Employing Fuzzy Controller. Presented at the International Conference on Renewable Energies and Power Quality (ICREPQ’15), La Coruña, Spain, 25–27 March 2015. [Google Scholar]
  32. Hamad, M.S.; Fahmy, A.M.; Abdel-Geliel, M. Power Quality Improvement of a Single-Phase Grid-Connected PV System with Fuzzy MPPT Controller. In Proceedings of the 39th IEEE conference in Industrial electronics (IECON 2013), Viena, Austria, 10–13 November 2013; pp. 1839–1944. [Google Scholar]
  33. Agamy, H.; Abdelgeliel, M.; Mosleh, M.; Elserafi, K.; Abdelrahman, N. Neural Fuzzy Control of the Indoor Air Quality Onboard a RO–RO Ship Garage. Int. J. Fuzzy Syst. Springer 2020, 22, 1020–1035. [Google Scholar] [CrossRef]
  34. Raghuwanshi, S.S.; Khare, V. FLC based MPPT controller for optimal tracking photovoltaic system. In Proceedings of the 2017 International Conference on Information, Communication, Instrumentation and Control (ICICIC), Indore, India, 17–19 August 2017; pp. 1–6. [Google Scholar]
  35. Soufi, Y.; Bechouat, M.; Kahla, S.; Bouallegue, K. Maximum power point tracking using fuzzy logic control for photovoltaic system. In Proceedings of the 2014 International Conference on Renewable Energy Research and Application (ICRERA), Milwaukee, WI, USA, 19–24 October 2014; pp. 902–906. [Google Scholar]
  36. Pesce, C.; Riedemann, J.; Pena, R.; Jara, W.; Maury, C.; Villalobos, R. A Modified Step-Up DC-DC Flyback Converter with Active Snubber for Improved Efficiency. Energies 2019, 12, 2066. [Google Scholar] [CrossRef] [Green Version]
  37. Joisher, M.; Singh, D.; Taheri, S.; Espinoza-Trejo, D.R.; Pouresmaeil, E.; Taheri, H. A Hybrid Evolutionary-Based MPPT for Photovoltaic Systems Under Partial Shading Conditions. IEEE Access 2020, 8, 38481–38492. [Google Scholar] [CrossRef]
  38. Alajmi, B.N.; Ahmed, K.H.; Adam, G.P.; Williams, B.W. Single-Phase Single-Stage Transformer less Grid-Connected PV System. IEEE Trans. Power Electron. 2013, 28, 2664–2676. [Google Scholar] [CrossRef]
  39. Othman, A.M.; El-arini, M.M.M.; Ghitas, A.; Fathy, A. Realworld maximum power point tracking simulation of PV system based on Fuzzy Logic control. Nriag J. Astron. Geophys. 2012, 1, 186–194. [Google Scholar] [CrossRef] [Green Version]
Figure 1. PV array including two series-connected modules (a) Circuitry diagram; (b) Block diagram.
Figure 1. PV array including two series-connected modules (a) Circuitry diagram; (b) Block diagram.
Energies 14 00841 g001
Figure 2. PV power curves for two modules at normal and partial shading conditions.
Figure 2. PV power curves for two modules at normal and partial shading conditions.
Energies 14 00841 g002
Figure 3. The FLC structure.
Figure 3. The FLC structure.
Energies 14 00841 g003
Figure 4. Membership function of (a) Error E (b) Change of Error CE (c) Duty ratio D.
Figure 4. Membership function of (a) Error E (b) Change of Error CE (c) Duty ratio D.
Energies 14 00841 g004
Figure 5. DSM definition.
Figure 5. DSM definition.
Energies 14 00841 g005
Figure 6. PV curve under different weather conditions for the KYOCERA KC200GT PV.
Figure 6. PV curve under different weather conditions for the KYOCERA KC200GT PV.
Energies 14 00841 g006
Figure 7. General configuration of MPPT using DSM based FLC.
Figure 7. General configuration of MPPT using DSM based FLC.
Energies 14 00841 g007
Figure 8. Flow chart of the proposed DSM based FLC MPPT.
Figure 8. Flow chart of the proposed DSM based FLC MPPT.
Energies 14 00841 g008
Figure 9. FLC using DSM for the PV system case study.
Figure 9. FLC using DSM for the PV system case study.
Energies 14 00841 g009
Figure 10. PV power curves for (a) three modules (b) four modules at normal and partial shading conditions.
Figure 10. PV power curves for (a) three modules (b) four modules at normal and partial shading conditions.
Energies 14 00841 g010aEnergies 14 00841 g010b
Figure 11. Normalized FLC structure.
Figure 11. Normalized FLC structure.
Energies 14 00841 g011
Figure 12. PV power curve for different PV modules at the normal operating conditions.
Figure 12. PV power curve for different PV modules at the normal operating conditions.
Energies 14 00841 g012
Figure 13. PV power curve for different PV modules for DSM based FLC at partially shaded mode.
Figure 13. PV power curve for different PV modules for DSM based FLC at partially shaded mode.
Energies 14 00841 g013
Figure 14. PV voltage for (a) one PV module (b) two PV modules (c) four PV modules at partial shading conditions.
Figure 14. PV voltage for (a) one PV module (b) two PV modules (c) four PV modules at partial shading conditions.
Energies 14 00841 g014
Figure 15. Practical system setup.
Figure 15. Practical system setup.
Energies 14 00841 g015
Figure 16. Practical and theoretical curves of the PV module at 80 W.
Figure 16. Practical and theoretical curves of the PV module at 80 W.
Energies 14 00841 g016
Figure 17. The measured PV voltage of DSM based FLC at normal condition.
Figure 17. The measured PV voltage of DSM based FLC at normal condition.
Energies 14 00841 g017
Figure 18. PV voltage simulation of DSM based FLC at normal condition.
Figure 18. PV voltage simulation of DSM based FLC at normal condition.
Energies 14 00841 g018
Figure 19. PV curve at normal and partial shading conditions.
Figure 19. PV curve at normal and partial shading conditions.
Energies 14 00841 g019
Figure 20. PV power for DSM based FLC at partial shading condition.
Figure 20. PV power for DSM based FLC at partial shading condition.
Energies 14 00841 g020
Figure 21. PV power for FLC at partial shading condition.
Figure 21. PV power for FLC at partial shading condition.
Energies 14 00841 g021
Table 1. FLC rule base structure.
Table 1. FLC rule base structure.
CE/ENBNSZEPSPB
NBZEZEPBPBPB
NSZEZEPSPSPS
ZEPSZEZEZENS
PSNSNSNSZEZE
PBNBNBNBZEZE
Table 2. Summary of simulation results.
Table 2. Summary of simulation results.
CaseFLCDSM Based FLC
PMPPT (W)VMPPT (V)PMPPT (W)VMPPT (V)
1 PV module 2002520025
2 PV modules2002530055
3 PV modules2002535085
4 PV modules20025450115
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Bakkar, M.; Aboelhassan, A.; Abdelgeliel, M.; Galea, M. PV Systems Control Using Fuzzy Logic Controller Employing Dynamic Safety Margin under Normal and Partial Shading Conditions. Energies 2021, 14, 841. https://doi.org/10.3390/en14040841

AMA Style

Bakkar M, Aboelhassan A, Abdelgeliel M, Galea M. PV Systems Control Using Fuzzy Logic Controller Employing Dynamic Safety Margin under Normal and Partial Shading Conditions. Energies. 2021; 14(4):841. https://doi.org/10.3390/en14040841

Chicago/Turabian Style

Bakkar, Mostafa, Ahmed Aboelhassan, Mostafa Abdelgeliel, and Michael Galea. 2021. "PV Systems Control Using Fuzzy Logic Controller Employing Dynamic Safety Margin under Normal and Partial Shading Conditions" Energies 14, no. 4: 841. https://doi.org/10.3390/en14040841

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop