A Methodology to Systematically Identify and Characterize Energy Flexibility Measures in Industrial Systems
Abstract
:1. Introduction
2. Production Facilities from an Energy Perspective
3. Key Concepts of DSEF and IEF
- An intelligent response to the volatility of energy prices: IEF, as mentioned before, have the capacity of optimizing the factory’s energy costs—in its simplest form, this means reducing energy costs via the reactive adjustment of consumption to price fluctuations in the electrical markets.
- Proactive marketing of the energy flexibility potentials in the grid service markets: the combination of IEF and production planning, can allow its proactive offering in the ancillary service markets of the electrical grid, thus obtaining a financial incentive from the grid operators.
- Maximize the usage of local energy sources/maximize the use of the renewable energy portfolio: through IEF, the energy consumption of an industrial system can be adapted to match the production profiles of local (within the factory boundaries) or nearby electricity generation plants. Hence, achieving balanced or real energy self-sufficiency in the production facility [24]. In the specific case of renewable electricity sources, IEF can reduce the carbon footprint of the factory, thus reducing potential Green House Gases-emissions related costs.
- Peak shaving and load management: peak shaving and load management are both benefits of IEF, eliminating the need for over-capacity to supply the peaks of highly variable loads and reducing time-of-use-related costs and stress on the energy distribution infrastructure.
- Improvement of the resilience of the proprietary energy infrastructure: IEF also can assist the energy infrastructure to recover quickly from energy supply disruptions or support self-sufficient operation. Thus, avoiding the considerable costs of production disruption. IEF can also serve to avoid or delay energy infrastructure expansions and their investment cost, by adapting the consumption patterns of different industrial systems to the capacity of the existing infrastructure.
3.1. Energy Flexibility Measures and their Energy Flexibility Potential
3.2. Categorization of Energy Flexibility Measures
4. Methodology to Systematically Identify and Characterize Energy Flexibility Measures
- Systematicity: as is the case with current industrial energy audits [28,29], the methodology has to follow a structured procedure on which all industrial systems in a production facility and their characteristics are progressively analyzed and decisions regarding their energy flexibility capabilities respond to procedural considerations.
- Focus in electrical flexibility: although different energy carriers are considered, the EFMs resulting from the application of the methodology should aim to optimize the electrical consumption of production facilities and its costs.
- Applicable to a plethora of industrial systems and production facilities: the methodology has to apply to the heterogeneous nature of modern industrial systems and production facilities.
- Agile: the methodology needs to be more agile, hence providing results in a shorter time-lapse, than a more exhaustive approach to identify EFMs, i.e., industrial system modelling [15].
- Current operation-friendly: the methodology does not aim to redesign industrial systems for energy flexible operation but to identify EFMs based on their current operation patterns.
- Outcome relevant for industrial stakeholders: the outcomes of the methodology should be qualitatively and quantitatively sufficient to inform the decision-making process of companies regarding the implementation and usage of the energy flexibility capabilities of their production facilities.
4.1. Delimitation of the Available Industrial Systems and Relevant Implementation Objectives
4.2. Determination of the Physical Characteristics of the Available Industrial Systems
- Technical Unit: Already defined in the previous step, the technical unit to which the industrial system belongs provides relevant insights on the task the system performs on the production facility and hence its energy consumption patterns.
- Industrial system layout: The arrangement of all, but particularly the energy-consuming, components in the industrial system help to understand the energy consumption chains, or how energy is distributed and used, across the system.
- Power rating and maximum system output: The power rating is the maximum allowable power input, meaning the aggregated maximum rate of energy transfer, of the energy-consuming components in the system. The maximum output of the industrial system is the maximum material or energy production provided by a system on each operative cycle.
- Operative Time: Aggregated utilization time of the components in the system, also understood as the duration of the task or tasks the system performs.
- Control Concept: The course of action through which the behavior of the industrial system is managed.
4.3. Inference of the Industrial Systems Suitable for Energy Flexible Operation
- Controllability: indicating how restrictive is the control concept of an industrial system in terms of additional variations in its operative state.
- Criticality: specifying the grade on which a change of operative state in an industrial system might alter the quality of the manufactured product or the continuity of the production processes within the factory.
- Input/output interdependence: defined by the level of decoupling between the energy input and the output of the industrial system along its operative cycle. The operative cycle of an industrial system is understood as the series of sequential tasks the system performs to achieve a unit of output.
4.4. Determination of the Relevant Operative Characteristics of the Suitable Industrial Systems
- Typical load profile: Typical pattern of energy consumption of the industrial system. A load profile consists of the curve of energy input versus time in the industrial system for a specific period. The typical load profile is usually a synthesis of the energy consumption record for a longer period, i.e., a year. There are several techniques to obtain the typical load profile, or profiles, of a system. The state-of-the-art consists on performing K-means clustering to the raw energy-consumption record of the system resulting in different clusters, or profiles, and calculating the median of the data samples in the cluster to obtain the typical curve profile. The optimal number of clusters is determined by using silhouette analysis and selecting the number of clusters that provide the maximum average silhouette scores. In practice, the clusters respond to the modes of operation of the industrial system under different operating conditions. The selected approach follows the recommendations of several research works that have dealt with the optimal approach to obtain the typical load profiles of electrical loads using machine learning algorithms, exalting the usage of silhouette scores and the k-means algorithm as the most fitting approach [33,34,35].
- Controlled Variable: Independent parameter(s) that determine the operating state of an industrial system. Their variation will induce a change in the operative state.
- Control horizon and latency: The control horizon is the minimum time interval between the variation of a control variable and the occurrence of the change in the operative state of the system. The control latency is the amount of time it takes signals to traverse the system or systems in the EMC Technical Unit.
- Operative continuity: Consistency of the operative cycles of the system. Three types can be discerned:
- ○
- Discontinuous, the operative cycle of the system, consists of multiple operative states that take place in irregular intervals throughout the operative time. The intervals are divided by irregular periods on which the system is idle.
- ○
- Part continuous, the operative cycle of the system involves a single operative state that occurs in regular intervals throughout the operative time. The intervals are divided by regular periods on which the system is idle.
- ○
- Continuous, the operative cycle of the system consists of a single operative state throughout the operative time. The system is never idle during its operative time.
- Operative Steps: Amount and type of successive steps that make up the operative cycle of the system.
- Output flexibility: The ability of a system to operate at a range of different output levels without incurring in major setup alterations.
- Bivalence or multivalence: The ability of a system to satisfy its energy demand with two or more energy carriers.
- Buffer Capability: Ability of an industrial system to store energy and/or media temporarily and locally. The storage capability might come from the system’s operative inertia (i.e., thermal or mechanical inertia) or dedicated storage components.
- Redundancy: The ability of more than one component within a system (system level), or more than one system within a technical unit (technical unit level) to perform a specific task.
- Operative Shiftability: The ability of a system to shift the totality or a part of their operation cycle to an earlier or later time point.
- Interruptible: The ability of a system to stop its operation cycle and continue at a later time point.
- Task Flexibility: The ability of a system to execute a variety of tasks for a production process, i.e., perform a range of operations or produce a variety of products, without incurring in any major setup variation.
- Routing Flexibility: The ability of a system to execute its tasks via alternative operative sequences.
4.5. Determination of the Production Characteristics of the Production Facility
- Manufacturing principle: The manufacturing principle follows the expected volume and variety of the manufactured product by the market. Four different principles are discernible [36]:
- ○
- Make-to-Stock (MTS), the product is made in their final form and stocked as finished goods.
- ○
- Assemble-to-Order (ATO), the product is assembled to its final form based on the customer’s purchase order.
- ○
- Make-to-Order (MTO), the product is completely manufactured after a customer has issued a purchase order.
- ○
- Engineer-to-Order (ETO), the product is designed and manufactured after the customer’s purchase order.
- Production Method: The production method is the basic approach to production planning, they fall into four categories [37]:
- ○
- Job processing, the production focuses on a single item at a time and usually requires a specific set of skills depending on the manufactured product.
- ○
- Batch processing, the production takes place in specific groups of pieces or completed products in small pre-set batch sizes.
- ○
- Flow processing, production involves passing of sub-assemblies or individual parts from one production station to the next until the final product is completed.
- ○
- Continuous processing, similar to flow production but there is no possible stop between production stations.
- Working shift model: Amount and extension of the working shifts on which the factory conducts its production processes.
- Production planning horizon: Minimum time-lapse between the end of detailed production planning and the start of production.
- Change in manufacturing orders: The possibility to change manufacturing orders once they have been issued.
- Change horizon: Minimum time-lapse between a request for a change in a manufacturing order and the enactment of this change.
- Product-based divergences: The influence that the manufactured product has on the energy consumption of the involved industrial systems.
- Multiple energy carriers: The presence of different energy carriers on the facility that can supply the energy consumption of the industrial system.
- Labor flexibility: The ability of labor to execute a range of different tasks.
- Relevant costs: Energy, maintenance and labor costs in the facility.
4.6. Identification of the Prospective Energy Flexibility Measures
- Crucial: A characteristic is crucial if it is decisive to the existence of an EFM belonging to a specific category. Meaning the way this characteristic manifests in the industrial system decides if the specific EFM-category is available in the industrial system.
- Influential: A characteristic is influential if it will delimit the EFP of the EFM belonging to the specific category.
- Relevant: A characteristic is relevant if it only serves to quantify additional characterization parameters, outside of the EFP, of the EFM.
- Irrelevant: the characteristic plays no role in the existence of a specific category of EFM or its characterization parameters.
4.7. Characterization of the Validated Energy Flexibility Measures
4.7.1. Functional Dimension
- Industrial system description: definition of the industrial system on which the EFM takes place. The description should at least include a system’s layout including all energy-consuming components, their performance data and an outline of the energy and material flows through which the system interacts with the other systems in the factory.
- EFM category: category of the identified prospective EFM based on the general categories defined in Table 1.
- Operative concept: a description of how the identified EFM induces a change of state in the industrial system.
- Adjustment factor and adjustment relationship: the adjustment factor is the independently controlled variable(s) that induces the change of state in the industrial system. The adjustment relationship describes the correlation between the adjustment factor and the rate of energy demand. Usually, a mathematical function describes this relationship in the form of a correlation, i.e., linear, polynomial or step.
- Amount and type of the modes of operation (MO): the MOs describe the operative states the EFM might induce in the industrial system. The modes of operation might be holding if only one operative step is induced on the system per activation of the EFM or modulating if the EFM induces more than one operative state per activation. The amount and type of the MOs are determined, among other characteristics, by the typical load profile of the industrial system, particularly its operative clusters.
- Execution level: highest level across the control pyramid on which the virtual part of an EFM will take place. The execution level usually tends to be the level on which the system is controlled.
4.7.2. Temporal Dimension
- Active Duration, ∆tactive: temporal element of the EFP, it comprises the minimum and maximum period on which the EFM is active, meaning the duration on which the industrial system operates under the EFM-induced operative state(s).
- Planning Duration, ∆tplanning: minimum and maximum period necessary to plan the activation of an EFM. This parameter responds to the operative continuity of the industrial system. In the case of industrial systems belonging to the MA technical unit is also majorly influenced by the production planning horizon and change horizon, both are determined at the planning level of the EMC technical unit. The planning duration can take place before or after the occurrence of the triggering event of the EFM.
- Perception Duration, ∆tperception: minimum and maximum period between the occurrence of a triggering event and the perception of this event by the control architecture in the EMC technical unit. The value of this parameter depends on the nature of the triggering event and the control latency in relevant systems in the EMC technical unit. The nature of the triggering event relates to the implementation objective of energy flexible operation as defined in Section 3.
- Decision Duration, ∆tdecision: minimum and maximum period ranging from the perception of a triggering event, t0, to the decision on the activation of the EFM. The performance, particularly the latency, of the systems that constitute the supervisory level of the EMC technical unit determine this parameter.
- Shift Duration, ∆tshift: minimum and maximum period covering the change in the operative state. This parameter is usually a function of the latency in the control concept of the industrial system. Nonetheless, it might be influenced by its operative stages and operative continuity.
- Activation Duration, ∆tactivation: minimum and maximum period covering from the perception of a triggering event to the achievement of the EFM-induced operative state. It can be understood as the addition of the perception, decision, planning (if it is performed after the triggering event) and shift duration. Their calculation is relevant because it will quantify the overall interval between the triggering event and the fully active EFM. The calculation formula for the Activation Duration is presented in Equation (1).
- Deactivation Duration, ∆tdeactivation: minimum and maximum period between the end of the active duration of the EFM and the return of the industrial system to its original operative state. As it was the case for the shift duration, this parameter depends on the control concept of the industrial system and its control horizon.
- Regeneration Duration, ∆tregeneration: minimum and maximum period that must elapse before an EFM can be activated again after it has been deactivated. The regeneration duration can be understood as the necessary time to bring stability to the material and energy flows altered by the activation of an EFM.
- Validity, V: parameter outlining the fraction of the operative time of the industrial system on which the EFM will be available for activation. This parameter is defined by the type and amount of operative steps of the industrial system and therefore the validity should include a reference to the specific operative step on which the EFM is available [38].
- Activation Frequency, Nactivation,T: the activation frequency parameter quantifies the maximum number of times an EFM can be executed over a specific period, T, usually a calendar year. Although it might be affected by other externalities, it might be calculated using the ratio between the product of the validity and the period, T, and the complete duration of the execution of an EFM. Equation (2) describes its calculation. The activation frequency should be referenced to the active duration for which it was calculated.
4.7.3. Performance Dimension
- Flexibility Type: describes the direction on which the operative state will be changed by the activation of each of the MOs of the EFM. The possible flexibility types are:
- ○
- Load increase (↑): increase in the energy demand rate compared to the reference consumption profile. The increase can involve just an increase in the rate consumption or the complete switch-on of the industrial system. In a load increase, there is no consumption compensation requirement. Therefore, the activation of an EFM of this type will constitute an overall increase in energy consumption of the system.
- ○
- Load decrease (↓): reduction in the energy demand rate compared to the reference consumption profile. Similarly, like the increase, the renunciation can involve both a reduction of energy consumption and a complete switch-off of the influenced industrial system. In a load renunciation, consumption compensation is also not required. Therefore, the activation of this type of an EFM will constitute an overall decrease in energy consumption.
- ○
- Bidirectional (↑↓): the ability of the EFM to offer both a load increase and renunciation. Nonetheless, once activated in either direction this type of EFM will not require a compensation of the altered energy consumption.
- ○
- Consumption shift (↔): temporary rearrangement of the energy consumption, increase or decrease, with proportional compensation. The consumption shift is backwards when consumption is shifted to an earlier point in time. Inversely, it will be forward if it is postponed to a later point in time. A special case of load shift is “valley-filling” where the tasks that generate the consumption profile are broke down and rearranged at different points in time, thus reducing peak-consumption. In any of the consumption shift cases, the net energy consumption will stay constant despite activating the EFM. The different flexibility types are typified in Figure 7.
- Flexible Power, ∆Pflex: the power delta of the EFP, it describes the maximum difference of rate of energy demand between the reference operative state and the EFM-induced operative state. The unit for this parameter is usually kWflex.
- Flexible Energy Carrier: this parameter, defines the energy carrier or carriers influenced by the activation of the EFM. Usually, as previously introduced, the focus, due to its attractiveness, is on the electrical energy consumption. Nonetheless, at least, for the Bivalent Operation and Energy Carrier Exchange EFM-categories, another energy carrier is also influenced.
- Flexible Energy, Eflex,T: the average amount of energy that could be adapted through the activation of an EFM over a specific period, T, typically a year. The flexible energy consists of the product of the average flexible power, the active duration and the retrieval frequency for this active duration, as presented in Equation (3). The unit for this parameter is usually MWhflex and it must be referenced to the active duration for which it is calculated.
4.7.4. Economic Dimension
- Investment Costs, Cinvestment: fixed, one-time expenses incurred to implement an EFM. Simply put the expenses necessary to bring the EFM to an operative status. The investment costs can be tangible including further development of component technology, further development of the IT-infrastructure and strengthening of the proprietary energy distribution infrastructure. These costs can also be intangible, like those associated with, the acquisition of software tools, hiring of third-party services or personnel training among others.
- Activation Costs, Cactivation: ongoing expenses related to the activation of the EFM. These expenses are only incurred when the EFM is executed and hence are a function of the activation frequency. Examples include increased material, energy or labor costs due to the adaptation of the operative cycle of the industrial system and potential opportunity costs due to the activation of the EFM.
- Maintenance Costs, Cmaintenance,T: ongoing expenses to keep the availability of the EFM over a specific time span, T, typically a calendar year. These costs are activation-independent. Therefore, they will stay unaffected by the activation frequency of the EFM. Examples include the hiring of third-party services to trade in energy markets and additional component wear and tear costs associated with energy flexible operation.
- Expected payback period, τpayback: the expected period, typically given in years, on which the EFM is expected to reach a break-even point or the point on which the revenues associated with the EFM offset its costs. The company’s management usually defines the expected payback period. Normally it obeys to their historical approach to factory-upgrade investments.
- EFM specific cost, cflex,T: cost summary indicator of the EFM, it represents the cost of the EFM by a unit of flexible energy over a specific period (T). It is calculated through the formula presented in Equation (4).
4.8. Calculation of the Economical and Viable EFP of the Characterized EFMs
5. Application of the Proposed Methodology
5.1. Delimitation of the Available Industrial Systems
5.2. Determination of the Relevant Physical Characteristics of the Chilled Water Air-Conditioning System
- Technical Unit: The system belongs to the TBS technical unit of the production facility.
- Industrial system layout: the chilled water air-conditioning system consists of a 7/12 °C chilled water (CHW) circuit that provides room cooling for a production hall and an on-site data center. The cooling output is provided by three water-cooled, screw-driven mechanical chillers (CHWDX) and two hot water, single-effect absorption chillers (CHWAB) plus a free cooling module (CHWFC). The heat abatement of these units is performed by a 32/37 °C cooling water (CW) circuit with three cooling towers and three pumps. The hot water for the CHWABs is usually fed from the two CHP engines on-site but through minor modifications might be sourced from the 95/60 °C hot water (HW) system onsite. The cooling is delivered through a series of air handling units to the production hall and a data center that supports the production activities. Due to their air-quality-specific operation pattern, the air-handling units were not considered in the analysis of this system. For analysis purposes, the hot water loop for the CHWABs is assumed as an energy carrier entering the system. Therefore, the HW generation sources were not analyzed. The layout of the chilled water system is depicted in Figure 8.
- Power rating and cooling output of the cooling units: The power rating and cooling output of the cooling generation units are summarized in Table 4.
- Power rating and output of the other energy-consuming components: The power rating and design output of the other relevant energy-consuming components, pumps and cooling towers, in the system, are presented in Table 5.
- Operative Time: The system operates 24/7 in stand-by mode, going into active operation when there is a cooling demand. Therefore, its maximum operative time is limited to the working shifts in the production facility.
- Control Concept: The cooling demand is a function of the ambient temperature on-site. The system is controlled at the supervisory level through a SCADA architecture that monitors the air return temperature in the air-handler units and the return water temperature in the chilled water circuit. The current control concept prioritizes the operation of the CHWDX units for cooling supply. These mechanical chiller units are activated sequentially, based on the return water temperature. Activation priority is given to CHWDX-3, due to its better performance at partial loads. The other mechanical chiller units, CHWDX-1 and CHWDX-2, are rotated to guarantee equalized running time among them. The absorption units, CHWAB-1 and CHWAB-2, are mostly activated in-junction with two combined heat and power (CHP) engines on site. The CHP engines are activated for peak-shaving purposes in the factory. The absorption chiller units are also used to provide redundancy to the mechanical chiller units. The free-cooling module, CHWFC-1 gains priority activation, when the ambient temperature drops below 10 °C.
5.3. Suitability of the Chilled Water System for Energy Flexible Operation
5.4. Determination of the Relevant Operative Characteristics of the Chilled Water Air-Conditioning System
- Typical load and output profile: There is a three-year data record of the cooling consumption in the factory on a 15 min basis. The data record also includes the cooling output and the electrical consumption of the components in Table 4 and Table 5. Employing the silhouette analysis and the K-means algorithm, as previously described, on the data record, values were clustered and an average cooling output and electrical input profile per cluster were calculated. As the measurements followed a normal distribution, their spread for each 15 min period was calculated using the two standard deviations over (2σ) and below (−2σ) the mean. The results are presented in Figure 9, the average consumption profile is color-highlighted and the range (±2 standard deviations) is shown in grey.
- Control Variable: As mentioned the system operates continuously, ramping up and down the different cooling generation units as a function of the return water temperature.
- Control horizon and latency: The ramping up and down of the system to a new operative state lasts between 5 and 10 min. The control components present a latency under five milliseconds.
- Operative Continuity: the system presents a discontinuous operative continuity.
- Operative steps: Each of the cooling units ramp up and down in single steps depending on the number of cooling circuits they present. The CHWDXs present 2 circuits, hence 2 operative steps, and the CHWABs present a single one, as does the CHWFC.
- Output Flexibility: the aforementioned cooling circuits in each of the cooling generation units provide the output flexibility.
- Bivalence: Due to the different functioning principle of the CHWDX and CHWFC, the system can be considered as presenting bivalence.
- Redundancy: As previously mentioned, the CHWAB act as redundancy for the CHWDX units. The other components in the CW and HW circuits present 2N + 1 redundancy, while the pumps in the CHW circuit present 3N + 1 redundancy.
5.5. Determination of the Relevant Production Characteristics of the Production Facility
- Manufacturing Principle: MTS
- Production Method: Flow Processing
- Working Shift Model: 3 shifts (8 h long), 5 days a week, 50 weeks per year
- Production planning horizon: Weekly
- Product-based divergence in energy consumption: None
- Multiple Energy Carriers on Site: Relevant to this system are natural gas and electricity.
5.6. Identification of Prospective EFMs in the Chilled Water Air-Conditioning System
- Adaptation of resource allocation: The adaptation of resource allocation EFM focuses on the possibility of switching between the CHWDX chillers and the CHWAB chillers while supplying the cooling consumption of the facility. Due to the considerable difference in the power rating between chiller types and hence in their electrical EER, the rotation of the absorption and mechanical chiller units induce a change in the electrical input of the chilled water system.
- Dedicated Energy Storage: The installation of CHW storage to supply the totality or a share of the cooling demand, at specific periods.
5.7. Characterization of the Validated EFM in the Chilled Water Air-Conditioning System
5.8. Calculation of the Economical and Viable EFP of the Identified EFM
6. Discussion
7. Conclusions and Outlook
Author Contributions
Funding
Acknowledgments
Conflicts of Interest
Acronyms
AS | Auxiliary Systems technical unit |
AGV | Automated Guided Vehicles |
ATO | Assembly to Order manufacturing principle |
CHP | Combined Heat and Power |
CHW | Chilled Water |
CHWAB | Chilled Water Absorption Chiller |
CHWDX | Chilled Water Mechanical Chiller |
CHWFC | Chilled Water Free-Cooling Module |
Co | Controllability |
Cr | Criticality |
In | Input/output Interdependence |
CW | Cooling Water |
DR | Demand Response |
DSEF | Demand Side Energy Flexibility |
EEP | Institute for Energy Efficiency in Production |
EER | Energy efficiency ratio |
EFM | Energy Flexibility Measure |
EFP | Energy Flexibility Potential |
EMC | Energy and Manufacturing Control technical unit |
EM | Energy and Media technical unit |
EMS | Energy Management System |
ERP | Enterprise Resource Planning System |
ETO | Engineering-to-Order manufacturing principle |
GHG | Green House Gases |
HMI | Human-Machine Interfaces |
HVAC | Heating, Ventilation and Air-conditioning systems |
HW | Hot Water |
IEF | Industrial Energy Flexibility |
IPA | Institute for Manufacturing Engineering and Automation |
IRENA | International Renewable Energy Agency |
MA | Manufacturing technical unit |
MES | Manufacturing Execution System |
MTO | Make-to-Order manufacturing principle |
MTS | Make-to-Stock manufacturing principle |
MO | Modes of Operation of the energy flexibility measure |
NDC | Nationally Determined Contribution |
PLC | Program Logic Controllers |
PM | Production Machines |
SCADA | Supervisory control and data acquisition system |
SSEF | Supply Side Energy Flexibility |
TBS | Technical Building Services technical unit |
VRE | Variable Renewable Energy Sources |
WBT | Wet-Bulb Temperature |
WS | Workstations |
References
- International Renewable Energy Agency. Global Energy Transformation: A Roadmap to 2050 (2019 Edition); International Renewable Energy Agency: Abu Dhabi, UAE, 2019; ISBN 978-92-9260-121-8. [Google Scholar]
- International Renewable Energy Agency. Global Renewables Outlook: Energy Transformation 2050; International Renewable Energy Agency: Abu Dhabi, UAE, 2020; ISBN 978-92-9260-238-3. [Google Scholar]
- International Renewable Energy Agency. Power System Flexibility for the Energy Transition, Part 1: Overview for Policymakers; International Renewable Energy Agency: Abu Dhabi, UAE, 2018; ISBN 9789292600891. [Google Scholar]
- Cochran, J.; Miller, M.; Zinaman, O.; Milligan, M.; Arent, D.; Palmintier, B.; O’Malley, M.; Mueller, S.; Lannoye, E.; Tuchy, A. Flexibility in 21st Century Power Systems; National Renewable Energy Laboratory: Golden, CO, USA, 2014. [Google Scholar]
- Bradley, P.; Leach, M.; Torriti, J. A review of the costs and benefits of demand response for electricity in the UK. Energy Policy 2013, 52, 312–327. [Google Scholar] [CrossRef] [Green Version]
- Publications Office of the European Union. Energy Balance Sheets, 2019 ed.; Publications Office of the European Union: Luxembourg, 2019; ISBN 9276087141. [Google Scholar]
- EU-28: Breakdown of Industrial Energy Use 2015|Statista. Available online: https://www.statista.com/statistics/859496/renewable-energy-consumption-by-source-european-union-eu-28/ (accessed on 9 May 2020).
- Sauer, A.; Abele, E.; Buhl, H.U. (Eds.) Energieflexibilität in der Deutschen Industrie: Ergebnisse aus dem Kopernikus-Projekt—Synchronisierte und Energieadaptive Produktionstechnik zur Flexiblen Ausrichtung von Industrieprozessen auf eine Fluktuierende Energieversorgung (SynErgie); Fraunhofer Verlag: Stuttgart, UAE, 2019; ISBN 9783839614792. [Google Scholar]
- Strbac, G. Demand side management: Benefits and challenges. Energy Policy 2008, 36, 4419–4426. [Google Scholar] [CrossRef]
- Munuera, L. Demand Response (Tracking Report). 2020. Available online: https://www.iea.org/reports/demand-response (accessed on 3 August 2020).
- Virag, A.; Jezdinsky, T. Flexible Industrial Demand Assessment. Case Studies Summary; Public Version. 2018. Available online: http://www.industre.eu/downloads/ (accessed on 4 August 2020).
- Wiendahl, H.-P.; Reichardt, J.; Nyhuis, P. Handbook Factory Planning and Design; Springer: Heidelberg, Germany, 2015; ISBN 9783662463901. [Google Scholar]
- Kiran, D.R. Production Planning and Control. A Comprehensive Approach; Butterworth-Heinemann: Amsterdam, The Netherlands, 2019; ISBN 9780128183649. [Google Scholar]
- Posselt, G. Towards Energy Transparent Factories, 1st ed.; Springer: Berlin, Germany, 2016; ISBN 9783319208688. [Google Scholar]
- Beier, J. Simulation Approach towards Energy Flexible Manufacturing Systems; Springer: Cham, Switzerland, 2017; ISBN 978-3-319-46639-2. [Google Scholar]
- Cannistraro, G.; Cannistraro, M.; Cannistraro, A.; Galvagno, A.; Trovato, G. Evaluation on the convenience of a citizen service district heating for residential use: A new scenario introduced by high energy efficiency systems. IJHT 2015, 33, 167–172. [Google Scholar] [CrossRef]
- Cannistraro, G.; Cannistraro, M.; Cannistraro, A.; Galvagno, A.; Trovato, G. Technical and Economic Evaluations about the Integration of Cotrigeneration Systems in the Dairy Industry. IJHT 2016, 34, S332–S336. [Google Scholar] [CrossRef]
- Sauer, A.; Weckmann, S. Industrial Smart Grids–Ein Beitrag für ein Nachhaltiges Energiesystem. In CSR und Digitalisierung; Hildebrandt, A., Landhäußer, W., Eds.; Springer: Berlin, Germany, 2017; pp. 209–226. ISBN 978-3-662-53201-0. [Google Scholar]
- Schnell, G.; Wiedemann, B. (Eds.) Bussysteme in der Automatisierungs- und Prozesstechnik Grundlagen Systeme und Trends der Industriellen Kommunikation, 6th ed.; Vieweg + Teubner: Wiesbaden, Germany, 2006; ISBN 9783834891082. [Google Scholar]
- Reinhart, G.; Reinhardt, S.; Graßl, M. Energieflexible Produktionssysteme: Einführungen zur Bewertung der Energieeffizienz von Produktionssystemen. WT Werkstattstech. Online 2012, 102, 622–628. [Google Scholar]
- Federal Energy Regulatory Commission; U.S. Department of Energy. Implementation Proposal for the National Action Plan on Demand Response; U.S. Department of Energy: Washington, DC, USA, 2011.
- Zancanella, P.; Bertoldi, P.; Kiss, B. Demand Response Status in EU Member States; Publications Office of the European Union: Luxembourg, 2016. [Google Scholar]
- Verein Deutscher Ingenieure (Ed.) Energieflexible Fabrik Grundlagen; VDI 5207; Blatt 1; VDI-Gesellschaft Produktion und Logistik (GPL): Düsseldorf, Germany, 2019. [Google Scholar]
- Schulze, C.; Blume, S.; Siemon, L.; Herrmann, C.; Thiede, S. Towards energy flexible and energy self-sufficient manufacturing systems. Procedia CIRP 2019, 81, 683–688. [Google Scholar] [CrossRef]
- Dufter, C.; Guminski, A.; Orthofer, C.; von Roon, S.; Gruber, A. (Eds.) Lastflexibilisierung in der Industrie–Metastudienanalyse zur Identifikation relevanter Aspekte bei der Potenzialermittlung. In Proceedings of the IEEWT 2017—10. Internationale Energiewirtschaftstagung, Vienna, Austria, 16 February 2017. [Google Scholar]
- Popp, R.S.H.; Zaeh, M.F. Determination of the Technical Energy Flexibility of Production Systems. AMR 2014, 1018, 365–372. [Google Scholar] [CrossRef]
- Grassl, M. Bewertung der Energieflexibilität von Produktionssystemen//Bewertung der Energieflexibilität in der Produktion, Dissertation; Technical University Munich: Munich, Germany, 2015; ISBN 978-3-8316-4476-6. [Google Scholar]
- DIN Deutsches Institut für Normung e. V. Energy Audits. Part 3: Processes; DIN Deutsches Institut für Normung e. V.: Berlin, Germany, 2014; DIN EN 16247-3:2014-08. [Google Scholar]
- ISO International Standards Organization. Energy Audits. Requirements with Guidance for Use; ISO International Standards Organization: Geneva, Switzerland, 2014; ISO 50002:2014. [Google Scholar]
- Abele, E.; Schraml, P.; Moog, D. Electric Load Management on Machine Tools. Procedia CIRP 2016, 55, 164–169. [Google Scholar] [CrossRef] [Green Version]
- Abele, E.; Schraml, P.; Beck, M.; Flum, D.; Eisele, C. Two Practical Approaches to Assess the Energy Demand of Production Machines. In Eco-Factories of the Future; Thiede, S., Herrmann, C., Eds.; Springer International Publishing: Cham, Switzerland, 2019; pp. 127–146. ISBN 978-3-319-93729-8. [Google Scholar]
- DIN Deutsches Institut für Normung e. V. Referenzmodell zur Charakterisierung der Energieflexibilität von Industrieunternehmen; DIN Deutsches Institut für Normung e. V.: Berlin, Germany, 2018; DIN SPEC 91366:2018-04. [Google Scholar]
- Wang, Y.; Chen, Q.; Kang, C.; Xia, Q. Clustering of Electricity Consumption Behavior Dynamics, Toward Big Data Applications. IEEE Trans. Smart Grid 2016, 7, 2437–2447. [Google Scholar] [CrossRef]
- Richard, M.-A.; Fortin, H.; Poulin, A.; Leduc, M.-A.; Fournier, M. Daily load profiles clustering: A powerful tool for demand-side management in medium-sized industries. In Proceedings of the ACEEE Summer Study on Energy Efficiency in Industry, Denver, CO, USA, 15–18 August 2017; pp. 160–171. [Google Scholar]
- Yilmaz, S.; Chambers, J.; Patel, M.K. Comparison of clustering approaches for domestic electricity load profile characterisation—Implications for demand-side management. Energy 2019, 180, 665–677. [Google Scholar] [CrossRef]
- Chapman, S.N. The Fundamentals of Production Planning and Control; Pearson/Prentice Hall: Upper Saddle River, NJ, USA, 2006; ISBN 9780130176158. [Google Scholar]
- Westkämper, E. Einführung in die Organisation der Produktion; Springer: Berlin/Heidelberg, Germany, 2006; ISBN 978-3-540-30764-8. [Google Scholar]
- Schott, P.; Sedlmeir, J.; Strobel, N.; Weber, T.; Fridgen, G.; Abele, E. A Generic Data Model for Describing Flexibility in Power Markets. Energies 2019, 12, 1893. [Google Scholar] [CrossRef] [Green Version]
- Grunewald, P.; Diakonova, M. Flexibility, dynamism and diversity in energy supply and demand: A critical review. Energy Res. Soc. Sci. 2018, 38, 58–66. [Google Scholar] [CrossRef]
- Lund, P.D.; Lindgren, J.; Mikkola, J.; Salpakari, J. Review of energy system flexibility measures to enable high levels of variable renewable electricity. Renew. Sustain. Energy Rev. 2015, 45, 785–807. [Google Scholar] [CrossRef] [Green Version]
- Industrial Electricity Prices across Europe 2018|Statista. Available online: https://www.statista.com/statistics/267068/industrial-electricity-prices-in-europe/ (accessed on 9 May 2020).
- Tristan, A.; Emde, A.; Reisinger, M.; Stauch, M.; Sauer, A. Energieflexibilität im Industrial Smart Grid. wt Werkstattstechnik Online 2019, 109, 301–306. [Google Scholar]
Name | Classification 1 | Description | Applicability 2 |
---|---|---|---|
Adaptation of staff free time | O | Aligning the staff break times to fit different energy consumption profiles. | MA |
Adaptation of working shifts | O | Aligning the work shift times to different energy consumption profiles. | MA |
Adaptation of order execution sequence | O | Changing the chronological execution sequence of manufacturing orders to different energy demand patterns. | MA |
Capacity planning adjustment | O | Changing the assignment of a product to a production resource (Production Machine/Work Station, Manufacturing Cell or Line) to alter the energy consumption profile. | MA |
Defer of production start | O | Premature or delayed start of production (all manufacturing orders) within different periods to fit different energy consumption profiles. | MA |
Manufacturing order interruption | O | Interruption of a manufacturing order and restart of the same order at a later time point. Duration might expand through minutes, hours or even full shifts. | MA |
Adaptation of order production sequence | O | Changing the chronological production sequence of a specific manufacturing order to adjust to a different energy consumption profile. | MA |
Adaptation of resource allocation | O | Targeted selection of specific components in an industrial system based on their energy consumption patterns. | MA TBS AS |
Adaptation of operation parameters | T | Adaptation of the control variables of an industrial system to fit different energy consumption profiles. | MA TBS AS |
Operation interruption | T | Temporary suspension of the operation, and hence of the energy consumption, of an industrial system. | MA TBS AS |
Adjustment of the operational sequence | T | Changing the operative sequence of an industrial system to adjust to different energy consumption profiles. | MA TBS AS |
Inherent energy storage | T | Use the operative inertia of an industrial system as energy storage. | MA TBS AS EM |
Bivalent operation | T | Switch between different energy carriers to supply the energy consumption of a specific industrial system. | MA TBS AS |
Dedicated energy storage | T | Storage of energy in a suitable storage medium. The storage can take place within a system (system-level), or serve multiple industrial systems (factory-level). | MA TBS AS EM |
Energy carrier exchange | T | Use of different energy carriers to supply the energetic demand of multiple industrial systems across the factory. | EM |
Characteristic Name | Organizational EFM-Categories | |||||||
---|---|---|---|---|---|---|---|---|
Adaptation of Staff Free Time | Adaptation of Working Shifts | Adaptation of Order Execution Sequence | Capacity Planning Adjustment | Defer of Production Start | Manufacturing Order Interruption | Adaptation of Order Production Sequence | Adaptation of Resource Allocation | |
Technical unit | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Industrial system layout | ○○○ | ○○○ | ○○○ | ●●● | ○○○ | ○○○ | ●●● | ●●● |
Power rating | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Operative time | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Control concept | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Typical load profile | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Control variable | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Control horizon and latency | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ |
Operative continuity | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Operative steps | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●● | ●●○ |
Output flexibility | ○○○ | ○○○ | ●●● | ●●● | ○○○ | ○○○ | ●●● | ●●● |
Bivalence | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ |
Buffer capability | ●●● | ●●● | ●●● | ○○○ | ●●● | ●●● | ○○○ | ○○○ |
Redundancy | ○○○ | ○○○ | ○○○ | ●●● | ○○○ | ○○○ | ●●● | ●●● |
Operative Shiftability | ●●● | ●●● | ○○○ | ●●● | ●●● | ●●● | ○○○ | ○○○ |
Interruptible | ●●● | ○○○ | ○○○ | ○○○ | ○○○ | ●●● | ○○○ | ○○○ |
Task flexibility | ○○○ | ●●● | ●●● | ●●● | ○○○ | ●●● | ●●● | ○○○ |
Routing flexibility | ○○○ | ○○○ | ○○○ | ●●● | ○○○ | ○○○ | ●●● | ○○○ |
Manufacturing principle | ●●○ | ●●○ | ●●● | ●●○ | ●●● | ●●● | ●●○ | ●●○ |
Production method | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●○ |
Working shift model | ●●● | ●●● | ●●○ | ●●○ | ●●● | ●●○ | ●●○ | ●●○ |
Production planning horizon | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ |
Change of manufacturing orders | ●○○ | ●○○ | ●●● | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ |
Change horizon | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ |
Product-based divergences | ●●○ | ●●○ | ●●● | ●●● | ●●○ | ●●○ | ●●● | ●●○ |
Multiple energy carriers | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ |
Labor flexibility | ●○○ | ●○○ | ●●● | ●●● | ●○○ | ●○○ | ●●● | ○○○ |
Relevant Costs | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ |
Characteristic Name | Technical EFM Categories | ||||||
---|---|---|---|---|---|---|---|
Adaptation of Operation Parameters | Operation Interruption | Adjustment of the Operational Sequence | Inherent Energy Storage | Bivalent Operation | Dedicated Energy Storage | Energy Carrier Exchange | |
Technical unit | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Industrial system layout | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Power rating | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Operative time | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Control concept | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Typical load profile | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Control variable | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● | ●●● |
Control horizon and latency | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ |
Operative continuity | ●●○ | ●●● | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Operative steps | ●●○ | ●●○ | ●●● | ●●○ | ●●○ | ●●○ | ●●○ |
Output flexibility | ●●● | ○○○ | ●●● | ●●● | ○○○ | ●●● | ○○○ |
Bivalence | ○○○ | ○○○ | ○○○ | ○○○ | ●●● | ○○○ | ●●● |
Buffer capability | ○○○ | ●●● | ○○○ | ●●● | ○○○ | ●●● | ○○○ |
Redundancy | ○○○ | ○○○ | ○○○ | ○○○ | ●●● | ○○○ | ○○○ |
Operative Shiftability | ○○○ | ●●● | ●●● | ●●● | ○○○ | ○○○ | ○○○ |
Interruptible | ○○○ | ●●● | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ |
Task flexibility | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ |
Routing flexibility | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ |
Manufacturing principle | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Production method | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Working shift model | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Production planning horizon | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ |
Change of manufacturing orders | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ |
Change horizon | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ | ○○○ |
Product-based divergences | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ | ●●○ |
Multiple energy carriers | ○○○ | ○○○ | ○○○ | ○○○ | ●●● | ○○○ | ●●● |
Labor flexibility | ○○○ | ●●● | ●●● | ○○○ | ○○○ | ○○○ | ○○○ |
Relevant Costs | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ | ●○○ |
Designation 1 | Type | Cooling Output | Power Rating |
---|---|---|---|
CHWDX-1 | Mechanical Chiller | 2814 kWTh | 484 kWElec |
CHWDX-2 | Mechanical Chiller | 2814 kWTh | 484 kWElec |
CHWDX-3 | Mechanical Chiller | 2575 kWTh | 479 kWElec |
CHWAB-1 | Absorption Chiller | 1653 kWTh | 6.9 kWElec |
CHWAB-2 | Absorption Chiller | 1653 kWTh | 6.9 kWElec |
CHWFC-1 | Free-cooling Module | 1250 kWTh | 0 kWElec |
Designation 1 | Output | Power Rating (kWElec) |
---|---|---|
Cooling towers | Flow: 43–260 L/s Range: 40/25 °C (WBT: 21 °C) | 30 |
CW Pumps | Flow: 250 L/s Head: 90 kPa | 37.3 |
HW Pumps | Flow: 65 L/s Head: 50 kPa | 5.6 |
CHW Pumps | Flow: 90 L/s Head: 100 kPa | 15 |
Criteria | Level | |
Controllability: State variable dependent | 1 | |
Criticality: Neutral influence | 3 | |
Interdependence: Inherent decoupling capabilities | 1 | |
Overall Score: Moderate suitability | 3 |
Parameter | Description | |||||
---|---|---|---|---|---|---|
System Description | CHW air-conditioning system to supply space cooling. | |||||
EFM Category | Adaptation of resource allocation | |||||
Operative Concept | Switching between types of cooling generation units to either increase (↑), by prioritizing the usage of mechanical chillers, or decrease (↓), by prioritizing the usage of the absorption chillers, the electrical demand of the system | |||||
Adjustment Factor | Ramp-Up and Down of the specific chiller units. | Adjustment Relationship | Step (On/Off) | |||
MO Amount | MO-1 | Cluster I, ↑ | MO-3 | Cluster II, ↑ | MO Types | Holding |
MO-2 | Cluster I, ↓ | MO-4 | Cluster II, ↓ | |||
Execution Level | Supervisory Level |
Parameter | Value (Min-Max) | Remarks 2 | |||
---|---|---|---|---|---|
Active Duration, ∆tActive | 12 min–8 h | Valid for all four MOs | |||
Planning Duration, ∆tPlanning | 0 | Valid for all four MOs | |||
Perception Duration, ∆tPerception | 15 min–24 h | Valid for all four MOs | |||
Decision Duration, ∆tDecision | <1 min | Valid for all four MOs | |||
Shift Duration, ∆tShift | 5–10 min | Valid for all four MOs | |||
Activation Duration, ∆tActivation | 10.5 min–24.2 h | Valid for all four MOs | |||
Deactivation Duration, ∆tDeactivation | 5–10 min | Valid for all four MOs | |||
Regeneration Duration, ∆tRegeneration | 12 min | Valid for all four MOs | |||
Validity, V | MO-1 | 69% | MO-3 | 31% | |
MO-2 | 69% | MO-4 | 31% | ||
Activation Frequency, NActivation,T | MO-1 | 7092 | MO-3 | 3232 | |
MO-2 | 7092 | MO-4 | 3232 |
Parameter | Value | |||
---|---|---|---|---|
Flexibility Type | Bidirectional (↑↓) | |||
Maximum and Average Flexible Power, ∆Pflex,max (∆Pflex,avg) (kWFlex) | MO-1 | 145.2 (117.2) | MO-3 | 42.9 (25.7) |
MO-2 | 498.9 (440.3) | MO-4 | 145.2 (117.2) | |
Flexible Energy Carrier(s) | Electricity/Hot Water (<95 °C) | |||
Average Flexible Energy 1 Eflex,avg,year (MWhFlex) | MO-1 | 665.1 | MO-3 | 66.5 |
MO-2 | 2498.7 | MO-4 | 303.3 |
Parameter | Value | Description | |||
---|---|---|---|---|---|
Investment Costs, Cinvestment | 33,599.25 € | Minor modifications in the system piping and acquisition of new components for the EMS. | |||
Activation Costs, Cactivation | 0.00 € | No activation costs are considered for the EFM. The costs of each energy carrier are excluded as activation costs as they are used in the net revenue analysis. | |||
Maintenance Costs, Cmaintenance,T | 53,019.56 € | Due to the added rotation, additional maintenance costs have to be accounted for the chiller units. | |||
Expected payback period, τpayback | 3 years | Defined by the company based on industry standards for these investments. | |||
EFM specific cost 1 cflex,T (€/MWhFlex) | MO-1 | 96.6 | MO-3 | 965.6 | Calculated using Equation (4). |
MO-2 | 25.7 | MO-4 | 211.8 |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2020 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
Share and Cite
Tristán, A.; Heuberger, F.; Sauer, A. A Methodology to Systematically Identify and Characterize Energy Flexibility Measures in Industrial Systems. Energies 2020, 13, 5887. https://doi.org/10.3390/en13225887
Tristán A, Heuberger F, Sauer A. A Methodology to Systematically Identify and Characterize Energy Flexibility Measures in Industrial Systems. Energies. 2020; 13(22):5887. https://doi.org/10.3390/en13225887
Chicago/Turabian StyleTristán, Alejandro, Flurina Heuberger, and Alexander Sauer. 2020. "A Methodology to Systematically Identify and Characterize Energy Flexibility Measures in Industrial Systems" Energies 13, no. 22: 5887. https://doi.org/10.3390/en13225887
APA StyleTristán, A., Heuberger, F., & Sauer, A. (2020). A Methodology to Systematically Identify and Characterize Energy Flexibility Measures in Industrial Systems. Energies, 13(22), 5887. https://doi.org/10.3390/en13225887