Next Article in Journal
Initialization and Synchronization of Power Hardware-In-The-Loop Simulations: A Great Britain Network Case Study
Previous Article in Journal
Liquid Lipase-Catalyzed Esterification of Oleic Acid with Methanol for Biodiesel Production in the Presence of Superabsorbent Polymer: Optimization by Using Response Surface Methodology
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Identification and Isolation of Faults in Multi-terminal High Voltage DC Networks with Hybrid Circuit Breakers

School of Electronic Information and Electrical Engineering, Shanghai Jiao Tong University, Shanghai 200240, China
*
Author to whom correspondence should be addressed.
Energies 2018, 11(5), 1086; https://doi.org/10.3390/en11051086
Submission received: 20 March 2018 / Revised: 25 April 2018 / Accepted: 25 April 2018 / Published: 28 April 2018
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
This paper presents a protection scheme to protect multi-terminal high voltage dc (MTDC) networks for interconnection of renewable energy sources. The proposed scheme detects faults by using the Consecutive Data Window Method (CDWM) and harmonics of the system voltage to avoid maloperation of breakers without communication. Fault location is classified and faulty parts is isolated from the rest of the healthier network by using hybrid circuit breakers (HCBs). Moreover; it also categorises the fault with the help of the voltage drop. The rapid response to isolate the faulty portion in a few milliseconds is primarily considered to enhance the reliability and security of the network. The results of simulations verify the efficient fault detection and isolation for different DC faults and the investigation for the impact of significant parameters of the proposed scheme has been considered. The simulations are performed in PSCAD for four terminal MTDC networks to validate the proposed scheme. The performance is also verified under different fault conditions by using Matlab after computing the data from simulations.

1. Introduction

The demand for electrical energy has increased dramatically in recent years and to increase the penetration of renewable energy, MTDC has recognized a key technology for connecting the offshore and onshore renewable energy with the corresponding national grids.
Currently, different concepts for the protection of MTDC network are characterized, each with their own merits and demerits [1,2,3,4,5,6,7]. The first concept is to apply AC breakers on the AC sides. AC interruption is much easier due to the natural zero crossing of the current, but the shortcoming of this concept is the de-energization of the whole system during any troubleshooting, and it clears the fault in 50–100 ms [1]. The second concept is to apply simple DC circuit breakers (DCCB’s) on the DC side of the converters to isolate the fault [2]. This needs more power switches since its cost is high and the on-state losses are intensified. Use of superconducting fault current limiters (FCLs) is a decent concept for the DCCB to limit the current, but it is a costly technology, and alone it cannot entirely break the fault currents [3,4]. The exemplary concept is to apply the HCB to break the faulty portion of the MTDC network selectively and achieve fast interruption during a rising slope within 2–7 ms [5]. Due to excessive dependence on semiconductor devices and new technology, the costs are high, and the technology is not fully mature [6]. It is also concerned with the development of the protection logic having less communication time for co-ordination when acquiring the data and tripping HCBs [7].
The significance of different techniques for the protection of MTDC has been acknowledged and discussed [8,9,10,11,12,13,14,15,16,17,18,19,20,21]. The faults in low voltage DC networks can be indicated by overcurrent [8]. The same concept is not feasible to implement for large-scale MTDC networks since the protection of non-faulted lines can sense the high values of the fault current and also, faults with high resistance are difficult to analyze with the overcurrent. The current differential scheme is an excellent choice to detect the fault selectivity [9]. Time delay to return the fault detection signal is a problem for remote areas in the case of long transmission lines. Moreover, distributed capacitance of line would distort the signal, and precise synchronization of data is required [10,11]. The single-ended differential protection scheme by using the multipoint optical current measuring sensors along with the whole length of transmission lines has been presented in [12]. The differential current method by using predefined threshold values is taken into account, if the load current changes suddenly, the predefined threshold value will not be valid, and it also uses the only current signal for detection of a fault. A method for tracing fault location using multiple measurements at different points with traveling waves in MTDC network is presented in [13]. The need for fast and reliable communication between multiple measuring units may limit its practical implementation. A non-communication- based protection algorithm for MTDC is presented and addresses some issues raised above by the use of current data at one end without communication in [14]. Adding the shunt capacitor may increase its cost as well as complexity for other parameters. The work done in [15] proposed wavelet transform analysis for detection of faulted cables in MTDC arrangements. A discrete wavelet transform is used as criterion for detection of a fault. However, the technique was tested for bolted faults, and not implemented for overhead lines. A differential protection algorithm has been proposed recently for MTDC networks [16]. Since high-speed communication is needed for the execution of the protection scheme, it increases the complications and the cost of the system.
The fault detection performance can be improved for DC lines by utilizing the transient components for designing the protection scheme without communication [17]. A transient fault current technique is used for the protection of MTDC in [18]. The protection scheme is presented for the line current commutated converters since the operation and control of voltage source converter (VSC) are entirely different. Furthermore, the VSC topology is promising and provides more control as compared to a line commutated converter (LCC). Protection schemes have been proposed for two terminal VSC-HVDC networks by using transient harmonics [19,20,21]. Transient harmonics analyzes each terminal of the line to detect the DC faults. Since fault detection is based on the single frequency component, it would be certainly affected by signal noise or filter capacitors. Further investigation is needed for adaptability of harmonic components as fault detection in MTDC networks.
The basic aim of this paper is to identify the fault and isolate the specific faulty portion of a MTDC network in a very short interval with high reliability. In order to solve the aforementioned problem, a protection scheme for the DC line faults is proposed by using CDWM and verified by the harmonics of the system voltage without communication between the terminals. Owing to the non-communication based scheme, the time interval for the protection of MTDC network is reduced significantly. It can carefully detect the fault location and isolate the faulty part from the rest of the MTDC network with the help of HCB. Moreover, it can also classify the nature of a fault with the help of the voltage drop. The proposed scheme is implemented on each terminal of a MTDC network for the protection of the overall system in case of L-L or L-G faults. The focus of the proposed method is to attain rapid fault detection, improving reliability by isolating the faulty part and differentiating among the different faults. Detailed simulations are performed in PSCAD/EMTDC to validate the performance of the proposed scheme for different possible cases in the MTDC network and results are confirmed in Matlab for the accuracy of the proposed method. As the proposed scheme is simulated under various fault conditions in standardized simulation environments, the remarkable response of the proposed scheme in handling the faults, as validated by the results, makes it advantageous for its implementation in real-time systems. Moreover, the response of the different key parameters on the system is also discussed.
The remaining structure of the paper is arranged as follows: Section 2 describes DC faults in MTDC networks. Section 3 and Section 4 present the methodology and protection scheme for detection and isolation of faults. Section 5 explains the simulation of the MTDC network, cable and the concept of HCB model. Results for the propagation delay in cables, different possible fault cases, validation of scheme in Matlab and comparative analysis are discussed in Section 6. The conclusions are drawn in Section 7.

2. DC Faults in MTDC Networks

Potential causes of faults in MTDC networks are mainly categorized into three groups depending on the network topology. The line to ground (L-G) faults either on positive or negative lines, Line to line (L-L) faults and AC side faults in MTDC networks. AC side faults should be isolated with conventional AC side breakers. In the following text, L-G faults and L-L faults are discussed to design the appropriate protection scheme. The protection scheme must protect and differentiate the faults reliably within milliseconds [22,23].
The DC side faults are a challenge to isolate in a limited interval of time to protect the whole system. Moreover, the short circuit with another line or ground faults with low impedance on the DC side propagates a low voltage surge with the speed of light in vacuum and reflects back as a high voltage surge after its arrival at the terminal.
Primary causes of tripping are the L-G faults in the case of overhead lines, due to arcing phenomena triggered by the weather being temporary [24]. The lightning surge can be modeled as a current source that is injected in the line, having the standard surge 1.2/50 µs. On the other hand, most of the faults in cables are permanent due to insulation damage. The healthy pole is significantly affected as the healthy-pole voltage usually jumps towards 2.0 p.u. This would impose significant voltage stress on the pole. Moreover, the L-G faults are not only dependent on the value of fault resistance, but also on the grounding configuration, the impedance of the grounding electrodes and the configuration of the converter transformer. The protection must operate within a minimum time to avoid damage to the converter and the collapse of the whole system.
For the L-L faults, the fault period can be divided into three stages. In the first stage, the capacitors discharge with a sharp peak. The insulated gate bipolar transistor (IGBTs) are blocked to be protected from over current, and the anti-parallel diodes across the IGBT’s conduct in the opposite direction to prevent the valves from over voltage. In the next stage, the DC voltage drops, and at the same time, the link inductance drives with the freewheeling diodes even when the voltage drops to zero. In the last stage, the AC infeed continuously feeds the fault current of DC through the freewheeling diodes in case of half-bridge converters, and the converter can not block it without protection scheme. On the other hand, AC-side infeed can be blocked in case of full-bridge modular multi-level converters (MMCs).
Overcurrents damage the valves, diodes and other sensitive equipment. The IGBTs are turned off within 10 µs at the time of the fault, but the current flows through the freewheeling diodes on the AC sides. Since the topology should have one cycle to avoid damage to the converter, it should work to isolate the fault within a minimum time [22].

3. Methodology

At the time of a fault, the system current and voltage change significantly. These changes should quickly and efficiently identify the fault by using the CDWM.
Consider x ( t ) being a sample of the current signal at an arbitrary time t with a fundamental frequency that is calibrated in radians per second:
x ( t ) = X c cos ω o t + X s sin ω o t
where X c and X s are real numbers.
Some notations are defined for the data window method: the fixed time interval between two samples is Δ t ; moreover, the primary frequency between samples, θ = ω o Δ t .
Also, we consider the samples are taken at different intervals of time at Δ t , 0 and Δ t as expressed below:
x 1 = x ( Δ t ) x 0 = x ( 0 ) x 1 = x ( Δ t )
By relating the samples with the signal amplitudes X c and X s :
[ x 1 x 0 x 1 ] = [ cos θ sin θ 1 0 cos θ sin θ ] [ X c X s ]
X c and X s can be obtained from two samples, and if X c = x 0 and X s = ( x 1 x 0 cos θ ) / sin θ then the output is:
X c = [ x 1 cos θ + x 0 + x 1 cos θ ] 1 + 2 cos 2 θ
X s = [ x 1 x 1 ] 2 sin θ
If the number of samples are k = 1, 2, 3, …; and, the number of windows are l = 1, 2, 3, …; so, the l-th and (l + 1)-th window are compared. In the case where the consecutive windows have different rates of change, a fault identification signal is generated and passes on for fault verification. The last three samples x k + 1 , x k and x k 1 based on the algorithm are pre-fault, fault, and the post-fault samples:
X c ( k ) = [ x k + 1 cos θ + x k + x k 1 cos θ ] 1 + 2 cos 2 θ
X s ( k ) = [ x k + 1 x k 1 ] 2 sin θ
The algorithm described by the equations has three samples of data. The newest sample can be calculated with the old samples. Existing algorithms use sampling rates from four to 64 samples per cycle [25]. In this paper, 16 moving windows in one cycle have been taken as a reference on the AC side for the DC side faults, and a current signal is expressed in Figure 1, the sample time ( Δ t ) will be 1.25 ms. A high sampling rate requires a more powerful processor that can calculate the next window in a very short time.
The fundamental frequency components for K samples per cycle expressed in [25]:
X c = 2 K k = 1 K x k cos ( k θ )
X s = 2 K k = 1 K x k sin ( k θ )
where θ = 2 π / K , and if L is the last sample and to make the results stationary, the equation rotates by the angle, ( K L ) θ :
X ¨ L = k = L K + 1 L x k e j k θ
X ¨ ( L 1 ) = k = L K L 1 x k e j k θ
The subtraction between (10) and (11) is the last point of (10) and first point of (11),
X ¨ L = X ¨ ( L 1 ) + [ x L x L K e j K θ ] e j L θ
Equation (12) is valid for any interval of the window, and the generalised formula for the algorithm becomes:
X c ( n e w ) = X c ( o l d ) + [ x n e w x o l d ] cos ( L θ )
X s ( n e w ) = X c ( o l d ) + [ x n e w x o l d ] sin ( L θ )

4. Identification and Isolation Scheme for MTDC Networks

Based on the aforementioned analysis, the identification and isolation scheme has been expressed in Figure 2. If the signal is entirely periodic, then x n e w = x o l d and the window remains same. On the other hand, when the consecutive windows have a different rate of change, then a trip signal must be generated that can initiate the protection scheme. The currents from each terminal of MTDC network are processed per pole, and the windows are calculated for each signal continuously as in Equation (15):
x 1 ( t ) = x 1 ( k ) , x 1 ( k + 1 ) , x 1 ( k + 2 ) x 1 ( n )
The new window can be calculated from the previous window and compared with each other. Comparison of the consecutive current window should help to identify the fault, and the fault identification criteria are expressed in Equation (16):
x n e w x o l d
There may be a fault or short time harmonics in the system. This can be verified by double-checking through the harmonics of the system voltage, which are extracted through the mathematical modeling based on the discrete Fourier Transform (DFT). Some notations are used for the data window method:
  • VmnH highest value of the harmonics of the system voltage;
  • VnmH second highest value of the harmonics of the system voltage;
  • Vhset the threshold value of the harmonics of the system voltage;
  • Vmn lowest terminal voltage in MTDC network;
  • Vnm second lowest terminal voltage in MTDC network;
The threshold value of the harmonics is set as 0.01 p.u. from a lot of simulations for fault criteria, and if the value of the harmonics VmnH or VnmH is higher than Vhset, a fault on the DC line is verified as expressed in (17). The corresponding relays trip the HCB without communication and initiate the post-fault analysis:
{ V m n H > V h s e t V n m H > V h s e t
For identification of fault location and categorization of the nature of the fault, further, analysis of the voltages and categorizing them by the voltage level is expressed in the post-fault analysis in Figure 2. The lowest terminal voltage Vmn is nearest to the fault place. Similarly, to find the direction of fault location from the lowest terminal voltage, the second lowest terminal voltage Vnm should help to find the direction of fault as presented in (18). A trip single is generated respectively for HCBs to isolate the faulty portion. Thus, to find the nature of the fault, the voltage drop must be compared to post-fault analysis. If the voltage drops to zero, then there should be a L-L fault. Otherwise, there would be a L-G fault. Moreover, the above statement is not valid in some conditions. If there is a highly resistive L-L fault, then the voltage will not drop to zero. In the case of L-G faults, the faulted pole voltage will collapse towards zero while the healthy pole voltage will jump towards 2 p.u.
V m n Ι Ι V n m = = 0

5. Simulation Model

Different fault situations are analyzed in a four-terminal MTDC network as expressed in Figure 3 by using the PSCAD. This section explains the simulation of different components of MTDC network.

5.1. Network and Converter Model

The four terminal MTDC network is modeled in PSCAD as expressed in Figure 3 and the parameters of the system are described in Table 1. Terminal 1 and 4 are connected to offshore wind generation. Terminal 2 and 3 are connected to the AC grids. Different fault cases are modeled to evaluate the performance of proposed protection scheme. Moreover, the effects of key parameters to identify the fault current and terminal voltage for different values are also examined critically.
The equivalent model of the VSC converter is modeled as ±300 kV bipolar half-bridge as expressed in Figure 4, which contains six IGBT valve group having its corresponding freewheeling diodes. For the protection of IGBT’s from the overcurrent, the firing pulses would block within the shortest time when the value of current reaches twice to its nominal value. Meanwhile, the fault current will feed to the DC side through freewheeling diodes from the AC side grids.

5.2. Cable Model

The precise frequency dependent cable model cross-section is obtained from a real 230 kV XLPE VSC-HVDC cable for submarine power transmission [26,27,28,29]. The cross-section of cable was calibrated up to 300 kV. The diameter of the insulations and copper conductor and material characteristics are based on values specified in [30]. All layers are separately illuminated with the diameters in Figure 5. The sheath of the cable is considered to be grounded at each cable connecting point that is about 900 m as presented in [31] to avoid over voltages in the sheath during the faults of line-to-sheath for equal ground potential.

5.3. MTDC Hybrid CB Model and Its Behaviour

Arc quenching processes are challenging in DC systems due to the absence of natural zero crossing and dissipation of stored energy as compared to AC systems. Arcless interruption of fault currents is presented in [32]. Interruption time for the fault current is a big concern for MTDC networks for isolation of faulty parts from rest of the system. The hybrid HVDC circuit breaker (HCB) is an essential component for a MTDC network to cope with the operation time constraints [33].
Figure 6 explains the construction and control logic of HCB for a MTDC network. The HCB contains a load commutation switch (LCS), ultrafast mechanical disconnector (UFMD) and main breaker (MB). During normal operation of the HCB, the load current flows through a nominal path that comprises of LCS and UFMD. At the time of fault, the conducting current rises proportionally, as the fault current. A 20% increase in LCS current above the nominal current level triggers the fault mode on, and an LCS switch off signal is generated. As the LCS is turned OFF, the fault current is commutated to the commutation path, and UFMD disconnects one side of LCS. At the moment, the commutation path interrupts the fault current, and energy of the fault is absorbed by the arrestor bank. As a result, the control logic can disconnect the fault within a short time period.
Simulations are performed in PSCAD/EMTDC for a fault current interruption sequence by the HCB and results are discussed below. In normal operating conditions, all current flows through the nominal path, which has negligible on state losses. At the time of the fault, the normal current exceeds the threshold limit, and the load commutation switch (LCS) triggers in 0.1 ms (magenta curve). After that, ultra-fast mechanical switch (UFMS) disconnects the nominal path and entire exceeded current moves towards commutation path (red curve) as exposed in Figure 7. The main MB interrupts the fault current in just 2 ms after the fault, and the arrestor absorbs the fault current energy (blue curve). The fault current completely dies out through the arrestor in the next few milliseconds. Similarly, the voltage of the system (light blue curve) also decreases to zero in a few microseconds as shown in Figure 7 for the voltage. The arrester has absorbed the fault current energy (magenta curve). The energy absorbed by the arrestor of HCB is 2.85 MJ. The di/dt can be reduced by the use of the current limiting reactor in series with HCB [34].

6. Results and Discussion

The simulation results are expressed and analyzed for four terminal MTDC network based on VSC. In this paper, different fault cases are discussed, which comprise of L-G and L-L faults at different locations. The L-L DC fault is more severe for interrupting the MTDC network as compared to the L-G fault. In all simulations, the currents in the DC cables, HCB’s currents and harmonics voltage of the VSC terminals are inspected to understand how the fault current progresses during fault conditions. Hence, these parameters are essential to implement the protection scheme. Fault location and clearing time are not foreseeable in large MTDC networks. Also, it is essential to check the terminal voltage and power in the VSC converters, which are used to analyze the system behavior. Moreover, the proposed protection scheme is also validated with the Matlab after computing the data from simulations. Furthermore, the impact of the key parameters for the proposed scheme is evaluated. At last, the proposed protection scheme is compared with some previously existing protection schemes.

6.1. Propagation Delay of the Cable

The significance of wave propagation delays from the fault point to the relay locations is considered in this section. The wave propagation delay is modeled by using a detailed DC cable model [35]. The propagation speed is taken as the speed of light through the fiber optic (200 km/ms). A L-G fault at t = 1.0 s is incepted in the middle of L3, and the length of the line is 400 km. Propagation delay in the MTDC network is verified in Figure 8. The fault surge should arrive after 1 ms time delay at each terminal. If is the fault current at the fault point If3 and If4 are the currents at the VSC3 and VSC4 terminals respectively. The fault surge arrived at terminal 3 and 4 after 1 ms time delay as can be seen in Figure 8. Consideration of time delay is an essential aspect in designing the protection scheme of MTDC network.

6.2. L-G Fault Without Protection Topology

Analysis of a fault without any protection scheme is motivating to evaluate the fault behavior in the network. It is interesting to find the fault current values to design the protection scheme for MTDC networks. Therefore, a L-G fault is analyzed at the center of L3 to examine the system voltage, power, currents in the circuit breakers (CB) and dc cables as expressed in Figure 9, Figure 10, Figure 11 and Figure 12. A fault is incepted at t = 1.0 s as can be seen in the results. Figure 9 depicts the terminal voltage and power of the system. At the time of the fault, all terminal voltages drop according to the distance from the fault location. Since Vdc3 and Vdc4 effects more because of the nearest location. However, Vdc4 drops greatly because of the single source at terminal 4 as compared to the terminal 3. Moreover, the power at terminal 3 rise more because of the nearest location to the fault and also due to the infeed of terminal 1 and 2. The findings of the DC current have shown that the capacitors at VSC’s discharge quickly and will cause the transient for a very short time during the first peak. After words, the ac infeed starts to feed the fault current as the dc voltage level below the voltage of the ac side of the terminal and freewheeling diodes become conducting. Meanwhile, it also charges the dc capacitors. The dc capacitors periodically charged and discharged during the fault time. The downfall current shows the charging of capacitances. The fault and pre-fault currents in the HCB’s is expressed in Figure 11. The initial transient fault currents drop to 1–2 p.u. with a time constant of 70–80 ms depending upon the location. Figure 12 expressed the 12th harmonic voltages for different faults. In the top Figure, the fault occurs in the middle of the line, and the harmonics are above the threshold limit, and it arrived at T-3 and T-4 at the same time. In the middle Figure, the fault is near to the T-3. Since the harmonics at T-3 (red curve) arrived earlier then T-4 (blue curve). Likewise in the bottom Figure, the fault is near to the T-4. The harmonics at T-4 (blue curve) arrived earlier then T-3 (red curve). In normal condition, the p.u. harmonics are zero, and at the time of the fault, its value exceeds the threshold value. As a result, it is concluded that whenever the fault occurs and the parameters of the system cross the boundary values, the protection scheme must be operated properly.

6.3. Different Fault Cases to Analyze the Proposed Scheme

To assess the suggested protection scheme performance of MTDC network, different fault cases are analyzed. All possible conditions are discussed and described in Table 2.

6.3.1. Case I

A L-G fault F1 is simulated at the center of line 3 to assess the performance of the proposed technique, and the fault occurs at t = 1.0 s. At the time of the fault, the current in the lines showed an abrupt change. This abrupt change has been identified by the CDWM and verified with the harmonics of the system voltage as explained in Section 4 to detect the fault. The proposed method has analyzed the fault location according to the protection technique and sent a trip signal to HCB34 (black curve) and HCB43 (green curve) at 3 ms after the fault to disconnect the faulty part as seen in Figure 13. The HCBs take 7 ms to completely break the circuit as observed in the HCB modeling. Afterward, the faulty part fully disconnects from the healthy network, and the remaining part becomes stable as shown in Figure 14, Figure 15 and Figure 16. Since before the fault, the voltage is stable to its rated values as can be seen in Figure 14. During the fault, the Vdc3 and Vdc4 get affected as they are nearest to the fault location. After clearing the fault by the HCB34 and HCB43, the faulted terminals are disconnected, and the voltage becomes zero. Therefore, rest of the system becomes stable. Similarly, Figure 15 expresses the DC currents of the system. Idc3 and Idc4 are tripped by the respective breakers.

6.3.2. Case II

A L-G fault F2 is simulated at an unequal distance on line 3 as it can be seen in Figure 3. The fault location is 100 km from terminal 4 and 300 km from terminal 3. Due to the propagation delay, the effect of fault propagates at terminal 4 earlier than terminal 3. Therefore, a trip signal is received earlier at HCB43 (green curve) than HCB34 (black curve) as displayed in Figure 17 after verifying the fault. The fault currents, voltages and powers of the effected part have been depicted in Figure 18. The effect of fault current at terminal 4 has arrived just in 0.5 ms (blue curve). Moreover, the fault current at terminal 3 has arrived with a delay of 1 ms (red curve).
The proposed method has tripped HCB34 and HCB43 to disconnect the faulty part with the same sequence of the protection scheme. Currents, voltages, and powers of the effected part become zero after clearing the fault and remaining part becomes stable.

6.3.3. Case III

A L-L fault F3 is simulated near the terminal 4 as can be seen in Figure 3. The L-L fault is the most severe case for the interruption in the MTDC network. The current rises multiple times, and the voltage drops to zero as shown in Figure 19. After identifying the aforementioned changes in the current, and harmonics voltages of the system. The proposed scheme successfully trips HCB43 and HCB34 without physical communication among the terminals and also classifies the nature of L-L fault with the post-fault analysis.

6.4. Validation of Protection Scheme with Matlab

The proposed protection scheme performance is tested and verified under different fault conditions by using Matlab after computing the data from simulations. Figure 20 shows the different fault conditions from fault A to fault F, and Table 3 express the output results. Results show that the harmonics of the voltage are above the set value of the fault detection criteria and it has successfully detected the fault for all cases and generated the trip signal for the closest circuit breaker from the fault point. Meanwhile, fault classification has been achieved by the use of post-fault analysis with communication. The outcomes prove that the proposed protection scheme is promising for VSC-MTDC network.

6.5. Impact Analysis of Different Key Parameters on the Proposed Scheme

DC capacitors and surrounding feeder cable capacitances are dominant elements for the first few microseconds, whenever a fault occurs. Subsequently, the capacitive discharges die out in a short time interval with higher di/dt values. Afterward, the infeed of the AC is the main contributor to the fault current, and it also charges the capacitive components periodically. This capacitive charge is discharged through fault resistance. Fault resistance, DC capacitance, and surrounding feeder length mainly affect the fault currents and terminal voltages. Hence, these are the key parameters that mainly affect the proposed scheme and detailed simulation results expressed in Table 4.
Fault resistance value influences the value of fault current; CB current and terminal voltage drop. Simulation results have illustrated the dependence of fault resistance to the proposed scheme. Size of fault resistance has been varied from 0.01 Ω to 200 Ω, keeping all other parameters constant. Results proved a decrease in the value of fault current and voltage drop with increasing value of fault resistor. At 200 Ω fault resistance, fault current reduced less than 1 kA, and voltage drop was also negligible.
Similarly, the value of the DC capacitor also affects the value of the fault current, CB current, and terminal voltage drop. The results of simulations have explained its dependence on the DC capacitance. Size of DC capacitor has been varied from 35     μ F to 1000 μ F , and all the other constraints are kept constant. Results proved that decrement in the value of voltage drop and fault current was associated with incremental DC capacitance values. More substantial value of capacitor size stabilized the terminal voltage.
Surrounding cable length has less influence on the fault current and voltage drop due to its capacitance. Hence it cannot be ignored. The value of surrounding cable L 2 affected the fault current and terminal voltage drop. Results illustrate the dependence of fault current and voltage drop on the length of the conductor. The length of cable has been varied from 100 km to 1000 km keeping all other parameters constant. The results have proven that the value of fault current and voltage drop increases with the increase of surrounding cable length. The surrounding cable length does not affect much and has the dominating effect of discharging cable in first few milliseconds. Increase in cable length can also increase the time delay of contribution from rest of the system that is connected to the cable.

6.6. Comparative Analysis

The proposed protection scheme is compared with some state-of-the-art techniques. DC fault ride through the scheme is expressed in [36], which is based on the differential current technique, and need physical communication for operating the protection scheme. The proposed scheme does not require any communication time delay, as no communication is required for obtaining current signals from both ends. In short, the operating time of CDWM is much rapid as compared to the existing schemes, and it is based on current as well as voltage to enhance the reliability of the system. The analytical formulas for the calculation of fault current are proposed in [37]. Hence, it is only valid for the L-G fault and discusses the dominating period of the ac infeed only. On the other hand, the proposed scheme is equally viable for both L-G and L-L faults, as shown in Table 3. The single-ended differential protection scheme is a reliable competitor for protection of MTDC by using multipoint optical current computing sensors across the intact length of transmission lines [12]. It uses a differential current method by utilizing the predefined threshold values. However, in case of sudden changes in the load current, the predefined threshold values are not valid. Moreover, the only current signal is used for fault detection. Likewise, multiple sensors are installed along the transmission line that may become less efficient or defective with the passage of time. As a result, it effects the performance of overall system. The other downsides of this technique are heavy capital and maintenance cost of the optical sensors as well as fiber optic cable. As compared to it, the proposed scheme doesn’t need any communication for measuring the differential current, it is not only based on the current signal to enhance the reliability of the system, there is no heavy cost in executing the proposed scheme.

7. Conclusions

This paper proposes a fault detection scheme based on CDWM for the protection of MTDC networks connected to large-scale renewable energy sources. It is found that the proposed protection scheme can correctly recognize and precisely identify a fault and its location with CDWM and the harmonics of the system voltage without communication. It offers significant fault clearing time by the use of hybrid CB with high reliability for the MTDC network. The proposed scheme can categorize the nature of faults in a way that is equally viable for all kinds of faults. Comprehensive simulation results validate the performance of our proposed scheme for four terminal MTDC networks with different fault scenarios. The results show the adequate isolation of the faulty parts and concurrent stabilization of the rest of the system. The outcomes are also verified with Matlab to recheck the results. Moreover, the impact of key parameters is taken into account at different values to examine the proposed protection scheme under different parameters.

Author Contributions

All authors contributed to this work. M.H.N. researched the fault analysis theories, fault identification principle and drafted the article. X.Z. provided the results of the simulation. Valuable comments on the first draft were received from N.T. and M. G. were involved in revising the final manuscript.

Acknowledgments

This work was partially supported by Shanghai Rising-Star Program (18QA1402100), National Key Research and Development Program of China (2016YFB0900601) and National Natural Science Foundation of China (51407115, 51377104).

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Franck, C.M. HVDC circuit breakers: A review identifying future research needs. IEEE Trans. Power Deliv. 2011, 26, 998–1007. [Google Scholar] [CrossRef]
  2. Merlin, M.M.C.; Green, T.C.; Mitcheson, P.D.; Trainer, D.R.; Critchley, D.R.; Crookes, R.W. A new hybrid multi-level voltage-source converter with dc fault blocking capability. In Proceedings of the 9th IET International Conference on AC and DC Power Transmission, London, UK, 19–21 October 2010. [Google Scholar]
  3. Chen, Y.; Liu, X.; Sheng, J.; Cai, L.; Jin, Z.; Gu, J.; An, Z.; Yang, X.; Hong, Z. Design and application of a superconducting fault current limiter in DC systems. IEEE Trans. Appl. Supercond. 2014, 24, 1–5. [Google Scholar] [CrossRef]
  4. Mokhberdoran, A.; Carvalho, A.; Silva, N.; Leite, H. Antonio Carrapatoso. Application study of superconducting fault current limiters in meshed HVDC grids protected by fast protection relays. Electr. Power Syst. Res. 2017, 143, 292–302. [Google Scholar] [CrossRef]
  5. Tahata, K.; El Oukaili, S.; Kamei, K.; Yoshida, D.; Kono, Y.; Yamamoto, R.; Ito, H. HVDC circuit breakers for HVDC grid applications. In Proceedings of the 11th IET International Conference on AC and DC Power Transmission, Birmingham, UK, 10–12 February 2015. [Google Scholar]
  6. Descloux, J.; Raison, B.; Curis, J.-B. Protection strategy for undersea MTDC grids. In Proceedings of the PowerTech (POWERTECH), Grenoble, France, 16–20 June 2013. [Google Scholar]
  7. Van Hertem, D.; Ghandhari, M. Multi-terminal VSC HVDC for the European super grid: Obstacles. Renew. Sustain. Energy Rev. 2010, 14, 3156–3163. [Google Scholar] [CrossRef]
  8. Baran, M.E.; Mahajan, N.R. Overcurrent protection on voltage source-converter-based multiterminal DC distribution systems. IEEE Trans. Power Deliv. 2007, 22, 406–412. [Google Scholar] [CrossRef]
  9. Sneath, J.; Rajapakse, A.D. Fault detection and interruption in an earthed HVDC grid using ROCOV and hybrid DC breakers. IEEE Trans. Power Deliv. 2016, 31, 973–981. [Google Scholar] [CrossRef]
  10. Wentao, H.; Tai, N.; Zheng, X.; Fan, C.; Yang, X.; Kirby, B.J. An impedance protection scheme for feeders of active distribution networks. IEEE Trans. Power Deliv. 2014, 29, 1591–1602. [Google Scholar]
  11. Zheng, X.; Tai, N.; Thorp, J.S.; Xia, Y. Improved differential protection scheme for long distance UHVDC transmission line. In Proceedings of the IEEE PES General Meeting Conference & Exposition, National Harbor, MD, USA, 27–31 July 2014. [Google Scholar]
  12. Tzelepis, D.; Dyśko, A.; Fusiek, G.; Nelson, J.; Niewczas, P.; Vozikis, D.; Orr, P.; Gordon, N.; Booth, C.D. Single-ended differential protection in mtdc networks using optical sensors. IEEE Trans. Power Deliv. 2017, 32, 1605–1615. [Google Scholar] [CrossRef]
  13. Azizi, S.; Afsharnia, S.; Sanaye-Pasand, M. Fault location on multi-terminal DC systems using synchronized current measurements. Int. J. Electr. Power Energy Syst. 2014, 63, 779–786. [Google Scholar] [CrossRef]
  14. Abu-Elanien, A.E.B.; Abdel-Khalik, A.S.; Massoud, A.M.; Ahmed, S. A non-communication based protection algorithm for multi-terminal HVDC grids. Electr. Power Syst. Res. 2017, 144, 41–51. [Google Scholar] [CrossRef]
  15. Yeap, Y.M.; Geddada, N.; Ukil, A. Analysis and validation of wavelet transform based DC fault detection in HVDC system. Appl. Soft Comput. 2017, 61, 17–29. [Google Scholar] [CrossRef]
  16. Abu-Elanien, A.E.B.; Elserougi, A.A.; Abdel-Khalik, A.S.; Massoud, A.M.; Ahmed, S. A differential protection technique for multi-terminal HVDC. Electr. Power Syst. Res. 2016, 130, 78–88. [Google Scholar] [CrossRef]
  17. Zheng, X.; Tai, N.; Yang, G.; Ding, H. A transient protection scheme for HVDC transmission line. IEEE Trans. Power Deliv. 2012, 27, 718–724. [Google Scholar] [CrossRef]
  18. Cheng, J.; Guan, M.; Tang, L.; Huang, H. A fault location criterion for MTDC transmission lines using transient current characteristics. Int. J. Electr. Power Energy Syst. 2014, 61, 647–655. [Google Scholar] [CrossRef]
  19. Zheng, X.; Tai, N.; Wu, Z.; Thorp, J.S. Harmonic current protection scheme for voltage source converter-based high-voltage direct current transmission system. IET Gener. Transm. Distrib. 2014, 8, 1509–1515. [Google Scholar] [CrossRef]
  20. Zheng, X.; Tai, N.; Thorp, J.S. A transient harmonic current protection scheme for HVDC transmission line. IEEE Trans. Power Deliv. 2012, 27, 2278–2285. [Google Scholar] [CrossRef]
  21. Liu, J.; Nengling, T.; Fan, C.; Huang, W. Protection scheme for high-voltage direct-current transmission lines based on transient AC current. IET Gen. Transm. Distrib. 2015, 9, 2633–2643. [Google Scholar] [CrossRef]
  22. Le Blond, S.; Bertho, R.; Coury, D.V.; Vieira, J.C.M. Design of protection schemes for multi-terminal HVDC systems. Renew. Sustain. Energy Rev. 2016, 56, 965–974. [Google Scholar] [CrossRef]
  23. Tahir, S.; Wang, J.; Baloch, M.H.; Kaloi, G.S. Digital Control Techniques Based on Voltage Source Inverters in Renewable Energy Applications: A Review. Electronics 2018, 7, 18. [Google Scholar] [CrossRef]
  24. Soares, A.J.; Schroeder, M.A.O.; Visacro, S. Transient voltages in transmission lines caused by direct lightning strikes. IEEE Trans. Power Deliv. 2005, 20, 1447–1452. [Google Scholar] [CrossRef]
  25. Phadke, A.G.; Thorp, J.S. Computer Relaying for Power Systems; John Wiley & Sons: New York, NY, USA, 2009. [Google Scholar]
  26. Bucher, M.K.; Franck, C.M. Contribution of fault current sources in multiterminal HVDC cable networks. IEEE Trans. Power Deliv. 2013, 28, 1796–1803. [Google Scholar] [CrossRef]
  27. Nadeem, M.H.; Zheng, X.; Tai, N.; Gul, M.; Baloch, M.H. Analysis of Fault Current Contribution and Impact of Key Parameters in MTDC Network. Interciencia J. 2017, 42, 257–268. [Google Scholar]
  28. Nadeem, M.; Haroon, T.N.; Zheng, X.; Gul, M. Multi-Terminal HVDC Fault Current Analysis During Line to Ground Fault. In Proceedings of the IEEE, Innovative smart grid technologies IGST Asia 2017, Auckland, New Zealand, 1–5 December 2017. [Google Scholar]
  29. Worzyk, T. Submarine Power Cables: Design, Installation, Repair, Environmental Aspects; Springer Science & Business Media: New York, NY, USA, 2009. [Google Scholar]
  30. Mura, F.; Meyer, C.; de Doncker, R.W. Stability Analysis of High-Power DC Grids. IEEE Trans. Ind. Appl. 2010, 46, 584–592. [Google Scholar] [CrossRef]
  31. Dodds, S.; Railing, B.; Akman, K.; Jacobson, B.; Worzyk, T.; Nilsson, B. HVDC VSC (HVDC light) transmission—Operating experiences. In Proceedings of the CIGRE Session, Paris, France, 22–27 August 2010. [Google Scholar]
  32. Howell, E.K. Arcless Circuit Interrupter. U.S. Patent No. 4,636,907, 13 January 1987. [Google Scholar]
  33. Callavik, M.; Blomberg, A.; Hafner, J.; Jacobson, B. The hybrid HVDC breakers: An innovation breakthrough enabling reliable HVdc grids. In Proceedings of the ABB Grid System Technology Paper, Dresden, Germany, 18–21 November 2012. [Google Scholar]
  34. Poor, A.H.; Hafner, J.; Jacobson, B. Technical assessment of load commutation switch in hybrid HVdc breaker. In Proceedings of the 7th ECCE ASIA International Conference Power Electron, Hiroshima, Japan, 18–21 May 2014. [Google Scholar]
  35. Descloux, J.; Raison, B.; Curis, J.-B. Protection strategy for undersea MTDC grids. In Proceedings of the IEEE Power Tech, Grenoble, France, 16–20 June 2013. [Google Scholar]
  36. Sanusi, W.; al Hosani, M.; El Moursi, M.S. A novel DC fault ride-through scheme for MTDC networks connecting large-scale wind parks. IEEE Trans. Sustain. Energy 2017, 8, 1086–1095. [Google Scholar] [CrossRef]
  37. Bucher, M.K.; Franck, C.M. Analytic approximation of fault current contribution from AC networks to MTDC networks during pole-to-ground faults. IEEE Trans. Power Deliv. 2016, 31, 20–27. [Google Scholar] [CrossRef]
Figure 1. Moving data window of the current signal for 16 windows per cycle.
Figure 1. Moving data window of the current signal for 16 windows per cycle.
Energies 11 01086 g001
Figure 2. Flow chart of the identification and isolation scheme.
Figure 2. Flow chart of the identification and isolation scheme.
Energies 11 01086 g002
Figure 3. MTDC network layout with different faults.
Figure 3. MTDC network layout with different faults.
Energies 11 01086 g003
Figure 4. VSC-based HVDC converter.
Figure 4. VSC-based HVDC converter.
Energies 11 01086 g004
Figure 5. Cable cross-sectional layout.
Figure 5. Cable cross-sectional layout.
Energies 11 01086 g005
Figure 6. Hybrid circuit breaker model.
Figure 6. Hybrid circuit breaker model.
Energies 11 01086 g006
Figure 7. Hybrid circuit breaker response during the fault interruption. (a) Fault current for nominal, commutation and absorber path; (b) System and breaker voltage; (c) Energy absorbed by the arrester.
Figure 7. Hybrid circuit breaker response during the fault interruption. (a) Fault current for nominal, commutation and absorber path; (b) System and breaker voltage; (c) Energy absorbed by the arrester.
Energies 11 01086 g007
Figure 8. Propagation delay due to line length.
Figure 8. Propagation delay due to line length.
Energies 11 01086 g008
Figure 9. L-G fault in MTDC network without protection topology (a) Terminal voltages; (b) system power.
Figure 9. L-G fault in MTDC network without protection topology (a) Terminal voltages; (b) system power.
Energies 11 01086 g009
Figure 10. Fault current during L-G fault in DC lines. (a) DC current in line 1 and 2; (b) DC current in line 3 and 4.
Figure 10. Fault current during L-G fault in DC lines. (a) DC current in line 1 and 2; (b) DC current in line 3 and 4.
Energies 11 01086 g010
Figure 11. Fault current during L-G fault in HCBs. (a) Current in HCB12 and HCB21; (b) Current in HCB13 and HCB31; (c) Current in HCB34 and HCB43.
Figure 11. Fault current during L-G fault in HCBs. (a) Current in HCB12 and HCB21; (b) Current in HCB13 and HCB31; (c) Current in HCB34 and HCB43.
Energies 11 01086 g011aEnergies 11 01086 g011b
Figure 12. Harmonic Voltage during a fault (a) L-G fault in the middle of the cable; (b) L-G fault near T-3; (c) L-L fault near T-4.
Figure 12. Harmonic Voltage during a fault (a) L-G fault in the middle of the cable; (b) L-G fault near T-3; (c) L-L fault near T-4.
Energies 11 01086 g012aEnergies 11 01086 g012b
Figure 13. The trip signal for HCBs in case I.
Figure 13. The trip signal for HCBs in case I.
Energies 11 01086 g013
Figure 14. L-G fault at the center of line 3 in MTDC network (a) Terminal voltages; (b) system power.
Figure 14. L-G fault at the center of line 3 in MTDC network (a) Terminal voltages; (b) system power.
Energies 11 01086 g014
Figure 15. Fault current in DC lines for case I. (a) DC current in line 1 and 2; (b) DC current in line 3 and 4.
Figure 15. Fault current in DC lines for case I. (a) DC current in line 1 and 2; (b) DC current in line 3 and 4.
Energies 11 01086 g015
Figure 16. Fault current in HCBs for the case I. (a) Current in HCB12 and HCB21; (b) Current in HCB13 and HCB31; (c) Current in HCB34 and HCB43.
Figure 16. Fault current in HCBs for the case I. (a) Current in HCB12 and HCB21; (b) Current in HCB13 and HCB31; (c) Current in HCB34 and HCB43.
Energies 11 01086 g016aEnergies 11 01086 g016b
Figure 17. The trip signal for HCBs in case II.
Figure 17. The trip signal for HCBs in case II.
Energies 11 01086 g017
Figure 18. System response during L-G fault on line 3, 100 km from terminal 4 (a) Fault current; (b) terminal voltage; (c) system power.
Figure 18. System response during L-G fault on line 3, 100 km from terminal 4 (a) Fault current; (b) terminal voltage; (c) system power.
Energies 11 01086 g018
Figure 19. System response during L-L fault on line 3 near terminal 4 (a) Fault current; (b) terminal voltage; (c) system power.
Figure 19. System response during L-L fault on line 3 near terminal 4 (a) Fault current; (b) terminal voltage; (c) system power.
Energies 11 01086 g019
Figure 20. Different fault condition for the validation of proposed scheme.
Figure 20. Different fault condition for the validation of proposed scheme.
Energies 11 01086 g020
Table 1. System parameters.
Table 1. System parameters.
ParametersValues
Rated power of the converter 1000 MW
AC voltage (L-L, RMS)500 kV
DC voltage±300 kV
X/R of AC network10
Transformer leakage reactance0.10 p.u.
Total resistance of converter diodes0.005 p.u.
Converter phase reactor0.06 p.u.
Table 2. Different fault cases for MTDC network.
Table 2. Different fault cases for MTDC network.
Fault CaseFault NameDescription
IF1L-G fault at the centre of DC line 3. HCB34 and HCB43 should open.
IIF2L-G fault of line 3, 100 km from terminal 4. HCB43 should open earlier than HCB34.
IIIF3L-L fault at line 3 near terminal 4. HCB43 and HCB34 should open, and voltage should drop to zero.
Table 3. Performance of the proposed protection scheme for different fault conditions.
Table 3. Performance of the proposed protection scheme for different fault conditions.
Fault NameVmnH (p.u.)VnmH (p.u.)Vmn (kV)Vnm (kV)Trip SignalClassification Result
A0.0660.043V4 = 157.37V3 = 249.99HCB34, HCB43L-G Fault
B0.0750.068V1 = 154.43V3 = 182.43HCB13, HCB31L-G Fault
C0.1380.099V1 = 139.35V2 = 151.21HCB12, HCB21L-G Fault
D0.0260.022V4 = 0V3 = 193.77HCB43, HCB34L-L Fault
E0.0440.021V2 = 0V1 = 151.23HCB21, HCB12L-L Fault
F0.0490.039V3 = 0V1 = 67.37HCB31, HCB13L-L Fault
Table 4. Influence of the key parameters for the proposed protection scheme.
Table 4. Influence of the key parameters for the proposed protection scheme.
Key ParameterParameter Values Ω/µF/kmIF (kA)VmnH (p.u.)VnmH (p.u.)Vmn (kV)Vnm (kV)
Influence of Fault Resistance0.0115.220.0660.049160.73257.13
1.0013.630.0680.046171.83254.99
10.07.630.0530.038220.09272.45
100.01.380.0270.022266.14291.65
200.00.720.0150.011274.62294.53
Influence of DC Capacitance3515.220.0660.049160.73257.13
10013.300.04380.0317209.86261.15
25010.600.0640.027257.94277.85
5008.380.02980.031281.49288.48
10005.780.01700.0196293.35294.57
Influence of Surrounding Feeder Length10015.220.0660.049160.73257.13
25015.270.0890.038160.17254.71
50015.900.0710.039159.08251.69
100016.110.0700.040158.81250.19

Share and Cite

MDPI and ACS Style

Nadeem, M.H.; Zheng, X.; Tai, N.; Gul, M. Identification and Isolation of Faults in Multi-terminal High Voltage DC Networks with Hybrid Circuit Breakers. Energies 2018, 11, 1086. https://doi.org/10.3390/en11051086

AMA Style

Nadeem MH, Zheng X, Tai N, Gul M. Identification and Isolation of Faults in Multi-terminal High Voltage DC Networks with Hybrid Circuit Breakers. Energies. 2018; 11(5):1086. https://doi.org/10.3390/en11051086

Chicago/Turabian Style

Nadeem, Muhammad Haroon, Xiaodong Zheng, Nengling Tai, and Mehr Gul. 2018. "Identification and Isolation of Faults in Multi-terminal High Voltage DC Networks with Hybrid Circuit Breakers" Energies 11, no. 5: 1086. https://doi.org/10.3390/en11051086

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop