Article

Analysis and Control of Battery Energy Storage System Based on Hybrid Active Third-Harmonic Current Injection Converter

1
School of Electric Power Engineering, South China University of Technology, Guangzhou 510640, China
2
China Electric Power Research Institute, Nanjing 210003, China
3
School of Electrical Engineering, Southeast University, Nanjing 210096, China
4
State Grid Jibei Electric Power Company Limited, Beijing 100045, China
*
Authors to whom correspondence should be addressed.
Energies 2021, 14(11), 3140; https://doi.org/10.3390/en14113140
Submission received: 21 March 2021 / Revised: 23 May 2021 / Accepted: 25 May 2021 / Published: 27 May 2021

Abstract

This paper applies the emerging hybrid active third-harmonic current injection converter (H3C) to the battery energy storage system (BESS), forming a novel H3C-BESS structure. Compared with the commonly used two-stage VSC-BESS, the proposed H3C-BESS has the capability to reduce the passive components and switching losses. The operation principle of the H3C-BESS is analyzed and the mathematical model is derived. The closed-loop control strategy and controller design are proposed for different operation modes of the system, which include the battery current/voltage control and the injected harmonic current control. In particular, active damping control is realized through the grid current control, which could suppress the LC-filter resonance without the need of passive damping resistors. Simulation results show that the proposed topology and its control strategy have fast dynamic response, with a setup time of less than 4 ms. In addition, the total harmonic distortions of battery current and grid currents are only 2.54% and 3.15%, respectively. The amplitude of the injected harmonic current is only half of the grid current, indicating that the current injection circuit generates low losses. Experimental results are also provided to verify the validity of the proposed solution.
Keywords: battery energy storage system; third-harmonic current injection; high efficiency; active damping battery energy storage system; third-harmonic current injection; high efficiency; active damping

Share and Cite

MDPI and ACS Style

Tao, Y.; Lei, J.; Feng, X.; Cao, T.; Hu, Q.; Chen, W. Analysis and Control of Battery Energy Storage System Based on Hybrid Active Third-Harmonic Current Injection Converter. Energies 2021, 14, 3140. https://doi.org/10.3390/en14113140

AMA Style

Tao Y, Lei J, Feng X, Cao T, Hu Q, Chen W. Analysis and Control of Battery Energy Storage System Based on Hybrid Active Third-Harmonic Current Injection Converter. Energies. 2021; 14(11):3140. https://doi.org/10.3390/en14113140

Chicago/Turabian Style

Tao, Yibin, Jiaxing Lei, Xinzhen Feng, Tianzhi Cao, Qinran Hu, and Wu Chen. 2021. "Analysis and Control of Battery Energy Storage System Based on Hybrid Active Third-Harmonic Current Injection Converter" Energies 14, no. 11: 3140. https://doi.org/10.3390/en14113140

APA Style

Tao, Y., Lei, J., Feng, X., Cao, T., Hu, Q., & Chen, W. (2021). Analysis and Control of Battery Energy Storage System Based on Hybrid Active Third-Harmonic Current Injection Converter. Energies, 14(11), 3140. https://doi.org/10.3390/en14113140

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.