Next Article in Journal
Decreasing Mining Losses for the Room and Pillar Method by Replacing the Inter-Room Pillars by the Construction of Wooden Cribs Filled with Waste Rocks
Next Article in Special Issue
Development of a Multiphysics Real-Time Simulator for Model-Based Design of a DC Shipboard Microgrid
Previous Article in Journal
Synergistic Effect of Expanded Graphite-Silane Functionalized Silica as a Hybrid Additive in Improving the Thermal Conductivity of Cementitious Grouts with Controllable Water Uptake
Previous Article in Special Issue
Application of the First Replica Controller in Korean Power Systems
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Comparison of DER Voltage Regulation Technologies Using Real-Time Simulations

1
Sandia National Laboratories, Albuquerque, NM 87123, USA
2
Electric Power Research Institute, Palo Alto, CA 94304, USA
3
Connected Energy, Pittsburgh, PA 15220, USA
*
Authors to whom correspondence should be addressed.
Energies 2020, 13(14), 3562; https://doi.org/10.3390/en13143562
Submission received: 18 May 2020 / Revised: 18 June 2020 / Accepted: 30 June 2020 / Published: 10 July 2020
(This article belongs to the Special Issue Advancements in Real-Time Simulation of Power and Energy Systems)

Abstract

:
Grid operators are now considering using distributed energy resources (DERs) to provide distribution voltage regulation rather than installing costly voltage regulation hardware. DER devices include multiple adjustable reactive power control functions, so grid operators have the difficult decision of selecting the best operating mode and settings for the DER. In this work, we develop a novel state estimation-based particle swarm optimization (PSO) for distribution voltage regulation using DER-reactive power setpoints and establish a methodology to validate and compare it against alternative DER control technologies (volt–VAR (VV), extremum seeking control (ESC)) in increasingly higher fidelity environments. Distribution system real-time simulations with virtualized and power hardware-in-the-loop (PHIL)-interfaced DER equipment were run to evaluate the implementations and select the best voltage regulation technique. Each method improved the distribution system voltage profile; VV did not reach the global optimum but the PSO and ESC methods optimized the reactive power contributions of multiple DER devices to approach the optimal solution.

1. Introduction

Installed variable distributed renewable energy is continuing to grow, with much of this growth being related to distribution systems [1]. In the past, utilities could assume unidirectional power flow and regulation of grid voltage within ANSI Standard C84.1 [2] limits. The penetration of distributed energy resources (DER) presents challenges for distribution circuit voltage regulation [3] because fluctuating DER current injection on the feeder from renewable energy resources leads to voltage perturbations [4]. The voltage swings are currently corrected by load tap changing (LTC) transformers, capacitor banks, and other voltage regulation equipment—often designed or placed prior to the addition of the DER systems. Many distribution system operators (DSOs) are concerned about increasing DER deployments, and often create screening criteria to limit the deployments [5,6,7], because they cannot guarantee power quality in high DER penetration scenarios [8].
New grid code requirements in Hawaii, California, and at the national level (i.e., IEEE 1547-2018 [9]) are requiring newly installed DER grid support functions, including volt–watt, fixed power factor, and volt–VAR. When these functions are configured correctly, distribution hosting capacity can be drastically increased by mitigating thermal and voltage excursions, minimizing losses, and maintaining ANSI limits [10,11].
Extensive research has been conducted to mitigate voltage deviations on distribution systems and can be categorized into three broad areas. The first area uses standardized DER grid support functions and can be further separated into supervised or unsupervised methods. The second area uses machine learning algorithms to mitigate the voltage deviations. The third area uses OLTCs and other distribution equipment to solve the voltage deviation problem, however, this is out of the scope of this paper.
Unsupervised functionality relies on the autonomous functionality in DER equipment and is characterized by speed and simplicity. Many of the original unsupervised voltage regulation studies were conducted by EPRI, Sandia National Laboratories (Sandia), National Renewable Energy Laboratory (NREL), and Georgia Institute of Technology in the 2010s, and typically focused on the autonomous voltage-reactive power (volt–VAR) function which adjusts DER-reactive power based on local grid measurements [12,13,14,15]. There has also been extensive research into the optimal placement of DER assets to avoid reaching voltage and thermal constraints [16,17].
Unfortunately, unsupervised voltage regulation algorithms rarely achieve the global optimal operation for a DER fleet because each DER does not have visibility into the rest of the circuit. Supervised control algorithms pull in data from multiple sources of telemetry in order to achieve greater control accuracy, accounting for the voltages at multiple points on the distribution circuit. These optimal DER setpoints are achieved with more sophisticated techniques combining distribution state estimation [18,19], and centralized or decentralized controls [20,21]. Other researchers have investigated the coordination of on-load tap changing (OLTC) transformers and wind systems reactive power control [22] and DER active power curtailment for voltage regulation [23]; while others have studied control of demand response loads [24] and community energy management systems on voltage regulation [25]. These supervised methods depend on bidirectional communications and novel optimization algorithms which require knowledge of the feeder states, topology of the circuit, and DER locations. Unfortunately, these approaches are currently infeasible because DSOs often do not have in-depth knowledge of their distribution system designs, locations where customer-owned DER equipment is interconnected, or the communications to end devices.
The two primary contributions of this work are (a) the development of a novel DER management system (DERMS), called the Programmable Distribution Resource Open Management Optimization System (ProDROMOS) [26], and (b) developing a standardized methodology to tune, evaluate, and compare different distribution voltage regulation approaches in increasing levels of fidelity. ProDROMOS was designed to ingest real-time feeder data to provide extensive visibility into distribution circuits using the Georgia Tech-developed Integrated Grounding System Analysis program for Windows (WinIGS) distribution system state estimation tool [27] and then optimize the DER-reactive power settings to meet voltage regulation and economic objectives. In the case of supervised voltage regulation methods, there are varying degrees of visibility into the power system. In some of the approaches (e.g., [28,29]), the DER are only aware of the other DER interconnection voltages and they adjust their reactive power to improve the visible voltage levels. In more sophisticated control methods, like that developed in ProDROMOS, distribution system state estimation [26,30,31,32] is used to expand the visibility into the distribution system, and therefore improve the ability of the DER to optimize their reactive power contributions to optimize the voltage profile across the entire feeder.
The second contribution is a standardized evaluation methodology comparing three DER-reactive power technologies using two different levels of fidelity: real-time (RT) power simulations and RT power hardware-in-the-loop (PHIL) simulations. For this project, the following voltage regulation methods were compared:
  • an unsupervised, volt–VAR (VV) function, defined by the IEEE 1547-2018 standard;
  • a real-time communication-based optimization technique called extremum seeking control (ESC) [33,34,35,36];
  • the ProDROMOS particle swarm optimization optimal power flow (PSO OPF) method.
In each of the fidelity levels, timing, control, and communication parameters were adjusted to enact the desired voltage regulation controls. A comparative analysis of the three methods was then performed to evaluate the effectiveness of each voltage regulation method for two reduced-order utility distribution circuits from Albuquerque, NM and Grafton, MA. The results showed that ESC and ProDROMOS provided the best voltage regulation and maintained ANSI C84.1-2011 Range A limits and reached near-optimal reactive power setpoints when controlling multiple DER. While not presented here, the results in this paper provided sufficient confidence in the control techniques that they were then executed on a live feeder in Grafton, MA—the results of the field demo are included in [26].
The reminder of the paper is organized as follows: Section 2 describes the voltage regulation problem, the DER control methods and the RT simulation platform; Section 3 describes the simulation tests and results; Section 4 provides a discussion of the results; Section 5 provides a conclusion to the study. The Supplementary Materials section provide access to portions of the non-proprietary models and code used for these experiments.

2. Voltage Regulation Methods

In a distribution circuit without generation, power flows from a substation to customers and the voltage generally drops from source to load. As previously stated, the utility will regulate the voltage with LTC transformers, capacitor banks, and other voltage regulation equipment. However, a distribution circuit with DER may create bidirectional power flows and increase voltages at the point of common coupling (PCC). The increasing voltage operating envelope and variable power output of the DER create voltage perturbations and may violate ANSI C84.1 Range A limits. The voltage perturbations increase the mechanical operations of the utility-owned voltage regulation equipment [8,35]. This equipment was not designed for such rapid switching, which increase operations and maintenance (O&M) costs and decreases the DSOs ability to provide safe and reliably power [8]. An alternative solution is to use the equipment that is causing the voltage rise to mitigate the problem by using the DER grid support functions with reactive power capabilities. In this paper, we investigate volt–VAR, ESC, and ProDROMOS controls. Volt-var is a common function required by many European and North American grid codes and interconnection standards [37,38,39] included in most DER devices. ESC and ProDROMOS are more sophisticated controllers which calculate the target reactive power of DER and then set a power factor function to produce the reactive power level. It should be noted that in new DER interconnection standards, such as IEEE Std 1547-2018, there are constant reactive power modes—but these functions were not available in the equipment at the time of these experiments.

2.1. Autonomous Volt–VAR Control

The volt–VAR (VV) function adjusts the reactive power of the DER based on the PCC voltage measurements according to an adjustable curve of (voltage and reactive power) points. This distributed autonomous control function was the first reactive power factor evaluated. In this project, the VV curve for the RT experiments was defined with non-aggressive voltage points = {95%, 99%, 101%, 105%} and Var points = {25%, 0%, 0%, −25%} because there were oscillations between the simulated DER device and the power simulation.

2.2. Extremum Seeking Control

Extremum seeking control (ESC) is a real-time optimization technique for multi-agent, nonlinear, and infinite-dimensional systems [33,34,35,36]. The decentralized, model free control algorithm operates by adjusting the reactive power to optimize measured outputs, in this case, feeder voltage. The system adjusts inputs; (u); via a sinusoidal injection, demodulates system outputs; (J(u)); to extract approximate gradients, and finally performs a gradient descent. A block diagram of this approach is shown in Figure 1. The designer sets the parameters k, l, h, a and ω. Additionally, unique probing frequencies for each controllable DER are chosen, but one must ensure that l and h << ω, ensuring proper operation of the high and low pass filters in each ESC loop. The reader is referred to [36] for more details.
The optimization function for the simulations is given in Equation (1):
J = 1 n i = 1 n p h = 1 3 ( V i , ph V nom , i , ph ) 2
where Vi, is the voltage measurement at Bus i and Vnon is the nominal voltage. This is a proposed new grid support function that can achieve the global optimum. We assume that each bus in the circuit feeder, can provide measurements in these experiments and more details will be provided in the RT simulation platform section.

Extremum Seeking Control Parameter Selection

These parameters were chosen based on prior experience with ESC simulations and laboratory demonstrations [33,34,35,36], and a systematic debugging process that considered communication latencies, DER power factor (PF) accuracies, and prior lessons learned. The sequence to implement ESC control follows:
  • The ProDROMOS manager constructs the objective function, J.
  • The ProDROMOS manager configures the DER with unique ωs to avoid controller conflict while producing 10 or more data points per cycle.
  • The parameters l and h are set significantly less than ω, such that the perturbation is passed through the washout filter s/(s + h) but is removed by the lowpass filter l/(s + l).
  • Parameter a is selected to produce the smallest reactive power oscillation that is observable in the objective function, J.
  • Parameter k is set based on designer experience, the stability of ESC simulation, and desired time to reach local minimum of J.
  • The ProDROMOS monitors the objective function and makes PF changes to each DER to improve the performance of the system.
The optimization of ESC parameters is a future research interest due to the time requirements necessary to tune the parameters for the application. The use of the ProDROMOS platform and the RT simulator allowed the ESC designer confidence in the parameters before real world deployment.

2.3. ProDROMOS

The ProDROMOS system completed the DER-reactive power setpoint optimization in multiple stages. Initially, intelligent electronic devices (IEDs) from the power system would collect data from the RT, PHIL, or live feeder and send those to the WinIGS state estimation system tool. For the RT and PHIL experiments, these data were collected from virtualized micro-phasor measurement units (μPMUs) and formatted in IEEE C37.118 format using a physical SEL-3373 Phasor Data Concentrator (PDC) in the Distributed Energy Technologies Laboratory (DETL) at Sandia National Laboratories. These data were then parsed into different sections of the WinIGS feeder. By segmenting the state estimation problem into smaller feeder pieces, WinIGS was able to solve the state estimation at 30 Hz. Details of the construction of the WinIGS models for the Public Service Company of New Mexico (PNM) and National Grid (NG) feeders in NM and MA are presented in [26]. The solution to the state estimation included active and reactive power values for different loads in the model. These values were passed to the optimization routine as another IEEE C37.118 data stream.
The Particle Swarm Optimization (PSO) was used to determine the Optimal Power Factor (OPF) settings for the DER devices because of the nonconvex fitness landscape [26]. PSO OPF uses a time-series OpenDSS simulation wrapped in a PSO loop to calculate the OPF values. The load data for OpenDSS were populated with state estimation solutions before each run of the optimization routine, which occurred every 1 or 2 min. A solar production persistence forecast was created to estimate the solar energy over the next time horizon (5 min). This forecast was used as the photovoltaic (PV) power profile in the OpenDSS simulation. The WinIGS software and the python-based PSO code were implemented in a portable Connected Energy cloud-based Windows virtual machine (VM) that allowed geographically distributed developers to access the environment. Figure 2 provides a simplified approach of the PSO OPF method.
Once populated with the anticipated PV production and the current—and assumed static—active and reactive power levels for the loads in the OpenDSS simulations, the PSO ran the OpenDSS model with different DER PF setpoints to calculate the optimal setpoints for each of the DER devices. The optimization formulation was designed to capture the voltage regulation and economic considerations of operating PV systems with a non-unity power factor (PF):
Minimize P F [ w 0 δ v i o l a t i o n ( V ) + w 1 σ ( V V b a s e ) + w 2 C ( P F ) ]
where
δ v i o l a t i o n ( V ) = 1
if any
|V| > Vlim
σ ( V V b a s e )
is the standard deviation of V V b a s e
C ( P F ) = 1 | P F |
V is a vector of bus voltages, Vbase is a vector of the nominal voltages for each bus, and PF is a vector of the DER PFs. The objective function is minimized when the bus voltages are at Vbase and PF = 1. Vlim was selected to be the ANSI C84.1 Range A limits of ±0.05 per unit (pu), so any solutions outside the limits would be highly penalized. The third term was a simplified method to discourage solutions that moved away from unity power factor, because these solutions would curtail active power (and expense the PV owner through net metering, power purchase agreements, etc.) at high irradiance times. More sophisticated methods for determining the curtailment magnitude were considered, but the simple approach shown here was implemented. For the experiments conducted in this project, w0 = 1.0, w1 = 2.0, and w2 = 0.05. The optimization was configured so that if all the bus voltages were within an acceptance threshold (set to 0.2% of nominal voltage) the PSO would not run. If any of the voltages were outside ANSI Range A the PSO would run. Furthermore, if the new PF values did not change the objective function by an objective threshold (set to 1 × 10−7), the new PFs would not be sent to the DER devices to minimize communications and DER memory writes.

3. Evaluation Environments

3.1. Distribution Systems of Study

Several distribution systems models were acquired from PNM and NG for evaluation. The PNM models were in the SynerGEE software format and NG models were in the CYME software format. To run the power hardware-in-the-loop (PHIL) experiments, a series of conversions were needed to convert the models to OPAL RT-Lab-compliant formats (MATLAB/Simulink). The CYME and SynerGEE models were first converted to OpenDSS. The objective of the project was to show voltage regulation with 50% PV penetration level (defined by feeder PV nameplate/peak feeder load). For those feeders that did not meet this threshold, additional residential PV systems were randomly added to the buses in the model to meet this goal. Time-domain RT-Lab simulations are not possible with feeder models with thousands of buses, so the full OpenDSS models were reduced in complexity to be incorporated in the RT-Lab and WinIGS platform. The circuit reduction algorithms reduced the number of buses in a model while maintaining an equivalent voltage profile throughout the model at feeder locations of interest [40,41]. Ultimately, a commercial 12.47-kV PNM feeder and a suburban 13.80 kV NG feeder were used for the evaluation of the different voltage regulation algorithms. The PNM reduced order feeder that was used in these experiments is shown in Figure 3 and the NG feeder is shown in Figure 4.

3.2. Real-Time Evaluation Platform

The evaluation platform could be run in a software-in-the-loop (SIL), a power-hardware-in-the-loop (PHIL), or a combination of SIL and PHIL setup. The SIL and PHIL simulations were conducted with an Opal-RT OP5600 real-time digital simulator running distribution feeder models in RT-LAB with a 100 us timestep. To complete the PHIL experiments, a physical 3.0-kW inverter was interfaced to the power simulation via a 180 kVA Ametek RS180 grid simulator. The current waveform was measured by a Person CT110 and returned to the power simulation via an analog input channel. The DC side of the inverter was connected to an Ametek TerraSAS PV simulator configured to represent a 3.0-kWp silicon PV system.
In the RT simulations, the EPRI-developed DER Simulator [42] software, emulated smart solar inverters with several grid support functionalities and communication interfaces. Any number of DER devices, with different nameplate capacities and phasing configurations, were instantiated with independent irradiance profiles. The EPRI-developed TCP/IP protocol called Data Bus (DBus) was used as the co-simulation interface to exchange data between the OPAL-RT simulator and the DER simulator. The DER simulator determined the active and reactive power of the DER devices based on irradiance profiles, voltage, frequency, and DER settings. The active and reactive power outputs are exchanged via DBus with the RT simulation. The RT simulation passed the voltage and frequency of the points of common coupling (PCCs) where the DER were interconnected to the feeder.
The PHIL simulations used the RT simulation environment but replaced one of the EPRI PV systems with a 3.0-kW residential inverter that was then scaled to a device in the PNM model (inverter 3, 258 kW) and NG feeder (inverter 1, 658 kW). The 258-kW and 684-kW inverters were three-phase balanced output inverters where each phase produced the same current magnitude and phase angle. The 3-kW inverter was scaled to match its per phase output to the 684-kW inverter for the NG experiments and the 258-kW inverter for the PNM experiments. The advantage of incorporating a physical inverter into the simulations was twofold: the control algorithms had to be built with communication interfaces to interact with real equipment over the public internet networks and the abnormal operations of physical equipment (e.g., startup times, ramp rates, non-optimal maximum power point tracking, converter losses, etc.) were represented in the power simulation and needed to be managed by the control algorithms. Scaling a residential PV system to represent a utility-owned site likely produced higher reactive power errors because of the lower-cost control and power electronics components in the 3-kW inverter, but this helped approximate inverter interoperability and control functionality, with the expectation that the fielded system would perform better.

4. Results for PNM Model

4.1. Simulations with the PNM Model

The PNM model included two scenarios. In the first scenario, there were three simulated EPRI PV inverters, and in the second scenario, the 258-kW inverter at bus 15 was replaced with a physical single phase 3.0 kW that was then scaled to the 258-kW rating in the simulation. The EPRI simulator provided three correlated, highly variable irradiance profiles from a PV site on the US east coast to feed the simulated inverters. These profiles were generated from a single Global Horizontal Irradiance (GHI) measurement and then shifted and scaled to account for geographical separation of the PV sites. The PV irradiance profiles were then smoothed based on the plant sizes using the Wavelet Variability Model [43,44,45,46] to account for spatial averaging with large PV systems. To understand the impact of spatial averaging on the irradiance profiles the reader is invited to review [47,48]. The final PV profiles are shown in Figure 5. The smoothed irradiance profiles are used because clouds do not instantaneously shade larger PV systems and it takes time for them to pass over the entire array. Additionally, variable load profiles were used on loads connected to bus 6 and bus 13 to create transient voltage variability.

4.2. Baseline Simulation

The PNM model was simulated using P/Q data passed from the EPRI DER simulator to the RT power simulation using the Data Bus (DBus) exchange. The hardware PV inverter was interfaced using the Ideal Transformer Method (ITM) [48]. The simulated PV inverters connected to bus 12 and bus 14 were simulated using a P/Q controlled PV inverter model [49]. In this feeder model, controllable capacitor banks were removed. At each PV site, irradiance is converted to AC power using pvlib-python [50]; an example of the power simulation is shown in Figure 6. The voltage profile for each of the 15 buses is shown in Figure 7. As can be seen from these results, there is relatively little voltage rise when the PV systems inject power at their points of common coupling (PCCs). Overall, the feeder maximum voltage is driven by the 10-MW PV system on this feeder.

4.3. Volt–VAR Simulation

The volt–VAR function was implemented by programming the VV function in the EPRI DER devices using a DNP3 command. The deadband was set to ±0.01 pu so the DER would support the feeder voltage. Aggressive VV parameters produced reactive power oscillations because the EPRI simulator-to-Opal-RT communication rates were limited to once/second—e.g., DBus read the DER bus voltage once a second and then DBus updated the Opal-RT DER-reactive power set point on the next DBus write. As a result, a stable VV curve defined as V = {92, 99, 101, 108} pu, Q = {25, 0, 0, −25}% nameplate VA capacity were used for the simulations. The reactive power contribution from the 10-MW plant was modest, but it reduced the maximum and average feeder voltages, as shown in Figure 8—where the minimum, maximum, and average voltages were plotted using for all buses and all phases. The line represents the average voltage for all the buses and the colored patch represents the range of voltages over time for the feeder. Notice from the simulation results that the VV function can bring the average bus voltage closer to the desired nominal value. These effects can also be observed from the maximum voltage, reducing the voltage band created from the maximum and minimum values.

4.4. Extremum Seeking Control Simulation

ESC was implemented with a RT model of the PNM feeder using multiple parameter sets. When selecting ESC parameters, there are multiple tradeoffs that make it challenging. For instance, large probing magnitudes help the objective function signal stand out from feeder noise, but it causes larger voltage deviations once a solution is reached. The normalized voltage deviation objective function was used with probing signal frequencies that could be independently demodulated. Ultimately, the parameters shown in Table 1 were used. As shown in Figure 9, the reactive power from the DER devices to move the average bus voltage toward the nominal set point, i.e., 1 pu as compared to the baseline simulation. The maximum and minimum bus voltage values were adjusted closer to nominal as well. The reactive power probing signal’s impact on the feeder voltage is clearly seen in the results.

4.5. State-Estimation-Based Particle Swarm Optimization

The setup for the PSO simulations is shown in Figure 2. In this case, the state estimation was used to update the load data in the OpenDSS time series simulation and forecasts of three-minute average DER power were used to update the OpenDSS power levels. Figure 10 illustrates the average power forecasts. The forecasts track the average irradiance reasonably well with some lag as is common for persistence forecasts. Note that it takes 1 h for the forecast to begin because it uses prior production data and the clear sky index to generate the power prediction.
The OpenDSS time series simulation was run multiple times using PSO to determine the optimal PF set points for each of the DER devices. It was found that absolute care must be taken to use the same component and settings for the Simulink/RT-Lab and OpenDSS models; otherwise erroneous solutions were found. Binary variables (e.g., capacitor banks) and discrete variables (e.g., tap changes) must also be re-initialized (i.e., reset) with each new run of the OpenDSS time series simulation to prevent initial conditions from being set by the prior simulation—an unfortunate byproduct of using the OpenDSS communication interface implementation. As shown in Figure 11, the reactive power from the DER devices to move the average bus voltage toward the nominal set point, i.e., 1 pu as compared to the baseline simulation. Interestingly, with the constraints placed on updating a new PF level (e.g., the solution must be a certain amount better than the previous one), there are only 3 times the DER devices had their PF setting updated as shown in Figure 12. This threshold can be tuned, but it is desirable because it reduces the number of PF write commands and shows the solution is robust to changing PV irradiance. As seen in Figure 12, the initial PF setpoints for DER 1 and 2 absorbed reactive power while DER 3 injected reactive power. For this feeder topology and DER locations, the global optimum required reactive power absorption or injection to minimize the voltage deviation from nominal at all buses in the feeder.

5. Results for National Grid Model

5.1. Simulations with the National Grid Model

Like the PNM model, VV, ESC, and PSO voltage regulation approaches were compared on the NG feeder model. In this model, there is a 684-kW utility-owned three-phase PV site and 30 single phase PV systems. The NG system was unbalanced, with phase B above nominal voltage, phase C below nominal voltage, and phase A operating approximately at nominal voltage. This prevented many of the voltage regulation methods from making significant improvements to the feeder voltage profile when only the three-phase utility-owned inverter was controlled. Therefore, we proposed controlling all 31 DER on the NG model for further testing.

5.2. Baseline Simulation with National Grid Model

Four-hour irradiance profiles, at one second resolution were created for the 31 DER devices in this model. Figure 13 shows the voltage profiles for each of the phases.

5.3. Volt–VAR

There were negligible reactive power contributions from the utility-owned 684-kW PV site because the average voltage at the PCC was within the VV dead band. However, the single-phase inverters were able to shrink the feeder voltage envelope, as shown in Figure 14.

5.4. Extremum Seeking Control

ESC was conducted on the NG feeder model. In this feeder, there was significant phase imbalance and at the PV system: phase A voltages are close to nominal (~0.99–1.01 pu), phase B voltages are significantly above nominal (at times >1.05 pu), and phase C voltages are <0.95 pu—as shown in Figure 15. This presented a challenge for the ESC approach (like all the other voltage regulation methods) because the DER can only inject symmetric (positive sequence) reactive power. This means all the phase voltages are shifted in the same direction with a change in the DER power factor. Grouping the DER based on what phase they were interconnected was a good method of limiting the number of probing frequencies but allowed each of the phases to adjust their reactive power contributions independently. Unfortunately, this also produced a sizable voltage ripple on the power system because all the inverters on each phase had the same probing frequency. Ultimately, the parameters shown in Table 2 were used for ESC testing on the NG model, and the feeder voltage profile is shown in Figure 16.

5.5. State-Estimation-Based Particle Swarm Optimization

The DER PF PSO optimization technique wrapped NG OpenDSS time-series simulations. The code was configured to execute once a minute to determine the optimal set point for all the DER devices. Using the same swarm size of 60, the solution often took 10 iterations, where it was capped. In those cases, it took longer than 60 s, so the optimization was configured to run every two minutes. As shown in Figure 17, optimizing 31 DER devices were difficult with a swarm size of 60 because the first two solutions produced results that pushed the minimum or maximum voltages outside the baseline envelope. However, after a few more solutions, the PSO significantly improved the voltage profile of the feeder for the remainder of the simulation. It should be noted that we did not attempt to optimize the PSO code to minimize run time.

6. PHIL Results

To further validate the operational effectiveness of the PSO voltage regulation method, realistic DER power hardware-in-the-loop (PHIL) simulations were conducted with both the PNM and NG feeder models. These simulations provide better fidelity because they show ProDROMOS can work with real PV communications systems and ramp rates.

6.1. PNM Baseline

To validate the PHIL setup for the PNM feeder model, a comparison was made between active power, reactive power, and bus voltage for the RT and PHIL simulations. Figure 18 shows the voltage profile for the RT and PHIL simulations. The positive and negative reactive power changes around 1000 s in the baseline case were due to setting the PF setpoint on the 10-MW system to +0.85 and −0.85 to verify communications and that the PHIL simulation was closed-loop. Overall, the RT and PHIL simulations are closely matched.

6.2. PNM Particle Swarm Optimixation PHIL

The only change from the RT simulations was that commands were communicated with the physical device to change the power factor and the DER was connected to the power simulation using a PHIL interface, as opposed to DBUS. The 258-kW system was recreated by scaling a 3-kW DER device. It was found that the physical equipment recreated the power profile reasonably well. Slight differences in the active power are due to efficiencies of the devices and slightly oversizing the simulated PV system in the Ametek PV simulator. The PSO solutions were repeatable for multiple runs. There were some deviations in the reactive power contributions from the PSO solutions, but overall, they matched well, as shown in Figure 19. Do note the PHIL PSO simulation was not started for approximately 10 min at the beginning of the RT-Lab simulation, which is why it takes some time for the reactive power on the physical DER to change. Similar results for the NG RT and PHIL simulations are described in [26].

7. Discussion

Each of the voltage regulation methods have their advantages and disadvantages in terms of communications and computational overhead, implementation complexity, and availability in DER equipment. Overall, each of them can reduce the voltage deviation from nominal and maintain the feeder well within ANSI Range A voltage limits. For the PNM model, the DER PCC voltages are barely outside the dead-band, so the DER does not absorb much reactive power. The ESC method produces a DER-reactive power probing signal that causes a voltage ripple on the feeder, but it allows the DER to track the optimal reactive power setpoint well. The PSO method is the most complicated to implement, but issues optimal set points to each DER every minute. A comparison of each of the voltage regulation methods is shown in Figure 20. The simulation results indicate ESC and PSO can regulate the voltage closer to nominal, compared to VV.
To better understand the differences in these approaches, an analytical score was developed to summarize the effectiveness of each voltage regulation method, and a best score was calculated where the voltage regulation approach drove the solution to 1 pu:
s c o r e = 1 T t = 0 t e n d 1 N b = 1 N ( | v b l ( t ) v n o m | | v r e g ( t ) v n o m | ) d t
b e s t   s c o r e = 1 T t = 0 t e n d 1 N b = 1 N ( | v b l ( t ) v n o m | ) d t  
where vbl is the baseline voltage, vnom is the nominal voltage (1 pu), vreg is the voltage from the voltage regulation method, T is the time period of the simulation, b is the bus, and t is the simulation time. The scores representing the average voltage improvement for all buses averaged over a four-hour simulation period in units of pu. Table 3 summarizes the effectiveness for the PNM model of each approach per phase as well as the average of each phase, calculated with:
I m p a c t = s c o r e b e s t   s c o r e
VV slightly improved the average bus voltage, with an impact percentage of 12.3%. Implementing ESC and PSO demonstrated a larger impact on the feeder, with an average impact percentage of 74.5% and 73.7% respectively. A more detailed look at the impact of this regulation approaches per phase, shows that, since the system is relatively balanced, each phase is affected equally.
A comparison of the bus voltages for the NG model is illustrated in Figure 21 for each of the control methods. VV, ESC, and PSO all collapse the voltage envelope toward nominal voltage. In this case, ESC slightly outperforms the other two methods, shown in Figure 21. Table 4 summarizes the effectiveness for the NG model of each method. Interestingly, all the methods caused phase A (that was close to nominal to start) to deviate from the nominal voltage. The phases of the distribution system are coupled; in order to reach the global minimum for the system, and substantially improve the voltages on phases B and C, there is an adverse impact on phase A. This results in phase A deviating further from the nominal voltage.

8. Conclusions

The novel RT and PHIL platform and scoring criterion introduced in this paper allow for the development of a standardized methodology to tune, evaluate, and compare different inverter-based distribution voltage regulation approaches on different feeder models. Utilities and distribution system operators generally do not have the sensor infrastructure or DERMS communication network to execute centralized control of DER. However, as the number of measurement devices and interoperable DER increases, it will become possible to calculate power system states and calculate optimal DER setpoints to provide voltage regulation and provide protection assurance on the system. These capabilities were demonstrated in this project with both SIL and PHIL simulations.
This project investigated and compared three voltage regulation approaches: volt–VAR, extremum seeking control, and particle swarm optimization. Each of the approaches were shown to help provide voltage support on a feeder with symmetrically elevated phase voltages. In the case of the imbalanced NG feeder voltages, the approaches were ineffective when employed with only the three-phase inverter, but an aggregate of single-phase devices were shown to improve the NG feeder voltage profiles. This was demonstrated using RT simulations with simulated PV devices and power hardware-in-the-loop simulations with a 3-kW PV inverter. The extremum seeking control voltage regulation technique was shown to be effective at controlling groups of DER devices to improve feeder voltages, even in cases of phase imbalance. This is the first reported demonstration of this ESC application. The particle swarm optimization approach worked well when the OpenDSS feeder matched the RT/PHIL simulation environment. The technique incorporated live telemetry and PV forecast data to generate the optimal PF setpoints for a collection of PV systems over a fixed time horizon.

9. Patents

A U.S. Provisional Patent titled “Digital Twin Advanced Distribution Management System (ADMS) and Methods” was filed on 9 March 2020 based on this work.

Supplementary Materials

The following are available online at https://www.mdpi.com/1996-1073/13/14/3562/s1, The anonymized, reduced-order OpenDSS and Opal-RT feeder models, and all portions of the non-proprietary ProDROMOS and ESC codebases are included in the project GitHub repository: https://github.com/sunspec/prodromos.

Author Contributions

Conceptualization, J.J.; methodology, J.J.; software, J.J., C.H., J.A. and C.S.; model preparation, R.D.-Z., A.S. and C.H; validation, A.S., R.D.-Z, J.J., and C.H.; formal analysis, J.J., A.S., and R.D.-Z.; resources, J.J. and C.S.; data curation, A.S. and R.D.-Z.; writing—original draft preparation, A.S.; writing—review and editing, J.J. and C.H.; visualization, C.H. and C.S; supervision, J.J.; project administration, J.J.; funding acquisition, J.J. All authors have read and agreed to the published version of the manuscript.

Funding

This work was sponsored by the US Department of Energy Solar Energy Technologies Office, grant DE-EE0001495-1593, under the “Voltage Regulation and Protection Assurance using DER Advanced Grid Functions” project in the Enabling Extreme Real-time Grid Integration of Solar Energy (ENERGISE) program. The DER ESC implementation was initially developed in the “Community Control of Distributed Resources for Wide Area Reserve Provision” project supported by the U.S. Department of Energy Grid Modernization Laboratory Consortium (GMLC), grant number GM0187.

Acknowledgments

The authors would like to thank the ENERGISE team that completed this work, including National Grid, Georgia Institute of Technology, Connected Energy, SunSpec Alliance, SunPower Corporation, and Electric Power Research Institute. The team would also like to thank Trimark for working with the team to establish specific DNP3 points to control and measure the NG PV system. Special thanks to Matthew Reno who validated a proof-of-concept PSO using a simulated feeder in OpenDSS. Sandia National Laboratories is a multi-mission laboratory managed and operated by National Technology and Engineering Solutions of Sandia, LLC., a wholly owned subsidiary of Honeywell International, Inc., for the U.S. Department of Energy’s National Nuclear Security Administration under contract DE-NA-0003525. SAND2020-5161 J.

Conflicts of Interest

This paper describes objective technical results and analysis. Any subjective views or opinions that might be expressed in the paper do not necessarily represent the views of the U.S. Department of Energy or the United States Government. The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript, or in the decision to publish the results.

Acronyms and Definitions

AbbreviationDefinition
ACAlternating Current
ANSIAmerican National Standards Institute
DbusData Bus
DERDistributed Energy Resource(s)
DERMSDistributed Energy Resource Management System
DETLDistributed Energy Technology Laboratory
DNP3Distributed Network Protocol 3
DSODistribution System Operator
EPRIElectric Power Research Institute
ESCExtremum Seeking Control
GHIGlobal Horizontal Irradiance
IEDIntelligent Electronic Device
IEEEInstitute of Electrical and Electronics Engineers
ITMIdeal Transformer Method
LTCLoad Tap Changer
MAMaine
NGNational Grid
NMNew Mexico
NRELNational Renewable Energy Laboratories
O&MOperations and Maintenance
OLTCOn-Load Tap Changer
OPFOptimal Power Flow
PCCPoint of Common Coupling
PFPower Factor
PHILPower Hardware-in-the-Loop
PNMPublic Service Company of New Mexico
PRoDROMOSProgrammable Distribution Resource Open Management
PSOParticle Swarm Optimization
PSO PFParticle Swarm Optimization Optimal Power Factor
puPer unit
PVPhotovoltaic
RTReal-Time
SANDIASandia National Laboratories
SILSoftware in-the Loop
VVVolt–VAR
WinIGSIntegrated Grounding System Analysis program for Windows

References

  1. International Renewable Energy Agency. Future of Solar Photovoltaic: Deployment, Investment, Technology, Grid Integration and Socio-Economic Aspects (A Global Energy Transformation: Paper); International Renewable Energy Agency: Abu Dhab, UAE, 2019. [Google Scholar]
  2. National Electrical Manufactures Association. American National Standard for Electric Power Systems and Equipment-Voltage Rating (60 Hz); National Electrical Manufactures Association: Rosslyn, VA, USA, 2016. [Google Scholar]
  3. Denholm, P.; Clark, K.; O’Connell, M. On the Path to SunShot: Emerging Issues and Challenges in Integrating High Levels of Solar into the Electrical Generation and Transmission System; EERE Publication and Product Library: Washington, DC, USA, 2016.
  4. Sadeghian, H.; Wang, Z. Photovoltaic generation in distribution networks: Optimal vs. random installation. In Proceedings of the 2018 IEEE Power Energy Society Innovative Smart Grid Technologies Conference (ISGT), Washington, DC, USA, 19–22 February 2018; pp. 1–5. [Google Scholar] [CrossRef] [Green Version]
  5. Coddington, M.; Kroposki, B.; Mather, B.; Ellis, A.; Hill, R.; Lynn, K.; Razon, A.; Key, T.; Nicole, K.; Smith, J. Updating technical screens for PV interconnection. In Proceedings of the 2012 IEEE Photovoltaic Specialists Conference, Austin, TX, USA, 3–8 June 2012. [Google Scholar]
  6. Reno, M.J.; Broderick, R.J. Technical evaluation of the 15% of peak load PV interconnection screen. In Proceedings of the 2015 IEEE 42nd Photovoltaic Specialist Conference (PVSC), New Orleans, LA, USA, 14–19 June 2015; pp. 1–6. [Google Scholar]
  7. Rylander, M.; Broderick, R.J.; Reno, M.J.; Munoz-Ramos, K.; Quiroz, J.E.; Smith, J.; Rogers, L.; Dugan, R.; Mather, B.; Gotseff, P.; et al. Alternatives to the 15% Rule; Sandia Technical Report SAND2015-10099; Sandia National Laboratories: Albuquerque, NM, USA, 2015.
  8. Seguin, R.; Woyak, J.; Costyk, D.; Hambrick, J.; Mather, B. High-Penetration PV Integration Handbook for Distribution Engineers Technical Report; NREL/TP-5D00-63114; National Renewable Energy Lab: Golden, CO, USA, 2016.
  9. IEEE. IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces; IEEE Std 1547-2018; IEEE: Piscataway, NJ, USA, 2018. [Google Scholar]
  10. Seuss, J.; Reno, M.J.; Broderick, R.J.; Grijalva, S. Improving distribution network PV hosting capacity via smart inverter reactive power support. In Proceedings of the 2015 IEEE Power Energy Society General Meeting, Denver, CO, USA, 26–30 July 2015; pp. 1–5. [Google Scholar] [CrossRef]
  11. Farivar, M.; Neal, R.; Clarke, C.; Low, S. Optimal inverter VAR control in distribution systems with high PV penetration. In Proceedings of the 2012 IEEE Power and Energy Society General Meeting, San Diego, CA, USA, 22–26 July 2012; pp. 1–7. [Google Scholar] [CrossRef] [Green Version]
  12. Ding, F.; Mather, B.; Gotseff, P. Technologies to increase PV hosting capacity in distribution feeders. In Proceedings of the 2016 IEEE Power and Energy Society General Meeting (PESGM), Boston, MA, USA, 17–21 July 2016; pp. 1–5. [Google Scholar]
  13. Rylander, M.; Reno, M.J.; Quiroz, J.E.; Ding, F.; Li, H.; Broderick, R.J. Methods to determine recommended feeder-wide inverter settings for improving distribution performance. In Proceedings of the 2016 IEEE 43rd Photovoltaic Specialists Conference (PVSC), Portland, OR, USA, 5–10 June 2016; pp. 1393–1398. [Google Scholar] [CrossRef]
  14. Haghi, H.V.; Pecenak, Z.; Kleissl, J.; Peppanen, J.; Rylander, M.; Renjit, A.; Coley, S. Feeder impact assessment of smart inverter settings to support high PV penetration in California. In Proceedings of the 2019 IEEE Power & Energy Society General Meeting (PESGM), Atlanta, GA, USA, 4–8 August 2019; pp. 1–5. [Google Scholar] [CrossRef]
  15. Reno, M.J.; Lave, M.; Quiroz, J.E.; Broderick, R. PV ramp rate smoothing using energy storage to mitigate increased voltage regulator tapping. In Proceedings of the IEEE Photovoltaic Specialists Conference (PVSC), Portland, OR, USA, 5–10 May 2016. [Google Scholar]
  16. Georgilakis, P.S.; Hatziargyriou, N.D. Optimal distributed generation placement in power distribution networks: Models, methods, and future research. IEEE Trans. Power Syst. 2013, 28, 3420–3428. [Google Scholar] [CrossRef]
  17. Reno, M.J.; Broderick, R.J. Optimal siting of PV on the distribution system with smart inverters. In Proceedings of the 2018 IEEE 7th World Conference on Photovoltaic Energy Conversion (WCPEC) (A Joint Conference of 45th IEEE PVSC, 28th PVSEC & 34th EU PVSEC), Waikoloa Village, HI, USA, 10–15 June 2018; pp. 1468–1470. [Google Scholar]
  18. Antoniadou-Plytaria, K.E.; Kouveliotis-Lysikatos, I.N.; Georgilakis, P.S.; Hatziargyriou, N.D. Distributed and decentralized voltage control of smart distribution networks: Models, methods, and future research. IEEE Trans. Smart Grid 2017, 8, 2999–3008. [Google Scholar] [CrossRef]
  19. Primadianto, A.; Lu, C. A review on distribution system state estimation. IEEE Trans. Power Syst. 2017, 32, 3875–3883. [Google Scholar] [CrossRef]
  20. Dehghanpour, K.; Wang, Z.; Wang, J.; Yuan, Y.; Bu, F. A survey on state estimation techniques and challenges in smart distribution systems. IEEE Trans. Smart Grid 2019, 10, 2312–2322. [Google Scholar] [CrossRef] [Green Version]
  21. Elkhatib, M.E.; El-Shatshat, R.; Salama, M.M.A. Novel coordinated voltage control for smart distribution networks with DG. IEEE Trans. Smart Grid 2011, 2, 598–605. [Google Scholar] [CrossRef]
  22. Salih, S.N.; Chen, P. On coordinated control of OLTC and reactive power compensation for voltage regulation in distribution systems with wind power. IEEE Trans. Power Syst. 2016, 31, 4026–4035. [Google Scholar] [CrossRef] [Green Version]
  23. Xie, Q.; Hara, R.; Kita, H.; Tanaka, E. Coordinated control of OLTC and multi-CEMSs for overvoltage prevention in power distribution system. IEEJ Trans. Electr. Electron. Eng. 2017, 12, 692–701. [Google Scholar] [CrossRef]
  24. Zhu, X.; Zhang, Y. Coordinative voltage control strategy with multiple resources for distribution systems of high PV penetration. In Proceedings of the 2018 IEEE 7th World Conference on Photovoltaic Energy Conversion (WCPEC) (A Joint Conference of 45th IEEE PVSC, 28th PVSEC & 34th EU PVSEC), Waikoloa Village, HI, USA, 10–15 June 2018; pp. 1497–1502. [Google Scholar]
  25. Tonkoski, R.; Lopes, L.A.C.; El-Fouly, T.H.M. Coordinated active power curtailment of grid connected PV inverters for overvoltage prevention. IEEE Trans. Sustain. Energy 2011, 2, 139–147. [Google Scholar] [CrossRef]
  26. Johnson, J.; Summers, A.; Darbali-Zamora, R.; Hansen, C.; Reno, M.; Castillo, A.; Gonzalez, S.; Hernandez-Alvidrez, J.; Gurule, N.; Xie, B.; et al. Optimal Distribution System Voltage Regulation using State Estimation and DER Grid-Support Functions; Sandia Technical Report, SAND2020-2331; Sandia National Laboratories: Albuquerque, NM, USA, 2020.
  27. Meliopoulos, A.P.S. Windows Based Integrated Grounding System Design Program. Training Guide. 2017. Available online: http://www.ap-concepts.com/_downloads/IGS_TrainingGuide.pdf (accessed on 18 January 2017).
  28. Quiroz, J.E.; Reno, M.J.; Lavrova, O.; Byrne, R.H. Communication requirements for hierarchical control of volt-VAr function for steady-state voltage. In Proceedings of the 2017 IEEE Power & Energy Society Innovative Smart Grid Technologies Conference (ISGT), Washington, DC, USA, 23–26 April 2017; pp. 1–5. [Google Scholar] [CrossRef]
  29. Reno, M.J.; Quiroz, J.E.; Lavrova, O.; Byrne, R.H. Evaluation of communication requirements for voltage regulation control with advanced inverters. In Proceedings of the 2016 North American Power Symposium (NAPS), Denver, CO, USA, 18–20 September 2016; pp. 1–6. [Google Scholar]
  30. Xie, B.; Meliopoulos, A.P.S.; Zhong, C.; Liu, Y.; Sun, L.; Xie, J. Distributed quasi-dynamic state estimation incorporating distributed energy resources. In Proceedings of the 2018 North American Power Symposium (NAPS), Fargo, ND, USA, 9–11 September 2018. [Google Scholar]
  31. Choi, S.; Kim, B.; Cokkinides, G.J.; Meliopoulos, A.P.S. Feasibility study: Autonomous state estimation in distribution systems. IEEE Trans. Power Syst. 2011, 26, 2109–2117. [Google Scholar] [CrossRef]
  32. Xie, B.; Meliopoulos, A.P.S.; Liu, Y.; Sun, L. Distributed quasi-dynamic state estimation with both GPS-synchronized and non-synchronized data. In Proceedings of the 2017 North American Power Symposium (NAPS), Morgantown, WV, USA, 17–19 September 2017; pp. 1–6. [Google Scholar]
  33. Johnson, J.; Summers, A.; Darbali-Zamora, R.; Hernandez-Alvidrez, J.; Quiroz, J.; Arnold, D.; Anandan, J. Distribution voltage regulation using extremum seeking control with power hardware-in-the-loop. IEEE J. Photovolt. 2018, 8, 1824–1832. [Google Scholar] [CrossRef]
  34. Johnson, J.; Gonzalez, S.; Arnold, D.B. Experimental distribution circuit voltage regulation using DER power factor, volt-var, and extremum seeking control methods. In Proceedings of the 2017 IEEE 44th Photovoltaic Specialist Conference (PVSC), Washington, DC, USA, 25–30 June 2017; pp. 3002–3007. [Google Scholar] [CrossRef]
  35. Arnold, D.B.; Sankur, M.D.; Negrete-Pincetic, M.; Callaway, D.S. Model-free optimal coordination of distributed energy resources for provisioning transmission-level services. IEEE Trans. Power Syst. 2018, 33, 817–828. [Google Scholar] [CrossRef]
  36. Arnold, D.B.; Negrete-Pincetic, M.; Sankur, M.D.; Auslander, D.M.; Callaway, D.S. Model-free optimal control of VAR resources in distribution systems: An extremum seeking approach. IEEE Trans. Power Syst. 2016, 31, 3583–3593. [Google Scholar] [CrossRef]
  37. Distributed Energy Resources Connection Modeling and Reliability Considerations. 2017. Available online: http://www.nerc.com/comm/Other/essntlrlbltysrvcstskfrcDL/Distributed_Energy_Resource_Report.pdf. (accessed on 5 March 2020).
  38. Bründlinger, R. Grid codes in Europe for low and medium voltage. In Proceedings of the 6th International Conference on Integration of Renewable and Distributed Energy Resources, Kyoto, Japan, 17–20 November 2014. [Google Scholar]
  39. Reno, M.J.; Coogan, K.; Broderick, R.; Grijalva, S. Reduction of distribution feeders for simplified PV impact studies. In Proceedings of the 2013 IEEE 39th Photovoltaic Specialists Conference (PVSC), Tampa, FL, USA, 16–21 June 2013; pp. 2337–2342. [Google Scholar] [CrossRef]
  40. Pecenak, Z.K.; Disfani, V.R.; Reno, M.J.; Kleissl, J. Multiphase distribution feeder reduction. IEEE Trans. Power Syst. 2018, 33, 1320–1328. [Google Scholar] [CrossRef]
  41. EPRI. Overview of EPRI’s DER Simulation Tool for Emulating Smart Solar Inverters and Energy Storage Systems on Communication Networks: An Overview of EPRI’s Distributed Energy Resource Simulator; EPRI Report 3002009851; EPRI: Palo Alto, CA, USA, 2018. [Google Scholar]
  42. PV Performance Modeling Collaborative. Wavelet Variability Model. Available online: https://pvpmc.sandia.gov/applications/wavelet-variability-model/ (accessed on 5 March 2020).
  43. Lave, M.; Kleissl, J.; Stein, J.S. A wavelet-based variability model (WVM) for solar PV power plants. IEEE Trans. Sustain. Energy 2013, 4, 501–509. [Google Scholar] [CrossRef] [Green Version]
  44. Lave, M.; Kleissl, J.; Arias-Castro, E. High-frequency irradiance fluctuations and geographic smoothing. Sol. Energy 2012, 86, 2190–2199. [Google Scholar] [CrossRef] [Green Version]
  45. Lave, M.; Kleissl, J. Cloud speed impact on solar variability scaling—Application to the wavelet variability model. Sol. Energy 2013, 91, 11–21. [Google Scholar] [CrossRef] [Green Version]
  46. Lohmann, G.M. Irradiance variability quantification and small-scale averaging in space and time: A short review. Atmosphere 2018, 9, 264. [Google Scholar] [CrossRef] [Green Version]
  47. Bosch, J.L.; Zheng, Y.; Kleissl, J. Deriving cloud velocity from an array of solar radiation measurements. Sol. Energy 2013, 87, 196–203. [Google Scholar] [CrossRef] [Green Version]
  48. Summers, A.; Hernandez-Alvidrez, J.; Darbali-Zamora, R.; Reno, M.J.; Johnson, J.; Gurule, N.S. Comparison of ideal transformer method and damping impedance method for PV power-hardware-in-the-loop experiments. In Proceedings of the 2019 IEEE 46th Photovoltaic Specialists Conference (PVSC), Chicago, IL, USA, 16–21 June 2019; pp. 2989–2996. [Google Scholar] [CrossRef]
  49. Hernandez-Alvidrez, J.; Summers, A.; Pragallapati, N.; Reno, M.J.; Ranade, S.; Johnson, J.; Brahma, S.; Quiroz, J. PV-inverter dynamic model validation and comparison under fault scenarios using a power hardware-in-the-loop testbed. In Proceedings of the 2018 IEEE 7th World Conference on Photovoltaic Energy Conversion (WCPEC) (A Joint Conference of 45th IEEE PVSC, 28th PVSEC & 34th EU PVSEC), Waikoloa Village, HI, USA, 10–15 June 2018; pp. 1412–1417. [Google Scholar]
  50. Holmgren, W.F.; Hansen, C.W.; Mikofski, M.A. pvlib python: A python package for modeling solar energy systems. J. Open Source Softw. 2018, 3, 884. [Google Scholar] [CrossRef] [Green Version]
Figure 1. Block diagram of extremum seeking control (ESC). Refer to [36] for description.
Figure 1. Block diagram of extremum seeking control (ESC). Refer to [36] for description.
Energies 13 03562 g001
Figure 2. The particle swarm optimization optimal power flow (PSO OPF) optimization method and information flows.
Figure 2. The particle swarm optimization optimal power flow (PSO OPF) optimization method and information flows.
Energies 13 03562 g002
Figure 3. One Line Diagram of PNM Feeder.
Figure 3. One Line Diagram of PNM Feeder.
Energies 13 03562 g003
Figure 4. One-line diagram of National Grid (NG) feeder.
Figure 4. One-line diagram of National Grid (NG) feeder.
Energies 13 03562 g004
Figure 5. PV irradiance profiles for the Public Service Company of New Mexico (PNM) model.
Figure 5. PV irradiance profiles for the Public Service Company of New Mexico (PNM) model.
Energies 13 03562 g005
Figure 6. PV power levels for 4- hour simulation.
Figure 6. PV power levels for 4- hour simulation.
Energies 13 03562 g006
Figure 7. Bus voltages for baseline simulation.
Figure 7. Bus voltages for baseline simulation.
Energies 13 03562 g007
Figure 8. Volt–Var (VV) vs baseline feeder voltage comparison.
Figure 8. Volt–Var (VV) vs baseline feeder voltage comparison.
Energies 13 03562 g008
Figure 9. ESC results for the PNM model with parameter set 2 for a period of 4 hours.
Figure 9. ESC results for the PNM model with parameter set 2 for a period of 4 hours.
Energies 13 03562 g009
Figure 10. Irradiance and PV Energy Forecast Profiles. 1000 W/m2 produces 1pu of Active Power.
Figure 10. Irradiance and PV Energy Forecast Profiles. 1000 W/m2 produces 1pu of Active Power.
Energies 13 03562 g010
Figure 11. PSO results for the OpenDSS PNM model without Switching Capacitor Banks.
Figure 11. PSO results for the OpenDSS PNM model without Switching Capacitor Banks.
Energies 13 03562 g011
Figure 12. PSO PNM target reactive power levels for each distributed energy resources (DER). The target reactive power is calculated from the PSO power factor (PF) set point and the PV forecast at that time.
Figure 12. PSO PNM target reactive power levels for each distributed energy resources (DER). The target reactive power is calculated from the PSO power factor (PF) set point and the PV forecast at that time.
Energies 13 03562 g012
Figure 13. Voltage profiles for the NG simulations with each phase colored.
Figure 13. Voltage profiles for the NG simulations with each phase colored.
Energies 13 03562 g013
Figure 14. Minimum, maximum, and average bus voltages vs time for the VV test compared to the baseline data controlling all PV inverters.
Figure 14. Minimum, maximum, and average bus voltages vs time for the VV test compared to the baseline data controlling all PV inverters.
Energies 13 03562 g014
Figure 15. Imbalanced phase voltages; DER device during ESC simulation using parameter set 1.
Figure 15. Imbalanced phase voltages; DER device during ESC simulation using parameter set 1.
Energies 13 03562 g015
Figure 16. Minimum, maximum, and average bus voltages vs time for the ESC test, compared to baseline results controlling all PV inverters.
Figure 16. Minimum, maximum, and average bus voltages vs time for the ESC test, compared to baseline results controlling all PV inverters.
Energies 13 03562 g016
Figure 17. Minimum, maximum, and average bus voltages vs time for the PSO test compared to the baseline results controlling all PV inverters.
Figure 17. Minimum, maximum, and average bus voltages vs time for the PSO test compared to the baseline results controlling all PV inverters.
Energies 13 03562 g017
Figure 18. Comparison between simulated and power hardware-in-the-loop (PHIL) baseline minimum, maximum, and average bus voltages for the PNM model.
Figure 18. Comparison between simulated and power hardware-in-the-loop (PHIL) baseline minimum, maximum, and average bus voltages for the PNM model.
Energies 13 03562 g018
Figure 19. Comparison between simulated and PHIL baseline minimum, maximum, and average bus voltages for the PNM model.
Figure 19. Comparison between simulated and PHIL baseline minimum, maximum, and average bus voltages for the PNM model.
Energies 13 03562 g019
Figure 20. Comparison of voltage regulation approaches for the PNM feeder.
Figure 20. Comparison of voltage regulation approaches for the PNM feeder.
Energies 13 03562 g020
Figure 21. Comparison of minimum, maximum and average voltage regulation approaches for the NG feeder controlling all PV inverters.
Figure 21. Comparison of minimum, maximum and average voltage regulation approaches for the NG feeder controlling all PV inverters.
Energies 13 03562 g021
Table 1. ESC Parameters.
Table 1. ESC Parameters.
J FunctionlhrcommInverter 1 (258 kW)Inverter 2 (10 MW)Inverter 3 (1 MW)
PfakPfakPfak
1 n i = 1 n ( V i V n V n ) 2 5 800 5 800 2 s258 kW 2 40 51.6 kVar−2.58 × 10710 MW 3 40 50 kVar−1 × 1091 MW 5 40 50 kVar−1 × 108
Table 2. ESC parameters for all inverters in the NG feeder model.
Table 2. ESC parameters for all inverters in the NG feeder model.
J functionlhrcommThree-Phase InverterInverters on Phase AInverters on Phase BInverters on Phase C
fakfakfakfak
2 n i = 1 n ( V i ¯ V n V n ) 2 5 800 5 800 2 s 1 40 S 15 S 100 2 40 S 10 S 100 3 40 S 10 S 100 5 40 S 10 S 100
Table 3. PNM voltage regulation scores.
Table 3. PNM voltage regulation scores.
PNM Feeder Score
Phase A (×1000)Phase B (×1000)Phase C (×1000)Average (×1000)Average Impact (%)
VV0.4670.4680.4661.40112.9%
ESC2.7452.7482.5918.08474.5%
PSO2.7272.7312.5417.99973.7%
Best Score3.6503.6813.51910.850
Table 4. NG feeder score results controlling all PV inverters.
Table 4. NG feeder score results controlling all PV inverters.
NG Feeder Score Controlling All PV
Phase A (×1000)Phase B (×1000)Phase C (×1000)Average (×1000)Average Impact (%)
VV−0.0581.8551.2813.07815.2%
ESC−0.3454.9713.0687.69438.0%
PSO−0.3451.8782.0793.61217.8%
Best Score2.9379.6247.67820.238

Share and Cite

MDPI and ACS Style

Summers, A.; Johnson, J.; Darbali-Zamora, R.; Hansen, C.; Anandan, J.; Showalter, C. A Comparison of DER Voltage Regulation Technologies Using Real-Time Simulations. Energies 2020, 13, 3562. https://doi.org/10.3390/en13143562

AMA Style

Summers A, Johnson J, Darbali-Zamora R, Hansen C, Anandan J, Showalter C. A Comparison of DER Voltage Regulation Technologies Using Real-Time Simulations. Energies. 2020; 13(14):3562. https://doi.org/10.3390/en13143562

Chicago/Turabian Style

Summers, Adam, Jay Johnson, Rachid Darbali-Zamora, Clifford Hansen, Jithendar Anandan, and Chad Showalter. 2020. "A Comparison of DER Voltage Regulation Technologies Using Real-Time Simulations" Energies 13, no. 14: 3562. https://doi.org/10.3390/en13143562

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop