Article

Improvement of Temperature Control Performance of Thermoelectric Dehumidifier Used Industry 4.0 by the SF-PI Controller

1
Department of Electric Control Engineering, Sunchon National University, 255 Jungang-ro, Suncheon-city, Jeollanam do 57922, Korea
2
Department of Software, Catholic University of Pusan, Geumjeong-gu, 57 Oryundae-ro, Geumjeong-gu, Busan 46252, Korea
3
Department of Computer Engineering, Sunchon National University, 255 Jungang-ro, Suncheon-city, Jeollanam do 57922, Korea
*
Author to whom correspondence should be addressed.
Processes 2019, 7(2), 98; https://doi.org/10.3390/pr7020098
Submission received: 22 January 2019 / Revised: 8 February 2019 / Accepted: 11 February 2019 / Published: 15 February 2019

Abstract

:
This paper proposes the series connected fuzzy-proportional integral (SF-PI) controller, which is composed of the fuzzy control and the PI controller to improve temperature control performance of dehumidifier using a thermoelectric element. The control of conventional PI controller usually uses fixed gain. For that reason, it is limited in achieving satisfactory control performance in both transient-state and steady-state. The fuzzy control within SF-PI controller adjusts the input value of PI controller according to operating condition. The PI controller within the SF-PI controller controls the temperature of the thermoelectric element using that value. The SF-PI controller can achieve more accurate temperature control than a conventional PI controller for that reason. The SF-PI controller has been tested for various indoor environmental conditions such as temperature and relative humidity conditions. The average temperature error of the SF-PI controller between the reference temperature and the thermoelectric element temperature is 22% of traditional PI’s value and consumption power is reduced by about 10%. Therefore, the SF-PI controller proposed in this paper can improved the performance of temperature control of dehumidifier using thermoelectric element. The power consumed by buildings accounts for a significant portion of the total power consumption, of which the air conditioner represents the largest energy consumer. In this paper, it is possible to reduce the energy consumption by improving the performance of the dehumidifier, one of the air conditioners, and it can be applied to various control fields in the future.

Graphical Abstract

1. Introduction

Energy consumption is increasing globally and energy demand is expected to increase by 30% by 2040. A climate change agreement was signed in Paris in 2015 to cope with the rapidly changing climate [1,2]. The energy consumed by buildings is about 80%–85% in high temperature and high humidity regions, and 39% and 40% in Europe and the USA, respectively [3,4]. The CO2 emissions from these buildings account for 30%–40% of all industries [5]. In particular, the air conditioning system occupies 10% of the total energy and in Japan, the United States, and Korea, 91%, 90%, and 86% of residents have air conditioners [6]. Such an air conditioning system is used for heating, ventilating, and cooling the room air, and it represents a financial burden for consumers since it is continuously used even in the peak load time of the building. The load on these air conditioning systems accounts for about 25% of the building load according to the data released by the US Energy Information Administration in 2017 [2].
The dehumidifier system includes a system using a moisture absorbent and a cooling system using a compressor. Among them, the dehumidifier system using compressors is the most widely used dehumidifier system [7]. This method has a similar structure and principle to the air conditioner [8]. Therefore, the power consumption of the dehumidifier is almost the same as that of the air conditioner. The difference between a dehumidifier and an air conditioner is the configuration of the condenser and vaporizer. The dehumidifier is composed of one unit, but the air conditioner is installed separately. The major objective of the dehumidifier is to remove moisture from the air, so the air passing through the vaporizer is slower than the air conditioner. Advantages of the compressor dehumidifier are that they are excellent in dehumidification performance in a climate of 15 °C or higher and can be maintained only by increasing the room temperature by 1–2 °C without cooling indoor air like an air conditioner. However, when the temperature of the air for dehumidification is 15 °C or less, the temperature of the vaporizer is close to the freezing point, and ice is formed on the coil of the vaporizer, thereby deteriorating the dehumidification performance. It also consumes 67% of time and energy to defrost the coil. In addition, the compressor cooling method is generally very heavy (weight of 10 kg or more), large in terms of volume, and noisy (more than 40 decibels) [7]. Therefore, the energy saving of an air conditioning system is essential to reducing the greenhouse gas emissions generated by the power consumption in buildings.
The Fourth Industrial Revolution is characterized by technology convergence, and the Fourth Industrial Revolution includes technologies such as Big Data Analysis, Artificial Intelligence, Robotics, and the internet of thing (IoT). Among them, the IoT is a function that can transmit data by connecting everything through a network regardless of the kind of thing. The IoT system can be applied to various fields by constituting the sensor, the actuator, and the control units. IoT systems can take advantage of the embedded hardware platform, and their interest in the open source platform is increasing due to their low cost, computational power, programming flexibility, I/O interface, low energy consumption, and reduced size [9,10]. Among the open source platforms, the Raspberry Pi and the Arduino are the most favored and widely studied and applied platforms for Industry 4.0 applications [9,10,11,12,13,14]. Recently, as the importance of indoor environment increases, interest in systems that can automatically control or check the indoor air state is increasing. Therefore, Industry 4.0 is widely applied to home appliances. To control systems automatically, it has to use a control method [15,16].
The methods used in automatic control systems use the Proportional Integral Derivative (PID) [17,18], Neural-Network [19,20], Fuzzy control [21,22], Genetic algorithm [23,24], etc. Among them, PID control is most widely used in the industrial field [25,26,27]. PID control has various advantages such as a simple structure, an excellent control performance, and easy adjustment of control gain. Furthermore, PI control is excellent in reducing errors in steady-state [28]. The PI controller predicts the control value of the next step using a proportional gain and an integral gain. The PI controller has good control performance for particular gains, however, if these gains are not selected an optimization value suitable for control condition, the performance of control will become worse. Therefore, it is necessary to study the method for reducing the dependence of gain of PI controller [29].
In this paper, the Series Connected Fuzzy-PI (SF-PI) controller controls temperature of a dehumidifier using the thermoelectric element. The conventional PI controller has a limitation in improvement of the control performance in transient-state due to the fixed gain value. To solve this problem, the SF-PI controller is configured, connecting the fuzzy controller and PI controller in series. The Fuzzy controller adjusts the input value of the PI controller, and then the PI controller controls the temperature of the thermoelectric element using the input value adjusted by the fuzzy controller.
This paper is organized as follows. In Section 2, the characteristics of thermoelectric devices are introduced. Section 3 shows the SF-PI (Series Fuzzy-PI) controller in which fuzzy control and PI controller are connected in series. In Section 4, Industry 4.0 implementation using web page and temperature control experiment result by SF-PI controller are presented and the validity of the proposed method is analyzed. Finally, Section 5 presents the conclusion and future work of this paper.

2. Dehumidifier System by Thermoelectric Element

Humid air entering the interior by the fan contacts the surface of the cooler and condenses into water [30]. In general, a dehumidifier removes moisture in the air by this method and discharges the dehumidified air. Dried exhaust air is used to cool the temperature of the refrigerant used to drop the temperature of the cooler. As a result, the temperature of the output air is raised. Figure 1 shows the principle of the dehumidifier. Figure 2 also shows the structure of the thermoelectric element.
When a current flows through a thermoelectric element, one side of the thermoelectric element made of P-N semiconductor absorbs heat and the other side outputs heat. The Joule’s heat caused by the current (I) flowing into the thermoelectric element each enters the top and bottom side. Therefore, the top side has low temperature (Tc), and bottom side has high temperature (TH). The temperature differential is as follows:
Δ T = T H T c
The amount of heat absorption (Qc) on the low temperature side and radiation of heat (QH) on the high temperature side are as follows [31]:
Q c = T c I I 2 R 2 K Δ T
Q H = T H I + I 2 R 2 K Δ T
where α (V/K) is the Seebeck coefficient, R (Ω) is the inner resistor of thermoelectric element, and K (W/m∙K) is the coefficient of thermal conductivity.
The first term is the influence of the Peltier effect, the second term is the influence of the Joule’s effect and the last term is the amount of thermal transfer by conduction from the high temperature side to the low temperature side in Equations (2)–(3).
The input power of the thermoelectric element is as follows:
P i n = I ( T c T H ) + I 2 R
The first term is the power by the Seebeck effect, and the second term is the power by the electric resistor in Equation (3). The sum of these powers becomes the total input power of the thermoelectric element.
The coefficient of performance (COP) of the thermoelectric element is the ratio of heat absorption to the input power, and is as follows [32]:
C O P = Q c P i n

3. SF-PI Control System

The PI controller is widely used in industrial fields because it has advantages in that the structure is simple and the response between the control and the control value is clear.
The typical PI controller calculates the control value using an error signal, a proportional (kp) and integral gain (ki) or integral time (Ti). The optimal gains of PI controller change by the operating state. Therefore, gain adjustment is necessary, and the adjustment has to consider the control characteristics suitable to the system. The characteristics requested to the PI controller are as follows.
-
Stable performance
-
Fast response
-
Minimize errors in the steady-state
The kp and ki (Ti) must be adjusted within a stability performance range. In generally, the increasing of gain kp and ki (decreasing of the integral time constant Ti) brings the system the quick response. However, excessive increase or decrease of these values causes vibration of the system. Therefore, the system becomes a divergent system at worst.
There is a close relationship between system performance and these gains, so the gains have to be adjusted suitably. These gains generally have the following influence on the system (Table 1).
Table 2 shows the various ways to adjust the gain of the PI controller [33,34]. This paper adjusts the gain of the PI controller through the trial and error method, which is one of the manual methods that does not need mathematical expression and can control the gain value online.
The adjusting method of kp and ki (Ti) is as follows.
First, after the command value is changed, if the response time is very slow, increase kp, and if the response time is fast but unstable, decrease kp.
Second, if the feedback value does not track the command value, decrease Ti, and if the feedback value unstably tracks the command value with vibration, increase Ti.
The PI controller used in this paper adjusts kp and ki using the manual method.
The manual method adjusts the PI controller with the procedure shown below.
1. Proportional gain setting.
The control is started with kp = 0, without the ki gain. Increase kp until the control loop achieves good (satisfactory) stability.
2. Integral time (Ti) & kp adjustment.
Set the integral time Ti, which is the time between the over-shoot and the under-shoot of the step response, with the proportional controller. Decrease Ti until the rising time achieves a satisfactory state. If the control state is unstable during the Ti setting, decrease kp.
The PI controller consists of a proportional control and an integral control. Among them, the integral operation causes the cumulative error due to the steady state. This problem causes saturation problems in the system. Therefore, the PI controller results in a control delay when the system is reversed until the cumulative error is removed. This phenomenon is called the windup. The avoiding method of the windup is called the anti-windup [35,36,37].
In this paper, anti-windup is applied using output limit. The problem of windup is that the output of the accumulator integrator reduces the influence of the proportional controller in the next state, resulting in delayed control. Therefore, the method used in this paper limits the output value from the PI controller and continues to use the limited value when calculating the next state value. Therefore, even if the state changes to the next state, the influence of the proportional controller output can be maintained because the output of the PI controller has a limited value. The following figure shows the PI controller used in this paper. The PI controller outputs the change value of the control signal with the error compensated by the fuzzy controller as an input, and outputs the control value of the next state in addition to the output value of the previous state. At this time, since the control value of the next calculated state is limited, the PI controller can maintain the influence of the proportional control. Figure 3 shows a PI controller with the anti-windup.
The purpose of this paper is to improve the temperature control performance of a dehumidifying system using a thermoelectric device. In this paper, we design a system to control the input value of the PI controller because the PI controller has a limitation in the performance improvement due to the fixed gain value. Control of input values of PI controller uses fuzzy control that does not require mathematical modeling and robustness to a nonlinear system.
The PI controller controls the pulse width modulation (PWM) for the thermoelectric device control, and the fuzzy control controls the input value of the PI controller. In this paper, fuzzy control and PI controller are arranged and connected in series to construct a system that operates like this.
The fuzzy control is performed by inputting the error (e) and the changing error (ce) values by the reference temperature (Tref) and the heat absorption side temperature of the thermoelectric element. If the dew point temperature (TDP) is used as the reference temperature for the thermoelectric device heat absorption side (HAS) temperature control, the change in temperature and relative humidity due to the ambient environment will greatly affect the dehumidification performance. Therefore, the reference temperature is set using the band gap temperature (ΔT), and the HAS temperature is controlled below that temperature.
If two or more thermoelectric elements are used in the dehumidifier, the temperature of each HAS is different. The HAS temperature is most closely related to the dehumidification performance, and if the HAS temperature is higher than the dew point temperature, dehumidification is not performed.
Therefore, each HAS temperature is measured and the temperature control is performed based on the higher HAS temperature. A block diagram of this system is shown in Figure 4.
TDP is the dew point temperature according to humidity and current temperature. ΔT is the setting temperature to control the temperature below the dew point temperature. Tref is the reference temperature for dew point temperature control. Tf1 and Tf2 are the temperature of heat absorption side in the thermoelectric element. If the thermoelectric element is over two, the input value of the controller is the temperature of the heat absorption side of the thermoelectric element that has high temperature.
T ( k ) r e f = T D P ( k ) Δ T ( k )
T ( k ) = max ( T f 1 , T f 2 )
e ( k ) = T ( k ) r e f T ( k )
c e ( k ) = e ( k ) e ( k 1 )
The input value of fuzzy control is an error (e) and a changing error (ce), and its output is a value (rc) to adjust the input value of PI controller. The fuzzy rule base is as Table 3, and Figure 5 and Figure 6 show the membership function for input and output value of fuzzy control.
The membership functions in fuzzy control are formed using straight or curved lines. The triangular membership function and trapezoidal membership function in straight membership function are the most common methods. Due to their simple formulas and computational efficiency, these methods have been used widely. The performances of the membership functions have compared about vary control and the triangular and trapezoidal types can obtain benefits to real time control. The advantages of the triangular and trapezoidal types are proposed by many studies [38,39,40,41,42]. Furthermore, since the triangular type has robustness in terms of the response speed and the error in steady-state, it has used extensively in the related region [38,39]. Therefore, the fuzzy control used in this paper has applied the triangular membership function.
The rc value is obtained in Equation (10) using the center-of-gravity defuzzification method.
r c ( k ) = i = 1 n ( r c ) i · μ [ ( r c ) i ] i = 1 n μ [ ( r c ) i ]
  T c ( k ) = T ( k ) r e f + r c ( k )
  e c ( k ) = T c ( k ) + T ( k )
P W M ( k ) r e f = P W M ( k 1 ) r e f + k p · { e c ( k ) e c ( k 1 ) } + k i · e c ( k ) · t s
Tc is the reference value adjusted by the fuzzy control, ec is the input value of PI controller, and kp and ki are the proportional gain and integral gain used in PI controller, respectively.

4. Experiment Result

Raspberry pi and the Arduino were used in this paper for the implementation of the IoT, one element of Industry 4.0. Raspberry pi builds the Apache HTTP server (Version: 2.2.22, Apache software Foundation, ASF, Forest Hill, MD, USA) and configures the database with MySQL (Version: 5.6.23, MySQL AB, Cupertino, CA, USA) to save the data needed for control. Arduino measures the temperature inside the dehumidifier, stores it in the database (DB), and controls the thermoelectric elements inside the dehumidifier.
Figure 7 shows a web page for the remote control. In addition, Table 4 shows the explanation of remote web page.
Figure 8, Figure 9 and Figure 10, respectively show the changing of the dehumidifier operating state according to set a web page for remote control.
Figure 11 shows a system structure and a circuit diagram used in this paper for experiment. Table 5 shows the major parts used in Figure 11.
In this paper, the atmospheric conditions are set as shown in Table 6 to analyze the temperature control performance of a dehumidifier using a thermoelectric device. Figure 12 and Figure 13 show the voltage, current, and power of a typical PI controller and SF-PI. The operation of the thermoelectric device causes the current to change constantly, which also changes the power consumption. Table 7 shows the average power consumption in Figure 12 and Figure 13. The proposed SF-PI method reduced power consumption to 93% of PI controller power consumption.
The temperature control of the thermoelectric element controls the cooling of the thermoelectric element by the supply of electric power, and when the temperature of the heat absorption side in the thermoelectric element is lower than the set value, that is controlled to rise by the supplied air.
Figure 14 shows the temperatures of the thermoelectric elements of PI and SF-PI when the temperature of the surface of the thermoelectric element reaches a steady state. Figure 14a shows the temperature of the PI controller and Figure 14b shows the temperature of the SF-PI controller. According to the SF-PI operation, the actual value can be divided into the section lower than the set value and the section where the actual value is larger than the set value. If the actual value is lower than the set value, control is required so that the actual value follows the set value quickly. To increase the set value, it increases the error input to the PI controller. Since the error value increases, the control value output from the PI controller rises to enable quick control. If the actual value is higher, control is performed in the opposite direction.
In Figure 14b, Zone A shows a lower temperature of the heat absorption side (HAS) of the thermoelectric element than the control temperature (CT) and Zone B shows a higher HAS temperature than CT. In Zone A, because it requires a rise in the HAS temperature, the temperature adjusted by the fuzzy control (ACT) rises. In Zone B, the ACT is going down for decreasing HAS temperature.
Figure 15 shows the temperature error between the Control Temperature (CT) and the thermoelectric element temperature. The conventional PI controller uses fixed gains and an input value. However, the SF-PI controller proposed in this paper uses PI’s input value adjusted by the fuzzy control according to a control state. Therefore, the SF-PI controller has a lower temperature error than the PI controller. Table 8 shows the average temperature error between the control temperature and the thermoelectric element temperature. In Figure 15, the SF-PI controller performs more accurate temperature control than the PI controller. For this reason, the average temperature error of SF-PI controller is 22% of PI’s value.
Figure 16 shows the consumption power and the average consumption power of the PI controller and the SF-PI controller under the conditions of Table 4. The consumption power of thermoelectricity is generated in a cooling period. Therefore, to decrease its consumption power, the cooling time has to be reduced. The SF-PI controller has a shorter cooling time than PI because the temperature error is low. Therefore, the SF-PI controller has a short cooling time, and the consumption power is reduced.
Table 9 shows the average consumption power in Figure 16.
The condition of Table 6 is a constant indoor environment. To analyze changing environments, Figure 17 shows an indoor environment condition where the dew point temperature is increasing according to decreasing relative humidity caused by indoor temperature increasing.
Figure 18 shows a response characteristic of PI and SF-PI controller at Figure 17 conditions. The control temperature (CT) is changed by the dew point temperature changing and the PI and SF-PI controller performs temperature control for tracking the CT.
In Figure 18b, Zone A is an area where a heat absorption side (HAS) temperate of thermoelectricity is lower than the CT. In this case, to reduce unnecessary cooling time, adjusted control temperature (ACT) increases, and because of this, the power feeding to thermoelectricity can stop quickly.
Zone B in Figure 18b is a region wherein the HAS temperature is higher than the CT. In this condition, the performance of dehumidification weakens because of insufficient cooling. Therefore, to improve the dehumidification performance, the HAS has to cool quickly. To meet this requirement, the ATC is decreasing, can obtain fast cooling of HAS.
Figure 19 shows a temperature error of the PI and the SF-PI controller under Figure 17 condition. The SF-PI controller can also achieve accurate temperature control under conditions of changing temperature and relative humidity by adjusting PI’s input value by fuzzy control. Table 10 shows the result of Figure 19. The temperature error of the SF-PI controller is reduced by about 50% compared to the PI controller.
Figure 20 shows the consumption power of SF-PI and PI controller under condition of Figure 17. Because the SF-PI controller has a low temperature error, its consumption power is also low under conditions of changing temperature and relative humidity. Table 11 shows analysis of Figure 20. The SF-PI controller reduces consumption power by about 2.3% compared to PI controller even in condition of Figure 17.
In the power consumption comparison of Table 7, Table 9, and Table 11, the difference between the PI controller and the SF-PI controller is 1.79 Wh, 2.4 Wh, and 0.5 Wh, respectively. The difference between these values seems to be very small from a typical numerical comparison. However, this is due to the small capacity of the system, and a percentage comparison shows a 7.6%, 11.9%, and 2.3% reduction in power consumption, respectively. Therefore, if the system capacity is increased or the used number increases and the usage time and duration are increased, the effect will be increased.

5. Conclusions

This paper proposes applying the IoT to dehumidifier, which is one of the Industry 4.0 techniques, and the method to improve the performance of dehumidifier using the thermoelectric element. To dehumidify using the thermoelectric element, the temperature of the heat absorption side in the thermoelectric element must remain under the dew point temperature. This condition is very closely connected to the dehumidification performance of the dehumidifier.
This paper proposes the SF-PI controller consisting of fuzzy control and PI controller connection. The conventional PI controller is not easily satisfied in both transient-state and steady-state because it is controlled using a fixed gain. However, the SF-PI controller can be expected to achieve satisfactory control performance compared to the conventional PI control because it controls the temperature using the adjusted value by fuzzy control according to the operating conditions.
The average temperature error of SF-PI controller between the reference temperature and the thermoelectric element temperature is 22% of traditional PI’s value. It also decreases the consumption power by about 10% by prevention of overwork cooling. Despite temperature and humidity variation, the temperature error and the consumption power of the SF-PI controller is respectively reduced by about 50% and 2.3% compared to the PI controller.
Therefore, the SF-PI controller proposed in this paper has excellent control performance compared to PI control, and therefore can improve the performance of a dehumidifier using a thermoelectric element. In addition, the IoT, part of Industry 4.0, of the dehumidifier is performed according to remote control by a web page. By applying Industry 4.0 to the dehumidifier system, it is possible to provide remote control and monitoring function to the user, and it is possible to analyze the usage pattern of the user and provide control operation tailored to the user.
This paper presents the improvement of the performance of the dehumidifier system using thermoelectric devices and the application of Industry 4.0. The most important performance in a dehumidification system is the ability to maintain the temperature for dehumidification. In this paper, we propose a SF-PI controller and confirm that the temperature control performance is improved compared to the conventional PI controller, and the power consumption of the dehumidification system is also reduced. Recently, the use of dehumidifying systems has been increasing because of the growing interest in the indoor environment. The system proposed in this paper has improved the performance and power consumption of the dehumidification system and can be used as a system that can provide convenience to users through the application of Industry 4.0.
This paper improves the temperature control performance of dehumidifier using a thermoelectric element by SF-PI controller. The SF-PI controller performs switching operation more frequently than a conventional PI controller for accurate temperature control. This results in a reduction in power consumption. Therefore, research to improve performance of the power loss and temperature control by optimized switching operating is necessary.

Author Contributions

Conceptualization, J.-S.K.; Data curation, J.-S.K., Jun-Ho Huh and J.-C.K.; Formal analysis, J.-S.K.; Funding acquisition, J.-S.K. and J.-H.H.; Investigation, J.-S.K. and J.-H.H.; Methodology, J.-H.H. and J.-C.K.; Project administration, J.-H.H. and J.-C.K.; Resources, J.-H.H. and J.-C.K.; Software, J.-H.H.; Supervision, J.-C.K.; Validation, J.-C.K.; Visualization, J.-C.K.; Writing—original draft, J.-S.K. and J.-H.H.; Writing—review & editing, J.-H.H. and J.-C.K.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Huh, J.-H. Server Operation and Virtualization to Save Energy and Cost in Future Sustainable Computing. Sustainability 2018, 10, 1919. [Google Scholar] [CrossRef]
  2. Kim, N.K.; Shim, M.H.; Won, D. Building Energy Management Strategy Using an HVAC System and Energy Storage System. Energies 2018, 11, 2690. [Google Scholar] [CrossRef]
  3. Shaikh, Z.; Chaudhry, H. Energy Modeling and Indoor Air Quality Analysis of Cooling Systems for Buildings in Hot Climates. Fluids 2018, 3, 77. [Google Scholar] [CrossRef]
  4. Amasyail, K.; El-Gohary, N.M. A review of data-driven building energy consumption prediction studies. Renew. Sustainable Energy Rev. 2018, 81, 1192–1205. [Google Scholar] [CrossRef]
  5. Lee, J.; Tae, S.; Kim, R. A Study on the Analysis of CO2 Emissions of Apartment Housing in the Construction Process. Sustainability 2018, 10, 365. [Google Scholar] [CrossRef]
  6. Schlanger, Z. The People Living in the Hottest Places on the Planet Are the Least Likely to Have Air Conditioners. Available online: https://qz.com/1285836/the-people-living-in-the-hottest-places-on-the-planet-are-the-least-likely-to-have-air-conditioners/ (accessed on 24 May 2018).
  7. Desiccant or Compressor Dehumidifier? Available online: http://www.andatech.com.au/resource/desiccant-or-compressor-dehumidifier/ (accessed on 9 February 2018).
  8. Disadvantages of A Dehumidifier. Available online: https://freshairguru.com/disadvantages-of-a-dehumidifier/ (accessed on 8 October 2018).
  9. Martinez, B.; Vilajosana, X.; Kim, I.H.; Zhou, J.; Tuset-Peiro, P.; Xhafa, A.; Possonnier, D.; Lu, X. I3Mote: An Open Development Platform for the Intelligent Industrial Internet. Sensors 2017, 17, 986. [Google Scholar] [CrossRef] [PubMed]
  10. Syafrudin, M.; Fitriyani, N.L.; Li, D.; Alfian, G.; Rhee, J.; Kang, Y.S. An Open Source-Based Real-Time Data Processing Architecture Framework for Manufacturing Sustainability. Sustainability 2017, 9, 2139. [Google Scholar] [CrossRef]
  11. Costa, D.G.; Duran-Faundez, C. Open-Source Electronics Platforms as Enabling Technologies for Smart Cities: Recent Developments and Perspectives. Electronics 2018, 7, 404. [Google Scholar] [CrossRef]
  12. Patnaik Patnaikuni, D.R. A Comparative Study of Arduino, Raspberry Pi and ESP8266 as IoT Development Board. Int. J. Adv. Res. Comput. Sci. 2017, 8, 2350–2352. [Google Scholar]
  13. Satapathy, L.M.; Bastia, S.K.; Mohanty, N. Arduino based home automation using Internet of things (IoT). Int. J. Pure Appl. Math. 2018, 118, 769–778. [Google Scholar]
  14. Zhong, X.; Liang, Y. Raspberry Pi: An Effective Vehicle in Teaching the Internet of Things in Computer Science and Engineering. Electronics 2016, 5, 56. [Google Scholar] [CrossRef]
  15. Lee, J.; Bagheri, B.; Kao, H.-A. A cyber-physical systems architecture for industry 4.0-based manufacturing systems. Manuf. Lett. 2015, 3, 18–23. [Google Scholar] [CrossRef]
  16. Wang, S.; Wan, J.; Zhang, D.; Li, D.; Zhang, C. Towards smart factory for industry 4.0: A self-organized multi-agent system with big data based feedback and coordination. Comput. Netw. 2016, 101, 158–168. [Google Scholar] [CrossRef]
  17. Ang, K.H.; Chong, G.; Li, Y. PID control system analysis, design, and technology. IEEE Trans. Control Syst. Technol. 2005, 13, 559–576. [Google Scholar] [Green Version]
  18. Li, Y.; Ang, K.H.; Chong, G.C.Y. Patents, software, and hardware for PID control: an overview and analysis of the current art. IEEE Control Syst. 2006, 26, 42–54. [Google Scholar] [Green Version]
  19. Mozer, M.C. The Neural Network House: An Environment that Adapts to Its Inhabitants; Technical Report; AAAI Spring Symp. Intelligent Environments: Palo Alto, CA, USA, 1998. [Google Scholar]
  20. Fang, H.; He, L. BP neural network for human activity recognition in smart home. In Proceedings of the 2012 International Conference on Computer Science and Service System, Nanjing, China, 11–13 August 2012; pp. 1034–1037. [Google Scholar]
  21. Ko, J.S.; Choi, J.S.; Chung, D.H. Hybrid Fuzzy Controller for DTC of Induction Motor Dirve. Korean Inst. Illum. Electr. Installation Eng. 2011, 25, 22–33. [Google Scholar] [CrossRef]
  22. Hwang, G.H. Development of Fuzzy Controller for Temperature Environment Tester Using Thermoelectric Module. J. Korea Inst. Inf. Commun. Eng. 2015, 19, 1228–1234. [Google Scholar] [CrossRef]
  23. Cho, J.H.; Kim, Y.T. Design of PID Controller for Magnetic Levitation RGV Using Genetic Algorithm Based on Clonal Selection. J. Korean Inst. Intell. Syst. 2012, 22, 239–245. [Google Scholar] [CrossRef]
  24. Hameed, S.; Das, B.; Pant, V. A self-tuning fuzzy PI controller for TCSC to improve power system stability. Electr. Power Syst. Res. 2008, 78, 1726–1735. [Google Scholar] [CrossRef]
  25. Qin, Y.; Sun, L.; Hua, Q.; Liu, P. A Fuzzy Adaptive PID Controller Design for Fuel Cell Power Plant. Sustainability 2018, 10, 2438. [Google Scholar] [CrossRef]
  26. Sun, L.; Li, D.; Lee, K.Y. Optimal disturbance rejection for PI controller with constraints on relative delay margin. ISA Trans. 2016, 63, 103–111. [Google Scholar] [CrossRef] [PubMed]
  27. Wang, J.-S.; Yang, G.H. Data-Driven Approach to Accommodating Multiple Simultaneous Sensor Faults in Variable-Gain PID Systems. IEEE Trans. Ind. Electron. 2019, 66, 3117–3126. [Google Scholar] [CrossRef]
  28. Ketata, R.; Geest, D.D.; Titli, A. Fuzzy controller: design, evaluation, parallel and hierarchial combination with a pid controller. Fuzzy Sets Syst. 1995, 71, 113–129. [Google Scholar] [CrossRef]
  29. Mudi, R.K.; Pal, N.R. A robust self-tuning scheme for PI- and PD-type fuzzy controllers. IEEE Trans. Fuzzy Syst. 1999, 7, 2–16. [Google Scholar] [CrossRef]
  30. Yin, Y.; Zhang, X.; Chen, Z. Experimental study on dehumidifier and regenerator of liquid desiccant cooling air conditioning system. Build. Environ. 2007, 42, 2505–2511. [Google Scholar] [CrossRef]
  31. Landecker, K. Some Further Remarks on the Improvement of Peltier Junctions for Thermoelectric Cooling. Energy Convers. 1974, 14, 21–33. [Google Scholar] [CrossRef]
  32. Yoo, S.Y.; Hong, C.P.; Shim, W.S. A Study on the Performance of Thermoelectric Module and Thermoelectric Cooling System. Korean J. Air-Conditioning Refrig. Eng. 2004, 16, 62–69. [Google Scholar]
  33. Barbosa, R.S.; Machado, J.A.T.; Ferreira, I.M. A fractional calculus perspective of PID tuning. In Proceedings of the ASME 2003 Design Engineering Technical Conferences and Computers and Information in Engineering Conference, Chicago, IL, USA, 2–6 September 2003. [Google Scholar]
  34. Barbosa, R.S.; Machado, J.A.T.; Ferreira, I.M. Tuning of PID controllers based on Bode’s ideal transfer function. Nonlinear Dyn. 2004, 38, 305–321. [Google Scholar] [CrossRef]
  35. Li, X.L.; Park, J.G.; Shin, H.B. Comparison and Evaluation of Anti-Windup PI Controllers. J. Power Electron. 2011, 11, 45–50. [Google Scholar] [CrossRef] [Green Version]
  36. Ghoshal, A.; John, V. Anti-windup Schemes for Proportional Integral and Proportional Resonant Controller. Natl. Power Electron. Conf. 2010, 1–6. [Google Scholar]
  37. John, G.S.; Vijayan, A.T. Anti-Windup PI Controller for Speed Control of Brushless DC Motor. In Proceedings of the 2017 IEEE International Conference on Power, Control, Signals and Instrumentation Engineering (ICPCSI), Chennai, India, 21–22 September 2017; pp. 1068–1073. [Google Scholar]
  38. Ali, O.A.M.; Ali, A.Y.; Sumait, B.S. Comparison between the Effects of Different Types of Membership Function, on Fuzzy Logic Controller Performance. Int. J. Emerging Eng. Res. Technol. 2015, 3, 76–83. [Google Scholar]
  39. Monicka, J.G.; Sekhar, N.G.; Kumar, K.R. Permormance Evaluation of Membership Functions on Fuzzy Logic Controlled AC Voltage Controller for Speed Control of Induction Motor Drive. Int. J. Comput. Appl. Technol. 2011, 13, 8–12. [Google Scholar]
  40. Sriparna, S.; Bhattacharya, S.; Konar, A. Comparison between Type-1 Fuzzy Membership Function for Sign Language Applications. In Proceedings of the 2016 International Conference on Microelectronics, Computing and Communications (MicroCom), Durgapur, India, 23–25 January 2016; pp. 23–25. [Google Scholar]
  41. Princy, S.; Dhenakaran, S.S. Comparison of triangular and Trapezoidal Fuzzy Membership Function. J. Comput. Sci. Eng. 2016, 2, 46–51. [Google Scholar]
  42. Hammell II, R.J.; Miao, S.; Hanratty, T.; Tang, Z. Comparison of Fuzzy Membership Functions for Value of Information Determination. In Proceedings of the 23rd Midwest Artificial Intelligence and Cognitive Science (MAICS 2012), Cincinnati, OH, USA, 21–22 April 2012. [Google Scholar]
Figure 1. Principle of the dehumidifier.
Figure 1. Principle of the dehumidifier.
Processes 07 00098 g001
Figure 2. Principle of thermoelectric element.
Figure 2. Principle of thermoelectric element.
Processes 07 00098 g002
Figure 3. PI controller with anti-windup.
Figure 3. PI controller with anti-windup.
Processes 07 00098 g003
Figure 4. Series connected Fuzzy (SF)-PI controller.
Figure 4. Series connected Fuzzy (SF)-PI controller.
Processes 07 00098 g004
Figure 5. Membership function for the input value (error (e) and changing error (ce)). (a) The error (e) membership function. (b) The changing error (ce) membership function.
Figure 5. Membership function for the input value (error (e) and changing error (ce)). (a) The error (e) membership function. (b) The changing error (ce) membership function.
Processes 07 00098 g005aProcesses 07 00098 g005b
Figure 6. Output membership function. NB: Negative Big, NM: Negative Medium, NS: Negative Small, ZE: Zero; PB: Positive Big, PM: Positive Medium, PS: Positive Small.
Figure 6. Output membership function. NB: Negative Big, NM: Negative Medium, NS: Negative Small, ZE: Zero; PB: Positive Big, PM: Positive Medium, PS: Positive Small.
Processes 07 00098 g006
Figure 7. Web page for remote control.
Figure 7. Web page for remote control.
Processes 07 00098 g007
Figure 8. Dehumidification control—“AUTO” mode.
Figure 8. Dehumidification control—“AUTO” mode.
Processes 07 00098 g008
Figure 9. Dehumidification control—“START” mode.
Figure 9. Dehumidification control—“START” mode.
Processes 07 00098 g009
Figure 10. Dehumidification control—“STOP” mode.
Figure 10. Dehumidification control—“STOP” mode.
Processes 07 00098 g010
Figure 11. System structure and circuit diagram for experiment.
Figure 11. System structure and circuit diagram for experiment.
Processes 07 00098 g011
Figure 12. Voltage, Current, and Power of PI controller. (a) Voltage and Current. (b) Power.
Figure 12. Voltage, Current, and Power of PI controller. (a) Voltage and Current. (b) Power.
Processes 07 00098 g012aProcesses 07 00098 g012b
Figure 13. Voltage, Current, and Power of SF-PI controller. (a) Voltage and Current. (b) Power.
Figure 13. Voltage, Current, and Power of SF-PI controller. (a) Voltage and Current. (b) Power.
Processes 07 00098 g013aProcesses 07 00098 g013b
Figure 14. Temperature comparison in steady-state. (a) PI Controller. (b) SF-PI Controller.
Figure 14. Temperature comparison in steady-state. (a) PI Controller. (b) SF-PI Controller.
Processes 07 00098 g014
Figure 15. Temperature error comparison.
Figure 15. Temperature error comparison.
Processes 07 00098 g015
Figure 16. Consumption power comparison in steady-state. (a) PI Controller. (b) SF-PI Controller.
Figure 16. Consumption power comparison in steady-state. (a) PI Controller. (b) SF-PI Controller.
Processes 07 00098 g016
Figure 17. Condition of changing temperature and humidity.
Figure 17. Condition of changing temperature and humidity.
Processes 07 00098 g017
Figure 18. Response characteristics by condition of changing temperature and humidity. (a) PI Controller. (b) SF-PI Controller.
Figure 18. Response characteristics by condition of changing temperature and humidity. (a) PI Controller. (b) SF-PI Controller.
Processes 07 00098 g018
Figure 19. Temperature error comparison for changing temperature and humidity.
Figure 19. Temperature error comparison for changing temperature and humidity.
Processes 07 00098 g019
Figure 20. Consumption power comparison for changing temperature and humidity. (a) PI Controller. (b) SF-PI Controller.
Figure 20. Consumption power comparison for changing temperature and humidity. (a) PI Controller. (b) SF-PI Controller.
Processes 07 00098 g020
Table 1. The effect of the proportional integral (PI) controller gain value on the system.
Table 1. The effect of the proportional integral (PI) controller gain value on the system.
ParameterRise TimeOvershootSettling TimeSteady-State Error
kp IncreaseDecreaseIncreaseSmall ChangeDecrease
ki Increase
(Ti Decrease)
DecreaseIncreaseIncreaseDecrease Significantly
Table 2. Methods of adjusting the gain of a PI controller.
Table 2. Methods of adjusting the gain of a PI controller.
MethodAdvantagesDisadvantages
ManualOnline method
No math expression
Requires experienced personnel
Ziegler-NicholsOnline method
Proven method
Some trial and error, process upset and very aggressive tuning
Cohen-CoonGood process modelsOffline method
Some math
Good only for first order processes
Software toolsOnline or Offline method, consistent tuning, supports Non-Steady State tuningSome cost and training involved
AlgorithmicOnline or offline method, consistent tuning, supports Non-Steady State tuning, very preciseVery slow
Table 3. Rule base of Fuzzy controller.
Table 3. Rule base of Fuzzy controller.
eNBNMNSZPSPMPB
ce
NBNBNBNBNBNMNSZ
NMNBNBNBNMNSZPS
NSNBNBNMNSZPSPM
ZNBNMNSZPSPMPB
PSNMNSZPSPMPBPB
PMNSZPSPMPBPBPB
PBZPSPMPBPBPBPB
Table 4. Operating explanation on web page.
Table 4. Operating explanation on web page.
No.OperationOperating Explanation
Current TimeCurrent time of dehumidifier
Temperature, humidityTemperature and humidity of intake air
Sensor StateOperating state of a temperature and humidity sensor
- Sensor normal operation: GOOD
- Sensor fault: ERROR (last operating time)
ex) ERROR(2018/11/2/ 12:11:11)
Dehumidification
control set humidity
Humidity setting for auto dehumidification control
Exhaust control set
humidity
Humidity setting for auto exhaust control
⑥⑧Dehumidification/
Exhaust control mode
setting
Mode selection for dehumidification/Exhaust
- AUTO: automatically control using set humidity,
current humidity and temperature
- START: forced starting
- STOP: forced stopping
⑦⑨Adjusting set humidity
value
Adjusting set humidity value
Table 5. Components used in the experiment.
Table 5. Components used in the experiment.
ComponentSpec
Thermoelectric elementModel: TEC1-12708, Q m a x : 71 W
Δ T m a x : 66 °C, I m a x : 8.5 A
V m a x : 15.4 V
ControllerModel: Arduino mega2560
Microcontroller: ATmega2560
Flash Memory: 256 KB
Digital I/O: 54. Analog I/O: 16
Temperature & Humidity SensorModel: DHT22
Temperature range: −40 °C–80 °C
Humidity range: 0–100%
Accuracy: Temperature (±0.5 °C), Humidity (2–5%)
Temperature SensorModel: DS18B20
Temperature range: −10 °C–85 °C
Accuracy: ±5 °C
Table 6. Condition to analyze the control characteristics.
Table 6. Condition to analyze the control characteristics.
Temperature (°C)Relative Humidity (%)Dew Point Temperature (°C)
Set value256016.69
Table 7. Comparison of average power consumption.
Table 7. Comparison of average power consumption.
PI ControllerSF-PI Controller
Average Power Consumption (Wh)25.2423.45
Table 8. Temperature error comparison.
Table 8. Temperature error comparison.
PI ControllerSF-PI Controller
Average Temperature Error (°C)0.450.1
Table 9. Average consumption power comparison in steady-state.
Table 9. Average consumption power comparison in steady-state.
PI ControllerSF-PI Controller
Average Power Consumption (Wh)22.520.1
Table 10. Comparison of average temperature error about changing temperature and humidity.
Table 10. Comparison of average temperature error about changing temperature and humidity.
PI ControllerSF-PI Controller
Average Temperature Error (°C)0.410.20
Table 11. Average consumption power comparison for changing temperature and humidity.
Table 11. Average consumption power comparison for changing temperature and humidity.
PI ControllerSF-PI Controller
Average Power Consumption (Wh)21.521.0

Share and Cite

MDPI and ACS Style

Ko, J.-S.; Huh, J.-H.; Kim, J.-C. Improvement of Temperature Control Performance of Thermoelectric Dehumidifier Used Industry 4.0 by the SF-PI Controller. Processes 2019, 7, 98. https://doi.org/10.3390/pr7020098

AMA Style

Ko J-S, Huh J-H, Kim J-C. Improvement of Temperature Control Performance of Thermoelectric Dehumidifier Used Industry 4.0 by the SF-PI Controller. Processes. 2019; 7(2):98. https://doi.org/10.3390/pr7020098

Chicago/Turabian Style

Ko, Jae-Sub, Jun-Ho Huh, and Jong-Chan Kim. 2019. "Improvement of Temperature Control Performance of Thermoelectric Dehumidifier Used Industry 4.0 by the SF-PI Controller" Processes 7, no. 2: 98. https://doi.org/10.3390/pr7020098