Next Article in Journal
A Compact and Wideband Active Asymmetric Transmit Array Unit Cell for Millimeter-Wave Applications
Previous Article in Journal
Sub-ppb Methane Detection via EMD–Wavelet Adaptive Thresholding in Wavelength Modulation TDLAS: A Hybrid Denoising Approach for Trace Gas Sensing
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Adaptive Virtual Impedance Droop Control of Parallel Inverters for Islanded Microgrids

1
Institute of Automation, Qilu University of Technology (Shandong Academy of Sciences), Jinan 250000, China
2
Qingdao Veccon Electric Co., Ltd., Qingdao 266200, China
*
Author to whom correspondence should be addressed.
Sensors 2025, 25(16), 5166; https://doi.org/10.3390/s25165166
Submission received: 13 June 2025 / Revised: 31 July 2025 / Accepted: 15 August 2025 / Published: 20 August 2025
(This article belongs to the Section Industrial Sensors)

Abstract

The droop control strategy, known for its communication-free nature, is widely adopted for the parallel operation of inverter units. However, in microgrids, mismatches in line impedances and various measurement inaccuracies often lead to imbalanced reactive power sharing among inverters and significant circulating current. To address these challenges, this paper proposes an adaptive droop control method that relies solely on local measurements from each inverter, eliminating the need for communication. The proposed approach integrates the deviation between the ratio of reactive power to output voltage and its reference value to generate an Adaptive Virtual Impedance Droop Control (AVIDC) mechanism. This enables a dynamic balance between reactive power output and voltage drop. The simulation and experimental results validate the effectiveness of the proposed control strategy, demonstrating a significant improvement in the accuracy of reactive power sharing.

1. Introduction

Microgrids are localized low-voltage power supply systems that coexist with the conventional power grid. Their design focuses on generating electricity at the point of consumption, aiming to minimize transmission losses and maximize the efficiency of the generated power. Power electronic inverters facilitate the smooth integration and dependable functioning of distributed energy resources (DERs), thereby presenting substantial prospects for extensive implementation [1,2,3]. Three-level inverters, a type of multilevel inverter, possess advantages such as reduced Total Harmonic Distortion (THD) over traditional two-level inverters, thus finding suitability in a wide range of industrial applications [4]. Figure 1 shows the microgrid architecture, where traditional generators, PV arrays, and battery systems are all connected to a shared AC bus. When the point of common coupling (PCC) is closed, the microgrid remains linked to the main grid; opening the PCC isolates the network, placing it in an islanded operation. Compared to a single distributed generation (DG) unit, microgrids offer greater capacity and enhanced control flexibility, allowing them to meet stringent power-quality requirements [5,6].
In islanded mode, effectively managing the rated power and suppressing circulating currents among DGs is critical. Droop control has become the preferred method owing to its scalability, modular design, built-in redundancy, and operational flexibility. This enables decentralized control and wireless parallel operation of multiple inverters, which is particularly advantageous for DG systems. However, this control strategy also presents several challenges: (1) low accuracy in reactive power sharing, (2) significant circulating currents among parallel units, and (3) voltage and frequency droop at the output of inverter units [7,8,9].
To address the issue of unequal power distribution and enhance the control performance of microgrids, various power-sharing control strategies have been proposed, as discussed in [10], including centralized control, master-slave control, and droop control based on voltage power droop and frequency reactive boost. However, these approaches typically rely on accurate line-impedance information to suppress power coupling, which limits their practical feasibility. To mitigate the impact of line impedance mismatches and improve the power-sharing accuracy, researchers have developed several enhanced droop control strategies. In [11], we reviewed a synchronized fixed-frequency droop control strategy based on a global satellite navigation system, and for the first time, we combined the satellite timing signal with droop control to realize the synchronized operation of a distributed power supply in microgrids without communication. In [12], improvements were made by introducing error reduction and voltage restoration operations to enhance reactive power sharing precision. In [13], the authors devised a self-adaptive control scheme that modifies system inertia and damping in real time to bolster frequency regulation and maintain voltage stability. In [14], a secondary frequency and voltage droop control method based on consensus theory and the concept of Virtual Synchronous Generators (VSGs) was introduced, enhancing system damping and stability. However, its application is limited to ideal conditions and depends heavily on communication links between distributed units. Gabl O. M. A. devised a multi-objective mixed integer nonlinear programming (MINLP) framework that incorporates secondary control zone constraints. Although the approach delivers good performance, it is highly model-dependent and therefore lacks the flexibility needed to cope with complex or rapidly changing operating conditions [15]. In [16], conventional droop control was complemented with voltage- and current-averaging regulators, which curtailed bus voltage deviations and improved the accuracy of load current sharing. Verma V proposed inserting an active power offset to decouple the power components, a step that subsequently refines reactive power allocation [17]. However, this method suffers from a slow dynamic response and high sensitivity to load types.
An alternative approach focuses on using adaptive virtual impedance to directly compensate for mismatches in the line impedance. This method not only improves power sharing performance and enhances the system’s ability to handle nonlinear loads, but also increases oscillation damping and strengthens overall system stability [18,19,20]. Over the past few years, numerous control schemes leveraging adaptive virtual impedance have been introduced. M. Ahmed proposed an adaptive virtual-impedance scheme for voltage-source converters in hybrid AC/DC microgrids; however, the approach overlooked the nonlinear characteristics intrinsic to microgrid environments [21]. In [22], the virtual resistance and reactance are designed as linear functions of the output current of the DG, which improves the conventional droop and inverse droop control, ensuring equal sharing of active and reactive power. R. An proposed a successive-approximation approach to virtual-impedance adjustment that alternates between conventional droop control and adaptive tuning; however, abrupt load changes may cause deviations in the equivalent line impedance [23]. In [24], frequency regulation and inter-inverter power balancing can be attained with a virtual synchronous generator that adjusts its inertia in real time; nevertheless, the method hinges on very precise impedance measurements and comprehensive frequency response characterization. The Distributed Adaptive Virtual Impedance Control (DAVIC) strategy proposed in [25] adjusts virtual impedance automatically based on the difference between local power and the average power across all modules, yet it depends on low-bandwidth CAN communication for data sharing, which introduces time delays. Adib proposed an adaptive inductance-feedforward scheme that preserves system stability even when the grid is weak or exhibits high impedance [26]. In [27], a dynamic model of the PCC was developed to elucidate the power coupling mechanism, and by adaptively tuning droop gains and feedforward coefficients in real time, the dynamic performance of the microgrid was significantly improved.
Existing methods that aim to improve the accuracy of reactive power sharing and minimize circulating currents among distributed units face limitations in terms of real-time adaptability and general applicability, making them inadequate for handling complex and variable line-impedance conditions. This study proposes an adaptive virtual impedance control scheme aimed at equalizing power sharing and eliminating circulating currents in parallel inverters. The principal contributions of this study are summarized as follows:
  • By examining the reactive power mismatch caused by conventional droop control in parallel inverter systems, this study paves the way for faster and more accurate reactive power balancing.
  • An adaptive virtual impedance control method is introduced, in which an adaptive controller is derived by integrating the deviation between the ratio of reactive power to output voltage and its desired reference value for each measurement unit.
  • To validate the effectiveness of the proposed control strategy, a prototype system was designed and constructed. Experimental results demonstrate that the output waveforms of the parallel inverters exhibit strong consistency and that circulating currents between inverter units are effectively suppressed.
The remainder of this paper is organized as follows. Section 2 reviews droop control fundamentals and pinpoints the reactive power sharing errors typical of conventional implementations. Section 3 elaborates on the proposed solution, the Adaptive Virtual Impedance Droop Control (AVIDC), and explains its operating principles. Section 4 presents the simulation and laboratory evidence that verifies the effectiveness of the AVIDC. Finally, Section 5 concludes the paper with a summary of the key findings.

2. Conventional Droop Control and Analysis of Power Sharing Errors

The parallel operation structure of multiple DG units is illustrated in Figure 2. In islanded mode, each DG unit is equipped with an independent controller. Considering a single DG unit as an example, the main circuit employs a simplified DC voltage source Udcn to represent the distributed energy source. The inverter INVn converts the DC voltage into three-phase AC voltage and current. The output stage includes a filter composed of inductance Lfn and capacitance Cfn, with Rfn representing the equivalent series impedance. Each DG unit is connected to the common AC bus via transmission lines Feedern (n = 1,2,3,…), forming a parallel network with the other DG units to complete the microgrid topology [28].

2.1. Conventional Droop Control Method

In islanded mode, droop control enables each DG unit to operate independently, thereby realizing a true “plug-and-play” capability without the need for internal communication. This study focuses on a droop control scheme that links active power to frequency (Pω) and reactive power to voltage (QU), assuming that the output impedance of the inverter is mainly inductive.
A simplified circuit of an islanded microgrid consisting of n DGs is shown in Figure 3. The complex power output Sn of a single DG unit can be expressed as:
S n = P n + j Q n
where Pn and Qn represent the active and reactive powers, respectively, and are given by the following expressions [29]:
P n = U n V P C C Z n cos ( θ n ϕ n ) V P C C 2 Z n cos θ n
Q n = U n V P C C Z n sin ( θ n ϕ n ) V P C C 2 Z n sin θ n
where Un signifies the inverter output voltage amplitude, and ϕn specifies its power angle. Variable Vpcc denotes the voltage magnitude measured at PCC. The output impedance is characterized by Zn as its magnitude and θn as its phase.
Given that sizable filter inductors are usually employed, the inverter output impedance can be regarded as chiefly inductive—the impedance Zn = Rn + jXn can be approximated as ZnjXn. Under this assumption, Equations (2) and (3) can be simplified as follows [30]:
P n = U n V P C C X n ϕ n
Q n = U n V P C C V P C C 2 X n
where Xn represents the output reactance of the inverter.
Drawing on these expressions and recognizing that the phase offset between Un and Vpcc is negligible (sinϕϕ and cosϕ ≈ 1), it can be seen that active power Pn is acutely responsive to variations in the power angle, whereas reactive power Qn is governed chiefly by differences in voltage magnitude. As a result, most communication-free load-sharing controllers incorporate a voltage droop U into the voltage reference of the inverter. To replicate this behavior, droop control schemes labeled (Pω) and (QU), as shown in Figure 4, are typically employed. Accordingly, the inverter output voltage reference, incorporating both its angular frequency and amplitude, can be expressed as follows [31]:
ω n = ω 0 G P n P n
U n = U 0 G Q n Q n
where ω0 and U0 denote the inverter’s nominal angular frequency and output voltage magnitude, respectively, and Gpn and GQn serve as the droop gains for active and reactive power. The corresponding frequency and voltage droop coefficients are obtained using the following expressions:
G P n = Δ ω P n *
G Q n = Δ U Q n *
where Δω and ΔU represent the maximum allowable deviations in frequency and voltage, respectively. Pn* and Qn* denote the nominal active and reactive power values at that operating point.

2.2. Reactive Power Analysis of Conventional Droop Control

Rearranging Equation (5) yields an alternative formulation for the output voltage magnitude of the distributed generator, as follows:
U n = V PCC + X n Q n V PCC
Figure 5 illustrates the QU curve associated with droop control, which is employed to investigate how reactive power is shared among sources. In practical deployments, the different geographical positions of the DG units lead to unequal line impedances. To simplify the analysis, a two-DG system is first considered and then generalized to an n-DG configuration. According to Equation (10), when line impedance mismatches occur, the power characteristic curves of DG1 and DG2 exhibit different slopes, leading to errors in reactive power sharing. Although steepening or flattening the droop curve can reduce current-sharing errors and yield a more precise reactive power allocation, the adjustment introduces a pronounced voltage droop that ultimately compromises overall system stability.
Proportional reactive power allocation across DG units is attained by choosing each unit’s QU droop coefficient to vary inversely with its rated reactive power capability. That is:
n 1 Q 1 * = n 2 Q 2 *
The voltage difference between two distributed generators leads to reactive power sharing errors and circulating currents. The relative reactive power error rate eQn can be derived as follows:
e Q n = Δ Q n Q n * = Q n Q n * Q n * × 100%
By combining Equations (7) and (10), the reactive power delivered by a DG unit can be expressed as:
Q n = V PCC ( U 0 V PCC ) ( X n + G Q V PCC )
From Equation (13), we can derive the following equation:
( Q 1 * + Δ Q 1 ) ( X 1 + G Q 1 V PCC ) = ( Q 2 * + Δ Q 2 ) X 2 + G Q 2 V PCC
Under steady state conditions, a pair of parallel DG units must deliver a fixed total amount of reactive power. Generalizing to any number of DG units, the algebraic sum of their reactive power sharing errors must therefore equal zero, as indicated by
Δ Q 1 + Δ Q 2 = 0
Based on Equations (10)–(15), the reactive power sharing error eQn for two DG units operating in parallel is expressed as
e Q 1 = G Q 1 X 2 G Q 2 X 1 G Q 2 X 1 + X 2 + G Q 1 V PCC + G Q 2 V PCC
e Q 2 = G Q 2 X 1 G Q 1 X 2 G Q 1 X 1 + X 2 + G Q 1 V PCC + G Q 2 V PCC
For two DG units with different capacities, a sufficient condition for achieving balanced reactive power sharing is
Q 1 * Q 2 * = X 2 X 1
Although line impedance is difficult to measure accurately in practical microgrid operations, a desirable performance can still be achieved through the adoption of appropriate control strategies.

3. Proposed AVIDC Method

3.1. Design of Equivalent Line Impedance

The output impedance of the closed-loop inverter is pivotal for accurate power sharing and underpins an effective droop control design. By judiciously shaping this impedance, one can counteract line impedance mismatches that would otherwise degrade performance. The total output impedance comprises three parts: the intrinsic impedance of the inverter, added virtual impedance, and feeder impedance. Of these, the intrinsic component dominates and exerts the greatest influence on the system stability and dynamic behavior.
Based on the model of the inverter’s main circuit, it is evident that coupling exists between the d-axis and q-axis components after coordinate transformation. To eliminate this coupling and achieve decoupled control of the dq-axis components, feedforward decoupling is introduced during the design of the voltage and current control loops. The outer voltage loop employs a proportional-integral controller GV = Kpv + Kiv/s, which ensures a stable voltage output. The inner current loop utilizes a proportional controller Gi = kpc, which enhances the dynamic response of the system [22].
Figure 6a presents a simplified equivalent control diagram for the decoupled voltage-current dual loop system. The corresponding closed-loop transfer function is therefore expressed as
u o d q = G u ( s ) u o d q * Z o ( s ) i o d q
where Gu(s) represents the voltage gain and Zo(s) denotes the output impedance, defined as follows:
G u ( s ) = K p ν G i K p w m s + K i ν G i K p w m C f L f s 3 + C f ( R f + G i K p w m ) s 2 + ( K p ν G i K p w m + 1 ) s + K i ν G i K p w m
Z o ( s ) = L f s 2 + ( R f + G i K p w m ) s C f L f s 3 + C f ( R f + G i K p w m ) s 2 + ( K p v G i K p w m + 1 ) s + K i v G i K p w m
where Kpv represents the voltage loop proportional gain, Kiv the voltage loop integral gain, Gi the current loop proportional gain, and Kpwm an inverter gain factor that scales with the output voltage. With these parameters defined, the inverter can be represented as a two-terminal Thévenin equivalent circuit, as depicted in Figure 7.
The behavior of Gu(s) is directly related to the voltage stability. Under ideal tuning, the controller gains are set such that Gu(s) = 1 and Zo(s) = 0, allowing the output voltage to follow its reference exactly. However, in real low-voltage microgrids, feeder impedances comprise both resistive and inductive elements, making it challenging to separate active and reactive power regulation.
To ensure that the total output impedance remains predominantly inductive, a virtual inductance Lv is introduced into the control block diagram and tuned around its nominal value, as shown in Figure 6b. The product of the inverter output current and virtual inductance is used as a negative feedback signal applied to the voltage reference. According to Thévenin’s theorem, Equation (19) can be rewritten as
u o d q = G u s u o d q * Z o ( s ) i o d q = G u s u o d q * Z o s + G u s s L v i o d q
System and controller parameters are listed in Table 1. Figure 8 displays the magnitude and phase response curves of variables Gu(s) and Zo(s), confirming that the closed loop is stable. At the fundamental frequency, the voltage loop gain Gu(s) = 1, enabling the output voltage to match its reference without a steady-state error. Moreover, Z’o(s) has a larger amplitude margin than Zo(s), resulting in better voltage stabilization when the load changes abruptly, and the high output impedance can suppress the loop current, making the power distribution more accurate. Z’o(s) has a large phase angle margin, which is less prone to oscillation and overshooting, and the system stability is high. At the same frequency, variable Zo(s) shows a phase lead of roughly 90°, giving the network a much stronger inductive character than in the case of Zo(s). The inclusion of virtual impedance thus achieves effective power decoupling and allows the overall output impedance to be treated as an ideal inductance.

3.2. Adaptive Virtual Impedance Droop Control

Since DG units are unable to determine the relative magnitude of their respective line impedances, it is challenging to appropriately adjust the virtual impedance values. To address this issue, an AVIDC method is proposed to compensate for line impedance mismatches. In this approach, the output reactive power and voltage magnitude are fed into an adaptive virtual impedance controller. Virtual impedance tuning is achieved solely through locally measured information without requiring any communication between the DG units.
Because the impedance angle of ΔLvir can be tuned to account for variations in the feeder impedance, the adaptive virtual impedance is intentionally chosen to be inductive so that the control concept can be more clearly demonstrated. Consequently, the adaptive virtual impedance for each DGn unit (n = 1, 2,…, n) is defined as
Δ L ν i r = k Q s 2 ( Q u Q * u * )
where kQ is the integral gain used to adjust the virtual inductance, and placing the Q/u ratio in the minuend position directly reflects the extent to which the system deviates from its ideal state. This deviation metric guides the system toward the desired operating points. Additionally, second-order integration continuously integrates the error caused by external disturbances, gradually compensating for their effects and enhancing system robustness.
By combining Equations (16) and (23), we can derive the expression for the relative reactive power error e*Q1 of DG1 after the introduction of virtual impedance:
e * Q 1 = G Q 1 X 2 n 2 X 1 + ω 0 k Q s 2 G Q 1 Q 2 U 2 Q 2 * U 2 * G Q 2 Q 1 U 1 Q 1 * U 1 * G Q 2 X 1 + X 2 + G Q 1 V P C C + G Q 2 V P C C + ω 0 k Q s 2 Q 1 U 1 Q 1 * U 1 * + Q 2 U 2 Q 2 * U 2 * = e Q 11 + e Q 12 e Q 11 = G Q 1 X 2 G Q 2 X 1 G Q 2 X 1 + X 2 + G Q 1 V P C C + G Q 2 V P C C + ω 0 k Q s 2 Q 1 U 1 Q 1 * U 1 * + Q 2 U 2 Q 2 * U 2 * e Q 12 = ω 0 k Q s 2 G Q 1 Q 2 U 2 Q 2 * U 2 * G Q 2 Q 1 U 1 Q 1 * U 1 * G Q 2 X 1 + X 2 + G Q 1 V P C C + G Q 2 V P C C + ω 0 k Q s 2 Q 1 U 1 Q 1 * U 1 * + Q 2 U 2 Q 2 * U 2 *
A review of Equations (16) and (24) shows that variable eQ11 closely matches relative reactive power error eQ1. When the adaptive virtual impedance is increased, |eQ11| becomes slightly smaller than |eQ1|.
Assuming that the reactive power droop coefficients of the two DG units are equal (GQ1 = GQ2) and the adaptive virtual impedance coefficients are the same (KQ1 = KQ2), then the equivalent line impedance of DG1 is greater than that of DG2. According to the analysis in Section 2.2, this implies X1 > X2, leading to the following relationships: Q1 > Q2 for reactive power, and U1 > U2 for output voltage magnitude. From Equation (24), we can infer that eQ12 > 0, eQ11 < 0, and therefore |e*Q1| < |eQ1|. These outcomes verify that the proposed control scheme markedly reduces errors in reactive power allocation.
Figure 9 depicts the QU profile under adaptive virtual impedance regulation. Equation (10) shows that the gradient of each curve is governed by the combined impedance of its branches. Under ideal conditions, the two DG units initially converge to operating points A and B. Due to differences in line impedance, adaptive virtual impedance is introduced to compensate for these deviations, resulting in the curves ultimately stabilizing at points C and D. As described by Equation (24), the addition of adaptive virtual impedance is effectively equivalent to adjusting the slopes of the QU curves, bringing them closer together. As shown in Figure 9, adaptive virtual impedance clearly improves the distribution of reactive power.
Implementing the adaptive virtual impedance scheme yields the following expression for each DG’s aggregate virtual impedance:
L vir = L v + Δ L v i r = L ν + k Q s 2 ( Q u Q * u * )
where Lv is the baseline virtual inductance that maintains the overall line impedance inductive, ΔLvir is the adaptive term that adjusts this impedance in real time, and Lvir denotes the aggregate virtual impedance assigned to each DG unit.
Figure 10 illustrates the system control structure employing adaptive virtual impedance. The three-phase current and voltage output by the inverter are collected using current and voltage sensors. The PQ calculation is performed using Equations (4) and (5), and droop control is implemented in accordance with Equations (6) and (7). The adaptive virtual impedance value is applied to the dq axis to obtain the reference voltage, which is defined as follows: Ultimately, through the voltage-current dual closed-loop control, the three-level active neutral point clamped diodes are driven to conduct and turn off via SPWM [32].
u d ref u q ref = u d u q s L vir ω L vir ω L vir s L vir i d i q

4. Simulation and Experimental Analysis

To verify the feasibility of the proposed AVIDC strategy, a simulation model of an islanded microgrid comprising two DG units was developed. In this system, two inverter units share a common load, with each connected through feeder lines of unequal impedances. The main parameters and their corresponding values for the target system are presented in Table 1.

4.1. Simulation Analysis

As shown in Figure 11, the power distribution under conventional droop control is illustrated for two DG units with identical rated powers. During the first stage (0 < t < 0.2 s), the microgrid is initially connected to Load 1 only. In the second stage (0.2 < t < 0.4 s), a sudden load change occurs as Load 2 is added to the system. In the third stage (0.4 < t < 0.6 s), DG2 is abruptly disconnected.
Under steady-state conditions, as depicted in Figure 11a, conventional droop control ensures acceptable active power sharing, even in the presence of a line impedance mismatch. However, there is a significant error in reactive power sharing, indicating that discrepancies in line impedance negatively impact the accuracy of power distribution.
Figure 11b summarizes the simulation results for the proposed control strategy when both DG units are rated at the same power level, and the test sequence replicates the events depicted in Figure 11a. This figure clearly shows that active and reactive power outputs are in a 1:1 ratio when the DG units have the same rated power, and that the output power maintains excellent consistency even when the load changes abruptly or the parallel inverter structure is altered. Corresponding error metrics for the conventional approach and the AVIDC scheme are listed in Table 2.
Figure 12 illustrates the variation in the proposed adaptive virtual impedance at different stages to accommodate line impedance mismatches. Figure 13 shows the three-phase output current waveforms of the two DG units, which maintain excellent consistency in terms of amplitude and phase under the same rated power conditions, ensuring that they have the same active and reactive power output. The proposed strategy enables a rapid response to sudden load changes and variations in DG unit availability, ensuring that the output currents of both DG units remain aligned. This effectively suppresses circulating currents between the units.
Therefore, the simulation results confirm that the same value of reactive power can be output with the same rated capacity of the inverters, and the equalization of reactive power is achieved, thus proving the validity of the proposed method.

4.2. Experiments Demonstrate

To verify the feasibility of the proposed strategy, a 5 kW three-phase DG system is designed and built. The prototype is shown in Figure 14, and its specifications are listed in Table 1. The DSP TMS320F28379D is employed as the main controller. To support higher voltages and power levels, STGW30V60DF power switches and an active neutral point-clamped three-level converter topology are employed.
Figure 15 illustrates the current-sharing performance of the two DG units. When the conventional method is applied, inconsistencies in line impedance between the inverters result in discrepancies in both the amplitude and phase of the currents.
Figure 16 shows that by employing the proposed control method, the two DG units maintain strong consistency in both current amplitude and phase. Additionally, the method demonstrates excellent performance in response to sudden load changes at time t1 and structural changes in the microgrid at time t2.
The active and reactive power outputs of each inverter under the conventional droop control strategy are shown in Figure 17a. It can be seen that while the active power of the parallel inverters is equally shared, disparities in line impedance among the inverters lead to deviations in reactive power distribution, preventing equal sharing of reactive power. Figure 17b illustrates the power-sharing performance of the two inverters after the proposed method is applied. The reactive power remains equally shared at t0 when both inverters supply the same load, at t1 when the load undergoes a sudden change, and at t2 when DG2 is disconnected, demonstrating the effectiveness of the proposed method.
Figure 18 illustrates the adaptive variation of the virtual impedance under the proposed control method when the DG units have identical rated powers, enabling effective averaging in reactive power sharing.
From the experimental analysis, it can be concluded that using the proposed control method, the value of virtual impedance can be adjusted in real time with changes in the working conditions, which offsets the difference in line impedance. The amplitude and phase of the output current of the inverter are maintained consistently, which ensures the consistency of the output power.
Table 3 compares the proposed strategy with those of previous studies. Compared with previous methods, the proposed method exhibits better reactive power allocation performance with less reactive power sharing error in the face of sudden load changes and inverter structure changes. Moreover, it relies solely on the local measurement data of the inverters and exhibits excellent scalability.

5. Conclusions

In islanded microgrids, mismatches in feeder impedance often lead to an uneven sharing of reactive power among parallel inverters and trigger circulating currents. To counteract these drawbacks, we first quantified the resulting reactive power error and then proposed an AVIDC strategy. The scheme dispenses with any communication links and relies exclusively on measurements local to each inverter. By continuously integrating the deviation between the instantaneous reactive power to voltage ratio and its rated power to voltage reference, the controller synthesizes a time-varying virtual impedance, thereby retuning the inverter output in real time and restoring balanced reactive power sharing across the microgrid. The results show that compared with the conventional droop control approach, the proposed strategy significantly improves the accuracy of reactive power sharing and maintains strong regulation performance even under sudden load changes and microgrid structural variations. This control method is of great significance in ensuring accurate power sharing in islanded microgrids with mismatched line impedances among distributed generation units. Finally, both simulation and experimental results verify the feasibility of the proposed control strategy.

Author Contributions

Conceptualization, H.Y.; methodology, H.Y.; software, H.Y.; validation, H.Y., Y.W. and Z.S.; formal analysis, H.W.; investigation, G.Z.; resources, L.G.; data curation, M.Z.; writing—original draft preparation, H.Y.; writing—review and editing, Y.W.; visualization, Z.S.; supervision, M.Z.; project administration, H.L.; funding acquisition, G.Z. All authors have read and agreed to the published version of the manuscript.

Funding

This research was supported in part by the Qingdao Key Technology Research Project under Grant 25-1-1-gjgg-4-gx; in part by the Shandong Province “Double-Hundred Talent Plan” under Grant WST2024010; in part by the Science and Technology Small and Medium-sized Enterprises Innovation Ability Enhancement Project of Shandong Province under Grant 2024TSGC0162; and in part by Young Talent of Lifting engineering for Science and Technology in Shandong, China under Grant SDAST2025QTB003.

Data Availability Statement

The data presented in this study are available in this article.

Conflicts of Interest

Author Hongzhang Lyv was employed by Qingdao Veccon Electric Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as potential conflicts of interest. The authors declare that the funder was not involved in the study design, collection, analysis, interpretation of data, writing of this article, or decision to submit it for publication.

References

  1. Bano, F.; Rizwan, A.; Serbaya, S.H.; Hasan, F.; Karavas, C.S.; Fotis, G. Integrating Microgrids into Engineering Education: Modeling and Analysis for Voltage Stability in Modern Power Systems. Energies 2024, 17, 4865. [Google Scholar] [CrossRef]
  2. Zhao, Z.L.; Guo, J.T.; Luo, X.; Lai, C.S.; Yang, P.; Lai, L.L.; Li, P.; Guerrero, J.M.; Shahidehpour, M. Distributed Robust Model Predictive Control-Based Energy Management Strategy for Islanded Multi-Microgrids Considering Uncertainty. IEEE Trans. Smart Grid 2022, 13, 2107–2120. [Google Scholar] [CrossRef]
  3. Wang, C.; Wang, Z.; Chu, S.H.; Ma, H.; Yang, N.; Zhao, Z.L.; Lai, C.S.; Lai, L.L. A two-stage underfrequency load shedding strategy for microgrid groups considering risk avoidance. Appl. Energy 2024, 367, 123343. [Google Scholar] [CrossRef]
  4. Rasoanarivo, I.; Tehrani, K.; Scalcon, F.P.; Nahid-Mobarakeh, B. A Dual Multilevel Adaptive Converter for Microgrid Applications. In Proceedings of the IECON 2022—48th Annual Conference of the IEEE Industrial Electronics Society, Brussels, Belgium, 17–20 October 2022; pp. 1–6. [Google Scholar]
  5. Yu, L.; Shi, D.; Xu, G.Y.; Guo, X.B.; Jiang, Z.; Jing, C.Y. Consensus Control of Distributed Energy Resources in a Multi-Bus Microgrid for Reactive Power Sharing and Voltage Control. Energies 2018, 11, 2710. [Google Scholar] [CrossRef]
  6. Jasim, A.M.; Jasim, B.H.; Bures, V.; Mikulecky, P. A New Decentralized Robust Secondary Control for Smart Islanded Microgrids. Sensors 2022, 22, 8709. [Google Scholar] [CrossRef]
  7. Ding, M.; Tao, Z.L.; Hu, B.; Tan, S.J.; Yokoyama, R. Parallel Operation Strategy of Inverters Based on an Improved Adaptive Droop Control and Equivalent Input Disturbance Approach. Electronics 2024, 13, 486. [Google Scholar] [CrossRef]
  8. Baneshi, E.; Kolahduzloo, H.; Ebrahimi, J.; Mahmoudian, M.; Pouresmaeil, E.; Rodrigues, E.M.G. Coordinated Power Sharing in Islanding Microgrids for Parallel Distributed Generations. Electronics 2020, 9, 1927. [Google Scholar] [CrossRef]
  9. Toub, M.; Bijaieh, M.M.; Weaver, W.W.; Robinett, R.D.; Maaroufi, M.; Aniba, G. Droop Control in DQ Coordinates for Fixed Frequency Inverter-Based AC Microgrids. Electronics 2019, 8, 1168. [Google Scholar] [CrossRef]
  10. Han, H.; Hou, X.C.; Yang, J.; Wu, J.F.; Su, M.; Guerrero, J.M. Review of Power Sharing Control Strategies for Islanding Operation of AC Microgrids. IEEE Trans. Smart Grid 2016, 7, 200–215. [Google Scholar] [CrossRef]
  11. Li, K.; Li, Y.D.; Fan, R.Q.; Liu, Z.H.; Lu, M.Z. A Review of Synchronous Fixed-Frequency Microgrid Droop Control Systems Based on Global Positioning System. Processes 2025, 13, 54. [Google Scholar] [CrossRef]
  12. Han, H.; Liu, Y.; Sun, Y.; Su, M.; Guerrero, J.M. An Improved Droop Control Strategy for Reactive Power Sharing in Islanded Microgrid. IEEE Trans. Power Electron. 2015, 30, 3133–3141. [Google Scholar] [CrossRef]
  13. Li, D.D.; Zhu, Q.W.; Lin, S.F.; Bian, X.Y. A Self-Adaptive Inertia and Damping Combination Control of VSG to Support Frequency Stability. IEEE Trans. Energy Convers. 2017, 32, 397–398. [Google Scholar] [CrossRef]
  14. Lu, L.Y.; Chu, C.C. Consensus-Based Secondary Frequency and Voltage Droop Control of Virtual Synchronous Generators for Isolated AC Micro-Grids. IEEE J. Emerg. Sel. Top. Circuits Syst. 2015, 5, 443–455. [Google Scholar] [CrossRef]
  15. Abo Gabl, O.M.; Shaaban, M.F.; Zeineldin, H.H.; Ammar, M.E. A Multiobjective Secondary Control Approach for Optimal Design of DG Droop Characteristic and Control Mode for Autonomous Microgrids. IEEE Syst. J. 2022, 16, 5445–5454. [Google Scholar] [CrossRef]
  16. Dadi, R.; Meenakshy, K.; Damodaran, S.K. A modified droop control method for dc microgrid with improved voltage regulation and current sharing. In Proceedings of the 2020 International Conference on Power, Instrumentation, Control and Computing (PICC), Thrissur, India, 17–19 December 2020; IEEE: New York, NY, USA, 2020; pp. 1–6. [Google Scholar]
  17. Verma, V.; Solanki, S.K.; Solanki, J. Improved Reactive Power Sharing Between Droop Controlled Inverters In Islanded Microgrid. In Proceedings of the IEEE-Power-and-Energy-Society General Meeting (PESGM), Montreal, QC, Canada, 3–6 August 2020. [Google Scholar]
  18. Fu, S.Q.; Sun, Y.; Li, L.; Liu, Z.J.; Han, H.; Su, M. Power Oscillation Suppression in Multi-VSG Grid by Adaptive Virtual Impedance Control. IEEE Syst. J. 2022, 16, 4744–4755. [Google Scholar] [CrossRef]
  19. Wang, F.; Zhang, L.J.; Feng, X.Y.; Guo, H. An Adaptive Control Strategy for Virtual Synchronous Generator. IEEE Trans. Ind. Appl. 2018, 54, 5124–5133. [Google Scholar] [CrossRef]
  20. Xiao, J.J.; Wang, L.; Bauer, P.; Qin, Z. Virtual Impedance Control for Load Sharing and Bus Voltage Quality Improvement in Low-Voltage AC Microgrid. IEEE Trans. Smart Grid 2024, 15, 2447–2458. [Google Scholar] [CrossRef]
  21. Ahmed, M.; Meegahapola, L.; Vahidnia, A.; Datta, M. Adaptive Virtual Impedance Controller for Parallel and Radial Microgrids With Varying X/R Ratios. IEEE Trans. Sustain. Energy 2022, 13, 830–843. [Google Scholar] [CrossRef]
  22. Vijay, A.S.; Parth, N.; Doolla, S.; Chandorkar, M.C. An Adaptive Virtual Impedance Control for Improving Power Sharing Among Inverters in Islanded AC Microgrids. IEEE Trans. Smart Grid 2021, 12, 2991–3003. [Google Scholar] [CrossRef]
  23. An, R.H.; Liu, Z.; Liu, J.J. Successive-Approximation-Based Virtual Impedance Tuning Method for Accurate Reactive Power Sharing in Islanded Microgrids. IEEE Trans. Power Electron. 2021, 36, 87–102. [Google Scholar] [CrossRef]
  24. Chang, G.W.; Nguyen, K.T. A New Adaptive Inertia-Based Virtual Synchronous Generator with Even Inverter Output Power Sharing in Islanded Microgrid. IEEE Trans. Ind. Electron. 2024, 71, 10693–10703. [Google Scholar] [CrossRef]
  25. Wei, B.Z.; Marzàbal, A.; Ruiz, R.; Guerrero, J.M.; Vasquez, J.C. DAVIC: A New Distributed Adaptive Virtual Impedance Control for Parallel-Connected Voltage Source Inverters in Modular UPS System. IEEE Trans. Power Electron. 2019, 34, 5953–5968. [Google Scholar] [CrossRef]
  26. Adib, A.; Fateh, F.; Mirafzal, B. Smart Inverter Stability Enhancement in Weak Grids Using Adaptive Virtual-Inductance. IEEE Trans. Ind. Appl. 2021, 57, 814–823. [Google Scholar] [CrossRef]
  27. Wang, J.Z.; Liu, Z.; Feng, K.W.; Liu, J.J. An Adaptive Droop and Feedforward Control Based Transient Power Sharing and Decoupling Method for Grid-Forming Inverters in Islanded Microgrids. IEEE Trans. Ind. Electron. 2025, 72, 4800–4810. [Google Scholar] [CrossRef]
  28. Zhu, M.M.; Zhou, G.X.; Guo, L.; Song, N.R.; Wang, Y.P.; Lv, H.Z.; Chu, S. Energy Storage Converter Off-Grid Parallel Cooperative Control Based on CAN Bus. Electronics 2025, 14, 2010. [Google Scholar] [CrossRef]
  29. Wu, M.; Wu, C.; Wang, L.; Yuan, Y. Reactive Power Equalization Strategy for Islanded Microgrids Based on Improved Adaptive Droop Factor. Electronics 2025, 14, 1981. [Google Scholar] [CrossRef]
  30. Zhang, Z.; Gao, S.; Zhong, C.M.; Zhang, Z.Y. Accurate Active and Reactive Power Sharing Based on a Modified Droop Control Method for Islanded Microgrids. Sensors 2023, 23, 6269. [Google Scholar] [CrossRef]
  31. Peng, J.C.H.; Raman, G.; Soon, J.L.; Hatziargyriou, N.D. Droop-Controlled Inverters as Educational Control Design Project. IEEE Trans. Power Syst. 2022, 37, 1623–1633. [Google Scholar] [CrossRef]
  32. Tehrani, K.A. Conception, Synthèse et Application d’une Nouvelle Commande Robuste par PID Fractionnaire pour Les Onduleurs Multiniveaux; Institut National Polytechnique de Lorraine: Nancy, France, 2010. [Google Scholar]
  33. Tu, B.E.; Xu, X.L.; Gu, Y.F.; Deng, K.T.; Xu, Y.L.; Zhang, T.Y.; Gao, X.R.; Wang, K.N.; Wei, Q.J. Improved Droop Control Strategy for Islanded Microgrids Based on the Adaptive Weight Particle Swarm Optimization Algorithm. Electronics 2025, 14, 893. [Google Scholar] [CrossRef]
Figure 1. Microgrid structure.
Figure 1. Microgrid structure.
Sensors 25 05166 g001
Figure 2. Topology of an isolated microgrid containing n DG units.
Figure 2. Topology of an isolated microgrid containing n DG units.
Sensors 25 05166 g002
Figure 3. Conceptual schematic of an isolated microgrid configuration.
Figure 3. Conceptual schematic of an isolated microgrid configuration.
Sensors 25 05166 g003
Figure 4. (a) Pω droops; (b) QU droops.
Figure 4. (a) Pω droops; (b) QU droops.
Sensors 25 05166 g004
Figure 5. Parallel DGS output Q-U loop and control.
Figure 5. Parallel DGS output Q-U loop and control.
Sensors 25 05166 g005
Figure 6. Transfer function schematic of the inverter (a) without virtual inductance (b) incorporating virtual inductance.
Figure 6. Transfer function schematic of the inverter (a) without virtual inductance (b) incorporating virtual inductance.
Sensors 25 05166 g006
Figure 7. Thévenin equivalent representation of the closed-loop configuration.
Figure 7. Thévenin equivalent representation of the closed-loop configuration.
Sensors 25 05166 g007
Figure 8. Bode plots showing the voltage gain response of the system and its corresponding equivalent impedance.
Figure 8. Bode plots showing the voltage gain response of the system and its corresponding equivalent impedance.
Sensors 25 05166 g008
Figure 9. Reactive power sharing for the two DG units twice—dotted for operation without adaptive virtual impedance and solid for operation with adaptive virtual impedance.
Figure 9. Reactive power sharing for the two DG units twice—dotted for operation without adaptive virtual impedance and solid for operation with adaptive virtual impedance.
Sensors 25 05166 g009
Figure 10. Block diagram illustrating the control architecture for virtual-impedance compensation.
Figure 10. Block diagram illustrating the control architecture for virtual-impedance compensation.
Sensors 25 05166 g010
Figure 11. (a) Simulation results of power sharing using traditional droop control (b) Simulated power-sharing performance under the AVIDC strategy.
Figure 11. (a) Simulation results of power sharing using traditional droop control (b) Simulated power-sharing performance under the AVIDC strategy.
Sensors 25 05166 g011
Figure 12. Simulation results of adaptive virtual impedance variation.
Figure 12. Simulation results of adaptive virtual impedance variation.
Sensors 25 05166 g012
Figure 13. The simulation results of the three-phase output currents of DG1 and DG2 under AVIDC control.
Figure 13. The simulation results of the three-phase output currents of DG1 and DG2 under AVIDC control.
Sensors 25 05166 g013
Figure 14. Experimental platform.
Figure 14. Experimental platform.
Sensors 25 05166 g014
Figure 15. Output current waveforms of the two DG units under conventional control. (a) Conventional droop method (load1 is connnected). (b) Conventional droop method with changeable load (load1 and load2 are connected). (c) Conventional droop method with changeable DG units (DG1 is connected).
Figure 15. Output current waveforms of the two DG units under conventional control. (a) Conventional droop method (load1 is connnected). (b) Conventional droop method with changeable load (load1 and load2 are connected). (c) Conventional droop method with changeable DG units (DG1 is connected).
Sensors 25 05166 g015
Figure 16. Output current waveforms of the two DG units under AVIDC control. (a) Proposed method (load1 is connnected). (b) Proposed method with changeable load (load1 and load2 are connected). (c) Proposed method with changeable DG units (DG1 is connected).
Figure 16. Output current waveforms of the two DG units under AVIDC control. (a) Proposed method (load1 is connnected). (b) Proposed method with changeable load (load1 and load2 are connected). (c) Proposed method with changeable DG units (DG1 is connected).
Sensors 25 05166 g016
Figure 17. (a) Experimental evaluation of power-sharing efficacy under conventional droop control; (b) experimental investigation of power-sharing performance under AVIDC.
Figure 17. (a) Experimental evaluation of power-sharing efficacy under conventional droop control; (b) experimental investigation of power-sharing performance under AVIDC.
Sensors 25 05166 g017
Figure 18. Experimental results of adaptive virtual impedance variation.
Figure 18. Experimental results of adaptive virtual impedance variation.
Sensors 25 05166 g018
Table 1. System Parameter.
Table 1. System Parameter.
System ParameterValues
MicrocontrollerDSPTMS320F28379D
IGBT ModuleSTGW30V60DF
Rated line to line RMS
voltage level, U0
155 V
Nominal frequency, f050 Hz
LC filter, Rf, Lf, Cf0.1 Ω, 3 mH, 30 μF
DC link voltage, Udc400 V
Low-pass filter, ωr50 rad/s
Switching frequency, fs10 kHz
Line 1 impedance, R1, L10.05 Ω, 0.05 mH
Line 2 impedance, R2, L20.1 Ω, 0.1 mH
GP5 × 10−6
GQ4 × 10−5
Kpv, Kiv, Gi0.02, 30, 20
Lv5 mH
kQ0.00027
Load1 R1, L110 Ω, 10 mH
Load2 R2, L220 Ω, 15 mH
Table 2. Simulation-based comparison of reactive power-sharing deviations.
Table 2. Simulation-based comparison of reactive power-sharing deviations.
System Operating ModeError/%DG Parallel
Operation
Change the LoadChange DG Unit
Traditional control methodsQerr_140.5%38.9%22.4%
Qerr_230.8%27.6%-
The proposed methodQerr_18.5%2.1%1.1%
Qerr_26.9%2.6%-
Table 3. Reactive power sharing deviations: AVIDC versus alternative control schemes.
Table 3. Reactive power sharing deviations: AVIDC versus alternative control schemes.
System Operating ModeCommunication ModeScalabilityError/%DG Parallel
Operation
Change The LoadChange DG Unit
Distributed adaptive virtual impedance control [25]CAN
Communication
YesQerr_117.4%13.4%9.6%
Qerr_216.5%11.7%-
Weight particle swarm
optimization algorithm [33]
NoNoQerr_113.5%8.4%5.9%
Qerr_211.4%6.8%-
Equivalent input disturbance [7]NoNoQerr_118.6%15.4%12.1%
Qerr_217.7%13.5%-
AVIDCNoYesQerr_19.1%2.3%1.4%
Qerr_27.6%3.1%-
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Yang, H.; Sun, Z.; Wang, H.; Wang, Y.; Zhu, M.; Guo, L.; Zhou, G.; Lyu, H. Adaptive Virtual Impedance Droop Control of Parallel Inverters for Islanded Microgrids. Sensors 2025, 25, 5166. https://doi.org/10.3390/s25165166

AMA Style

Yang H, Sun Z, Wang H, Wang Y, Zhu M, Guo L, Zhou G, Lyu H. Adaptive Virtual Impedance Droop Control of Parallel Inverters for Islanded Microgrids. Sensors. 2025; 25(16):5166. https://doi.org/10.3390/s25165166

Chicago/Turabian Style

Yang, Hongzhi, Zibo Sun, Haoran Wang, Yipei Wang, Mengmei Zhu, Lei Guo, Guangxu Zhou, and Hongzhang Lyu. 2025. "Adaptive Virtual Impedance Droop Control of Parallel Inverters for Islanded Microgrids" Sensors 25, no. 16: 5166. https://doi.org/10.3390/s25165166

APA Style

Yang, H., Sun, Z., Wang, H., Wang, Y., Zhu, M., Guo, L., Zhou, G., & Lyu, H. (2025). Adaptive Virtual Impedance Droop Control of Parallel Inverters for Islanded Microgrids. Sensors, 25(16), 5166. https://doi.org/10.3390/s25165166

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop