3.1. Effect of Smoke-Layer Height on Fire Spread Along a Single Cable Tray at a Burner HRR of 10 kW
In this section, the effects of smoke-layer height established by the side-wall configurations on fire spread along a single cable tray are examined with the ignition source conditions kept constant. The burner HRR was fixed at 10 kW, and the side-wall configurations were set to SW0%, SW25%, and SW50%. Fixing the burner HRR ensured that the plume generated by the ignition source provided comparable thermal and buoyancy forcing across tests, so that differences in fire spread could be attributed primarily to changes in the compartment smoke-layer environment. As defined in
Figure 3a, changing the side-wall configuration alters the opening height (h) for smoke discharge. As h decreases, smoke discharge from the upper region is increasingly restricted, and smoke-layer formation is promoted. However, h does not necessarily coincide with the height of the lower smoke-layer interface, because the interface is not spatially uniform due to internal flow and mixing and can fluctuate over time. Accordingly, h is used as a nominal proxy for smoke-layer height under each side-wall configuration and is referred to hereafter as the smoke-layer height. The key factor governing fire spread is the relative position of the smoke layer with respect to the tray elevation, i.e., whether the tray is located within the smoke layer or near its lower boundary. For reference, the tray elevation was set to z = 0.80 m (
Figure 2). Under SW25% (h = 0.79 m), the tray is nominally within, or very close to, the smoke layer. This proximity can simultaneously modify the gas temperature, incident heat flux at tray height, and local oxygen concentration near the tray, thereby influencing cable pyrolysis and fire spread.
Figure 4 compares the fire spread state along the tray immediately before self-extinction with the cable damage area observed after complete extinction for the side-wall configurations SW0%, SW25%, and SW50%. Under all configurations, the flame front did not reach the right end of the tray. This indicates that, within the present test range, fire spread was constrained by the compartment thermal and ventilation conditions and ultimately terminated by self-extinction. However, the spread distance and the damaged area differed across configurations. Under SW0%, fire spread remained limited, and the damaged area was relatively small. Under SW25%, the longest spread distance and the largest damaged area were obtained. By contrast, the spread distance under SW50% was comparable to that under SW0%. These results indicate that fire spread may not increase monotonically with decreasing h (i.e., as the side-wall vertical length increases). As h decreases, the tray becomes more exposed to the smoke layer, and the local heat transfer environment around the tray can be modified. Thermal feedback by radiative and convective heat transfer can increase, which can promote cable pyrolysis and fire spread. However, when the smoke layer becomes overly developed, vitiation in the upper region can intensify and oxygen availability near the tray can be reduced. Under such conditions, sustained flaming can be inhibited even when thermal feedback is present, and fire spread can instead be suppressed. In the following sections, these differences in spread behavior are quantified using HRR, incident heat flux and gas temperature at tray height, and gas composition in the upper and lower layers.
Figure 5 compares HRR histories measured based on the oxygen consumption principle for SW0%, SW25%, and SW50%.
Figure 5a shows the time evolution of HRR generated by cable burning. The burner HRR of 10 kW is also indicated as a reference line to represent the nominal ignition source condition. The fuel supply was shut off when the cable tray fire reached self-extinction. In
Figure 5a, the time axis is aligned with the cable ignition time identified through the viewing window. The period before ignition is denoted as the heating period before cable ignition. This alignment allows the growth, decay, and termination by self-extinction to be compared across configurations. The fire duration is defined as the interval from cable ignition to self-extinction, and it was 1043 s, 1717 s, and 1479 s for SW0%, SW25%, and SW50%, respectively.
Figure 5b presents the peak HRR and the total heat release (THR). The peak HRR shows limited variation among configurations, whereas THR varies with the fire duration and the overall spread behavior. Notably, although
Figure 4 indicates limited visible flame spread in the SW50% configuration, the higher THR implies that a larger fraction of the cable mass participated in burning, suggesting more extensive involvement of the cable cross-section (through-thickness) in the combustion process.
Figure 5c presents the fire growth rate (FGR), estimated using the t
2 law based on the cable ignition time and the time to reach the peak HRR, and the detailed procedure is described in Ref. [
15]. In addition, the mean fire spread rate is defined as the maximum fire spread distance divided by the time required for the flame front to reach that location from cable ignition and is denoted hereafter as FSR. The FGR was highest under SW25%, indicating a more rapid initial rise in HRR. This suggests that early burning can be enhanced when increased thermal influence near the tray and local oxygen availability act together. Although the maximum fire spread distance was greatest under SW25%, the highest FSR was obtained under SW0%, with lower values under SW25% and SW50%. This trend is likely attributed to the spread history under SW0%, where the flame advanced rapidly over the initial portion of the tray, approximately one third of the tray length, and then terminated by self-extinction. As a result, the time to reach the maximum spread position was short, which increases the distance over time metric. This initial portion can be regarded as a region in which the cable was forcibly ignited by the direct influence of the burner flame. Therefore, the FSR under SW0% may not be fully representative of cable-driven fire spread independent of the ignition source. Under SW25%, both the spread distance and the fire duration were larger, so the mean FSR can appear relatively lower when expressed as a distance-over-time metric. Under SW50%, h was further reduced and the smoke layer became more developed, while the spread distance remained limited and the spread process became more gradual, resulting in the longest time and the lowest FSR. FSR should therefore be interpreted as a mean rate and discussed together with the maximum fire spread distance and fire duration, while accounting for the region directly affected by the ignition source.
To quantify the thermal environment around the tray for different h values,
Figure 6 presents the incident heat flux measured by plate thermometers (PTs) installed at the tray elevation and the gas temperature measured by thermocouples at the L1 level. Because the PT receiving surfaces faced the ceiling, the measured heat flux primarily represents radiative input from the upper smoke layer and the flame to the tray elevation. Depending on the test environment, a convective contribution can also be included and the measurement can be interpreted as an incident total heat flux. The heat flux and temperature shown in
Figure 6 are time-averaged over the burning period from cable ignition to self-extinction. In
Figure 6a, SW0% exhibits relatively low mean heat flux because smoke was discharged more readily before a sufficiently developed smoke layer was established, which limited thermal feedback at the tray height. In contrast, SW25% and SW50% show similar trends in the mean heat flux distributions with respect to PT location. At some locations, SW50% exhibits slightly higher values, but the difference between SW25% and SW50% remains limited. A similar trend is observed in
Figure 6b for the mean gas temperature. The L1 thermocouples were installed approximately 0.05 m below the ceiling, and the region expected to be directly affected by the burner flame (x ≤ 0.3 m) is denoted as the burner flame region. For all configurations, the mean gas temperature decreased as x increased along the tray, and the lowest mean temperature at L1 was obtained under SW0%, consistent with a weakly developed smoke layer. SW25% and SW50% exhibit quantitatively similar overall temperature distributions. Under SW25%, locally higher mean temperatures were observed at some locations, which is consistent with the longer fire spread distance and the resulting influence of burning farther along the tray.
These results show that, although faster and longer fire spread was observed under SW25% than under SW50%, the incident heat flux and gas temperature evaluated at tray height were overall similar between the two configurations. This suggests that, within the present test range, the observed differences in spread behavior cannot be explained solely by thermal factors. Instead, changes in oxygen concentration near the tray associated with decreasing h may have provided an additional controlling influence. Accordingly, the spread behavior observed in this section is interpreted as resulting from the combined effects of thermal feedback and local ventilation conditions near the tray. To examine this possibility, the oxygen concentration near the tray is evaluated below.
Figure 7 compares the time histories of gas composition, reported as the volume fractions of O
2, CO, and CO
2, measured above and below the tray for the side-wall configurations SW0%, SW25%, and SW50% at a burner HRR of 10 kW. In the upper layer measurements (
Figure 7a), the SW0% configuration shows O
2, CO, and CO
2 levels close to ambient. This is attributed to the upper sampling probe being located in a region weakly influenced by the smoke layer. In contrast, under SW25% and SW50%, clear vitiation trends were observed in the upper layer, with decreased O
2 and increased CO and CO
2 associated with smoke-layer formation. Under SW50%, O
2 was lower and CO and CO
2 were higher than under SW25%, indicating that the upper region remained more vitiated. The increase in CO is consistent with a greater tendency toward incomplete combustion under reduced oxygen availability. The increase in CO
2 can reflect sustained product formation together with changes in dilution and discharge, which can alter the measured volume fraction. The lower-layer measurements (
Figure 7b) were more strongly influenced by air inflow, mixing, and entrainment than the upper layer. When the lower smoke-layer interface approached the tray elevation, the lower sampling probe could be affected by a transition region near the interface rather than sampling a uniform lower layer. For example, under SW25% (h = 0.79 m), the lower probe located at z = 0.80 m was positioned very close to the nominal interface. In this case, the measured composition can be influenced by mixing between smoke-layer gases and incoming air, leading to more gradual changes in O
2, CO, and CO
2 and larger temporal fluctuations than those observed in the upper layer. Although the thermal environment at tray height was evaluated as broadly similar for SW25% and SW50% in
Figure 6, clear differences in fire spread, HRR behavior, and FSR were observed in
Figure 4 and
Figure 5. Collectively, the gas composition results indicate that oxygen availability near the tray differed across side-wall configurations. The lower O
2 level maintained under SW50% suggests that oxygen supply to the vicinity of the tray was more restricted, supporting the interpretation that local oxygen availability contributed to the observed differences in fire spread behavior.
In summary, with the burner HRR fixed at 10 kW, fire spread along the cable tray differed markedly with the smoke-layer environment established by the side-wall configuration. Under SW25%, h was close to the tray elevation, indicating that the smoke layer extended to near the tray level. Under this condition, thermal feedback could be enhanced while oxygen availability sufficient to sustain burning appeared to be relatively maintained, resulting in the longest fire spread. Under SW50%, although the mean incident heat flux and gas temperature at tray height were broadly similar to those under SW25%, oxygen availability near the tray was reduced and fire spread was suppressed. These findings indicate that smoke-layer formation can promote fire spread by increasing thermal feedback, whereas an overly developed smoke layer can impose local oxygen depletion that limits sustained flaming and prevents the thermal promotion effect from translating into increased fire spread. The side walls can also affect local radiative feedback, but their limited area fraction relative to the total compartment surfaces suggests that the differences observed in the present tests were governed primarily by coupled changes in the thermal environment and oxygen availability near the tray associated with variation in h.
3.2. Combined Effects of Smoke-Layer Temperature and Oxygen Concentration on Fire Spread Along a Single Cable Tray Under Different Burner HRR Conditions
In the previous section, the effect of smoke-layer conditions induced by the side-wall configuration on fire spread was examined with the burner HRR fixed at 10 kW. In this section, as shown in
Figure 3b, the burner HRR and burner elevation were varied so that the flame tip was positioned at the underside of the tray. This approach was used to compare fire spread under conditions where the smoke-layer temperature increased while oxygen availability near the tray changed concurrently.
Figure 8 presents photographs for SW25% and SW50% at burner HRRs of 14 and 18 kW. The photographs show the fire spread state at the time of peak HRR, when the flame front reached x = 0.65 m (approximately two thirds of the tray length), and when it reached the tray end at x = 1.0 m. The elapsed time from cable ignition is provided in each image to facilitate a qualitative comparison of the temporal evolution of fire spread under different burner HRR and side-wall configurations. The SW0% configuration is excluded from the discussion because cable-driven fire spread remained limited after cable ignition even when the burner HRR was increased to 14 and 18 kW.
Interpreting
Figure 8 based on the elapsed times annotated in each image, the effect of changing the side-wall configuration (SW25% to SW50%) is evident at a given burner HRR. Under SW50%, h is reduced relative to SW25%, which promotes smoke accumulation in the upper region and results in a more developed smoke layer. Under such conditions, the supply of incoming air to the vicinity of the tray is more likely to be restricted, which is reflected in longer times to reach peak HRR and for the flame front to reach x = 0.65 m and x = 1.0 m. For a fixed side-wall configuration, increasing the burner HRR from 14 to 18 kW does not change h and thus is not expected to substantially alter the inflow condition. Because h is unchanged, the thermal effect of the higher burner HRR can become more prominent, strengthening the thermal environment near the tray, including the smoke-layer temperature, and thereby promoting cable pyrolysis and faster fire spread. This trend is observed under SW25%, where the time for the flame front to reach the tray end (x = 1.0 m) is shorter at 18 kW than at 14 kW. In addition, the SW50% images at 14 and 18 kW show a bluish green flame that was not observed under SW25%. This coloration may be related to the formation of copper halide-emitting species at elevated temperatures, arising from interactions between chlorine-containing products generated during PVC pyrolysis and copper from the cable conductor [
23,
24]. In the present study, this behavior is reported as an observation, and further investigation is required to determine the cause conclusively.
Figure 9 compares HRR time histories aligned to cable ignition for SW25% and SW50% at burner HRRs of 14 and 18 kW, showing the corresponding growth and decay behavior. The period before ignition can be interpreted as a preheating period in which the cable is heated by the external source until ignition occurs. After ignition, HRR increases, reaches a peak, and then decreases toward self-extinction. At 14 kW, both SW25% and SW50% exhibit a delayed rise in HRR, indicating the onset of sustained cable burning. The peak HRR level was similar for the two configurations, whereas the time to reach the peak was shorter under SW25%. This is consistent with the higher h under SW25%, which can allow relatively better oxygen supply near the tray and a more rapid strengthening of early burning. Under SW50%, a more developed smoke layer and stronger vitiation can reduce initial oxygen availability and delay the HRR rise.
In addition, the limited difference in peak HRR between SW25% and SW50% suggests that, at the present burner HRR levels (14–18 kW), fire spread along the tray progressed sufficiently after cable ignition. Once burning develops beyond an initial stage, the overall HRR behavior can be governed primarily by the thermal conditions established by the ignition source, including the smoke-layer temperature and the associated thermal feedback. Differences in oxygen availability induced by the side-wall configuration can still influence the temporal development, such as the rise rate and the time to reach the peak. However, when the thermal forcing is sufficiently strong, the peak HRR during the developed burning phase can approach a similar level across configurations. A similar trend was observed at 18 kW. Accordingly, the effect of a more developed smoke layer associated with reduced h is reflected more clearly in the growth process and timing than in the peak HRR magnitude. In the early growth stage, oxygen availability near the tray can act as a key limiting factor, which is consistent with the FGR comparison presented below.
Figure 10 compares the fire growth rate (FGR) and fire spread rate (FSR) for SW25% and SW50% at burner HRRs of 10, 14, and 18 kW. In
Figure 10a, the FGR under SW25% was higher than under SW50% for all burner HRR conditions, which is consistent with the trend observed in
Section 3.1. Under SW25%, a higher h can allow relatively better oxygen supply near the tray, leading to an earlier and steeper rise in HRR after cable ignition and, consequently, a higher FGR. Under SW50%, reduced h promotes a more developed smoke layer and stronger vitiation, which can lower initial oxygen availability near the tray. The HRR rise can then be delayed or more gradual, yielding a lower FGR. This interpretation is in line with the longer time to reach peak HRR observed in
Figure 9.
Figure 10b compares FSR along the tray after cable ignition. At burner HRRs of 14 and 18 kW, the flame front reached the tray end (x = 1.0 m), so the maximum fire spread distance was the same for SW25% and SW50%. Accordingly, differences in FSR were governed primarily by the time required for the flame front to reach x = 1.0 m. At 14 and 18 kW, the FGR under SW50% was lower than under SW25%, whereas the FSR under SW50% was comparable to, or slightly higher than, that under SW25%. This suggests that oxygen availability alone does not fully explain FSR during the spread phase and that changes in the fire spread mode may also contribute. Under SW50%, the flame was less stably attached to the cable surface and intermittently exhibited a partially lifted structure. In this mode, sustained surface burning can be locally weakened, while the flame front can advance relatively rapidly along regions where pyrolysis has been promoted. This behavior is consistent with the flame photographs in
Figure 8. Accordingly, interpretation of FSR under elevated burner HRR conditions should consider the combined effects of enhanced thermal feedback associated with higher smoke-layer temperatures, oxygen availability near the tray, and changes in flame attachment stability.
Figure 11 compares the mean incident heat flux measured by the plate thermometers (PTs) for SW25% and SW50% at burner HRRs of 14 and 18 kW. Because the PT receiving surfaces faced the ceiling, the measured heat flux is dominated by radiative input from the upper smoke layer and the flame to the tray height. At a given burner HRR, the mean incident heat flux was generally higher under SW50% than under SW25%. This trend is consistent with reduced h promoting stronger accumulation of hot gases and smoke in the upper region, which can increase thermal feedback to the tray height. Increasing the burner HRR from 14 to 18 kW increased the mean heat flux for both configurations, indicating that greater energy input elevated the smoke-layer temperature level and enhanced the radiative environment. The relatively higher heat flux under SW50% supports the interpretation that thermal feedback can contribute to the spread stage under elevated burner HRR conditions, which is consistent with the FSR trend observed in
Figure 10b.
Figure 12 presents mean gas temperature distributions within the smoke layer measured using thermocouple trees. Each value was time-averaged over the burning period after cable ignition. The x-axis denotes thermocouple locations along the tray (0.1–0.9 m). In
Figure 12a, the L1 results show that, within a given side-wall configuration, the mean temperature distributions at 14 and 18 kW were not well separated. In contrast, the overall temperature level differed more clearly between SW25% and SW50%. This suggests that, within the present range, the mean temperature level near the ceiling can be more directly affected by changes in h, through changes in smoke-layer development and in the accumulation, dilution, and discharge characteristics of hot gases and smoke, than by the increase in burner HRR. However, this observation does not imply that the burner HRR has a minor role. Once a sufficiently developed smoke layer is established, the upper-layer mean temperature can show limited variation, and time averaging can further reduce apparent differences between conditions. Moreover, increasing the burner HRR can be critical in determining whether fire spread can be sustained and whether the flame front can reach the tray end. This is supported by the contrast with
Section 3.1, where the flame front did not reach the tray end at 10 kW under any configuration, whereas it reached x = 1.0 m at 14–18 kW.
In
Figure 12b, the L4 results show a more distinct separation between side-wall configurations. Although the direct influence of the burner plume can vary with x location, higher mean temperatures were consistently maintained under SW50% than under SW25%. This trend suggests that reduced h promoted a more developed smoke layer and allowed the influence of accumulated hot gases to extend farther downward toward the tray region. The effect of increasing burner HRR can also be expressed more clearly near the tray, such as at L4, than near the ceiling, which is consistent with the mean incident heat flux distributions in
Figure 11. The L1 results therefore suggest that the upper-region temperature level is more sensitive to side-wall configuration, whereas the L4 results indicate that increasing burner HRR elevates temperatures near the tray and strengthens the thermal conditions relevant to continued fire spread.
Figure 13 compares the time histories of O
2 volume fraction measured above and below the tray for the side-wall configurations SW25% and SW50% at burner HRRs of 14 and 18 kW. For both HRR conditions, higher O
2 levels were maintained under SW25% than under SW50% in both the upper and lower layers, and the upper–lower difference remained relatively small. Under SW50%, the lower layer exhibited consistently lower O
2 than the upper layer, indicating more pronounced layer separation. This behavior persisted at 18 kW. These results indicate that reducing h can decrease the overall O
2 level while also increasing the nonuniformity of local oxygen availability above and below the tray. The observed layer dependence can be attributed to changes in ventilation and internal mixing. Under SW25%, the larger h can allow more effective air inflow and mixing, which can reduce the upper–lower difference in O
2. Under SW50%, a more developed smoke layer can modify the air supply paths and mixing patterns near the tray. In this case, oxygen in the lower layer can be consumed more rapidly because this region is closer to the burner and cable flames, and the influence of accumulation and recirculation of combustion products and pyrolysis gases can be strengthened. Local vitiation may therefore persist near the tray before sufficient exchange with the upper region occurs. This interpretation is consistent with the delayed HRR rise and the lower FGR observed under SW50% in
Figure 9 and
Figure 10a. Accordingly, spread behavior under elevated burner HRR conditions should be interpreted by considering the thermal environment together with local O
2 availability above and below the tray and the degree of interlayer mixing.
As observed under the 10 kW condition in
Section 3.1, smoke-layer formation can increase thermal feedback near the tray while simultaneously reducing local oxygen availability. Fire spread can therefore differ depending on the relative importance of these two effects. Under the present conditions, with the burner HRR increased to 14 and 18 kW and the burner elevation adjusted, the flame front reached the tray end, unlike at 10 kW. This suggests that the thermal environment near the tray became more favorable for sustained spread. Variations in the side-wall configuration modify h and thereby alter smoke-layer development and the O
2 distribution above and below the tray, such that the growth and spread stages can diverge in their relative prominence. Under SW25%, relatively high O
2 levels were maintained in both layers with a small upper–lower difference, and the HRR rise was strengthened earlier, resulting in a higher FGR. Under SW50%, the incident heat flux and temperatures near the tray were higher, indicating stronger thermal feedback during the spread stage. Accordingly, FSR was comparable to, or in some cases higher than, that under SW25%. At the same time, the lower-layer O
2 level remained below the upper-layer level, indicating enhanced local vitiation that may have contributed to delayed early growth and influenced the development toward sustained burning. These results show that, when fire spread to the tray end is possible, the relative prominence of growth (FGR) and spread (FSR) is governed by coupled changes in thermal feedback and local oxygen availability associated with the smoke-layer environment.