1. Introduction
Cables are the backbone of the modern power distribution grid. For instance, the total length of medium-voltage (MV) cable circuits in China had exceeded one million kilometers by the end of 2025, with an average annual growth rate of 7% over the past decade [
1,
2]. In medium-voltage distribution networks, single-phase grounding faults are the most common type of fault, accounting for more than 70% of the total. Medium-voltage cable-based distribution networks utilize three-core cables as power lines; these cables feature a belted structure and offer high safety performance as well as strong electromagnetic interference suppression capability [
3]. For this reason, the centralized laying of multi-circuit three-core cables is quite prevalent in areas with dense power loads. However, underground cables are susceptible to multiple factors, including third-party construction damage, mechanical stress, and environmental temperature and humidity fluctuations. These factors can degrade the insulation performance of cables and consequently lead to single-phase grounding faults [
4]. Accurate identification of the fault phase is crucial for the rapid restoration of the power supply. Nevertheless, traditional methods require invasive operations at both ends of the cable, which increases the maintenance workload and prolongs the fault handling cycle. Therefore, there is an urgent need to develop more efficient and intelligent fault phase identification methods to enhance the overall reliability of power supply systems.
In previous work, phase selection methods in MV power distribution grid mainly focused on overhead lines rather than cables. Due to differences in line structures and parameters [
5], overhead lines and three-core cable lines exhibit distinct voltage and current characteristics after single-phase grounding faults. Overhead lines feature small ground capacitance, pronounced zero-sequence voltage and current characteristics, and rich transient components, enabling effective fault identification based on voltage and current features [
6]. In contrast, three-core cable lines exhibit large ground capacitance and strong inter-phase coupling, resulting in capacitive-dominated zero-sequence currents [
7], weak phase discrimination, and rapidly decaying transients, which significantly complicate faulty phase identification. Aiming at this key problem of fault phase selection in distribution networks, scholars at home and abroad have carried out systematic and in-depth research and proposed a variety of fault phase selection methods with different characteristics. In the field of fault phase selection based on abrupt quantities, References [
8,
9] proposed a phase selection method based on power–frequency amplitude differences in phase-to-phase current fault components. This method has been widely applied in transmission networks, but its application effectiveness is limited due to the complexity of distribution networks. In terms of steady-state phase selection research, Reference [
10] uses a single sequence component to reflect all fault types and comprehensively identify fault phases; however, it requires a long data acquisition window, and when the system operation mode changes, the characteristics may weaken or even disappear, resulting in poor phase selection performance. In research on transient phase selection, Reference [
11] takes the transient current of short circuit faults as the analysis object and proposes a fault phase selection method based on wavelet entropy weight. In addition, Reference [
12] extracts the modulus phasor of a single frequency of fault current using the S-transform and puts forward a phase selection method based on modulus relationships and phase current integration. Although these methods have high phase selection accuracy, they are susceptible to the influence of system parameters, and their effectiveness has not been verified in engineering practice. Reference [
13] introduces deep learning into this field and realizes automatic phase selection with strong anti-interference ability through convolutional neural networks; however, its engineering application is restricted by problems such as data acquisition and model training.
The present authors have invented a Hall-element-based surface magnetic field sensor and used it for phase current measurement; however, it was not used in transient magnetic sensing or phase selection [
14,
15]. In recent years, with the rapid development of magnetic field sensing technology, using magnetic fields instead of electric currents as characteristic quantities in distribution systems has emerged as a new research trend [
16]. Traditional distribution network monitoring primarily relies on invasive current sensors, which require circuit interruption for installation and thus increase the difficulty of system maintenance. In contrast, TMR magnetic sensors have demonstrated broad application prospects in distribution network monitoring due to their advantages, such as high sensitivity, strong anti-interference capability, and non-invasiveness. Particularly in monitoring applications of three-core cables, given that such cables adopt an integral sheath structure, sensors can only be arranged outside the cables, which imposes higher requirements on sensor arrangement and detection accuracy. To address this challenge, relevant studies have proposed various solutions. For instance, Reference [
17] proposes a novel magnetic field sensing technique for detecting underground power cables and verifies its effectiveness using simulation models of 11 kV and 132 kV underground power cables. Reference [
18] presents a novel coreless current sensor unit for measuring electrical current in circular conductors. Unlike conventional designs, these sensors do not need to be fixed directly onto the conductor, which significantly enhances their flexibility and ease of deployment. Reference [
19] proposes a theoretical and experimental method for evaluating crosstalk interference in a circular array of fluxgate sensors used for current measurement. Reference [
20] investigates a differential array of magnetic field sensors. In this differential approach, the Moore–Penrose inversion method is used to obtain the set of currents at different positions inside the sensor by measuring the radial difference in the magnetic fields. Reference [
21] provides an in-depth analysis of measurement errors in circular magnetic sensor arrays used for current measurement. By introducing a theoretical framework based on vector mathematics, the paper investigates the effects of conductor position variations on measurement accuracy. Reference [
22] designed an annular magnetic field sensor array with a 45° mutual spacing, which effectively expanded the angular coverage of magnetic field detection. References [
23,
24] developed an annular giant magnetoresistive sensor array with a 90° mutual spacing tailored to the monitoring requirements of three-core cables; by increasing the sensor arrangement density, the accuracy of magnetic field measurement was significantly improved. Reference [
18] constructed a sensor array composed of three Hall sensors with a 120° mutual spacing and further enhanced the detection capability for superimposed magnetic fields in cables by optimizing the spatial layout between sensors. Reference [
14] designed an annular Hall sensor array with a 60° mutual spacing, whose research mainly focused on the inversion of steady-state phase currents. Reference [
15] considered the influence of the steel tape shield layer of three-core cables on the inverted phase current, but neither involved engineering application research in the field of distribution network fault diagnosis. Despite the remarkable progress made in existing research on surface magnetic field sensing for three-core cables [
25], its practical application in the field of single-phase grounding fault diagnosis remains relatively limited, and there is still a lack of effective methods for single-phase grounding fault phase selection.
In this paper, an annular TMR magnetic sensor is adopted to realize non-invasive fault phase selection for single-phase grounding faults in three-core cables. First, a differential evolution algorithm is used to invert the rotation angle under steady-state system conditions. Then, the difference value is selected as the time-domain characteristic quantity, and six measurement points are arranged on the surface of the annular TMR magnetic sensor as spatial characteristic quantities; the magnetic field intensity difference is used to distinguish the fault phase at the moment of a single-phase grounding fault transient. The feasibility of the above-mentioned phase selection method is analyzed via simulation, and it is verified that this method is not affected by factors such as rotation angle or neutral grounding mode. Finally, systematic verification of the proposed phase selection method based on the annular TMR magnetic sensor is carried out on a 10 kV cable network prototype test platform. Test results demonstrate that this method effectively selects the fault phase for single-phase grounding faults in three-core cables, offering a novel approach to developing fault phase selection technology in distribution networks.
3. Results
3.1. Simulation
To verify the proposed fault phase selection method for three-core cables, a medium-voltage cable feeder single-phase grounding fault simulation model is built in MATLAB/Simulink (R2023a). As shown in
Figure 9, the transformer turns ratio is 220 kV/10 kV with a Y/△ connection, the arc suppression coil adopts an 8% over-compensation mode, and the small resistance is set to 10 Ω. A single-phase grounding fault is set in a 1924 m long cable feeder. The fault point is set 1301 m away from the 10 kV bus and 623 m away from the load. The detection point is arranged 200 m in front of the fault point. The line terminal is unloaded, and the sampling rate is 1 MHz.
The structural parameters of the three-core cable are shown in
Table 4. The rotation angles
α,
β, and
γ between OA, OB, OC, and the positive direction of the
x-axis are 2π/3 apart. The cable radius
R is 46.3 mm, and
rA =
rB =
rC = 21 mm.
Based on the three-phase currents obtained from the simulation, this paper substitutes them into the surface magnetic field formulas of BS1~BS6 to forward calculate the magnetic field intensity of the six measurement points S1~S6 on the surface of the three-core cable.
3.1.1. Steady-State Inversion of Rotation Angle
Set
α,
β, and
γ to 3π/2, 5π/6, and π/6, respectively. Based on the differential evolution algorithm, the three-phase currents
IA,
IB, and
IC and the surface magnetic field intensities
BS1~
BS6 obtained from the simulation at any time are inverted, and the obtained
α,
β, and
γ parameters are shown in
Table 5.
It can be seen from
Table 4 that the minimum absolute error of the inverted rotation angle is 0.00111π, the maximum absolute error is 0.00311π, and the relative errors of
α,
β, and
γ inversions are all less than 1%.
3.1.2. Transient Phase Selection for Single-Phase Grounding Fault
Analysis of Fault Phase Selection for Three-Core Cables
Taking an ungrounded neutral system as an example, the transition resistance at the fault point is set to 0 Ω, the rotation angles
α,
β, and
γ are set to 3π/2, 5π/6, and π/6, respectively, and single-phase grounding faults occur in phases A, B, and C. The magnetic field intensity waveforms at S1~S6 are shown in
Figure 10. Calculate the magnetic field intensity differences at the six measurement points S1~S6 on the surface of the three-core cable when single-phase grounding faults occur in phases A, B, and C, and obtain the magnetic field intensity difference curves as shown in
Figure 11.
Based on the rotation angles α, β, and γ and the planar relative arrangement of the six measurement points of the annular TMR array, it can be concluded that when the magnetic field intensity difference BS1pp of the S1 measurement point is the largest, a single-phase grounding fault occurs in phase A; when the magnetic field intensity difference BS5pp at the S5 measurement point is the largest, a single-phase grounding fault occurs in phase B; when the magnetic field intensity difference BS3pp at the S3 measurement point is the largest, a single-phase grounding fault occurs in phase C.
Influence of Different Rotation Angles
Different rotation angles affect the magnetic field intensity differences at the six measurement points. To eliminate situations where specific rotation angles result in two or more measurement points to obtain the same maximum magnetic field intensity difference, leading to phase selection errors. It is assumed that a single-phase grounding fault occurs in phase A. The rotation angle
α is increased from 0 to 2π with an increment of π/1800 each time, and the resulting magnetic field intensity difference intervals at the six measurement points are shown in
Figure 12.
Analysis shows that during the continuous change in the rotation angle
α ∈ [0, 2π], the magnetic field intensity differences
BSipp at measurement points S1~S6 show periodic distribution characteristics. For any measurement point Si, there exists an interval [
θi1,
θi2] ∈ [0, 2π] such that the magnetic field intensity difference in the measurement point within this interval satisfies the following:
In the formula, i ≠ j, i = 1, 2, …, 6; ∀α ∈ [θi1, θi2].
When α ∈ [1.334π, 5π/3], the magnetic field intensity difference BS1pp of S1 is greater than that of other measurement points, and BS1pp reaches its maximum when α = 3π/2. When α ∈ [1.668π, 0], BS2pp is greater than that of other measurement points, and BS2pp reaches its maximum when α = 11π/6. When α ∈ [π/1800, π/3], BS3pp is greater than that of other measurement points, and BS3pp reaches its maximum when α = π/6. When α ∈ [0.334π, 2π/3], BS4pp is greater than that of other measurement points, and BS4pp reaches its maximum when α = π/2. When α ∈ [0.667π, π], BS5pp is greater than that of other measurement points, and BS5pp reaches its maximum when α = 5π/6. When α ∈ [1.001π, 4π/3], BS6pp is greater than that of other measurement points, and BS6pp reaches its maximum when α = 7π/6.
Through the analysis of arbitrary rotation angles, it can be seen that different rotation angles have no effect on the phase selection method proposed in this paper.
Influence of Cable Core Eccentricity
From the above analysis, it can be concluded that when a single-phase grounding fault occurs in phase A and α = 3π/2, such that S1 is directly facing the phase A conductor and the geometric structure of the cable cores is symmetric, the magnetic field intensity difference at the S1 measurement point, BS1pp, should be greater than those at the other five measurement points. In practical operation, external mechanical compression of the conductors or cable eccentricity may occur, resulting in geometric asymmetry of the cable structure. Considering the eccentricity of the phase A conductor, the distance rA from point O to the center of the phase A core, as well as the rotation angle α between OA and the positive x-axis, may vary within a certain range.
To verify the effectiveness of the fault phase selection method under cable eccentricity conditions, the parameter ranges are determined based on field operating experience. Specifically, the range of rA is set to 19 mm~23 mm, and the range of the rotation angle α is set to 1.444π~1.556π. The distance from point O to the center of the phase B conductor is set to rB = 20mm, with the rotation angle β between OB and the positive x-axis being 5π/6. The distance from point O to the center of the phase C conductor is set to rC = 22 mm, with the rotation angle γ between OC and the positive x-axis being π/6. The cable radius R is 46.3 mm.
This section investigates the variations in magnetic field intensity differences at different measurement points when the distance
rA and the rotation angle
α deviate within the parameter ranges defined in the model. In the simulation, a single-phase grounding fault is assumed to occur on phase A. The variations in magnetic field intensity differences at different measurement points are shown in
Figure 13. When
rA is set to 19 mm, 20 mm, 21 mm, 22 mm, and 23 mm, respectively, as the rotation angle
α increases from 1.444π to 1.556π, the magnetic field intensity difference at the S1 measurement point,
BS1pp, consistently remains higher than that at the other five measurement points. Within the range of α = 1.444π~1.556π,
BS1pp exhibits a symmetric distribution and reaches its maximum at
α = 3π/2, corresponding to the condition where S1 is directly facing the phase A conductor.
Influence of Different Neutral Grounding Modes and Transition Resistances
There are three types of small current grounding systems in distribution networks: ungrounded neutral, neutral grounded through an arc suppression coil, and neutral grounded through small resistance. The amplitude of the fault phase current varies greatly among the three different grounding modes in the fault steady-state, and the change in the fault phase current further affects the change in the surface magnetic field intensity of the three-core cable. In the transient stage of a single-phase grounding fault, under the three different grounding modes, the fault phase current will experience a transient impact to increase, causing an increase in the surface magnetic field intensity of the three-core cable. The transition resistance range is set to 50 Ω~300 Ω, a single-phase grounding fault occurs in phase A, and the rotation angles α, β, and γ are 3π/2, 5π/6, and π/6, respectively.
The influence trend of the neutral point transition impedance on the magnetic field intensity difference is shown in
Figure 14. Under the three neutral point grounding modes, the magnetic field intensity difference at the S1 measurement point is the largest, which is identified as phase A short circuit. Under the condition of non-high-resistance grounding at the fault point, different neutral point grounding modes and the value of the transition resistance have no effect on the phase selection method proposed in this paper.
3.2. Test Verification and Analysis
To further verify the effectiveness of the proposed method for fault phase selection in the case of single-phase grounding faults of three-core cables, a single-phase grounding fault is simulated on a 10 kV cable prototype test platform. The test site adopts two neutral point grounding modes: ungrounded and grounded through an arc suppression coil. The line length, fault point location, surface magnetic field measurement point layout, and load conditions are consistent with the simulation settings. The cable network frame is shown in
Figure 8, and the structural parameters of the three-core cable are shown in
Table 3. A single-phase grounding fault is set to occur in phase B during the test.
The test equipment and on-site layout are shown in
Figure 15, including an annular TMR magnetic sensor composed of six TMR215x tunneling magnetoresistors and a six-channel acquisition card with a sampling rate of 1 MHz. A data receiving terminal with a built-in FPGA system board and an annular TMR magnetic sensor are arranged in the cable channel. The fault point uses a three-core cable with three-phase stripping. One phase conductor is drilled to the copper core, and the drilled conductor is immersed in water to simulate the actual cable immersion environment. The circuit breaker in the ring main unit is closed, and the system directly enters the single-phase grounding fault transient operation state. The annular Hall magnetic sensor is used for steady-state measurements in Reference [
14] and is not applicable to single-phase grounding transient conditions.
The test is divided into two stages: system steady-state operation and single-phase grounding fault. In the early stage, the annular TMR magnetic sensor needs to be pre-installed on the surface of the three-core cable. In the steady-state operation stage, the system adopts the ungrounded neutral mode. The cable surface magnetic field and three-phase current data are collected through the annular TMR magnetic sensor and the oscilloscope, the rotation angles are calculated, and the planar relative arrangement of the three-phase conductors and the annular TMR array is determined. In the fault stage, two grounding modes are adopted: ungrounded neutral and grounded through an arc suppression coil. The surface magnetic field intensity of the three-core cable when a single-phase grounding fault occurs is recorded, and the fault phase selection is realized by calculating the magnetic field intensity difference during the transient process.
During steady-state operation, the cable surface magnetic field is detected by the annular TMR magnetic sensor, and then the collected six magnetic field signals are denoised based on the wavelet transform to obtain the magnetic field waveforms of the six measurement points, as shown in
Figure 16. The oscilloscope detects that the amplitudes of the A-, B-, and C-phase currents are 0.87 A.
Based on the measured magnetic field waveforms of the six measurement points and the current recordings, the three-phase currents IA, IB, and IC and the surface magnetic field intensity BS1~BS6 at any time are inverted, and the calculated α, β, and γ parameters are 1.792π, 1.145π, and 0.411π, respectively. In actual operation, the three-core cable will be squeezed by external forces, resulting in eccentricity of the three-phase conductors inside the cable and making the rotation angles α, β, and γ between the three phases unable to be exactly 2π/3 apart.
During transient operation, the transient magnetic field waveforms of the S1~S6 measurement points are shown in
Figure 17 and
Figure 18. The spike at 0.015 s is an overvoltage caused by the closing of the circuit breaker and is not considered.
During the transient state of a single-phase grounding fault, for the ungrounded neutral mode, the magnetic field intensity differences at measurement points S1~S6 are 1.28 mT, 1.14 mT, 0.96 mT, 1.04 mT, 1.39 mT, and 1.75 mT, in sequence. For the neutral mode grounded via an arc suppression coil, the magnetic field intensity differences at measurement points S1~S6 are 1.16 mT, 0.56 mT, 0.46 mT, 0.90 mT, 1.58 mT, and 1.66 mT, in sequence. Under both grounding modes, the magnetic field intensity difference at measurement point S6 is the largest.
Under steady-state conditions, the planar relative arrangement of the three-core cable and the annular TMR array is determined by the surface magnetic field and three-phase current. Under single-phase grounding fault transient conditions, analysis of the six measurement points shows that the magnetic field intensity difference at the S6 measurement point is the largest. Both different grounding modes identify the fault phase as phase B, which is consistent with the test fault phase setting.
The detection performance of the proposed method was quantitatively evaluated through repeated trials, with a total of 16 single-phase grounding fault tests conducted. Out of these, 15 trials successfully identified the faulted phase, yielding a TPR of 93.75%. Only one phase selection failure occurred, resulting in a false alarm rate of 6.25%, which was attributed to noise-induced triggering under low effective SNR conditions and a relatively low triggering threshold setting. The faulted phase was identified based on the magnetic field intensity difference feature following the occurrence of a single-phase grounding fault. A 20 ms data window was used to calculate the magnetic field intensity difference and complete faulted phase identification, ensuring that the detection latency does not exceed one fundamental power–frequency cycle. Additionally, assuming a binomial distribution of the detection results, the 95% confidence interval of the detection accuracy is approximately [70%, 99%]. The width of this confidence interval is primarily influenced by the limited number of experimental samples. Overall, despite the limited sample size, the proposed method shows high faulted phase selection reliability and strong potential for engineering applications under single-phase grounding fault conditions. As the device is deployed and more data is gathered, the statistical results are expected to become more stable and accurate.
4. Discussions and Limitations
This paper proposes a non-intrusive online fault phase selection method for 10 kV three-core cables based on an annular TMR magnetic sensor. The method combines steady-state sensing model parameter inversion and transient phase selection for single-phase grounding, which effectively solves the problem of fault phase identification in single-phase grounding faults. Compared with traditional fault phase selection methods, this method avoids invasive operations at both ends of the cable, reducing maintenance workload and shortening the fault handling period.
In terms of the selection of characteristic quantities, the proposed magnetic field intensity difference, as a time-domain characteristic quantity, can effectively amplify weak transient changes at the moment of the fault and maintain high phase selection reliability under high-resistance grounding conditions, which is superior to traditional maximum and minimum values and rate-of-change characteristic quantities. In terms of spatial characteristic quantities, by comparing the phase selection effects of different numbers of measurement points, it is verified that arranging six measurement points can avoid situations where phase selection cannot be performed correctly due to equal magnetic field intensity differences at partial measurement points, thereby ensuring the reliability of fault phase selection.
The simulation analysis shows that the differential evolution algorithm used in this paper has high inversion accuracy for the rotation angle, with a relative error of less than 1%, which lays a solid foundation for accurate fault phase selection. At the same time, the method is not affected by factors such as rotation angle and neutral grounding mode, which enhances the adaptability of the method. The prototype test further verifies the effectiveness of the method. Under two different neutral point grounding modes, the fault phase can be accurately identified, which confirms the engineering application value of the method.
This study also has certain limitations. The research focuses on the fault phase selection of single-phase grounding faults of three-core cables under non-high-resistance grounding conditions, and the applicability under high-resistance grounding conditions needs to be further studied. In addition, the influence of factors such as cable aging and temperature drift on the measurement accuracy of the sensor array has not been considered, which may affect the long-term stability of the method. Future research can focus on optimizing the algorithm to improve the phase selection accuracy under high-resistance grounding conditions and carry out research on temperature compensation and aging adaptation of the sensor array to further enhance the engineering application prospects of the method.
Temperature variation and long-term drift are inherent characteristics of magnetoresistive sensors, including TMR devices, and may affect absolute magnetic field measurements. However, the proposed faulted phase selection method does not rely on absolute magnetic field amplitudes. Instead, it is based on a magnetic field intensity difference feature extracted within a short fault transient window. This differential feature effectively suppresses slow-varying offset drift and low-frequency temperature-induced variations, which typically evolve over time scales much longer than the fault transient duration. Under practical operating conditions, temperature changes within the short fault transient interval are negligible compared with long-term environmental variations. Moreover, the proposed phase selection criterion depends on the relative magnitude relationship of BSipp among multiple measurement points rather than on their absolute values. Since all TMR sensors are mounted on the same annular structure and operate under nearly identical thermal conditions, temperature-induced drift predominantly manifests as a common-mode component, thereby exerting limited influence on the relative ranking used for faulted phase identification. From an implementation perspective, mature temperature compensation techniques can be readily applied, including periodic offset calibration under steady-state conditions, reference-based compensation using integrated temperature sensors, and software-based baseline tracking. These methods are well established in industrial TMR sensing systems and introduce minimal computational or hardware overhead.
Regarding calibration frequency, sensor offset and rotation angle parameters can be considered quasi-static under normal operating conditions. Consequently, calibration is generally required only during initial installation or commissioning, after sensor repositioning, or following prolonged operation or significant environmental changes, rather than on a frequent basis.
In the prototype test, the single-phase grounding fault is introduced by breaker closing. While this method allows for controllable and repeatable fault initiation, it may also introduce operation-induced transient disturbances. In contrast, practical single-phase grounding faults are primarily caused by sudden insulation breakdown, which occurs randomly and typically results in a steeper current rise and richer high-frequency transient components. These differences mainly affect the detailed transient waveform characteristics in the time-domain. However, the proposed phase selection method does not depend on specific transient waveform shapes or frequency-domain features. Instead, it is based on the spatial distribution of the surface magnetic field intensity differences around the three-core cable. Regardless of whether the fault is triggered by breaker closing or sudden insulation breakdown, a single-phase grounding fault causes the abrupt appearance of zero-sequence current and a dominant increase in current in the faulted phase. As a result, the measurement point closest to the faulted phase consistently shows the maximum magnetic field intensity differences, which form the foundation of the proposed phase selection criterion. Therefore, although the two fault scenarios differ in transient signal details, they are equivalent in terms of the spatial magnetic field variation characteristics used for phase selection, and the proposed method remains effective.
In practical field environments, strong electromagnetic pulse interference may introduce short-duration spikes in the measured magnetic field signals. The proposed method mitigates the impact of such interference through the following mechanisms. First, BSipp is extracted over a predefined transient time window, reducing the likelihood that pulse interference dominates the extrema. Second, the phase selection criterion is based on the relative magnitude of BSipp among multiple spatially distributed measurement points. Global pulse interference will affect all sensors similarly, without changing the relative ranking, while localized interference is typically short-lived and unlikely to dominate the maximum–minimum difference. Additionally, preprocessing techniques such as band-limited filtering, outlier rejection, or median smoothing can further suppress impulsive noise without affecting fault-induced magnetic field variation. Although strong pulse interference may introduce transient disturbances, it is unlikely to cause incorrect phase selection, and the proposed method demonstrates robust performance in practical field environments.