Next Article in Journal
Cost-Energy Optimum Pathway for the UK Food Manufacturing Industry to Meet the UK National Emission Targets
Previous Article in Journal
Data-Driven Optimization Control for Dynamic Reconfiguration of Distribution Network
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Harmonic Compensation Strategy in a Grid-Connected Photovoltaic System Using Zero-Sequence Control

by
Amirreza Naderipour
1,
Zulkurnain Abdul-Malek
1,*,
Mohammad Reza Miveh
2,
Mohammad Jafar Hadidian Moghaddam
3,
Akhtar Kalam
4,* and
Foad. H. Gandoman
4,5
1
Institute of High Voltage & High Current Faculty of Electrical Engineering, Universiti Teknologi Malaysia, Johor 81300, Malaysia
2
Department of Electrical Engineering, Tafresh University, Tafresh 39518-79611, Iran
3
College of Engineering and Science, Victoria University, Melbourne 3047, Australia
4
Research Group MOBI—Mobility, Logistics, and Automotive Technology Research Center, Vrije Universiteit Brussel, Pleinlaan 2, 1050 Brussels, Belgium
5
Flanders Make, 3001 Heverlee, Belgium
*
Authors to whom correspondence should be addressed.
Energies 2018, 11(10), 2629; https://doi.org/10.3390/en11102629
Submission received: 12 September 2018 / Revised: 25 September 2018 / Accepted: 27 September 2018 / Published: 1 October 2018
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
Mitigation of harmonics for a grid-connected inverter is an important element to stabilize the control and the quality of current injected into the grid. This paper deals with the control method of a three-phase Grid-Connected Inverter (GCI) Photovoltaic (PV) system, which is based on the zero-sequence current adjuster. The proposed method is capable of removing the harmonic current and voltage without using any active and passive filters and without the knowledge of the microgrid topology and also impedances of distribution bands and loading conditions. This concept is adopted for the control of a Distributed Generator (DG) in the form of grid-connected inverter. The proposed control can be applied to the grid connected inverter of the PV. The fast dynamic response, simple design, stability, and fast transient response are the new main features of the proposed design. This paper also analyzes the circuit configuration effects on the grid connected inverter capability. The proposed control is used to demonstrate the improved stability and performance.

1. Introduction

In recent years, the DGs based on Renewable Energy Sources (RESs) have been playing an important role in the world’s energy supply systems [1]. DGs can operate in parallel to the main grid or in a Microgrid (MG) mode [2]. A microgrid can be defined as a group of DGs, load, communication systems, protection devises, and distributed energy storage systems that behave as a controllable entity [3]. These DGs are mainly used to deliver renewable and clean energy such as Photovoltaic (PV) power to the utility through Grid-Connected Inverters (GCI). Increased changes in the stability of the MG are prompted by the uneven voltage and current due to harmonics, or Total Harmonic Distortion (THD) [4]. The switching by Insulated-Gate Bipolar Transistor (IGBT) in power electronic devices such as GCIs are the origin of the harmonic distortion. Hence, power electronics systems have inherited the task of reducing the harmonic pollution that they create [5]. To remove the current or voltage harmonics injected by power electronic devices and nonlinear loads, compensation devices such as Active Power filters (APFs) and Unified Power Quality Conditioner (UPQC) are being extensively employed [6]. The current control strategy is the main part in APFs, and many current control schemes such as proportional-integral (PI) control [7,8], Proportional Resonant (PR) control [9], hysteresis control [10], and Deadbeat (DB) control [11], have been proposed. A Droop control and a control scheme for injecting the negative sequence voltage are suggested in Reference [12]. In Reference [13], the utilization of secondary and tertiary controls for improving the voltage quality was proposed. Tonyma et al. [14] in a capacity-limiting action for compensating the harmonic current and unbalanced current, proposed a multifunctional three-phase power conditioner. One of the problems is existence of zero-sequence circulating current flowing between parallel converters. It ought to be specified that in previous studies around three-phase MGs, the zero-sequence component of voltage and current in the grid-connected inverter in microgrids are not taken into account [15,16,17].
V. Khadkikar in [18] presents a comprehensive review of the UPQC to enhance the electric power quality at distribution levels. It provides an overview of the different possible UPQC system configurations for single-phase (two-wire) and three-phase (three-wire and four-wire) networks, different compensation approaches, and recent developments in the field. Paper [19] proposed a synchronous reference frame control method for current unbalance compensation in the microgrid. This method is based on the proper control of Distributed Generations (DGs) interface converters. It also proposed the direct change of the current reference to compensate for current unbalance. The fault analysis with hybrid compensation for unbalanced distribution systems is discussed in Reference [20]. The method employs the unbalanced three-phase model to analyse faults. Two matrices containing information on the topological characteristics of distribution networks were built along with the proposed hybrid-compensation method for analysis. Ting-Chia Ou et al. [21] have shown dynamic operation and control strategies for a microgrid hybrid wind-Photovoltaic (PV)-Fuel Cell (FC) based power supply system. The system consists of the PV power, wind power, FC power, Static VAr Compensator (SVC), and an intelligent power controller. Paper [22] proposed a novel intelligent damping controller for the Static Synchronous Compensator (STATCOM) to reduce the power fluctuations, voltage support, and damping in a hybrid power multi-system. This paper also discussed the integration of an offshore wind farm and a seashore wave power farm via a high-voltage, alternating current electric power transmission line that connects the STATCOM and the 12-bus hybrid power multi-system.
Author in [23] proposed a novel unsymmetrical faults analysis method with hybrid compensation for microgrid (MG) distribution systems. The method employs the actual three-phase models to handle unsymmetrical faults. Likewise, two matrices, which are built from the topological characteristics of MG distribution networks, and then combined with the proposed hybrid compensation method for injecting branch mismatch currents caused by the fault are used to analyze the branch mismatch currents and bus mismatch voltages directly. Author in [24] depicted a direct building algorithm for microgrid distribution ground fault analysis. In this paper, four possibilities of the network topology changes were considered with the proposed iterative process for ground fault analysis. Furthermore, it discusses the ground fault model of a battery energy storage system as a distributed energy resource, which can be used for both islanded and grid-connected modes. M. Tavakoli Bina et al. [25] focused on the distribution unbalance, completing the available definitions in order to maintain tangible relationships between the level of unbalance and the cited consequences in distribution networks. Furthermore, practical works were performed on 11 selected 20 kV/0.4 kV substations within the Tehran north-west distribution system, where data loggers have been installed for 7 days to measure and record operating conditions of substations. Author [26] proposed a UPQC topology with reduced DC-link voltage without compromising its compensation capability. The topology consists of capacitors in series with the interfacing inductor of the shunt active filter. This proposed topology also helps to match the dc-link voltage requirement of the shunt and series active filters of the UPQC.
Several studies, such as References [27,28,29,30,31,32] have proposed to use the APFs and UPQC for the cancellation of the voltage and current harmonics in MG. Along this line, Cheng et al. [27] proposed a control strategy using distributed APFs to weaken the voltage harmonics of the system. In Reference [28] an islanding detection method to detect the islanding phenomenon in a distribution system has been proposed. The proposed method is a hybrid islanding detection method which consists of a remote detection method and a passive method. The proposed method utilizes error rates of system parameter such as voltage and power to readjust generator controllers and maintain the system stability. Khadem S et al. [29] has proposed the integration technique and powerful control of UPQC in Distributed Generation (DG) at the microgrid system. The results show that the UPQC can compensate for the voltage and current disturbance at the Point of Common Coupling (PCC) during interconnected mode. It is used in [30] as a flexible digital-control design in a three-phase APF, which is used in variable-frequency grid conditions. The design consisted of a grid-frequency flexible resonant current adjuster and an upgraded synchronous-reference-frame phase-locked loop. In [31], a single-stage 3 Phase-4 Wire grid-linked PV system that operated with a UPQC is presented. The UPQC with old load harmonic currents and atoning reactive power. The PV-UPQC denominated the power circuit of the system and is built from twin back-to-back linked neutral-point fastened inverters. In Reference [32], an advanced UPQC has been proposed to fine tune the existing solutions for producing perfect sinusoidal air turbine-end currents within both bent-unbalanced load-terminal voltages and non-linear load cases.
The flexible UPQC and APFs could add outstanding redemption for current and voltage distortions, yet they are far from being a cost-effective solution because of high design and working costs. Compared to the additional investment for equipment purchasing, the improved control method of GCI can be practically incorporated.
It is to be noted that the current work targets the redemption of voltage and grid current harmonics. Wherever big disorders exist in the main grids, for example, the harmonic or THD, the GCI with the proposed control method is seldom useful to redeem the grid, including MG problems. To verify the performance of the suggested control solution, the system has been simulated and implemented in MATLAB/Simulink.
This paper is organized as follows: Section 2 describes the control approach for a DG grid-connected inverter. Section 3 presents the proposed control method for photovoltaic GCI. In this section, details of the entire control structure, including the power stage and the harmonic current and voltage compensation stage, are explained. Simulation results with three case studies are presented in Section 4. Finally, in Section 5, the conclusions are presented.

2. Control Approach for Distributed Generation (DG) Grid-Connected Inverter

Figure 1 shows the DG structure with power stage and local controller (without power quality controllers). Evidently, a feedforward loop might be incorporated to measure small variation of DC-link voltage ( V d c ) . The DGs power level included the DC-link with voltage ( V d c ) which can be assumed as an almost constant voltage in the DC link to control the interface inverter of the DG and inverter and an LCL-filter. An LCL filter is often used to interconnect an inverter to the utility grid in order to filter the harmonics produced by the inverter. However, as shown in this figure, it can be seen that fluctuations of the DC link voltage in the production of inverter gate signals can be considered by using a feed-forward loop.
This framework used the instantaneous active and reactive power theory to calculate the positive sequence of active and reactive powers [33]. Droop controllers generated the droop-based voltage V d r o o p , α β in the control system. The “Mode Selector” switch enables the compensation modes to be chosen for harmonic and voltage or current unbalance. Transformation of the variables between a b c and α β frames was made possible through Clarke transformation [33]. For the transformation, Equations (1) and (2) were utilized.
v α β , i α β = 2 3 [ 1 1 2 1 2 0 3 2 3 2 ] · v a b c , i a b c
v a b c , i a b c = 2 3 [ 1 0 1 2 3 2 1 2 3 2 ] · v α β , i α β
where v α β , i α β and v a b c , i a b c represent the instantaneous output voltage ( v o a b c and v o α β ), the output current ( i o a b c and i o α β ) or the LC filter inductor current ( i L a b c and i L α β ) in the abc and αβ frames, respectively.
The angle between the main grid ( ϕ ) , voltage amplitude ( E ) , and an output voltage of DG are identifiers of the positive sequence (PS) of active and reactive powers if the GCI is connected to the inductive grid. Accordingly, in this study, P ϕ and Q E power droops were utilized to produce a reference voltage. As these power droops add virtual inertia to the power inverters, they are presented as shown by Equations (3) and (4):
φ * = φ 0 + ( m P ( P * P + ) + m I ( P * P + ) d t )
E * = E 0 + ( n P ( Q * Q + ) + n I ( Q * Q + ) d t )
where φ 0 is rated and φ * is the voltage-phase angle reference. Hence, P + is a basic positive-sequence active power and Q + is the positive-sequence reactive power. Meanwhile, rated and reference values of voltage amplitude are E 0 and E * , m P is positive sequence active power proportional, and m I is positive sequence integral coefficients. The integral and proportional coefficients related to reactive power are represented by n P and n I , respectively. References to active and reactive powers are P * and Q * , respectively. If the MG functions in an islanded mode [34], P * , Q * , and n I need to be zero.
As previously mentioned, based on the assumption that the microgrid is inductive, the P ϕ and Q E droops were created. Inductive virtual impedance loop for droop-controlled three-phase GCI was used to compensate the effect of the resistance and designation of the P ϕ and Q E droops. Equations (5) and (6) represent the main frequency virtual impedance as:
V v α = R v i 2 α L v ω i 2 β
V v β = R v i 2 β + L v ω i 2 α
where the virtual resistance and inductive impedances are represented by R _ v and L _ v , respectively. The following Equation (7) represents the reference voltage:
V r e f , α β = V d r o o p , α β V v , α β

Proportional–Resonant (PR) Controllers of Voltage and Current

The PR current controllers based on stationary reference frames are commonly suitable to manage the voltage and current [35]. In this study, the PR voltage and current controllers are used, as represented by Equations (8) and (9).
G V ( s ) = k p V + k r V s s 2 + ( ω * ) 2
G I ( s ) = k p I + k r I s s 2 + ( ω * ) 2
where k p V ( k p I ) and k r V ( k r I ) are the proportional and resonant factors of the voltage and current controller, respectively.

3. Proposed Control Method

Figure 2 shows the flowchart of the proposed control method of the PV grid-connected inverter. The main blocks of the method are discussed as follows. The computation starts with the parameter of PV-GCI control method, power stage parameter, and electrical system parameters. The parameters of the power stage parameter consist of the DC-link voltage, LCL-filter, nonlinear load tie lines, distribution lines, and also PV-GCI control parameters, which include power controllers and voltage/current controllers.
Figure 3 shows a block diagram of the flexible proposed control method for a PV three-phase GCI. The system was performed in two separate parts. First, the power stage of a DG, which was comprised of an LCL filter, a three-phase inverter, and a DC link like PV Module. Second, the proposed controller part was modeled by means of the selective harmonic compensator theory. By controlling the instantaneous filter inductor current ( i L α β ) in Figure 3, which is controlled by a current controller, the influx of the load current on the control system performance is properly rejected [15].
Certain controllers, namely, the control method of PV, are implemented in α β reference frame to adjust the grid currents in the α β reference frame.
In the “photovoltaic local adjuster” block, the reference of the DG output voltage in the α β frame ( v α β ) was given by virtual impedance loop, compensation effort adjuster, and power adjusters. At this point, as indicated by *vαβ and the instantaneous measured output voltage ( o v α β ), the reference current ( i α β ) was produced.
Contrarily, the LC filter inductor current was estimated and transformed to the α β frame ( L _ ( i _ α β ) ) and the desired controlled signals were used in the Pulse Width Modulator (PWM) process to produce the changing signals for the PV-GCI.
The Phase Locked Loop (PLL) is widely used for GCI to obtain the grid synchronization information, and its dynamic characteristics have an effect on the stability of the system. The DC components (average values of p and q) are fundamental positive sequence active and reactive powers that can be extracted using Low-Pass filters (LPFs) [36]. The DC-link voltage controller provides the Alternating Current (AC) active power reference. The AC reference is then determined by active and reactive power references and the AC voltage angle. The fixed DC link voltage is definitely greater than peak values of AC voltage. Hence, regulating DC bus voltage by controlling d a x i s current of DC/AC converter and regulating Maximum Power Point Tracking (MPPT) by controlling input of DC/DC converter will reduce the complexity of circuitry of a commercial grid-connected PV system. Controlling the DC bus by regulating d q current of DC/AC inverter is the best solution to maintain high dynamic response on the AC side. Hence, a PV system designed to provide V d c in proposed control method.

Voltage and Current Control Loops

The results presented in this section suggest that the voltage, current, and virtual impedance control loops were created without taking into account the results of unbalance compensation.
Based on the symmetrical components theory [25], it is possible to analyze an unbalanced electrical power system by separating positive and negative-sequence balanced systems.
Figure 4 shows that G P W M ( s ) presenting the transfer role of the PWM block that frequently represented as a lag aspect. PWM lag was ignored G P W M ( s ) = 1 in this study.

4. Simulation Result

As shows in Figure 5, an MG with two PV was considered. The nominal power of PV1 and PV2 was the same. Therefore, the parameters of PV1 and PV2 can be adjusted based on their nominal power. Stability can also be analyzed for PV1 and PV2, and similar results can be achieved [37]. In this regard, this described how to control the droop controllers of the power control.

4.1. Improved Droop Control Method

Most of previous research only reported the implementation of DGs for the injection of active and reactive power into the grid. In the current work, the objectives of GCI is to improve the control strategy for a three-phase GCI of distributed generation sources such as PV. The GCI structure consists of two main parts: The power control part, and the harmonic current and voltage compensation part.
The DC-link voltage of the proposed method is given by:
v D C = D 2 + A ω C sin ( 2 ω t + φ ) = ( D + B ) 2 B 2
where D is average grid voltage approximation, C is DC-link capacitance. A and B is given by:
A = I G = ( ω L I G ) 2 + V G 2 / 2
B = A sin ( 2 ω t + φ ) / 2 ω C D
where L is AC filter inductance, I G is AC grid current and V G is AC grid voltage. The three-phase voltages are measured with respect to an artificial voltage v a b c , which is calculated as follows:
v a = v m cos ( ω 0 t )
v b = v m cos ( ω 0 t 2 π 3 )
v c = v m cos ( ω 0 t 4 π 3 )
where v a , v b and v c are three-phase grid voltages, ω 0 is rated angular frequency and v m is peak voltage. The PV-GCI that is connected to the grid through the impedance Z < θ . The following characteristics were applied to control P + and Q + in the microgrid that was connected to the main grid:
* = 0 + ( k p P + k i P s ) · ( P + * P * )
E * = E 0 + ( k p Q + k i Q s ) · ( Q + * Q * )
P + = 3 · ( E · V Z cos V 2 Z ) cos + 3 · E · V Z sin sin θ
Q + = 3 · ( E · V Z cos V 2 Z ) sin 3 · E · V Z sin cos θ
In these equations, P + * and Q + * are the reference values of powers, and k p Q and k i Q are the integral coefficient of active and reactive powers, respectively. Hence, k p P and k p Q are the proportion coefficient of active and reactive powers, respectively. Furthermore, E is the phase root-mean-square (rms) value of the PV inverter Fundamental Positive Sequence (FPS) output voltage, V represents the grid phase rms voltage, is the load angle, and Z and θ are the magnitude and the phase of the impedance, respectively.
Equation (17) acted as a PI controller for voltage with the aim of bringing injection reactive power by the PV to the reference value. Meanwhile, Equation (16), acted as a proportional-derivative controller for the frequency. In fact, since all systems have the same frequency, and there was no frequency error, integral coefficient (zero steady-state error) was not required for following the reference active power. P + * can be determined in a similar manner to the maximum value of power produced by the original source of PV. For example, MPPT can be used to determine P + * (even in islanded mode) in the case of a solar system. Additionally, Q + * can be set as zero in order to achieve unity power factor or a positive value to support the reactive power of the network. The P + * and Q + * can also be determined by a central controller of the microgrid. As explained in Reference [33], the instantaneous values of active and reactive powers can be writen according to the Equations (20) and (21):
p = v o α i o α + v o β i o β
q = v o α i o β v o β i o α
Thus, Equations (20) and (21) can be modified as follows to calculate instantaneous FPS active and reactive powers, respectively:
P + = v o α + i o α + + v o β + i o β +
Q + = i o α + i o β + v o β + i o α +
Furthermore, according to the aforementioned explanations, Equation (24) can be applied for calculation of instantaneous fundamental negative-sequence reactive power in Equation (24):
Q = i o α i o β v o β i o α
The FNS reactive power and LPF(s) can be expressed by the following Equations (25) and (26) respectively:
Q ( s ) = Q ( s ) · L P F ( s )
L P F ( s ) = ω c S + ω c
where s is the laplace variable, LPFs is transfer function of LPF, and ω c is cutoff frequency of LPFs.
Using LPF in Equation (25) improves the stability of unbalance compensation by preventing the sudden change of Q as aresult of compensation. Finally, the THD of the output current of the inverter can be obtained using Equation (27).
T H D I = I 2 2 + I 3 2 + I 4 2 + I n 2 I 1 × 100 % = k = 2 n I k 2 I 1
where I n is the RMS current of the nth harmonic, and n = 1 is the fundamental frequency.
The THD was mainly affected by the output impedance at the harmonic frequencies. Therefore, it is feasible to optimize the design of the output impedance at higher frequencies to minimize the THD of the output voltage and current. It can be achieved without affecting the impedance at the fundamental frequency.

4.2. Current Compensation

The simulation results were obtained using the Matlab/Simulink software to verify the effectiveness of the suggested control strategy shown in Figure 5.
As shown in Figure 5, the rated voltage and frequency are considered to be 230 V and 50 Hz, respectively. The system also consisted of twin Nonlinear Loads (NLLs) including three-phase diode rectifier as well as three unbalanced single-phase diode rectifiers generating the bent wave structure. The nonlinear loads are responsible for producing the distorted waveforms [38,39]. A proposed control methods were applied to PVs and the values of the three-phase power band and control system are presented in Table 1 and Table 2, respectively.
Table 1 lists the positive and the negative-sequence Bode plots of G + ( s ) and Table 2 lists the positive and the negative-sequence Bode diagrams of G ( s ) , which were considered as the power stage and PV-GCI control parameters.
Figure 5 shows the magnitude of G ( s ) for positive and negative sequences. Where G ( s ) is output impedance and can be extracted:
G ( s ) = G V ( s ) · G I ( s ) L C s 2 + ( r L + G I ( s ) ) · C s + G V ( s ) · G I ( s ) + 1
In this system, one set of phasors has the same phase sequence as the system. Furthermore, the positive and negative sequences can usually be seen in the opposite phase. The positive sequences are needed for unity and negative sequences needed to zero.
Bode diagrams of the magnitude and G ( s ) are compared in Figure 6. Moreover, the phase angle of 5th and 7th voltages and currents harmonic components are zero. Thus, the gain and the phase angle of the closed-loop transfer function are unity and zero, respectively. Hence, voltage references are used to provide proper tracking.
The NLLs including GCI resulted to nonlinear system current and unbalanced which need the insertion of harmonic currents added to MG and grid. The uncompensated nonlinear loads and DGs current wave structures also displayed by Figure 7.
This figure shows the currents NLL1 and NLL2 and PV1 and PV2, equipped without any compensation devices, which is connected alone to the microgrid. The THD of the current is 5.86% (NLL1), 17.51% (NLL2), 27.41% (PV1), and 27.41% (PV2), respectively. The precompensation and post-compensation waveforms of PV1 and PV2 three-phase output currents are depicted in Figure 8.
For all simulations, the results of using the proposed control method are compared with those using the control method of UPQC and APFs.
According to the IEEE standards, the current total harmonic distortion should be maintained below 5%. Figure 8 displays the wave structures of the system currents inserted by the GCI in the case of PVs and nonlinear loads without particular filters working. Prior to proposed control method being switched in, the system current is unbalanced due to harmonics contents. The THDs of NLL1, NLL2, PV1, and PV2 are 0.12%, 0.17%, 0.09%, and 0.08%, respectively. Apparently, the proposed compensation method works by rectifying the bent.

4.3. Voltage Compensation

Figure 5 is also considered as a grid-connected system to test voltage compensation. The power and control system parameters are listed as Table 1 and Table 2 respectively. The switching frequency for the grid-connected inverter is set to 10 Hz. According to Figure 5, two nonlinear loads can cause a harmonic voltage in the microgrid, this ultimately leads to an imbalance in the microgrid. The balanced three-phase line is connected at the PCC point. According to the figure, zl1 and zl2 denote the distribution lines between PVs and PCC. The voltage compensation to balance voltage starts at t = 0.1 s. Voltage Unbalance Factor (VUF) is adjusted up to 0.5%.
The three-phase output voltages of the grid-connected unit under varying unbalanced load changes, with the conventional control strategy, is depicted in Figure 9. This figure also shows the transient load voltages as zoomed figures. As can be observed from this figure, the load voltage in phase ‘a’ and ‘c’ are increased by at least 3 line cycles unbalanced due to the inclusion of the line-to-line load between phase ‘a’ and ‘c’. A large distortion voltage is observed in the output voltages with this control strategy; however, it is restored with a slow transient response. Afterwards, the connected load between phase ‘c’ and the neutral line is changed. Consequently, the voltage in phase ‘c’ is gradually increased. Similarly, a unbalanced waveform in the load voltages, and is restored slowly because of the sudden load change. As can be seen from the zoomed figure, the load disconnection leads to unequal voltage values on three-phases. Nevertheless, the output voltage values are restored with a slow transient response.
The PLL is taken into account in the impedance model of the inverter to analyze the impact of PLL on the system, and evaluate the stability of the GCI system. The d q frame coincides with the controller d q system in a steady state. If there are perturbations in the grid voltage, an angle exists between the two frames due to the PLL dynamics, which will have an impact on the system stability. The transfer function matrix from system d q frames to controller d q frames can be expressed by T Δ θ .
T Δ θ = [ cos Δ θ sin Δ θ sin Δ θ cos Δ θ ]
The Voltage Unbalance Factor (VUF) at the PCC point follows the reference value properly and defined as follows, is considered as the index of unbalance (40):
VUF = V o r m s V o r m s + · 100
where the V o r m s is the rms values of the negative of the DG output voltage and the V o r m s + is the rms values of the positive of the DG output voltage.
Besides this, the quality of the PCC voltage is improved by PVs output voltage disruption. On the other hand, due to the low impedance of the line between PV2 and PCC, VUF is slightly increased. The negative sequence voltages are observed in phase at the PCC point and the PVs terminal. Accordingly, the negative sequence voltage of the PCC is reduced by increasing the negative sequence of the PV output voltage. In addition, in order to show the imbalance compensation, the three-phase output voltages at the PCC before compensation shown in Figure 9.
The harmonic value of the voltage is 5.73%. The output of the PV2 voltage is similar to PV1. As it is observed after the compensation, while the PV output voltage is unstable, the voltage imbalance at the PCC point is reduced effectively.
The output voltages of PV1 and PV2, equipped with the proposed control method, are shown in Figure 10. The balanced voltage is shown as zoomed figures. As can be observed from this figure, the three-phase output voltage is sharply increased due to the inclusion of the three-phase unbalanced load. Afterwards, the output voltage rapidly changes as a consequence of the connection of the three-phase load between phase ‘c’ and the neutral. It is surprising to see that the output voltages of the PV1 and PV2 remain balanced under all unbalanced load changes. Comparing the two PV waveforms, it can be seen that both PVs have the ability to provide balanced output voltages under unbalanced load situations, even when they have to supply a three-phase load in the grid-connected microgrid.
Based on Figure 10, the voltage THD is reduced from 5.73% to 0.3%, which is approved by the IEEE-519 standard.
Finally, according to Reference [29], in addition to the current compensation, voltage compensation is also carried out in this paper so that in Reference [29], only harmonic current compensation is implemented. Therefore, according to the results, the proposed control method is capable of harmonic compensation and the simultaneous unbalance of voltage and current in the presence of nonlinear loads in the microgrid.
The next step is to develop a control method to compensate for other harmonic current and voltage problems at the presence of larger nonlinear loads and more distributed generation sources and also the other PCC voltage power quality problems such as voltage sags.

5. Conclusions

A control method has been presented as an improved current control strategy for three-phase photovoltaic grid-connected inverters under unbalanced and nonlinear load conditions. It is difficult to suppress the harmonic content in the output current of lower than the pre-set value in the GCI. It is also difficult to compensate for unbalanced loads, especially when the grid is under disruption due to total harmonic distortion. Therefore the proposed control method has significant advantages over the conventional methods, and is able to produce clean output grid currents that are free from grid voltage and current harmonics. The results show that the harmonic current and voltage compensation loop have the ability to compensate for the current harmonics and could be able to correct the system unbalance. Furthermore, the proposed control method has the ability to accurately share the active and reactive powers between DGs, as well as providing balanced output current and voltage with low THD under unbalanced and nonlinear load conditions. The voltage and current THD under the proposed control method were reduced from 5.73% to 0.3% and 27.41% to less than 0.2 respectively. The results clearly verify the effectiveness of the proposed control methods.

Author Contributions

All authors have contributed equally to this work. All authors of this manuscript jointly have conceived the theoretical analysis, modeling, and obtained the simulation.

Funding

This research was funded by the Ministry of Education (MOE) and Universiti Teknologi Malaysia under the Post-Doctoral Fellowship Schem grant number 4F828, 04E54, and 18H10.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

C DC-link capacitance
L The transformation matrix
P Real powers injected
Q Reactive powers injected
u Grid voltage
ω Grid angular frequency
V r e f Reference voltage
V d c DC link voltage
P + Positive-sequence active power
Q + Positive-sequence reactive power
P * References to active powers
Q * References to reactive powers
v m Peak voltage
P I Proportiona lintegral
k i Q Integral coefficient of reactive power
k p Q Integral coefficient of active power
k p P Proportion coefficient of active power
k p Q Proportion coefficient of reactive power
R _ v Virtual resistance
L _ v Inductive impedances
k p V Proportional factors of the voltage
k r V Resonant vactors of the voltage
k p I Proportional factors of the current
k r I Resonant factors of the current
i L α β Instantaneous filter inductor current
v α β Voltage in the α β frame
o v α β Instantaneous measured output voltage
i α β Reference current
G P W M ( s ) Presenting the transfer role of the PWM
G ( s ) Output Impedance
V d r o o p , α β Droop-based voltage
v o a b c and v o α β Instantaneous output voltage
i o a b c and i o α β Instantaneous output current
I G AC grid current
V G AC grid voltage
V o r m s The rms values of the negative of the DG output voltage
V o r m s + The rms values of the positive of the DG output voltage
APFActive power filter
DBDeadbeat
DGDistributed generation
DPGSsDistributed power Generation Sources
FPSFundamental positive sequence
GCIGrid-connected inverters
MGMicrogrid
NNLNonlienar load
PCCPoint of common coupling
PLLPhase locked loop
PRProportional resonant
PVPhotovoltaic
PSPositive sequence
PWMPulse width modulator
RESsRenewable energy sources
RCRepetitive control
RMSRoot-mean-square
THDTotal Hharmonic distortion
UPQCUnified power quality conditioner
VUFVoltage unbalance factor

References

  1. Bouloumpasis, I.; Vovos, P.; Georgakas, K.; Vovos, N.A. Current harmonics compensation in microgrids exploiting the power electronics interfaces of renewable energy sources. Energies 2015, 8, 2295–2311. [Google Scholar] [CrossRef]
  2. Golovanov, N.; Lazaroiu, G.C.; Roscia, M.; Zaninelli, D. Power quality assessment in small scale renewable energy sources supplying distribution systems. Energies 2013, 6, 634–645. [Google Scholar] [CrossRef]
  3. Lasseter, R.H.; Paigi, P. Microgrid: A conceptual solution. In Proceedings of the 2004 IEEE 35th Annual Power Electronics Specialists Conference, Aachen, Germany, 20–25 June 2004; pp. 4285–4290. [Google Scholar]
  4. Salgado-Herrera, N.M.; Campos-Gaona, D.; Anaya-Lara, O.; Medina-Rios, A.; Tapia-Sánchez, R.; Rodríguez-Rodríguez, J.R. THD Reduction in Wind Energy System Using Type-4 Wind Turbine/PMSG Applying the Active Front-End Converter Parallel Operation. Energies 2018, 11, 2458. [Google Scholar] [CrossRef]
  5. Miceli, R.; Schettino, G.; Viola, F. A Novel Computational Approach for Harmonic Mitigation in PV Systems with Single-Phase Five-Level CHBMI. Energies 2018, 11, 2100. [Google Scholar] [CrossRef]
  6. Djazia, K.; Krim, F.; Chaoui, A.; Sarra, M. Active Power Filtering Using the ZDPC Method under Unbalanced and Distorted Grid Voltage Conditions. Energies 2015, 8, 1584–1605. [Google Scholar] [CrossRef] [Green Version]
  7. Buso, S.; Malesani, L.; Mattavelli, P. Comparison of current control techniques for active filter applications. IEEE Trans. Ind. Electron. 1998, 45, 722–729. [Google Scholar] [CrossRef] [Green Version]
  8. Zmood, D.N.; Holmes, D.G.; Bode, G.H. Frequency-domain analysis of three-phase linear current regulators. IEEE Trans. Ind. Appl. 2001, 37, 601–610. [Google Scholar] [CrossRef]
  9. Yuan, X.; Merk, W.; Stemmler, H.; Allmeling, J. Stationary-frame generalized integrators for current control of active power filters with zero steady-state error for current harmonics of concern under unbalanced and distorted operating conditions. IEEE Trans. Ind. Appl. 2002, 38, 523–532. [Google Scholar] [CrossRef] [Green Version]
  10. Buso, S.; Fasolo, S.; Malesani, L.; Mattavelli, P. A dead-beat adaptive hysteresis current control. IEEE Trans. Ind. Appl. 2000, 36, 1174–1180. [Google Scholar] [CrossRef]
  11. Malesani, L.; Mattavelli, P.; Buso, S. Robust dead-beat current control for PWM rectifiers and active filters. In Proceedings of the 1998 IEEE Industry Applications Conference, Thirty-Third IAS Annual Meeting, St. Louis, MO, USA, 12–15 October 1998; pp. 1377–1384. [Google Scholar]
  12. El-Naggar, A.; Erlich, I. Control approach of three-phase grid connected PV inverters for voltage unbalance mitigation in low-voltage distribution grids. IET Renew. Power Gener. 2016, 10, 1577–1586. [Google Scholar] [CrossRef]
  13. Tang, F.; Zhou, X.; Meng, L.; Guerrero, J.M.; Vasquez, J.C. Secondary voltage unbalance compensation for three-phase four-wire islanded microgrids. In Proceedings of the 2014 11th International Multi-Conference on Systems, Signals & Devices (SSD), Barcelona, Spain, 11–14 February 2014; pp. 1–5. [Google Scholar]
  14. Ma, T.T.; Chiang, S.J. A multi-functional power conditioner with real-time voltage regulation for energy saving. Int. Trans. Electr. Energy Syst. 2008, 18, 15–28. [Google Scholar] [CrossRef]
  15. Rodriguez, P.; Timbus, A.V.; Teodorescu, R.; Liserre, M.; Blaabjerg, F. Flexible active power control of distributed power generation systems during grid faults. Ind. Electron. IEEE Trans. 2007, 54, 2583–2592. [Google Scholar] [CrossRef]
  16. Lee, T.-L.; Hu, S.-H.; Chan, Y.-H. D-STATCOM with positive-sequence admittance and negative-sequence conductance to mitigate voltage fluctuations in high-level penetration of distributed-generation systems. IEEE Trans. Ind. Electron. 2013, 60, 1417–1428. [Google Scholar] [CrossRef]
  17. Naderipour, A.; Zin, A.A.M.; Habibuddin, M.H.B.; Miveh, M.R.; Guerrero, J.M. An improved synchronous reference frame current control strategy for a photovoltaic grid-connected inverter under unbalanced and nonlinear load conditions. PLoS ONE 2017, 12, 1–17. [Google Scholar] [CrossRef] [PubMed]
  18. Khadkikar, V. Enhancing electric power quality using UPQC: A comprehensive overview. IEEE Trans. Power Electron. 2012, 27, 2284–2297. [Google Scholar] [CrossRef]
  19. Zin, A.M.; Naderipour, A.; Habibuddin, M.H.; Guerrero, J.M. Harmonic currents compensator GCI at the microgrid. Electron. Lett. 2016, 52, 1714–1715. [Google Scholar] [Green Version]
  20. Lin, W.-M.; Ou, T.-C. Unbalanced distribution network fault analysis with hybrid compensation. IET Gener. Transm. Distrib. 2011, 5, 92–100. [Google Scholar] [CrossRef]
  21. Ou, T.-C.; Hong, C.-M. Dynamic operation and control of microgrid hybrid power systems. Energy 2014, 66, 314–323. [Google Scholar] [CrossRef]
  22. Ou, T.-C.; Lu, K.-H.; Huang, C.-J. Improvement of transient stability in a hybrid power multi-system using a designed NIDC (Novel Intelligent Damping Controller). Energies 2017, 10, 488. [Google Scholar] [CrossRef]
  23. Ou, T.-C. A novel unsymmetrical faults analysis for microgrid distribution systems. Int. J. Electr. Power Energy Syst. 2012, 43, 1017–1024. [Google Scholar] [CrossRef]
  24. Ou, T.-C. Ground fault current analysis with a direct building algorithm for microgrid distribution. Int. J. Electr. Power Energy Syst. 2013, 53, 867–875. [Google Scholar] [CrossRef]
  25. Bina, M.T.; Kashefi, A. Three-phase unbalance of distribution systems: Complementary analysis and experimental case study. Int. J. Electr. Power Energy Syst. 2011, 33, 817–826. [Google Scholar] [CrossRef]
  26. Karanki, S.B.; Geddada, N.; Mishra, M.K.; Kumar, B.K. A modified three-phase four-wire UPQC topology with reduced DC-link voltage rating. IEEE Trans. Ind. Electron. 2013, 60, 3555–3566. [Google Scholar] [CrossRef]
  27. Cheng, P.-T.; Lee, T.-L. Distributed active filter systems (DAFSs): A new approach to power system harmonics. IEEE Trans. Ind. Appl. 2006, 42, 1301–1309. [Google Scholar] [CrossRef]
  28. Pouryekta, A.; Ramachandaramurthy, V.K.; Mithulananthan, N.; Arulampalam, A. Islanding Detection and Enhancement of Microgrid Performance. IEEE Syst. J. 2017, 5, 809–819. [Google Scholar]
  29. Khadem, S.; Basu, M.; Conlon, M. Intelligent Islanding and Seamless Reconnection Technique for Microgrid with UPQC. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 483–492. [Google Scholar] [CrossRef]
  30. Hogan, D.J.; Gonzalez-Espin, F.J.; Hayes, J.G.; Lightbody, G.; Foley, R. An Adaptive Digital-Control Scheme for Improved Active Power Filtering Under Distorted Grid Conditions. IEEE Trans. Ind. Electron. 2018, 65, 988–999. [Google Scholar] [CrossRef]
  31. Campanhol, L.B.G.; da Silva, S.A.O.; de Oliveira, A.A.; Bacon, V.D. Single-stage three-phase grid-tied PV system with universal filtering capability applied to DG systems and AC microgrids. IEEE Trans. Power Electron. 2017, 32, 9131–9142. [Google Scholar] [CrossRef]
  32. Rahmani, B.; Bina, M.T. Reciprocal effects of the distorted wind turbine source and the shunt active power filter: Full compensation of unbalance and harmonics under “capacitive non-linear load”condition. IET Power Electron. 2013, 6, 1668–1682. [Google Scholar] [CrossRef]
  33. Akagi, H.; Kanazawa, Y.; Nabae, A. Instantaneous reactive power compensators comprising switching devices without energy storage components. Ind. Appl. IEEE Trans. 1984, IA-20, 625–630. [Google Scholar] [CrossRef]
  34. He, J.; Li, Y.W.; Blaabjerg, F. Flexible microgrid power quality enhancement using adaptive hybrid voltage and current controller. IEEE Trans. Ind. Electron. 2014, 61, 2784–2794. [Google Scholar] [CrossRef]
  35. Blaabjerg, F.; Teodorescu, R.; Liserre, M.; Timbus, A.V. Overview of control and grid synchronization for distributed power generation systems. Ind. Electron. IEEE Trans. 2006, 53, 1398–1409. [Google Scholar] [CrossRef]
  36. Peng, F.Z.; Ott, G.W., Jr.; Adams, D.J. Harmonic and reactive power compensation based on the generalized instantaneous reactive power theory for three-phase four-wire systems. Power Electron. IEEE Trans. 1998, 13, 1174–1181. [Google Scholar] [CrossRef]
  37. Ghanizadeh, R.; Ebadian, M.; Gharehpetian, G.B. Non-linear load sharing and voltage harmonics compensation in islanded microgrids with converter interfaced units. Int. Trans. Electr. Energy Syst. 2017, 27. [Google Scholar] [CrossRef]
  38. Xie, G.-L.; Zhang, B.-H.; Li, Y.; Mao, C.-X. Harmonic Propagation and Interaction Evaluation between Small-Scale Wind Farms and Nonlinear Loads. Energies 2013, 6, 3297–3322. [Google Scholar] [CrossRef] [Green Version]
  39. Dolara, A.; Leva, S. Power quality and harmonic analysis of end user devices. Energies 2012, 5, 5453–5466. [Google Scholar] [CrossRef]
Figure 1. Level of power and base control structure of Distributed Generation (DG). PMW: pulse width modulator.
Figure 1. Level of power and base control structure of Distributed Generation (DG). PMW: pulse width modulator.
Energies 11 02629 g001
Figure 2. Flowchart of the control method of photovoltaic-grid-connected inverters (PV-GCI).
Figure 2. Flowchart of the control method of photovoltaic-grid-connected inverters (PV-GCI).
Energies 11 02629 g002
Figure 3. Proposed compensation control method for PV-GCI. LPF: low-pass filter; PLL: phase locked loop; PCC: point of common coupling.
Figure 3. Proposed compensation control method for PV-GCI. LPF: low-pass filter; PLL: phase locked loop; PCC: point of common coupling.
Energies 11 02629 g003
Figure 4. The block diagram of a positive-sequence controller.
Figure 4. The block diagram of a positive-sequence controller.
Energies 11 02629 g004
Figure 5. Structure of the microgrid (MG) used for simulation.
Figure 5. Structure of the microgrid (MG) used for simulation.
Energies 11 02629 g005
Figure 6. Bode diagram of G ( s ) .
Figure 6. Bode diagram of G ( s ) .
Energies 11 02629 g006
Figure 7. Output current waveforms of PVs and NLLs in different simulation.
Figure 7. Output current waveforms of PVs and NLLs in different simulation.
Energies 11 02629 g007
Figure 8. Output current waveforms of DGs and nonlinear loads (NLLs) after proposed control method.
Figure 8. Output current waveforms of DGs and nonlinear loads (NLLs) after proposed control method.
Energies 11 02629 g008
Figure 9. Three-phase voltages at PCC before compensation.
Figure 9. Three-phase voltages at PCC before compensation.
Energies 11 02629 g009
Figure 10. Three-phase voltages at PCC after compensation with proposed control method.
Figure 10. Three-phase voltages at PCC after compensation with proposed control method.
Energies 11 02629 g010
Table 1. Power stage parameter.
Table 1. Power stage parameter.
DC-Link VoltageLCL-FilterNonlinear Loads Tie Lines
V d c ( V ) L ( mH ) ,   C ( μ F ) Z ( Ω ,   mH )
7501.28, 300.11, 1.62
Distribution LinesNonlinear Load 1Nonlinear Load 2
Z l 1 , Z l 2 , ( Ω , mH ) R N L 1 / L N L 1
( Ω ) / ( mH )
R N L 2 / L N L 2
( Ω ) / ( mH )
0.12, 1.7850/0.083200/0.9
Table 2. Photovoltaic-grid-connected inverters (PV-GCI) control parameters.
Table 2. Photovoltaic-grid-connected inverters (PV-GCI) control parameters.
Power Controllers (PV1 and PV2)
m D ( rad / W ) m P ( rad / W · s ) n D ( V / VAr )
0.5 × 10 5 / 1.2 × 10 5 0.5 × 10 4 / 1.2 × 10 4 1.5 × 10 1 / 2.8 × 10 1
Voltage/Current Controller
k p v / k p 1 k r v 1 / k r 11 k r v 3 / k r 13 k r v 5 / k r 15 k r v 7 / k r 17 ω c V / ω c 1
( rad / s )
1/4100/1000200/40050/100100/1002/2
Electrical System Parameters
L ( mH ) C ( μ F ) L 1 ( mH ) L 2 ( mH ) Z L ( Ω )
1.93253.441.9368/57 + 4.6j

Share and Cite

MDPI and ACS Style

Naderipour, A.; Abdul-Malek, Z.; Miveh, M.R.; Hadidian Moghaddam, M.J.; Kalam, A.; Gandoman, F.H. A Harmonic Compensation Strategy in a Grid-Connected Photovoltaic System Using Zero-Sequence Control. Energies 2018, 11, 2629. https://doi.org/10.3390/en11102629

AMA Style

Naderipour A, Abdul-Malek Z, Miveh MR, Hadidian Moghaddam MJ, Kalam A, Gandoman FH. A Harmonic Compensation Strategy in a Grid-Connected Photovoltaic System Using Zero-Sequence Control. Energies. 2018; 11(10):2629. https://doi.org/10.3390/en11102629

Chicago/Turabian Style

Naderipour, Amirreza, Zulkurnain Abdul-Malek, Mohammad Reza Miveh, Mohammad Jafar Hadidian Moghaddam, Akhtar Kalam, and Foad. H. Gandoman. 2018. "A Harmonic Compensation Strategy in a Grid-Connected Photovoltaic System Using Zero-Sequence Control" Energies 11, no. 10: 2629. https://doi.org/10.3390/en11102629

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop