1. Introduction and Literature Review
The global energy landscape is undergoing a profound transformation, driven by the dual imperatives of climate change mitigation and energy security. The depletion of conventional oil reserves and the carbon-intensive nature of fossil fuels have significantly disrupted the global carbon cycle, leading to an accelerated accumulation of greenhouse gases and alarming climate change [
1]. This reality, compounded by a growing imbalance between energy production and consumption, has galvanized the international research community to rapidly integrate renewable energy sources (RES) primarily solar photovoltaic (PV) and wind power into electrical grids [
2,
3].
However, the stochastic and intermittent nature of these resources poses major challenges to the stability, power quality, and reliability of modern power systems. Ensuring the balance of future energy systems will require advanced strategies for seamless integration and continuous service, even under dynamic and unbalanced operating conditions [
4,
5]. A critical aspect of this challenge is managing electrical power quality, particularly when RES are connected to the grid under non-ideal conditions. These conditions often manifest as imbalances in voltage and current amplitude and frequency, which can cause equipment malfunction, reduced efficiency, and voltage flicker [
6].
The foundational framework for analyzing unbalanced three-phase systems was established by Charles LeGeyt Fortescue in 1918 with his introduction of the Symmetrical Components Method (SCM) [
7]. This seminal technique decomposes an unbalanced three-phase system into three sets of balanced sequences: the positive sequence (representing normal balanced operation), the negative sequence (representing phase imbalance), and the zero sequence (representing ground or neutral currents). For nearly a century, Fortescue’s theory has been the cornerstone of power system analysis, fault detection, and protection design, proving highly effective for handling imbalances in voltage or current amplitude under a constant grid frequency [
8,
9].
However, the effectiveness of SCM is intrinsically tied to the assumption of a single, stable system frequency. As established in fundamental textbooks and reaffirmed in contemporary reviews like [
10], the classical transformation matrices are valid only when the phase angles evolve at a synchronous speed,
.
The large-scale integration of RES, which are interfaced through power electronic converters, has fundamentally altered power system dynamics. Unlike synchronous generators with significant rotational inertia that stabilize grid frequency, converter-based resources can exhibit rapid frequency variations due to several factors:
- ✓
Intermittency of RES: Sudden variations in solar irradiance or wind speed cause immediate fluctuations in the power output frequency [
11].
- ✓
Low Grid Inertia: In weak grids or microgrids, low inertia makes the system frequency highly susceptible to fluctuations from load changes and generation imbalances [
12,
13].
- ✓
Inverter Control Dynamics: Complex control loops in grid-following and grid-forming inverters can introduce frequency oscillations, particularly during unbalanced grid conditions [
14,
15].
When a PV generator operates at a frequency that deviates from the grid’s, a fundamental synchronization problem arises at the Point of Common Coupling (PCC). This frequency mismatch means the inverter’s output is no longer synchronized with the grid voltage, directly manifesting as voltage flicker and power oscillations at the beat frequency. These effects severely degrade power quality for other local loads.
This situation is critically exacerbated by the behavior of grid-following inverters, which rely on Phase-Locked Loops (PLLs) for synchronization. A fluctuating PV frequency can cause PLL instability, leading to control failures and potentially triggering protective shutdowns. Such a trip not only results in a loss of generation but also injects further instability into the grid by suddenly removing active power. Consequently, rather than acting as a stable power source, a PV system with frequency fluctuations becomes a source of disturbance, undermining local power quality and threatening the stability of the microgrid or weak grid to which it is connected.
The principal advantage of Fortescue’s method over direct analytical techniques for resolving asymmetrical faults lies in its powerful decomposition of a complex, unbalanced system into decoupled positive, negative, and zero-sequence networks. This transformation simplifies calculation by reducing the problem to the analysis of simpler, single-phase equivalent circuits. Furthermore, it provides unparalleled physical insight by directly quantifying imbalance through the negative-sequence component. This capability not only enables root-cause analysis and accurate assessment of harmful effects like machine heating but also forms the critical foundation for designing sensitive and selective protective relaying systems. As such, Fortescue’s method offers a standardized and comprehensive framework that direct techniques lack.
These frequency deviations
create a scenario where the fundamental assumption of the classical Fortescue theory is violated. When
, the traditional sequence components, as calculated by the fixed Fortescue operator
, are no longer constant in a rotating reference frame but become oscillatory, leading to inaccurate analysis and ineffective control [
16]. Recognizing the limitations of classical methods, researchers have developed advanced techniques to handle unbalanced conditions, primarily focusing on amplitude unbalance but laying the groundwork for frequency-variation analysis. Dual/Second-Order Generalized Integrator (DSOGI) and Dual Synchronous Reference Frame (DSRF) PLL: These techniques are highly effective for decomposing sequences under amplitude unbalance. The DSRF-PLL, for instance, uses two rotating frames (positive and negative) to extract DC components from each sequence [
17,
18]. However, their performance degrades under frequency variations, as the filters and controllers are tuned for a nominal frequency [
19].
Advanced Phase-Locked Loops (PLLs): Numerous enhanced PLL structures, such as the Decoupled Double Synchronous Reference Frame (DDSRF) PLL [
20] and adaptive PLLs [
21], have been proposed to improve synchronization under unbalanced and distorted grids. While robust to amplitude imbalances, their response to rapid frequency changes can be slow or oscillatory, and they do not provide a generalized theoretical framework for sequence decomposition under frequency unbalance.
Signal Processing Approaches: Methods based on the Kalman Filter [
22], the Teager Energy Operator [
23], and mathematical morphology [
24] have been applied for frequency estimation and flicker detection. These are excellent for measurement but are not inherently designed to reconstruct balanced sequence components for control purposes under combined amplitude and frequency imbalance [
25]. A critical gap identified in the literature is the absence of a unified theoretical extension of Fortescue’s method that explicitly accounts for frequency unbalance. Existing solutions are often control-centric or signal-processing-based, addressing the symptom rather than redefining the underlying analytical model [
26]. As demonstrated, the classical Fortescue theory is inadequate for systems experiencing frequency deviations, a common occurrence in RES-dominated grids. While modern control techniques offer practical workarounds, they lack the foundational analytical elegance and generality of Fortescue’s approach [
27].
This paper links this gap by proposing a Modified Fortescue Theory. The core contribution is the introduction of a new transformation operator,
, which incorporates the frequency deviation term
. This modification allows for the decomposition of a three-phase system with simultaneous amplitude and frequency unbalance [
28] into three distinct, balanced sequences. The resulting components are constant in their respective reference frames, providing ideal references for control systems. This theoretical advancement is not merely an academic exercise; it is a necessary step towards developing more robust and intelligent control strategies for future power systems [
29]. By providing a mathematically sound basis for analyzing frequency unbalance, this work paves the way for enhanced stability, power quality, and reliability in the era of renewable energy. The final objective of this work is to study the behavior of currents and voltages when a renewable energy source is connected to a three-phase electrical grid under conditions of both amplitude and frequency unbalance [
30]. The classical analytical tools, while powerful, are insufficient to fully address the complexities introduced by frequency deviations. This paper, therefore, introduces a Modified Fortescue Theory to resolve frequency unbalance problems, providing new balanced components that will serve as references for advanced control strategies in subsequent research.
Our paper is structured to systematically develop and validate the proposed Modified Fortescue Theory. It begins with a system description and mathematical presentation, establishing the foundational models and highlighting the limitations of the classical theory under frequency unbalance. The subsequent section analyzes the influence of the PV generator frequency variation on system performance, demonstrating the resulting oscillations and flicker phenomena. Following this, a load voltage calculation method is detailed to model the system’s behavior under these unbalanced conditions. The core of our contribution is then presented in the strategy for evaluating the load voltage sequences, which introduces the new transformation operator and derives the balanced sequence components. The validity and effectiveness of the proposed theory are subsequently demonstrated through
Section 6. Finally, the paper concludes by summarizing the key findings, emphasizing the significance of the work, and outlining potential future research directions.
2. System Description and Mathematical Presentation
The benchmark system, shown in
Figure 1, models a three-phase PV generator connected to the main grid. The PV source is interfaced at the Point of Common Coupling (PCC), which also supplies a local three-phase load. This topology is ideal for analyzing key power quality issues. Specifically, we investigate the system’s response to a frequency deviation between the PV generator and the grid (
), as well as to voltage amplitude sags [
31], thereby simulating realistic grid fault conditions.
This paper establishes the theoretical foundation for advanced control strategies to enable the robust integration of renewable energy sources—such as photovoltaic, wind, and hybrid systems—into modern power grids. The work is motivated by a critical limitation of the classical Fortescue theory: its restriction to amplitude unbalance and its inability to handle the frequency unbalance inherent to inverter-based resources. To address this gap, we introduce a novel theoretical identification method that precisely traces the origin of fluctuations in a three-phase system
[
32] under simultaneous amplitude and frequency deviations. The system is modeled using complex phasors, as defined in Equation (1), where the quantities
and
are complex numbers of the form
.
The angular position
is defined by the relation
, where
represents the grid’s fundamental angular velocity. When the three-phase system
is unbalanced in amplitude
, its behavior can be decomposed into symmetrical components. The positive, negative, and zero sequences, which characterize different aspects of the system’s response, are calculated using the standard Fortescue transformations given in Equations (2)–(4) [
33,
34]:
The decomposition yields three sets of symmetrical components: the positive-sequence
, the negative-sequence
, and the zero-sequence
, derived from the unbalanced system
using the Fortescue operator
. The characteristic spatial orientation of each sequence, which provides a clear means of differentiation, is depicted in
Figure 2 [
35].
The system under study, illustrated in
Figure 1, comprises a photovoltaic (PV) generator defined by its three-phase voltages (
and currents (
interfaced with a three-phase electrical grid, supplying a three-phase load
. Under ideal synchronous conditions, the PV generator frequency
matches the grid frequency
. However, in practice, the intermittent nature of solar generation inevitably introduces a frequency deviation
. To analyze this effect, a deviation of
is considered.
Similarly, while the objective is to maintain balanced voltage amplitudes at the load, real-world grid conditions often lead to imbalances. To simulate this, a 10% voltage drop in phase 1 is applied at
t = 0.5 s. The frequency deviation between the PV generator and the grid is quantified by Equation (5):
The frequency variation
directly impacts the mathematical description of the three-phase system established in Equation (1). To account for this deviation, the system’s representation is modified by introducing the angular displacement
, leading to the revised expressions given in Equation (6):
The system in
Figure 1 was simulated in MATLAB/Simulink R2025a under conditions of simultaneous frequency and amplitude unbalance.
Figure 3 shows the resulting load voltage over time, illustrating the resulting flicker phenomenon [
36]. The electrical parameters and simulation settings used for this study are detailed in
Table 1.
To obtain the simulation results shown in
Figure 3, fundamental circuit laws were applied to the electrical system comprising the photovoltaic generator, the load, and the electrical grid. The voltage across a single phase of the load is given by the following expression:
where
and
represent the resistance and inductance of the single-phase load, respectively, and
is the current through it. The current in the single-phase load is defined as:
where
and
are the currents in the first phase of the photovoltaic generator and the electrical grid, respectively. Applying Kirchhoff’s voltage law to the PV generator-load loop yields:
where
is the first-phase voltage of the photovoltaic generator,
is its current,
and
are the resistance and inductance of its first phase, respectively. Similarly, applying Kirchhoff’s voltage law to the electrical grid-load loop gives:
where
is the first-phase voltage of the electrical grid,
is its current,
and
are the resistance and inductance of the grid’s first phase.
Figure 3 demonstrates the onset of pronounced load voltage fluctuations; a phenomenon known as voltage flicker; immediately after the fault occurrence at
t = 0.5 s. Considering a three-phase system
with amplitude unbalance
and a modified pulsation
(
), its direct and quadrature
axis components are given by Equation (7):
In summary, the integration of renewable energy poses significant challenges to grid stability, particularly through power quality issues arising from operational imbalances. Although classical Fortescue theory offers a foundational framework for analyzing amplitude unbalance, its limitations are critically exposed under the dynamic conditions of modern power systems, where frequency deviations are increasingly prevalent. This gap necessitates an expanded analytical approach to accurately characterize system behavior during loss of synchronization.
The following section addresses this exact scenario by analyzing the direct impact of PV generator frequency variations on system performance. The results demonstrate that even a minimal deviation—as small as 1 Hz—between the generator frequency () and the grid frequency () propagates through the system, causing measurable oscillations in key operational parameters. This empirical evidence underscores the critical need for the modified theoretical framework introduced in this work.
3. PV Generator Frequency Variation Influence
To quantitatively assess the impact of frequency unbalance on system stability, a case study was conducted on the power system illustrated in
Figure 1. A random fault scenario was simulated, inducing a frequency deviation in the photovoltaic (PV) generator such that its operating frequency diverges from the grid frequency by
. This perturbation creates an asynchronous operating condition between the generator and the grid. Under these circumstances, the direct and quadrature
axis components of the load voltage,
[
37], which are typically constant in a perfectly synchronized steady state, exhibit significant oscillatory behavior. The resulting temporal evolution, depicted in
Figure 4, clearly demonstrates the destabilizing effect of frequency unbalance, manifesting as sustained oscillations that compromise power quality and highlight the insufficiency of conventional control strategies based solely on the classical Fortescue decomposition.
The positive-sequence components of the load voltage system , expressed in the reference frame, exhibit oscillations at the perturbation frequency of .
Furthermore, these signals are characterized by a secondary frequency component at 100 Hz, which corresponds to twice the grid frequency (2 × 50 Hz). It is important to note that this 100 Hz component is distinct from the classical “dual frequency” phenomenon [
38], as it is not a harmonic of the 1 Hz fundamental perturbation. Consequently, the temporal evolution of both the positive-sequence components
and the negative-sequence components
, referenced to the positive and negative synchronous reference frames (PSF and NSF), respectively [
39], are presented in
Figure 5 and
Figure 6.
To investigate the origins of the fluctuations observed in the positive sequence
and negative sequence
components, the mathematical expressions for the positive
, negative
, and zero
sequence components are derived with respect to the positive and negative synchronous reference frames (PSF, NSF). These formulations are presented in Equation 8 [
40].
Consequently, the
axis components for these sequences are formulated as shown in Equations (9) and (10).
The classical Fortescue theory is inadequate for identifying the origin of fluctuations in sequence components caused by PV generator frequency variations or grid faults. Under these dynamic conditions, the standard Fortescue operator
fails to provide an accurate sequence decomposition, as it is strictly limited to systems with amplitude perturbations. To overcome this limitation, we are introducing a new transformation operator, denoted as
. Developed from the principles in [
41], this modified operator is specifically designed to handle the challenges of variable-frequency environments.
In the system of Equations (11), the angular displacement is defined as
. Utilizing this new operator, the system of Equations (6) can be reformulated as follows:
To compensate for frequency variation, we introduce a phase correction factor,
. This leads to a new transformation matrix that replaces the one used in classical Fortescue theory. The modified matrix decomposes the system into three balanced subsystems: direct (positive-sequence), inverse (negative-sequence), and homopolar (zero-sequence). The new positive-sequence components are thus defined as follows:
Thus, expanding Equation (13) yields the following expressions for the new positive-sequence components:
Following an analogous procedure to that applied for the positive sequence, the negative-sequence components are derived as follows:
Thus, expanding Equation (15) yields the following expressions for the new negative-sequence components:
The zero-sequence components are similarly derived using the following matrix relationship:
After expansion, the new zero-sequence components are given by the system of Equation (18).
This section has established the core theoretical framework for handling frequency unbalance through the novel transformation operator
and its corresponding matrix. This development enables the decomposition of an unbalanced system into balanced positive-, negative-, and zero-sequence subsystems, specifically for scenarios involving frequency deviations from PV generator integration. With this analytical foundation in place, the subsequent
Section 4 will detail the computational model for determining the load voltage under these unbalanced conditions. This application will quantify the concrete impact of combined PV generator frequency and amplitude variations on electrical load operation.
4. Load Voltage Computing Method
To apply the modified Fortescue theory in practice, a precise method for calculating load voltage under imbalance conditions is required. This section presents a computational model for determining load voltage dynamics during simultaneous PV-grid frequency and amplitude variations.
The system topology is shown in
Figure 7, a detailed single-line diagram of the grid-connected PV system. The model comprises three primary components:
- ✓
The Photovoltaic (PV) Generator: Represented as an ideal three-phase voltage source, it is characterized by its generated currents
and voltages
. Its interface with the grid includes a line impedance [
42], modeled by a resistance
and an inductance
.
- ✓
The Electrical Load: A local three-phase load is connected at the Point of Common Coupling (PCC), drawing a current
at a voltage
. The load itself is modeled with its own impedance
[
43].
- ✓
The Electrical Grid: Modeled as a second ideal three-phase voltage source with currents
and voltages
, representing the main grid. Its connection to the PCC also includes a line impedance
[
42].
This configuration creates two primary current paths: one from the PV generator to the load, and another from the main grid to the load. The load voltage
is the critical variable at the PCC [
44], determined by the interaction of these two sources and the load impedance. The objective of the calculating method is to derive
considering the potential frequency deviation of the PV generator
and possible voltage amplitude sags [
45].
The calculation begins by defining the balanced three-phase voltage systems for both the PV generator and the electrical grid, as shown in Equations (19) and (20). To analyze these quantities in a rotating reference frame [
46] that simplifies the control and analysis, Park’s transformation [
47] is applied. The PV generator voltages are transformed using the Park matrix
referenced to the PV generator’s angle
as per Equation (21). Similarly, the grid voltages are transformed using
, referenced to the grid angle
, as per Equation (22). By applying Kirchhoff’s voltage laws to the loops formed between the PV generator, the grid, and the load, the dynamic equations for the system in the
reference frame are established. These equations, presented in Equations (24)–(26), form a complete set of differential equations that describe the system’s electrical dynamics. Solving this system of equations allows for the precise computation of the load voltage components
and
under the defined unbalanced operating conditions, thereby providing a direct link between the theoretical sequences derived in the previous section and their practical manifestation in the system’s voltages.
As shown in
Figure 7, the balanced voltages for the PV generator system are given by the following equations:
Similarly, the balanced voltages for the electrical grid are given by the system of Equation (20).
The PV generator voltages are transformed into the Park reference frame
using the Park matrix
, as defined in Equation (21). Similarly, the three-phase grid voltages
are transformed using the Park matrix
, given by Equation (22).
The Park matrix
, which is used in both Equations (21) and (22), is defined in Equation (23).
In the preceding equations, the angles are defined as
and
. Based on the interaction between the PV generator and the electrical load, the system dynamics are described by equation set (24).
Similarly, for the loop comprising the grid and the load, the
-axis components of the grid voltage and the load voltage are given by Equations (25) and (26), respectively.
Under normal operating conditions, in the absence of disturbances and with the PV generator connected to the grid supplying the load, the grid and the PV generator share the same frequency, as stated in Equation (27).
When a fault occurs, causing a frequency deviation
in the PV generator relative to the grid, Equation (27) is no longer valid and is replaced by Equation (28).
The system was simulated in MATLAB/Simulink with a PV generator frequency variation as defined by Equation (28). The results, shown in
Figure 8, demonstrate the emergence of a voltage flicker phenomenon in the load voltage, consistent with prior research [
48,
49,
50]. This flicker not only disrupts industrial equipment but also has documented adverse physiological effects on humans. Its severity is rigorously quantified according to standard EN 61000-4-15 [
51], which defines the methodologies for flicker measurement and assessment [
52].
Following the frequency deviation
, the
-axis components of the load voltages exhibit sustained oscillations. As illustrated in
Figure 9, these oscillations occur precisely at the deviation frequency
, demonstrating a direct propagation of the disturbance from the PV generator through the system to the load bus.
The second case study examines an amplitude imbalance, simulated by applying a 10% voltage drop to the first phase of the photovoltaic generator. This single-phase fault induces significant oscillations in the load voltage’s direct and quadrature components (
). As
Figure 10 shows, these oscillations occur at twice the grid frequency (
), a characteristic signature of unbalanced conditions in three-phase systems [
53]. This result demonstrates how a localized amplitude disturbance propagates through the system, manifesting as a second-harmonic oscillation in the synchronous reference frame [
54].
5. Strategy for Evaluating the Sequences of Load Voltage
Building upon the previous section’s method for calculating load voltage, this section provides a critical analysis of its sequence components. While the conventional Fortescue decomposition is effective for amplitude unbalance, it fails under frequency deviations. To address this, we develop a comprehensive strategy for evaluating load voltage sequences using the novel transformation operator and the modified symmetrical components theory. Our objective is to deconstruct the fluctuating load voltage into its positive, negative, and zero sequences under frequency unbalance. This decomposition precisely identifies the origins of the observed oscillations, thereby establishing a foundation for their effective mitigation through advanced control strategies.
Due to random disturbances, the frequency
of the electrical quantities exchanged between the PV generator and the load deviates from the grid frequency
by a value of
, as defined by the following relationship:
Under these conditions of frequency unbalance, the standard Fortescue theory is invalidated, as the amplitudes of the symmetrical sequences become oscillatory. To demonstrate this limitation, the positive sequence components of the load voltage
are evaluated using the conventional theory as follows [
55]:
Expanding Equation (30) yields the temporal expressions for the positive sequence components
, as given in Equation (31).
To address the limitations of the conventional Fortescue theory under frequency unbalance, the new transformation operator
is applied. This operator compensates for the frequency deviation, enabling a correct evaluation of the positive sequence components
of the load voltage system. The calculation, based on this modified approach, is defined by Equation (32).
Developing the expression in Equation (32) leads to a new temporal form for the positive sequence components
, which is fundamentally different from the result obtained using the standard Fortescue theory in Equation (31). Crucially, the frequency deviation term
cancels out in the derivation, resulting in the simplified and balanced expressions given in Equation (33). This elimination demonstrates the new operator’s ability to compensate for the frequency unbalance, producing a steady-state sequence.
The expressions for the positive sequence components derived in Equation (33) can be succinctly generalized into a single, condensed mathematical form presented in Equation (34). This formulation provides a unified representation for the three phases
, significantly streamlining subsequent analysis and implementation in control algorithms.
Applying the same methodological framework established for the positive sequence, the negative sequence components
of the load voltage system are now derived. This involves utilizing the new transformation operator
within a dedicated transformation matrix for the negative sequence, as defined in Equation (35).
The expansion of the transformation in Equation (35) yields the explicit time-domain expressions for the negative sequence load voltage components
. These temporal expressions, detailed in Equation (36), reveal the specific oscillatory behavior of the negative sequence under the influence of the frequency unbalance, completing the symmetrical component analysis initiated for the positive sequence.
For mathematical consistency and compactness, the negative-sequence components are also expressed in a generalized form. Analogous to the positive-sequence formulation, this provides a unified expression for the three phases:
Completing the symmetrical component analysis, the zero sequence components
of the load voltage system are derived. This is achieved by applying the transformation defined in Equation (38), which utilizes the new operator to extract the zero sequence under frequency unbalance conditions.
The zero-sequence component can be consolidated into the compact form of Equation (39). This generalized representation simplifies the expression considerably, yielding a concise and versatile formula suitable for computational analysis and control system design.
Having independently derived the positive
, negative
, and zero
sequence components using the modified theory, the final step is to reconstruct the original load voltage vector
. This reconstruction is performed by summing the respective sequences according to the fundamental principle expressed in Equation (40), thereby verifying the consistency and completeness of the decomposition process.
The final load voltage vector is synthesized from its individual sequence components using Equation (40). By substituting the compact forms of the positive-, negative-, and zero-sequence components (Equations (34), (37), and (39)) into this superposition, we arrive at the comprehensive result in Equations (41) and (42). This derivation culminates in a simplified expression that accurately represents the original unbalanced system.
To analyze the dynamic behavior of each symmetrical component, the load voltage sequences are transformed into their respective Park components within the Positive (PSF) and Negative (NSF) Synchronous Reference Frames.
Figure 11 illustrates this essential relationship, which forms the basis for the subsequent control strategy.
The positive sequence components of the load voltage
are transformed into the synchronous positive reference frame (PSF) using the Park transformation matrix defined in Equation (43). This operation projects the balanced positive sequence onto a rotating reference frame aligned with the grid voltage vector, converting the three-phase quantities into DC components
under ideal balanced conditions.
Substituting the explicit form of the Park transformation matrix
into Equation (43) yields the expanded expression given in Equation (44). This step provides the complete mathematical operation for converting the positive sequence voltages
into their direct and quadrature-axis components within the positive synchronous reference frame.
Substituting the time-domain expressions for the positive sequence voltages
into the transformation of Equation (44) allows for the analytical derivation of the dq-axis components
. The resulting expressions, given in Equation (45), reveal that under the defined conditions, the quadrature and zero-sequence components become zero, while the direct-axis component reflects the average amplitude of the three phases. This result confirms the effective transformation of the balanced positive sequence into a pure DC quantity in the synchronous frame.
The negative sequence voltage components
are transformed into the Negative Synchronous Reference Frame (NSF) using the Park transformation matrix defined in Equation (46). This specific transformation, denoted as
, is designed to effectively isolate and analyze the negative sequence by rotating in the direction opposite to the positive sequence, converting its oscillatory nature into simplified components.
Substituting the explicit form of the Negative Synchronous Reference Frame (NSF) Park transformation matrix
into the general framework of Equation (46) yields the expanded matrix Equation (47). This step provides the complete computational formulation required to project the negative sequence voltages
onto the dq-axes of the NSF, explicitly defining the trigonometric operations for this specific transformation.
Substituting the analytical expressions for the negative sequence voltages
into the transformation matrix of Equation (47) allows for the derivation of the corresponding
dq-axis components
in the NSF. The resulting expressions, given in Equation (48), demonstrate a key characteristic: the quadrature and zero-sequence components resolve to zero, while the direct-axis component
is a function of the voltage amplitudes. This confirms the successful isolation of the negative sequence into a simplified, non-oscillatory form within its dedicated reference frame.
The balanced dq-axis components, essential for robust control, are synthesized by subtracting the negative-sequence components in the NSF (Equation (48)) from the positive-sequence components in the PSF (Equation (45)). As defined in Equation (49), this operation yields balanced references (
). Crucially, this subtraction cancels the oscillatory terms caused by system unbalance, resulting in steady-state DC quantities that are immune to imbalances.
This analytical development successfully reconstructs perfectly balanced direct and quadrature-axis components for the voltage and current systems by strategically combining the positive and negative sequences within their respective synchronous reference frames (PSF and NSF). The specific balanced components, defined as and , constitute the principal result of this methodology. These components are impervious to the oscillations caused by system unbalance and will serve as the critical reference signals to be assigned within the advanced control strategies developed in a subsequent publication.
The core objective of this theoretical framework is to precisely identify the origin of fluctuations during unbalanced conditions. To achieve this, the analysis within the Positive and Negative Synchronous Frames (PSF and NSF) must account for the interaction between sequence components. This analysis is based on the following fundamental relationships:
The transformation of sequence components between the Positive and Negative Synchronous Reference Frames (PSF and NSF) is governed by a fundamental kinematic relationship. A component in one frame is converted to the other by accounting for the relative angular displacement of
, as defined by the following equations:
Therefore, by strategically combining sequence components from the PSF and NSF, we reconstruct a set of perfectly balanced voltage components. These synthesized components, defined in Equation (52), provide the essential balanced references (
) for the load voltage. As they are impervious to the imbalances studied here, they form the direct foundation for the control strategies developed in subsequent research.
The subscript denotes “balanced,” indicating components synthesized to be free from oscillatory effects caused by system unbalance. The resulting signals, and , are thus designated as critical reference signals. These references will be fed to the controller of the grid-interfacing PV inverter to ensure stable, high-quality power injection, even in the presence of upstream imbalances.
The Modified Fortescue Theory developed in this work provides the foundation for an advanced, robust control system for grid-connected PV inverters. The transition from theory to practice involves a structured implementation strategy where these balanced components serve as the critical input to an intelligent controller. The proposed implementation is architected as follows:
- ✓
Real-Time Signal Conditioning Block: A dedicated processing unit must be implemented in the inverter’s digital signal processor (DSP) to execute the modified symmetrical components transformation in real-time. This block will continuously sample the three-phase voltages at the Point of Common Coupling (PCC), compute the frequency deviation , and apply the new transformation operator to generate the perfectly balanced reference signals and , as defined by Equation (52). These signals, being constant in the synchronous reference frame even under grid imbalance, form the ideal setpoints for the control system.
- ✓
Controller Core: The balanced references and are fed into a Controller as the target setpoints. The controller is designed to regulate the inverter’s output currents by processing the error and its derivative between these balanced references and the measured inverter currents in the frame. The key advantage here is that the controller’s decision-making is based on clean, non-oscillatory error signals, allowing its rule base to operate effectively without being misled by the oscillatory components traditionally induced by grid imbalances.
- ✓
Actuation and Modulation Stage: The output of the controller (the commanded inverter voltage in the frame) is transformed back to the three-phase stationary frame using an inverse Park transformation. These voltage commands are then synthesized by the inverter’s power switches using a Space Vector Pulse Width Modulation (SVPWM) technique, renowned for its high DC-link utilization and low harmonic distortion.
In conclusion, this implementation strategy directly leverages the core contribution of this paper: the generation of imbalance-immune reference signals. By integrating these signals into a controller, the inverter is endowed with the capability to maintain stable, high-quality power injections and provide effective grid support, even in the presence of severe amplitude and frequency unbalances. This paves the way for the development of a new generation of highly resilient and intelligent grid-connected renewable energy systems.
7. Conclusions
This paper has established a novel theoretical framework by extending the classical Fortescue symmetrical components theory to address the critical challenge of frequency unbalance in modern electrical systems, a phenomenon increasingly prevalent with the high penetration of renewable energy sources like photovoltaics. The conventional Fortescue decomposition, while robust for amplitude unbalances, proves inadequate under frequency deviations, leading to oscillatory sequence components and compromised power quality, as demonstrated by the flicker phenomenon observed in our simulations.
The core contribution of this work is the introduction of a modified transformation theory, centered on the new operator , which successfully compensates for frequency variations. This modification allows for the derivation of balanced positive, negative, and zero sequence components even when the PV generator frequency deviates from the grid frequency . The culmination of this analytical effort is the synthesis of perfectly balanced direct and quadrature-axis voltage components, and , which are impervious to both amplitude and frequency imbalances. These components are not merely a theoretical result; they are specifically engineered to serve as the foundational reference signals for advanced control systems.
The immediate and practical application of this methodology lies in the control of the three-phase voltage source converter (VSC) that interfaces the PV generator with the power grid. The balanced references
and
can be directly integrated into a high-performance control loop. Specifically, these DC-like reference signals will be used as the setpoints for the inner current controllers in the synchronous reference frame. The output of these controllers, the required converter voltage vectors, will then be synthesized using the Space Vector Pulse Width Modulation (SVPWM) technique [
57].
The application of SVPWM is particularly suitable for this context due to its inherent advantages: it provides superior DC-link voltage utilization, generates lower total harmonic distortion (THD) compared to conventional sinusoidal PWM, and offers a digital implementation that is ideal for modern microprocessor-based controllers. By feeding the SVPWM algorithm with the voltage commands derived from the balanced references and , the inverter will generate switching signals that produce a three-phase voltage waveform which counteracts the effects of the source imbalance. This ensures that the power injected into the grid remains stable and of high quality, even during disturbances, thereby mitigating flicker and protecting sensitive equipment.
In conclusion, this paper provides the essential theoretical groundwork for a new generation of robust control strategies. The proposed modified Fortescue theory delivers the precise reference quantities needed to effectively decouple the converter operation from system imbalances. The subsequent research will detail the implementation of an intelligent control scheme, leveraging these balanced references within a fuzzy logic-based controller to dictate the SVPWM-driven inverter, ultimately assigning remarkable fault-tolerant capabilities to grid-connected PV systems and enhancing the stability and reliability of future power networks.