2.1. Steady-State Impedance Analysis of High-Impedance Grounding Faults in Ungrounded Neutral-Point Systems
During steady-state single-phase grounding fault analysis, line admittance effects are negligible. Line resistance and inductive reactance magnitudes fall significantly below circuit capacitive reactance, permitting their omission in equivalent circuits [
20]. This paper establishes a coal mine distribution network model (
Figure 1) reflecting actual 10 kV underground configurations. The neutral point remains ungrounded, with a single busbar supplying four feeders. Asymmetrical faults—single-phase grounding, two-phase shorts, and phase breaks—represent unbalanced conditions. These induce unequal three-phase impedances, resulting in divergent RMS voltage/current values and phase shifts, thus warranting symmetrical component analysis for fault examination [
21].
In
Figure 1, four cables operate normally. Assume a single-phase high-impedance ground fault occurs on the second cable. This generates zero-sequence current in the system. The equivalent zero-sequence network is depicted in
Figure 2. When a fault emerges on the second line, a voltage source identical in magnitude and phase to the zero-sequence voltage is introduced at the fault point within the zero-sequence network. This voltage source serves as the equivalent circuit. For coal mine power grids, the longest cable supply line generally does not exceed 3 km. In short-distance cables, employing π-type or T-type equivalent circuit parameters exerts negligible influence on steady-state analysis outcomes. This work adopts T-type equivalent circuits for lines in the zero-sequence network. In the figure,
are the zero-sequence impedances of the four cable lines,
are the insulation impedance of the first line, the third line, and the fourth line, respectively; the end of the line is connected with the load.
in the figure are the zero-sequence currents of the four lines.
In
Figure 3, the insulation impedance of the cable is the sum of the three-phase insulation impedances, where the insulation impedance consists of the parallel combination of the insulation resistance and the distributed capacitance
. Moreover, the cable insulation impedance is much greater than the line’s zero-sequence impedance, i.e.,
. Therefore,
Figure 2 can be simplified, ignoring the zero-sequence impedance of the line and showing the insulation impedance. The simplified zero-sequence network diagram is shown in
Figure 3.
The relationship between the zero-sequence current and the zero-sequence voltage of the non-fault phase line is as follows:
(n = 1,3,4) is the zero-sequence current of the non-faulty line.
For faulted lines, Equation (1)’s zero-sequence current–voltage relationship fails. This work thus analyzes single-phase grounding faults, examining fault-line zero-sequence characteristics. The equivalent zero-sequence network appears in
Figure 4. Assuming phase-A grounding faults—where metallic/high-resistance faults represent special cases—different fault types are simulated via grounding resistance adjustment. High-resistance values denote single-phase high-impedance faults. In the figure,
represent the phase voltage of the three-phase power supply,
represent the insulation resistance to ground for the three phases,
represent the distributed capacitance to ground for the three phases, and
represents the equivalent resistance value of the faulted line. Based on the three-phase characteristics of the line, the three-phase insulation impedance and three-phase distributed capacitance of the cable are all equal, i.e.,
,
[
22].
According to Kirchhoff’s current law, the zero-sequence current of a fault line is as follows:
In Equation (2), the following values apply:
,
,
, and according to symmetry,
. For the convenience of calculation simplification, let
, and the sum of the three-phase voltages is always zero, i.e.,
; substituting these conditions into Equation (2) simplifies to the following:
As per Equation (3), zero-sequence voltage originates from the collective action of grounding impedance
, insulation impedance
, and phase voltage
of the faulted phase. Based on the formula, internal equivalence for the zero-sequence voltage in
Figure 3 is achievable. The equivalent circuit is illustrated in
Figure 5.
According to Kirchhoff’s current law, the following is obtained:
Using Ohm’s law to express the currents in Equation (4) in terms of voltage and impedance, the relationship between the zero-sequence voltage and phase voltage of the system at fault is as follows:
In the formula:, , .
Thus, the phase voltage of the faulted phase leads the zero-sequence voltage by (
) degrees [
23]. Integrating zero-sequence current analysis, prior to single-phase grounding fault occurrences in the system, grounding resistance is absent (i.e.,
). Substituting this condition into Equation (2) yields the pre-fault system zero-sequence current as
. The post-fault system zero-sequence voltage follows Equation (3). Subtraction of the pre-fault from the post-fault system zero-sequence currents yields the zero-sequence current variation, as Equation (6) demonstrates:
In Equation (6),
and
are the zero-sequence voltage before and after the fault, respectively. And
, so the change in zero-sequence voltage can be ignored, and so Equation (6) can be simplified as follows:
In the formula, is the phase-to-ground voltage of the faulted phase A.
Similarly, the zero-sequence current difference before and after the fault of the non-fault line is as follows:
In practical engineering, since it is impossible to predict the time when the fault occurs, the vector of the zero-sequence current can be collected in real time, and the variation in the zero-sequence current can be obtained by the difference in the vector of the zero-sequence current collected at two different times, as shown in Equation (9):
In the formula, is the zero-sequence current vector of the nth cycle, is the zero-sequence current vector of two cycles before the nth cycle, and is the zero-sequence current variation in practical engineering.
2.2. Steady-State Impedance Analysis of High-Impedance Ground Faults in a Neutral-Point Grounding System with an Arc-Suppression Coil
Certain coal mine power grids use arc-suppression-coil grounding. While facilitating single-phase fault arc extinction, its compensation effect hampers precise faulted line identification via conventional methods [
24]. This work thus analyzes arc-suppression-coil grounding circuits. Coal mine networks primarily operate in over-compensation mode, modeled in
Figure 6.
The equivalent operational circuit for the fault is shown in
Figure 4. The zero-sequence equivalent network of the arc-suppression-coil grounding system during a fault is shown in
Figure 7.
The relationship between zero-sequence voltage and phase voltage in the neutral grounding fault model through an arc-suppression coil is shown in Equation (10):
In the formula, L is the inductance of the grounding arc-suppression coil, , .
Comparing Equation (5) with Equation (10) reveals that variation in the system’s overall insulation parameters is influenced by the system’s neutral grounding method. Although the neutral grounding method affects the system’s zero-sequence voltage, it does not affect the relationship between the cable’s zero-sequence electrical signals and the insulation parameters.
Comparing Equation (7) with Equation (8) reveals the following: (1) fault line zero-sequence current variation exhibits distinct phase/magnitude characteristics versus that of non-fault lines, while non-fault lines share identical variations; (2) the fault line variation phase matches its faulty phase voltage.
Thus, fault line selection is achieved through the cross-line comparison of zero-sequence current variation phase and magnitude differences.
Coal mining environments yield microampere-scale line zero-sequence current changes. Practically, minute signals resist reliable recognition and incur high interference vulnerability. This work tackles this via a novel high-resistance grounding fault detection method merging steady-state impedance analysis with Holmes–Duffing oscillators. The approach extracts zero-sequence current features through impedance analysis, feeds them into noise-immune Holmes–Duffing systems for precise identification, and resolves minute fault signal recognition.