Both the experimental and simulaton results presented in the section “Analysis of Experimental and Simulation Results” show that the temperature uniformity within the environmental simulation test system is poor, which is due to insufficient air convection inside the environmental simulation system. To improve the temperature uniformity, more air convection should be involved. This study employs a fan to provide airflow to enhance convective heat transfer in the environmental simulation test system.
As shown in the section “Analysis of Experimental and Simulation Results”, the simulated temperature distribution with only natural convection shows great consistence with the experimental temperature distribution, implying the feasibility of the simulation method. In this section, the simulation method is still used to evaluate the temperature distribution after wind involved in the environment simulation test system.
4.1. Simulation of Temperature Field in NSESTS with Wind Involved
This paper investigates the following two configurations: (1) downwind configuration, where the fan is located in the front of the chamber and faces backward to the back of the chamber; and (2) upwind configuration, where the fan is located in the back of the chamber and faces forward to the gate of the chamber.
In the simulation, the system pressure is set to be 0.6 kPa, and the temperature at the center of the pressure vessel (location of temperature probe T07) is set to be −49 °C. The fan outlet is assigned a velocity inlet boundary condition, and the boundary condition for velocity magnitude is 5 m/s. The other parts of the fan are set as adiabatic fixed no-slip walls. This problem involves low-velocity flow in an enclosed space, so an incompressible steady pressure-based solver is used for computation. The simple algorithm, a pressure–velocity coupling method, is utilized to indirectly satisfy the mass conservation equation. This method solves the momentum equation and pressure correction equation iteratively, adjusting the velocity field gradually to meet the continuity condition, and is suitable for low-velocity flow scenarios. Convergence is deemed to be achieved when the velocity residual falls below 0.001.
Figure 8 illustrates the fan configuration for the near space downwind simulation and the physical arrangement of the fan when tested. The fan is modeled as a cylindrical body with a radius of 15 cm, whose central axis coincides with the central axis of the environmental simulation test system. It blows wind in the direction from the gate side to the rear side of the test system and is located 350 mm away from the gate of the test system.
Figure 9 displays the temperature distribution contour plots and spatial flow field plots on the centrally symmetric planes z = 0 and x = 0, respectively. The simulation results visually demonstrate the convective process and temperature distribution throughout the entire space. The white rectangle in
Figure 9a,c is the longitudinal section of the fan model. The heat sink reduces the ambient temperature through thermal radiation, while the heating cage raises it via radiant heating. Their interaction results in higher temperatures inside and near the heating cage and lower temperatures around the heat sink. The introduction of the wind field enhances convective heat transfer, generating multiple vortices within the test system and creating a more complex spatial flow field, leading to better spatial temperature uniformity.
Table 6 and
Figure 10 present a comparative analysis of simulation results before and after the involvement of the fan near the gate side of the environmental simulation test system. The simulation results confirm that after involving the wind, the non-uniformity coefficient reduces to 0.2012, reflecting a 27.1% decrease versus the simulation without fan (=0.2759). This demonstrates that after introducing wind near the gate of the environmental simulation test system, the temperature distribution exhibits significantly reduced dispersion and markedly improved uniformity compared with the simulation without additional wind.
In this paper, we also consider another configuration of fan placement and airflow direction: the near space upwind simulation, which is defined as having the fan located near the rear end of the test system, directing airflow toward the gate side.
The environmental condition configuration is the same with that of the near space upwind simulation.
Figure 11 illustrates the fan configuration for the near space upwind simulation and the physical arrangement of the fan when tested. The fan is also modeled as a cylindrical body with a radius of 15 cm, whose central axis coincides with the central axis of the environmental simulation test system. It blows wind with the direction from the rear side to the gate side of the test system and is located 350 mm from the rear side of the test system.
Figure 12 displays the temperature distribution contour plots and spatial flow field plots on the centrally symmetric planes z = 0 and x = 0, respectively. The simulation results visually demonstrate that the introduction of the wind field enhances convective heat transfer, generating multiple vortices within the test system and creating a more complex spatial flow field, leading to better spatial temperature uniformity, which brings the similiar improvement as with the near space downwind situation.
Table 7 and
Figure 13 present a comparative analysis of simulation results between the fan involved near the rear side of the environmental simulation test system and the TRX-2000(A) running without the fan. Numerical results confirm that after involving the upwind simulation, the non-uniformity coefficient reduces to 0.2055, reflecting a 25.5% decrease versus the simulation without fan (
). This demonstrates that after introducing wind near the rear section of the environmental simulation test system, the temperature distribution exhibits significantly reduced dispersion and markedly improved uniformity compared to the simulation without wind, which brings the similiar improvement as with the near space downwind situation.
From the near space downwind and upwind simulations, we can conclude that after introducing the wind, the non-uniformity coefficient of the temperature field within the environmental simulation system decreases significantly and the temperature uniformity markedly improves compared with the simulation without wind.
4.2. Experimental Validation of Temperature Field Simulation for Near Space Wind Field Environment
In
Section 4.1, the introduction of airflow into the near space temperature field simulation was implemented to improve the temperature distribution within the environmental simulation test system, resulting in a more uniform internal temperature distribution. Simultaneously, by accounting for the wind field conditions in near space, the near space wind field environment was considered to better replicate the actual near space conditions.
To experimentally validate the simulation results from
Section 4.1, this section incorporates airflow into the environmental simulation test system through the use of a fan.
In the near space downwind simulation, the fan was positioned on the central axis of the environmental simulation test system, a 350 mm distance from the gate side, blowing toward the rear section of the system. The fan is powered by an external power source.
Figure 8c shows the physical arrangement of the fan installed near the door.
The environmental simulation test system was set with the pressure target to be 0.6 kPa and the temperature target to be −49 °C at the central location (where temperature probe T07 is positioned). After the temperature and pressure reached their set value, the fan was activated. The airflow brought by the fan enhanced convection within the system. Temperature readings for all probes are recorded after the fan was running for 1.5 h, 2 h, and 2.5 h.
Table 8 presents the experimental temperature value recorded by each probe in the environmental simulation test system before fan activation and after the fan was running for 1.5 h, 2 h, and 2.5 h from the gate side.
Table 9 shows the non-uniformity coefficient of the environment simulation test system after the fan (located near the gate side) was running for 1.5 h, 2 h, and 2.5 h and the experimental values without the fan running. Non-uniformity coefficient decreases from 0.2094 when there is no fan to 0.1920 after the fan was running for 1.5 h, which is an 8.3% decrease for non-uniformity improvement. This indicates that after introducing the fan near the gate side, it shows a more concentrated temperature distribution and improved temperature uniformity within the system. Furthermore, the temperature uniformity across all probes stabilized after 1.5 h of fan operation. The observed trend aligns with the simulation results presented in
Section 4.1, reaffirming that applying the numerical simulation method to analyze the temperature field distribution characteristics in the environmental simulation test system described in this study is appropriate.
With respect to the near space upwind simulation, we also validated the results through experiment. We also incorporated airflow into the environmental simulation test system through the use of a fan.
The fan is positioned on the central axis of the environmental simulation test system, a 350 mm distance from the rear section, blowing toward the gate side of the system.
Figure 11c shows the physical arrangement of the fan installed near the rear section.
The environmental simulation test system was set with the pressure target to be 0.6 kPa and the temperature target to be −49 °C at the central location (where temperature probe T07 is positioned). After the temperature and pressure reached their setting values, the fan was activated. The airflow brought by the fan enhanced convection within the system. Temperature data for all probes are recorded after the fan was running for 1.5 h, 2 h, and 2.5 h.
Table 10 presents the experimental temperature values recorded by each probe in the environmental simulation test system before fan activation and after the fan was running for 1.5 h, 2 h, and 2.5 h at the gate side.
Table 11 shows the non-uniformity coefficient of the environment simulation test system after the fan (located near the gate side) was running for 1.5 h, 2 h, and 2.5 h and the experimental values without the fan running. Non-uniformity coefficient decreases from 0.2184 when there is no fan to 0.2153 after the fan was running for 1.5 h, which is a 1.4% decrease for non-uniformity improvement. This indicates that after introducing the fan near the gate side, it shows a more concentrated temperature distribution and improved temperature uniformity within the system. Furthermore, the temperature uniformity across all probes stabilized after 1.5 h of fan operation. The observed trend aligns with the simulation results presented in
Section 4.1, reaffirming that applying the numerical simulation method to analyze the temperature field distribution characteristics in the environmental simulation test system described in this study is appropriate.
Through the experiment validation for the near space downwind and upwind simulation, we can conclude that after introducing the fan, the non-uniformity coefficient of the temperature field within the environmental simulation system decreases and the temperature uniformity improves compared to the TRX-2000(A) NSESTS running without wind.