Next Article in Journal
Fault-Structure-Based Active Fault Diagnosis: A Geometric Observer Approach
Previous Article in Journal
Simulation-Based Coyote Optimization Algorithm to Determine Gains of PI Controller for Enhancing the Performance of Solar PV Water-Pumping System
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

The Analysis of the Symmetrical Short-Circuit Currents in Backup Power Supply Systems with Low-Power Synchronous Generators

by
Dominik Mamcarz
*,
Paweł Albrechtowicz
,
Natalia Radwan-Pragłowska
and
Bartosz Rozegnał
Institute of Electromechanical Conversion, Cracow University of Technology, Warszawska 24 St., 31-155 Cracow, Poland
*
Author to whom correspondence should be addressed.
Energies 2020, 13(17), 4474; https://doi.org/10.3390/en13174474
Submission received: 14 July 2020 / Revised: 20 August 2020 / Accepted: 27 August 2020 / Published: 31 August 2020
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
This paper presents an analysis of the short-circuit currents of a synchronous generator with a rated power of 16 kVA. For this purpose, the authors carried out measurements of real short-circuit currents during laboratory tests. Additionally, a simulation model of the generator was developed according to the individual machines data from the catalog and field calculations in ANSYS Maxwell software. Based on the mentioned research, the authors compared waveforms of the symmetrical short-circuit currents. In this paper, the last compared family of short-circuit current waveforms was obtained using analytic calculations. As the presented comparison shows, the assumed method of selecting short-circuit waveforms impacted their values. However, the difference in energy related to short-circuit currents did not influence on the selection of the short-circuit protections, especially at low values of steady-state short-circuit currents and short time constants characteristic for the generators, performing the functions of an alternative power supply. Regardless of the research method, the results presented in the article show that the selection of the short-circuit protections is complicated in case of hybrid electrical systems equipped with low power generators.

Graphical Abstract

1. Introduction

In recent years, a significant increase in the use of low-power generators by both industrial and individual users has been noticeable, e.g., among generators with diesel engine setups [1]. On the one hand, the installation of low-power generators increases the reliability of the operation of the electrical installation, and thus minimizes losses in the event of a power cut from the industrial network, increasing comfort and safety for households at the same time. On the other hand, the use of generating sets is associated with operational problems and ensuring usage safety.
In the case of high-power generators operating in professional power plants, the use of many protection systems are required, which are designed for rapid interference elimination based on various measurement signals, e.g., measurements based on the method of symmetrical components [2,3]. On the other hand, the occurrence of low- and medium-power generators in grid structures makes it difficult to correctly select adequate protections, especially in hybrid power supply systems, where the installation can be powered from the power system or a generator set operating at low-voltage (LV) and medium-voltage (MV) levels. The protection used in these grids is mainly apparatuses in the form of molded case circuit breakers, fuse switch-disconnectors, and circuit breakers [4,5,6].
Due to the above, an important aspect related to the safety and reliability of hybrid installations is the analysis of generator short-circuit currents. Analyzing the transient states that appear during the occurrence of short-circuits in hybrid systems makes it possible to present the nature of transient phenomena in installations powered from backup sources of electricity [7]. This exposes the problem associated with the selection of protection devices in such installations in terms of their correct operation. This aspect is important due to the widespread use of hybrid installations to power priority receivers, e.g., fire protection installations.
The literature has widely described the phenomena connected with the generator short-circuits [8,9,10,11], but the authors have rarely examined these phenomena in the context of low-power hybrid systems, for example, diesel generators (DGs), where the characteristic low values of the time constants cause fast reaching of the steady-state short-circuit current (which is low as well). The analysis of the obtained results allowed the verification of individual applications of generators in electrical installations in the context of the selection or checking of the installed safety equipment.

2. Synchronous Generators Short-Circuits in Installations

Synchronous generators in the Polish national power system (KSE) are the basic machines used in main power plants (the main generators nodes of KSE) of this system. Also, in the case of generating sets installed as a backup energy sources or electricity sources in places without access to the power grid, synchronous generators are widely used.
Depending on the location of the short-circuit in the power supply system, the short-circuits near and far from generator can be distinguished. These cases have been presented in detail in publications [10,11,12]. Considering the case of using low- and medium-power generators as electricity locations, one can talk about the occurrence of electricity near the generator short-circuit.
The short-circuit current of the cylindrical generator can be described by the following Formulas [10,11,13]:
i k = U f m X d [ g 3 ( t ) c o s   ( ω t + γ 0 ) e t τ a   c o s   γ 0 ] ,
g 3 ( t ) = X d [ ( 1 X d 1 X d ) e t τ d + ( 1 X d 1 X d ) e t τ d + 1 X d ] ,
where
  • U f m = 2   U f maximum phase voltage value,
  • γ 0 —phase shift angle,
  • X d —synchronous reactance,
  • X d —transient reactance,
  • X d —subtransient reactance,
  • τ a —aperiodic time constant [s].
Function given by Formula (2) refers to the three-phase short-circuits.
In the case of dependence on the short-circuit current of generators with salient poles, different values of direct and quadrature parameters of the generator should be taken into account [10,11,14,15]:
i k = U f m X d g 3 ( t ) c o s   ( ω t + γ 0 ) U f m 2 e t τ a   [ ( 1 X d + 1 X q ) c o s   γ 0   ( 1 X d 1 X q ) c o s   ( 2 ω t + γ 0 )   ]
where
  • X q quadrature axis subtransient reactance.
Both Formulas (1) and (3) refer to three-phase short-circuits. This type of short-circuit does not cause asymmetry in the load of individual generator windings.
An important problem associated with the operation of low-power synchronous generators are the relatively small values of the subtransient and transient electromagnetic time constants of these generators, generally defined as:
τ d = L d R a [ s ] ,
τ d = L d R a [ s ] ,
where
  • τ d —direct axis short-circuit transient time constant [s],
  • τ d —direct axis short-circuit sub-transient time constant [s],
  • L d —direct axis transient inductance [H],
  • L d —direct axis sub-transient inductance [H],
  • R a —armature resistance [].
Due to fact that in low-power generators, the time constants take values from a few to several dozen milliseconds, the processes of displacing the magnetic flux from the rotor pass away in a short time and the generator quickly goes to steady-state short-circuit.
An important issue related to the analysis of short-circuit currents in installations with a low-power synchronous generator is the resistance of conductors, as well as their inductive reactance. It should be noticed that unlike commercial power, the engineering near the generator short-circuits, as well as the modification of the formula for the near the short-circuit current of a generator, are slightly different. In Formula (1), considering the generators operating in the KSE, in the case of a short-circuit on a transmission line close to the power plant, one should also take into account the line reactance X s to the short-circuit location, which defines the relationship:
i k = U f m [ ( 1 X d + X s 1 X d + X s ) e t τ d s + ( 1 X d + X s 1 X d + X s ) e t τ d s + 1 X d + X s ] ,
where time constant are as follows:
τ d s =   τ d 1 + X s X d 1 + X s X d ,
τ d s = τ d 1 + X s X d 1 + X s X d .
On the other hand, for the analyzed case of a low-power generator working in a low-voltage grid, the considerations should also take into account the wire resistance. The reason is that in the low-voltage installations the resistance R s can have values many times higher than the value of the short-circuit reactance. The near to generator short-circuit current of the low-voltage generator can be calculated from Formula (9).
i k ( t ) = i m ( t ) · ( cos ( ω t + γ 0 ) e t τ a · cos ( γ 0 ) ) ,
where
  • γ 0 —rotor angle in the moment of short-circuit occurring,
i m ( t ) =   i   e t τ d R +   i   e t τ d R + i
i = U f m ( X d + X s ) 2 + R s 2
i = U f m ( 1 ( X d + X s ) 2 + R s 2 1 ( X d + X s ) 2 + R s 2 )
i = U f m ( 1 ( X d + X s ) 2 + R s 2 1 ( X d + X s ) 2 + R s 2 )
  • i —short-circuit steady-state component
  • i   —short-circuit transient component
  • i —short-circuit subtransient component
where time constants are defined as:
τ d R = τ d 1 + X s X d ( 1 + X s X d ) ( 1 + R s R a ) ,
τ d R = τ d 1 + X s X d ( 1 + X s X d ) ( 1 + R s R a ) ,
τ a = X d ω · R a .
Considering the case of a symmetrical short-circuit in a hybrid power supply system with a low-power generator, a significant problem with the value of the short-circuit current is noticeable. For the considered case, the current value is on average equal to about two–three-times the rated current of the generator using field forcing [6]. In installations with installed classic short-circuit protection devices, such as molded case circuit breakers, fuse switch-disconnectors, and circuit breakers, this value of short-circuit current may be insufficient to ensure effective shutdown of the system within the required time, determined by the relevant regulations [16].
Due to such conditions, in order to verify the correctness of short-circuit selection of protection, in the case of a short-circuit, it is important to analyze short-circuit currents in installations powered from synchronous generators (low power) working autonomously or in hybrid installations.
Examples of data for two-poles synchronous generators with a rated voltage of 400 V are presented in Table 1 and Table 2. The generator design has a significant impact on the individual parameters of the synchronous machine equivalent circuit.
Depending on the synchronous generator design, the given values of electrical parameters are expressed in relative units and remain at a similar level to that presented in Table 1 and Table 2. These data are characteristic for specific series of generators from particular manufacturer.
Electromagnetic time constants of subtransient and transient states are presented in Table 3. One can see the extension of time constants (4) and (5) due to generator rated power, which results from the increase of the generator’s inductance according to its resistance with the increase of the generator’s rated power.
For low-voltage electrical installations, the resistance value is greater than the wire reactance. However, these values are small comparing with the generator electrical parameters. Depending on the cross-sectional area, the unit resistance value can vary widely (from hundreds of mΩ/km to single Ω/km). It should be noticed that this value is several times smaller than the value of synchronous reactance X d (in steady-state) for a low-power synchronous generator.

3. Laboratory System and Numerical Model

3.1. Description of the Laboratory System

The analysis of short-circuit currents was carried out for the system fed from a synchronous generator with a rated power of 16 kVA (generator rating data are presented in Table 1).
Despite the generator, the laboratory system consisted of a DC drive machine (MS1322 M32 (made by Leroy-Somer, Angouleme Cedex, France)—shown in Figure 1), a sectional model of the second type line, static load type RL (adjustable resistance load from 0 kW to 9 kW with step 0.6 kW, and inductance reactance from 0 kVAr to 9 kVAr), prepared short-circuit module (Figure 2) and measuring system with data acquisition (diagram of the laboratory model shown in Figure 3), current clamps FLUKE ac i1000s (measurement range 100 A (10 mV/A, accuracy 2% of reading ±5 mV) and 1000 A (1 mV/A, accuracy 1% of reading ±1 mV)), NI USB-6259 measuring card and NI LabView Signal Express software in ver. 15.0.0 (National Instruments Corp., Austin, TX, USA) [19].
The short-circuit module (Figure 2) constructed in the laboratory enabled us to set a short-circuit with a maximum duration time of 2 s and a maximum current withstand of up to 1600 A. According to the appropriate module design, it was possible to perform various types of short-circuits (from single-phase to three-phase). The short-circuit module was placed between transmission line sections. The parameters of each section were the same and equal: R S = 0.22   Ω ,   X S = 0.04   Ω .
This module was also the source of an external trigger for the data acquisition system. The switching moment of the measuring system could be selected in the range of 50–500 ms before a short-circuit occurred. The data acquisition system was created using a National Instruments measuring card, Signal Express software and current sensors using the Hall effect [20].

3.2. Description of the Simulation Models

At first, the simulation model for testing transient processes (short-circuits) in the grid fed from low-power synchronous generators in Matlab/Simulink software in version 10.1 (R2020a) (MathWorks Inc., Natick, MA, USA) was developed (Figure 4) [9].
Field analysis is a useful tool for verifying the correctness of created peripheral models. In this thesis, the authors used the ANSYS Maxwell software in version 2019 R1 (ANSYS Inc., Canonsburg, PA, USA), which complements the concept of generator work modeling [21,22], with the calculation of synchronous generator parameters [23] using the Matlab/Simulink package. Field analysis make it possible not only to model phenomena occurring in electric machines, but also to test selected generator structures before the changes are checked in the real object. According to the fact that the technical data provided in the specification did not contain enough information to enable a faithful reproduction of the analyzed generator in the ANSYS software, technical data were extended by the own dimensioning of the machine in order to reduce the inaccuracy of the field model.
Field analysis were carried out in the ANSYS Maxwell 2D and 3D simulation software for a 16-kVA salient pole synchronous generator. The generator model [24] was created according to the geometric dimensions and electrical data contained in Table 4 and is presented in Figure 5. The created three-dimensional field model of the machine contained 331,743 mesh elements.
The Table 5 summarizes the results of individual parameters of the tested generator based on the catalog data and results obtained from the field calculations.
where
  • R a —armature resistance
  • R f —field resistance
  • R k d —damping cage resistance
Comparing the generator data provided by the manufacturer and the obtained values from the field model, it can be seen that they are similar, except for the direct axis subtransient reactance X d and quadrature reactance X q . Despite these differences, the results of field analysis based on limited construction data were considered sufficient to perform next simulations. In addition, measurements were carried out in the laboratory to determine the real direct axis subtransient reactance X d according to the low slip method. The value obtained was 1.68 Ω, and therefore its result is close to the value determined in the field analysis.

4. Results from Laboratory Measurements, Simulation Tests, and Analytical Calculations

With the usage of Matlab/Simulink program, the simulation model corresponding to the laboratory system was created. Based on the data declared by the manufacturer and those calculated from the field model in the ANSYS Maxwell software, the proper simulations were carried out. Additionally, for manufacture data, the short-circuit currents ware calculated based on the analytical Formulas (9)–(16) mentioned in second paragraph of the article (the results included in Table 6). The obtained simulation results were compared with the real short-circuit current. The authors carried out a series of six measurements of the generator short-circuit current waveform, starting from the short-circuit occurring directly at the synchronous generator clamps, through short-circuits modeled after the first, second, third, and fourth section of the second-type line model (counting from the generator side), and ending with the disturbance occurring after the fifth section of the line.
The obtained waveforms were compared with the simulation results according to the catalog data, as well as with the simulation results in which the synchronous machine parameters (determined from field analysis) were used. Figure 6 and Figure 7 show a comparison of the obtained three-phase symmetrical short-circuit current waveforms for the selected generator phase.
The short-circuit current waveforms for the selected generator phase obtained from computer simulations, presented in Figure 6, definitely differ from each other by the surge current values of the short-circuits. The surge current recorded using a laboratory model was 238 A, while for simulations using generator manufacturer data and simulations based on parameters obtained from field analysis, these values were 209 A and 183 A, respectively. The differences appeared due to the inaccuracy of the synchronous machine model used in the Matlab/Simulink software.
This inaccuracy consists in simplifications used in models that do not reflect all phenomena appearing in the generator in a short-circuit, as opposed to the physical laboratory system. Due to the asymmetrical rotor of the machine, a constant component existed for all fault current waveforms. For this reason, the steady-state short-circuit currents were given as peak-to-peak values. The peak-to-peak value for the real measurement was 20 A, for catalog data 16 A, and for calculations based on field results 17 A.
In the last measurement, presented in Figure 7, the surge current value for the laboratory measurement and simulation based on the field model was the same and amounted to 161 A. For the simulation based on the manufacturer’s data, the surge value was 181 A. Partially, the difference follows that the value of γ0 angle was not taken into account in case of the laboratory research. As expected, the steady-state short-circuit currents did not change.
Figure 8 shows the changes in the surge current value depending on the distance of the short-circuit location. The significant impact of each section impedance on the surge current is noticeable as opposed to the steady-state short-circuit current. These data are summarized in Table 6.
  • S—section number (G—generator clamps),
  • LM—results from laboratory model,
  • CM—results based on catalog data,
  • FM—results based on field model.
  • AC—results from analytical calculations (based on catalog data).
For each modeled short-circuit, one can see a change in generator speed. As a result of the generator’s rotational speed decrease, the frequency in power supply network was reduced (Figure 9).
As a result of a short-circuit, one can see a greater decrease in the generator rotor speed directly on the generator clamps than for a short-circuit after the fifth section of the line. This difference resulted from a higher short-circuit current, and thus the generator load moment (which was confirmed by the current values for the initial short-circuit states). Figure 9 shows a reduction of more than 15% in generator speed, which was also associated with the same drop in the frequency of the supply voltage. In the case of a short-circuit after the line fifth section, the frequency decreased by approximately 7%. It should be underlined that, based on the analytical Formulas (1)–(16), the mentioned phenomena does not occur.
However, independent of the short-circuit location, the value of the short-circuit current was the same for both cases. This confirms that for this type of power sets, the line impedance has a negligible effect on the value of the steady short-circuit current. It significantly affected for the initial short-circuit current (for the analyzed cases, the initial current value changes from approximately 240 A to 160 A). This occurred because the values of attached sequentially impedances of each line section constituted approximately 20% of the value of the direct axis subtransient reactance X d declared by the manufacturer. For a steady short-circuit, the impedance of one section was only 0.5% of the direct axis reactance X d of the generator (Figure 9).
Additionally, tests of the generator short-circuit process were carried out, including field forcing (Figure 10). The value of the short-circuit surge current at the generator clamps was close to 270 A. However, a significant difference was visible in the waveforms for the steady-state of the short-circuit, because while using field forcing, the peak-to-peak value was 94 A. Therefore, in the case of properly selected field forcing control system for low-voltage synchronous generator, the achieved short-circuit current was equal about twice the generator rated current.
Due to the design of low-power synchronous generators, time constants values of electrodynamic processes (subtransient and transient) were very small. As a result, for each investigated case, a rapid disappearance of subtransient and transient components was visible. In the second period of the short-circuit, the current amplitude was already at 75 A. In the next one, it was about 50 A (Figure 6 and Figure 7) and still decreased, reaching the value of the steady-state short-circuit current. The protections used in electrical installations for this type of short-circuit current did not work quickly enough and did not disable the short-circuit within two to three periods, for which the current values were relatively large.

5. Conclusions

The short-circuit analysis of low-power synchronous generators presented in the article confirms the thesis of the significant problem of breaking the short-circuit by protections in low-voltage installations.
There are some manufactures recommendations of the generator set need to be take into account regarding the starting currents values of installed devices while choosing the generator power, which, in turn, prevents the full backup supply set use.
Currently, at the Cracow University of Technology, some researches are being conducted concerning the patenting of a new type of protection dedicated to the power sets, which allows for a quick power-off in the case of a short-circuit in a system powered by a low-power synchronous generator, even in the absence of the field forcing. As shown in the waveforms, as a result of the lack of field forcing, the steady short-circuit current has very small values for that currently used on a wide-scale protection, such as fuse switch-disconnectors and miniature circuit breakers, which do not allow the release of a given protection device. The work results on the test device will be disclosed after obtaining patent protection.
The developed field model allowed for an approximate analysis of short-circuit conditions. However, a significant difference in the values of waveforms for small short-circuit loop impedances was visible. It resulted from a much higher value of the subtransient reactance determined in the field model as compared with the catalog data. With full construction data (which the manufacturer does not disclose), it would be possible to create a more accurate model that would allow for more accurate analysis of the low-power generators dynamic states. However, it should be noted that the simulation results for catalog data also differ from the measured current waveforms. These differences are a consequence of numerical calculations and simplifications of the generator model itself implemented in Simulink. Also, in the analytical calculations, there were some differences in short-circuit current value as compared to the other research method. However, regardless of the assumed research method, despite of the impact on the peak values of the short-circuit current, the difference in overall energy carried by the short-circuit current was quite small. Therefore, the adoption of the most simplified research method did not affect the protections selection in electrical systems supplied by synchronous generators as backup energy sources. In turn, the fault location was notable in reference to short-circuit energy (Joule integral).
Nevertheless, the phenomena occurring in the generator for short-circuits are consistent with reality (subtransient, transient, and steady short-circuit). It is worth noticing that the results from laboratory measurements were carried out under more restrictive selection conditions of protective devices. The current values for the initial short-circuit state disappeared very quickly, resulting from short electromagnetic time constants, while the current for the steady-state short-circuit took values lower than the generator’s rated current.
The presented difference between the lack of field forcing and the use of this control method in short-circuit current waveforms leads to the conclusion that it is possible to turn off the circuit faster with a short-circuit by forcing because more energy is released. On the other hand, for all the presented short-circuit cases without the field forcing (unless it is switched off at the surge current), the steady-state short-circuit prevents the correct turn-off of the protected circuit due to the value of the current in this state, which is less than the rated current of the generator.
The short-circuit analysis presented in this paper has shown that due to the relatively low energy of the short-circuit currents in case of hybrid electrical systems, the generators of this systems require individual short-circuit protections. For this reason, while using these systems with the typical short-circuit protections, it is not possible to obtain selectivity of their operation, and their selection is complex.

Author Contributions

Conceptualization, D.M., P.A., N.R.-P. and B.R.; methodology, D.M. and P.A.; software, N.R.-P. and B.R.; formal analysis, B.R.; investigation, D.M. and P.A.; resources, D.M. and P.A.; data curation, D.M.; writing—original draft preparation, P.A. and N.R.-P.; writing—review and editing, D.M. and P.A. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by Polish Ministry of Science and Higher Education and perform by Institute of Electromechanical Energy Conversion (E-2) of Cracow University of Technology.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Drozdowski, P.; Warzecha, A. Mathematical Study and Control of Diesel Rotary Uninterruptible Power Supply. In Proceedings of the 2019 15th Selected Issues of Electrical Engineering and Electronics (WZEE), Zakopane, Poland, 8–10 December 2019; pp. 469–475. [Google Scholar]
  2. Ciontea, C.I. The Use of Symmetrical Components in Electrical Protection. In Proceedings of the 72nd Conference for Protective Relay Engineers (CPRE), College Station, TX, USA, 25–28 March 2019; pp. 1–8. [Google Scholar]
  3. Chicco, G.; Mazza, A. 100 Years of Symmetrical Components. Energies 2019, 12, 450. [Google Scholar] [CrossRef] [Green Version]
  4. Ludwinek, K.; Szczepanik, J.; Sułowicz, M. Experimental analysis of assessing of the tripping effectiveness of miniature circuit breakers in an electrical installation fed from a synchronous generator set. Electr. Power Syst. Res. 2017, 142, 341–350. [Google Scholar] [CrossRef]
  5. Ryszard, K.; Andrzej, K.; Marek, K.; Piotr, M.; Marek, S.; Krzysztof, L.; Jan, S.; Roman, N. Assessing of the tripping effectiveness of fuses in electrical installation fed from a synchronous generator set. In Proceedings of the 2015 Selected Problems of Electrical Engineering and Electronics (WZEE), Kielce, Poland, 17–19 September 2015; pp. 1–4. [Google Scholar]
  6. Albrechtowicz, P.; Szczepanik, J. The analysis of the effectiveness of standard protection devices in supply systems fed from synchronous generator sets. In Proceedings of the 2018 International Symposium on Electrical Machines (SME): SME 2018, Andrychów, Poland, 10–13 June 2018; pp. 1–5. [Google Scholar]
  7. Razzaghi, R.; Davarpanah, M.; Sanaye-Pasand, M. A Novel Protective Scheme to Protect Small-Scale Synchronous Generators against Transient Instability. IEEE Trans. Ind. Electron. 2013, 60, 1659–1667. [Google Scholar] [CrossRef]
  8. Chiver, O.; Neamt, L.; Matei, O. Comparative study on sudden short-circuit currents of a synchronous generator. In Proceedings of the 2015 IEEE 15th International Conference on Environment and Electrical Engineering (EEEIC), Rome, Italy, 10–13 June 2015; pp. 1688–1693. [Google Scholar]
  9. Hassan, M.A. Dynamic behavior analysis of synchronous generator using MATLAB/SIMULINK. In Proceedings of the 2015 International Conference on Computing, Control, Networking, Electronics and Embedded Systems Engineering (ICCNEEE), Khartoum, Sudan, 7–9 September 2015; pp. 143–148. [Google Scholar]
  10. Latek, W. The Theory of Electrical Machines; WNT: Warszawa, Poland, 1987. (In Polish) [Google Scholar]
  11. Kacejko, P.; Machowski, J. Short Circuits in the Electroenergetic Systems; WNT: Warszawa, Poland, 2020. (In Polish) [Google Scholar]
  12. Parise, G.; Massimiano, M.; Halpin, M. Short circuit analysis on a simple power system network: The “characteristic” currents method. In Proceedings of the Twenty-Seventh Southeastern Symposium on System Theory, Starkville, MS, USA, 12–14 March 1995; pp. 30–34. [Google Scholar]
  13. Samoylenko, V.O.; Korkunova, O.L.; Pazderin, A.V.; Novikov, N.N. Overcurrent protection adjustment when connecting synchronous generation to power supply systems. In Proceedings of the 2015 IEEE International Conference on Industrial Technology (ICIT), Seville, Spain, 17–19 March 2015; pp. 2368–2373. [Google Scholar]
  14. Das, J.C. Short-Circuits in AC and DC Systems: ANSI, IEEE and IEC Standards; Taylor & Francis Inc.: Portland, OR, USA, 2017. [Google Scholar]
  15. Gao, J.; Zhang, L.; Wang, X. AC Machine Systems. Mathematical Model and Parameters, Analysis, and System Performance; Springer: Berlin/Heidelberg, Germany, 2009. [Google Scholar]
  16. Regulation of the Minister for Infrastructure and Construction Amending the Regulation of the Minister for Infrastructure of 12 April 2002 on the Technical Conditions to Be Met by Buildings and Their Location, Dz.U. 2002 nr 75 poz. 690. Available online: http://isap.sejm.gov.pl/isap.nsf/download.xsp/WDU20020750690/O/D20020690.pdf (accessed on 15 June 2002).
  17. Linz Electric Generators. Available online: https://www.linzelectric.com/index.cfm/en/products/ (accessed on 6 July 2020).
  18. Stamford Generators. Available online: https://www.stamford-avk.com/stamford-avk/downloads/data-sheets (accessed on 1 July 2020).
  19. Szczepanik, J.; Rozegnał, B. The development of the real life model of the five node power system. Czas. Tech. Elektrotech. 2015, 112, 83–102. [Google Scholar]
  20. Ludwinek, K. Measurement of momentary currents by Hall linear sensor. Przegląd Elektrotech. 2009, 10, 182–187. [Google Scholar]
  21. Berhausen, S.; Boboń, A. Polowa metoda wyznaczania parametrów i charakterystyk maszyny synchronicznej. Zesz. Probl. Masz. Elektr. 2011, 91, 43–49. [Google Scholar]
  22. Radwan-Pragłowska, N.; Wegiel, T.; Borkowski, D. Parameters identification of coreless axial flux permanent magnet generator. Arch. Electr. Eng. 2018, 67, 391–402. [Google Scholar]
  23. Ai, C.; Lee, C.H.; Kirtley, J.L.; Huang, Y.; Wang, H.; Zhang, Z. A Hybrid Methodology for Analyzing the Performance of Induction Motors with Efficiency Improvement by Specific Commercial Measures. Energies 2019, 12, 4497. [Google Scholar] [CrossRef] [Green Version]
  24. Tikhonova, O.; Malygin, I.; Plastun, A. Electromagnetic calculation for induction motors of various designs by ANSYS maxwell. In Proceedings of the 2017 International Conference on Industrial Engineering, Applications and Manufacturing (ICIEAM), St. Petersburg, Russia, 16–19 May 2017; pp. 1–5. [Google Scholar]
Figure 1. Tested generator with modified excitation system and driving DC machine.
Figure 1. Tested generator with modified excitation system and driving DC machine.
Energies 13 04474 g001
Figure 2. The outside (a) and inside (b) view on the short-circuit module.
Figure 2. The outside (a) and inside (b) view on the short-circuit module.
Energies 13 04474 g002
Figure 3. Diagram of a laboratory system for short-circuit currents analysis in installations powered by a synchronous generator.
Figure 3. Diagram of a laboratory system for short-circuit currents analysis in installations powered by a synchronous generator.
Energies 13 04474 g003
Figure 4. Simulation model in Matlab/Simulink.
Figure 4. Simulation model in Matlab/Simulink.
Energies 13 04474 g004
Figure 5. Three-dimensional model of the tested generator in ANSYS Maxwell 3D.
Figure 5. Three-dimensional model of the tested generator in ANSYS Maxwell 3D.
Energies 13 04474 g005
Figure 6. Waveform of the short-circuit current phase for L 1 phase (first phase of generator) of the synchronous generator for a short-circuit case modeled directly on the generator clamps.
Figure 6. Waveform of the short-circuit current phase for L 1 phase (first phase of generator) of the synchronous generator for a short-circuit case modeled directly on the generator clamps.
Energies 13 04474 g006
Figure 7. Waveform of the short-circuit current phase for L 1 (first phase of generator) phase of the synchronous generator for a short-circuit case modeled after the fifth line section.
Figure 7. Waveform of the short-circuit current phase for L 1 (first phase of generator) phase of the synchronous generator for a short-circuit case modeled after the fifth line section.
Energies 13 04474 g007
Figure 8. Measured peak of short-circuit current value.
Figure 8. Measured peak of short-circuit current value.
Energies 13 04474 g008
Figure 9. Comparison of short-circuit currents and the rotor speed of the generator at the generator clamps and after the fifth line section.
Figure 9. Comparison of short-circuit currents and the rotor speed of the generator at the generator clamps and after the fifth line section.
Energies 13 04474 g009
Figure 10. Short-circuit current while field forcing (case of short-circuit modeled directly on the generator clamps).
Figure 10. Short-circuit current while field forcing (case of short-circuit modeled directly on the generator clamps).
Energies 13 04474 g010
Table 1. Two-poles synchronous generators data with a rated voltage of 400 V from the Linz Electric company [17].
Table 1. Two-poles synchronous generators data with a rated voltage of 400 V from the Linz Electric company [17].
S n   [kVA]1111.513.5162227
Number of Poles222222
X d [%]280239275382373350
X d [%]211922262931
X d [%]5.84.65.3101211
X q [%]155130150166162152
Table 2. Two-poles synchronous generators data with a rated voltage of 400 V from the Stamford company [18].
Table 2. Two-poles synchronous generators data with a rated voltage of 400 V from the Stamford company [18].
S n [kVA]12.51517.52025324045
Number of Poles22222222
X d [%]202185199191204209173186
X d [%]2119201921211813
X d [%]131213121313118
X q [%]1019299961021048693
Table 3. The values of electromagnetic time constants for the subtransient and transient states [11,17].
Table 3. The values of electromagnetic time constants for the subtransient and transient states [11,17].
S n [kVA]71013.5162227 2 × 10 5 6 × 10 5 15 × 10 5
τ d [ms]3333464147548308501210
τ d [ms]5.565.9667232830
Table 4. Geometric and electrical parameters of the 16-kVA generator used in the ANSYS Maxwell.
Table 4. Geometric and electrical parameters of the 16-kVA generator used in the ANSYS Maxwell.
Dimensions
Outer stator diameter270 mm
Inner stator diameter141 mm
Stator length240 mm
Number of stator slots27
Outer rotor diameter135 mm
Inner rotor diameter30 mm
Rotor length240 mm
Shaft diameter30 mm
Electrical data
Rated speed3000 rpm
Rated voltage400 V
Rated apparent power 16 kVA
Rated current23.1 A
Rated power factor0.8
Exciting current7.5 A
Table 5. The 16-kVA generator electrical parameters for catalog data and field model.
Table 5. The 16-kVA generator electrical parameters for catalog data and field model.
Data
Source
R a
[Ω]
R f
[Ω]
R k d
[Ω]
X d
[Ω]
X d
[Ω]
X d
[Ω]
X q
[Ω]
Catalog0.549.791.3038.202.601.0016.60
Field model0.679.84-39.493.221.7010.79
Table 6. Peak short-circuit ( i p ) and peak to peak steady-state short-circuit current ( 2 2 I k = I k p p ) .
Table 6. Peak short-circuit ( i p ) and peak to peak steady-state short-circuit current ( 2 2 I k = I k p p ) .
i p
[A]
I k p p
[A]
i p
[A]
I k p p
[A]
i p
[A]
I k p p
[A]
i p
[A]
I k p p
[A]
i p
[A]
I k p p
[A]
i p
[A]
I k p p
[A]
SG12345
LM238202152020020185201712016120
CM209162031619917191171861718117
FM183171781717417169171651716117
AC190171821717017155171421713017

Share and Cite

MDPI and ACS Style

Mamcarz, D.; Albrechtowicz, P.; Radwan-Pragłowska, N.; Rozegnał, B. The Analysis of the Symmetrical Short-Circuit Currents in Backup Power Supply Systems with Low-Power Synchronous Generators. Energies 2020, 13, 4474. https://doi.org/10.3390/en13174474

AMA Style

Mamcarz D, Albrechtowicz P, Radwan-Pragłowska N, Rozegnał B. The Analysis of the Symmetrical Short-Circuit Currents in Backup Power Supply Systems with Low-Power Synchronous Generators. Energies. 2020; 13(17):4474. https://doi.org/10.3390/en13174474

Chicago/Turabian Style

Mamcarz, Dominik, Paweł Albrechtowicz, Natalia Radwan-Pragłowska, and Bartosz Rozegnał. 2020. "The Analysis of the Symmetrical Short-Circuit Currents in Backup Power Supply Systems with Low-Power Synchronous Generators" Energies 13, no. 17: 4474. https://doi.org/10.3390/en13174474

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop