To verify the preceding analysis and the proposed protection principle, we referred to the relevant opinions in reference [
4] and constructed a 110 kV tie-grid-type power grid connection system, as shown in
Figure 6 [
30]. The 5 MW IIDG connected to bus N operates under a virtual synchronous generator (VSG) control scheme. An inertia time constant of 1 s and a damping coefficient of 0.002 p.u. are adopted, while the active- and reactive-power droop coefficients are set to 20 and 10, respectively. The model further incorporates low-voltage ride-through and current-limiting functions, and the converter output current is limited to 3.67 p.u. during faults. The photovoltaic source has a total capacity of 100 MW. The 0.38 kV/35 kV step-up transformer has a capacity of 120 MVA and a leakage reactance of 0.0676 pu. The busbar length is 200 m, with positive-sequence impedance
Z1 = 0.33 + j0.41 Ω/km, positive-sequence capacitive reactance to ground
XC1 = −j4.5473 × 10
5 Ω·km, zero-sequence impedance
Z0 = 1.04 + j1.25 Ω/km, and zero-sequence capacitive reactance to ground
X0 = −j7.9577 × 10
5 Ω·km. The local load consumes 15 MW active power and 1.5 Mvar reactive power. The 35 kV/110 kV step-up transformer has a capacity of 150 MVA, and its positive-sequence leakage reactance is 0.1 pu. The ab interconnection line is 20 km long, with positive-sequence impedance
Z1 = 0.01 + j0.41 Ω/km, positive-sequence capacitance-to-ground reactance
X′C1 = −j3.5886 × 10
8 Ω·km, zero-sequence impedance
Z0 = 0.33 + j1.32 Ω/km, and zero-sequence capacitance-to-ground reactance
X′C0 = −j5.1175 × 10
8 Ω·km. The grid-side equivalent impedance is
Zg = 0.020 + j14.137 Ω, and the grid source is modeled as an ideal 110 kV voltage source.
In the simulation model, a line fault is applied at 1 s. After fault inception, voltage and current data are collected from both line terminals, and the proposed criterion is used to protect line ab. The sampling frequency of the simulated voltage and current signals is 20 kHz.
5.1. Feature-Space Modeling
Because feature variations are relatively stable under normal operation and external faults, and because the fault features show strong clustering, a feature space can be constructed from normal-operation and external-fault samples. This space provides the basis for discriminating internal and external faults. Using the three-dimensional feature vector F = [S, Dx=y, Davg]T, the simulation samples are statistically analyzed and represented by an ellipsoidal envelope in three-dimensional feature space.
The sample set includes several external-fault conditions: single-phase-to-ground faults, phase-to-phase faults, phase-to-phase-to-ground faults, three-phase-to-ground faults, and three-phase faults. The transition resistance is varied from 50 Ω to 200 Ω, and 30 dB noise is superimposed to improve the adaptability of the feature-space construction to complex operating environments. The PCA-based rotating ellipsoid method described above is then used to determine the center, principal-axis directions, and semi-axis lengths of the feature space.
To construct the ellipsoidal feature space, 80 external-fault cases under different operating conditions were selected as the training samples. These cases include representative and extreme scenarios, such as metallic grounding faults at the protected line end and external faults with 30 dB noise. The ellipsoidal feature space is then obtained from the second-order sample moments of the selected
dF values, which determine the center, principal-axis directions, and semi-axis lengths of the ellipsoid. This construction ensures that the selected external-fault samples are enclosed within the ellipsoidal feature region. The resulting ellipsoidal feature space for external faults and normal operation is shown in
Figure 7. As can be seen from the graph, the values of the external fault samples are lower than 1.1, while the values of the internal fault samples are significantly higher than 1.1.
The ellipsoid center is μ = [0.7687, 0.0518, 1.6535], with semi-axes a = b = 0.6844 and c = 1.3889. The normal operation and external-fault samples are mainly distributed within or near this ellipsoidal feature space, indicating that the constructed space captures the statistical distribution of external operating conditions.
This feature space defines the discrimination criterion. If the feature vector of a test sample lies within the ellipsoidal space, namely dF < 1.1, the condition is classified as an external fault or normal operation. If the feature vector exceeds the feature-space boundary, namely dF > 1.1, the condition is classified as an internal fault.
5.2. Performance of the Protection Criterion
It should be noted that a total of 150 cases were generated, including 40 internal faults, 100 external faults, and 10 normal operating cases. The training and test subsets contain 100 and 50 cases, respectively. The training subset, containing only normal-operation and external-fault cases, was used to estimate the mean vector and covariance matrix of the ellipsoid. Internal-fault samples were not used in fitting the external-fault feature space. The independent test subset was then used only once for final performance evaluation.
Using the ellipsoidal feature space, internal-fault samples under different fault locations, transition resistances, fault types, noise levels, and CT-saturation conditions were tested to evaluate the effectiveness and robustness of the proposed method.
Single-phase-to-ground faults at different locations were simulated and compared.
Figure 8 shows the UICs and current waveforms at both line terminals for a single-phase-to-ground fault inside the protected zone with a transition resistance of 50 Ω. The fault is located 2 km from end a and 2 km from end b. In both cases, the change in line topology causes the fault components to be affected by the fault branch. The components fluctuate substantially, and the currents at ends a and b differ markedly from those observed during external faults and normal operation.
Table 1 lists the identification results for single-phase-to-ground faults at different locations along the 20 km line (2, 5, 10, and 18 km from measurement point a), confirming the effectiveness of the proposed method.
- 2.
Effect of transition resistance
For ground faults,
Table 2 lists the identification results for single-phase-to-ground faults at the midpoint of line ab with transition resistances of 0, 10, 100 and 300 Ω. In the event of an external fault, the fault location is set at a distance of 2 km from the b end of the protected line. As shown in the table, the size of the transition resistance has little impact on the calculation results of
dF. Even at high transition resistance, the current difference between the two line terminals remains substantial for faults inside the protected zone, and the proposed line protection method remains effective.
- 3.
Effect of fault type
Although single-phase-to-ground faults are the most common transmission-line fault type, other fault types must also be considered.
Table 3 lists the identification results for single-phase-to-ground, phase-to-phase, three-phase, phase-to-phase-to-ground, and three-phase-to-ground faults at the midpoint of line ab, with a transition resistance of 50 Ω. In the event of an external fault, the fault location is set at a distance of 2 km from the b end of the protected line. Across these fault types, the voltage–current characteristic curves of the faulted phase at both line terminals retain the internal-fault features, and the proposed protection method remains effective.
- 4.
Noise disturbance
To evaluate robustness under practical operating conditions, a single-phase-to-ground fault at the midpoint of line ab was simulated with a transition resistance of 50 Ω and noise levels of 20 and 30 dB.
Figure 9 shows the corresponding voltage and current response curves, and
Table 4 lists the identification results. In the event of an external fault, the fault location is set at a distance of 2 km from the b end of the protected line. The proposed protection scheme operates correctly under noisy conditions and shows good noise immunity.
If the noise level becomes sufficiently severe to affect the reliability of the protection decision, an appropriate filtering or denoising procedure may be incorporated before feature extraction. This limitation and the possible improvement have been clarified in the revised manuscript.
- 5.
CT saturation
To evaluate performance under CT saturation, an external single-phase-to-ground fault with a transition resistance of 50 Ω was simulated outside the protected zone. The rated transformation ratio of the CT was 1200/1 A, with a rated frequency of 50 Hz, an accuracy class of 5P20, a secondary winding resistance of 5 Ω, and a rated secondary burden of 15 VA. Since the rated secondary current was 1 A, the corresponding burden resistance was 15 Ω, resulting in a total secondary-loop resistance of 20 Ω. The knee-point voltage of the excitation characteristic was set to approximately 400 V. In the conventional saturation case, the primary fault current was 12 kA and the initial remanent flux was zero. The system X/R ratio was set to 20, corresponding to a decaying-DC time constant of approximately 63.7 ms at 50 Hz.
Figure 10 shows the voltage–current curve when slight CT saturation occurs on the a-side current transformer before correction.
Table 5 lists the identification results under several CT-saturation conditions. In the event of an external fault, the fault location is set at a distance of 2 km from the b end of the protected line. As can be seen from the table, after the CT saturation occurs, regardless of whether the current data has been corrected or not, the method proposed in this paper can reliably identify the fault.
- 6.
Composite power supply
To investigate the adaptability of the proposed criterion to changes in source-side composition, an additional grid-following inverter-based source was connected in parallel with the original grid-forming source. The grid-following inverter adopts PLL-based synchronization and constant P-Q control. It further incorporates low-voltage ride-through and current-limiting functions, and the converter output current is limited to 1.1 p.u. during faults. The grid-forming and grid-following sources have rated capacities of 100 MVA. Thus, the source-side system represents a mixed grid-forming/grid-following configuration.
As shown in
Table 6, for the composite power supply scenario, the calculated dF values are obtained when different fault locations, transition resistances, and fault types occur. In the event of an external fault, the fault location is set at a distance of 2 km from the b end of the protected line. It can be seen that even if the power characteristics of the source side and the control strategy are changed, the method proposed in this paper is still applicable.
5.3. Method Comparison
The conventional distance protection of line ab was tested using the simulation model in
Figure 6 and standard distance-protection setting principles. Four simulation cases were selected: the fourth fault condition in
Table 1, the seventh fault condition in
Table 2, and the third and fifth fault conditions in
Table 3. The results are shown in
Figure 11. In all four cases, the measured impedance did not enter the setting range, so conventional distance protection failed to operate. This failure is caused by the low fault current and weak current-transfer characteristics of inverter-based power sources, together with the influence of control strategies.
In
Table 7, the discrimination results obtained by the two methods under several scenarios are presented. Compared with this, the fault protection scheme proposed in this paper is extremely accurate and reliable. In contrast, the identification accuracy rate of the traditional distance protection method is only 42.9%, and it is more prone to misjudgment.
Meanwhile, this method will also be compared with the parameter identification method [
18] and the dual-end current protection method [
31,
32]. The fault condition is set as a single-phase grounding fault, the transition resistance is 0 Ω, and the fault location is 18/20 km. The calculation results are shown in
Table 8. From the perspective of computational complexity, this method is simpler and faster compared to the parameter identification methods, and it can correctly identify the fault under this condition.
Additionally, 50 independent Monte Carlo test cases were evaluated. Taking an internal fault as the positive class, the test results were TP = 40, FN = 0, FP = 0, and TN = 10, as shown in
Figure 12. The resulting dependability, security, sensitivity, false-operation rate, and overall accuracy were 100.0%, 100.0%, 100.0%, 0.0%, and 100.0%, respectively. Therefore, the proposed method is more suitable than conventional distance protection for grid-connection scenarios involving grid-forming inverters.