A Three-Stage Procedure for Controlled Islanding to Prevent Wide-Area Blackouts

1
State Grid Henan Economic Research Institute, Zhengzhou 450000, China
2
School of Electrical Engineering, Zhejiang University, Hangzhou 310027, China
3
Department of Electrical, Computer and Systems Engineering, Rensselaer Polytechnic Institute, Troy, NY 12180, USA
*
Author to whom correspondence should be addressed.
Received: 11 October 2018 / Revised: 29 October 2018 / Accepted: 4 November 2018 / Published: 7 November 2018
(This article belongs to the Section Electrical Power and Energy System)
Full-Text   |   PDF [2510 KB, uploaded 7 November 2018]   |  

Abstract

Controlled islanding has been proposed as a last resort action to stop blackouts from happening when all standard methods have failed. Successful controlled islanding has to deal with three important issues: when, and where to island, and the evaluation of the dynamic stability in each island after islanding. This paper provides a framework for preventing wide-area blackouts using wide area measurement systems (WAMS), which consists of three stages to execute a successful islanding strategy. Normally, power system collapses and blackouts occur shortly after a cascading outage stage. Using such circumstances, an adapted single machine equivalent (SIME) method was used online to determine transient stability before blackout was imminent, and was then employed to determine when to island based on transient instability. In addition, SIME was adopted to assess the dynamic stability in each island after islanding, and to confirm that the chosen candidate island cutsets were stable before controlled islanding was undertaken. To decide where to island, all possible islanding cutsets were provided using the power flow (PF) tracing method. SIME helped to find the best candidate islanding cutset with the minimal PF imbalance, which is also a transiently stable islanding strategy. In case no possible island cutset existed, corresponding corrective actions such as load shedding and critical generator tripping, were performed in each formed island. Finally, an IEEE 39-bus power system with 10 units was employed to test this framework for a three-stage controlled islanding strategy to prevent imminent blackouts. View Full-Text
Keywords: blackouts; cascading outages; controlled islanding; power flow (PF) tracing; slow coherency blackouts; cascading outages; controlled islanding; power flow (PF) tracing; slow coherency
Figures

Figure 1

This is an open access article distributed under the Creative Commons Attribution License which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited (CC BY 4.0).
SciFeed

Share & Cite This Article

MDPI and ACS Style

Shao, H.; Mao, Y.; Liu, Y.; Liu, W.; Sun, S.; Jia, P.; Miao, F.; Yang, L.; Han, C.; Zhang, B. A Three-Stage Procedure for Controlled Islanding to Prevent Wide-Area Blackouts. Energies 2018, 11, 3066.

Show more citation formats Show less citations formats

Note that from the first issue of 2016, MDPI journals use article numbers instead of page numbers. See further details here.

Related Articles

Article Metrics

Article Access Statistics

1

Comments

[Return to top]
Energies EISSN 1996-1073 Published by MDPI AG, Basel, Switzerland RSS E-Mail Table of Contents Alert
Back to Top