Figure 1.
Structure of three-core cable.
Figure 1.
Structure of three-core cable.
Figure 2.
Current distribution diagram of three-core cable.
Figure 2.
Current distribution diagram of three-core cable.
Figure 3.
Leakage current distribution of metal sheath.
Figure 3.
Leakage current distribution of metal sheath.
Figure 4.
Steps of DC component feature extraction.
Figure 4.
Steps of DC component feature extraction.
Figure 5.
Flow chart for calculation of polar characteristics.
Figure 5.
Flow chart for calculation of polar characteristics.
Figure 6.
Flow chart of comprehensive section location algorithm.
Figure 6.
Flow chart of comprehensive section location algorithm.
Figure 7.
Schematic diagram of cable arc fault.
Figure 7.
Schematic diagram of cable arc fault.
Figure 8.
PSCAD simulation model of 35 kV distribution network.
Figure 8.
PSCAD simulation model of 35 kV distribution network.
Figure 9.
Waveform comparison of zero-sequence and ground wire current of 10 Ω ground fault.
Figure 9.
Waveform comparison of zero-sequence and ground wire current of 10 Ω ground fault.
Figure 10.
Waveform comparison of zero-sequence and ground wire current of continuous arc fault.
Figure 10.
Waveform comparison of zero-sequence and ground wire current of continuous arc fault.
Figure 11.
Waveform comparison of zero-sequence and ground wire current of intermittent arc fault.
Figure 11.
Waveform comparison of zero-sequence and ground wire current of intermittent arc fault.
Figure 12.
Simulation results of grounding fault section based on transient polarity 10 Ω constant resistance under different fault angles.
Figure 12.
Simulation results of grounding fault section based on transient polarity 10 Ω constant resistance under different fault angles.
Figure 13.
Continuity (left) and intermittent (right) arc fault location results based on transient polarity under different fault angles.
Figure 13.
Continuity (left) and intermittent (right) arc fault location results based on transient polarity under different fault angles.
Figure 14.
Zero-sequence currents measured with low and high sampling frequencies.
Figure 14.
Zero-sequence currents measured with low and high sampling frequencies.
Figure 15.
Zero-sequence currents at local ends of L1, L2 and L3 with 20 dB noise when a fault occurs in L1.
Figure 15.
Zero-sequence currents at local ends of L1, L2 and L3 with 20 dB noise when a fault occurs in L1.
Figure 16.
Zero-sequence currents at local ends of L1, L2 and L3 with a fault in L1.
Figure 16.
Zero-sequence currents at local ends of L1, L2 and L3 with a fault in L1.
Figure 17.
RTDS-based hardware-in-the-loop platform.
Figure 17.
RTDS-based hardware-in-the-loop platform.
Figure 18.
Zero-sequence and grounding wire currents of all lines.
Figure 18.
Zero-sequence and grounding wire currents of all lines.
Figure 19.
Attenuation DC components in zero-sequence and grounding wire currents of all lines when the fault occurs in L4.
Figure 19.
Attenuation DC components in zero-sequence and grounding wire currents of all lines when the fault occurs in L4.
Table 1.
Maximum and minimum amplitudes of zero-sequence and grounding wire currents.
Table 1.
Maximum and minimum amplitudes of zero-sequence and grounding wire currents.
| Fault Type | IFDC_min | IHDC | IFGW_min | IHGW | R0DC | RGW |
|---|
| IAF | 5.01 A | 0.49 A | 8.68 | 0.32 | 10.22 | 27.1 |
| SF | 3.16 A | 0.28 A | 5.47 | 0.17 | 11.29 | 32.2 |
| CAF | 4.87 A | 0.46 A | 8.35 | 0.28 | 10.58 | 29.8 |
Table 2.
Grounding wire currents for faulty and healthy sections under various fault inception angles.
Table 2.
Grounding wire currents for faulty and healthy sections under various fault inception angles.
| Fault Angles | 0° | 30° | 45° | 60° | 90° |
|---|
| Grounding wire currents for healthy sections/A | 0.0382 | 0.2643 | 0.3951 | 0.4965 | 0.5969 |
| Grounding wire currents for faulty sections/A | 16.6886 | 14.9870 | 12.5055 | 9.2445 | 0.9972 |
Table 3.
Parameters of the cable.
Table 3.
Parameters of the cable.
| Location | Material | Thickness/mm | Resistivity /(Ω·m) | Relative Permeability /(H·m−1) |
|---|
| Core | Copper | 9.2 | 1.7241 × 10−8 | 1 |
| Insulation | XLPE | 10.5 | 1 × 1014 | 1 |
| Shielding | Copper | 0.2 | 1.7241 × 10−8 | 1 |
| Liner | PVC | 2.0 | 1 × 1014 | 1 |
| Armor | Steel | 0.8 | 1.71 × 10−7 | 300 |
| Sheath | PVC | 4.5 | 1 × 1014 | 1 |
Table 4.
Simulation results of 10 Ω constant resistance ground fault and section location.
Table 4.
Simulation results of 10 Ω constant resistance ground fault and section location.
| Fault Resistance | Line Number | Rdc | Kdc | Ldc |
|---|
| 10 Ω | L1 | 93.485 | 0.9843 | L4 |
| L4 | 95.966 | 0.0362 |
Table 5.
Based on attenuated DC component, ground fault simulation and section location results for 100 Ω and 1000 Ω constant resistance values.
Table 5.
Based on attenuated DC component, ground fault simulation and section location results for 100 Ω and 1000 Ω constant resistance values.
| Fault Resistance | Line Number | Rdc | Kdc | Ldc | Result |
|---|
| 100 Ω | L1 | 858.27 | 0.9982 | 0 | × |
| L4 | 861.27 | 0.0035 | 1 | √ |
| L7 | 1.2565 | 0.005 | −1 | × |
| L10 | 1.4098 | 0.0075 | −1 | × |
| 1000 Ω | L1 | 17.775 | 0.9187 | −1 | × |
| L4 | 20.306 | 0.1690 | −1 | × |
| L7 | 1.4836 | 0.0021 | −1 | × |
| L10 | 1.6418 | 0.003 | −1 | × |
Table 6.
Results of 1000 Ω constant resistance ground fault and section location.
Table 6.
Results of 1000 Ω constant resistance ground fault and section location.
| Fault Resistance | Line Number | Lpi/Lpj | Result |
|---|
| 1000 Ω | L1 | −49/−49 | L4 |
| L4 | −49/47 |
| L7 | 47/50 |
| L10 | 50/47 |
Table 7.
Continuous arc fault simulation and section location results.
Table 7.
Continuous arc fault simulation and section location results.
| Fault Resistance | Line Number | Rdc | Kdc | Ldc | Result |
|---|
| Continuous arc fault | L1 | 93.485 | 0.9843 | 0 | L4 |
| L4 | 95.966 | 0.0362 | 1 |
| L7 | 1.4766 | 0.0001 | −1 |
| L10 | 1.7683 | 0.0001 | −1 |
Table 8.
Intermittent arc fault simulation and section location results.
Table 8.
Intermittent arc fault simulation and section location results.
| Fault Resistance | Line Number | Rdc | Kdc | Ldc | Result |
|---|
| Continuous arc fault | L1 | 111.234 | 0.9889 | 0 | L4 |
| L4 | 113.603 | 0.0253 | 1 |
| L7 | 1.2211 | 0.0015 | −1 |
| L10 | 1.4633 | 0.0002 | −1 |
Table 9.
The fault section location results of 10 Ω constant resistance ground fault at 90° fault angle.
Table 9.
The fault section location results of 10 Ω constant resistance ground fault at 90° fault angle.
| Fault Angle | Line Number | Lpi/Lpj | Location Results |
|---|
| 90° | L1 | 56/54 | L4 |
| L4 | 54/−52 |
| L7 | −52/−57 |
| L10 | −57/−52 |
Table 10.
Location results of continuous and intermittent arc grounding fault at 90° fault angle.
Table 10.
Location results of continuous and intermittent arc grounding fault at 90° fault angle.
| Fault Angle | Fault Type | Line Number | Lpi/Lpj | Location Results |
|---|
| 90° | Continuity | L1 | −42/−43 | L4 |
| L4 | −43/57 |
| L7 | 57/33 |
| L10 | 33/57 |
| Intermittent | L1 | 52/51 | L4 |
| L4 | 51/−48 |
| L7 | −48/−54 |
Table 11.
Location results at different sampling rates.
Table 11.
Location results at different sampling rates.
| Fault Type | Sampling Rate | Fault Resistance | Accuracy |
|---|
| Continuity | 50 kHz | 100 Ω | 100% |
| Intermittent | 10 kHz | 100 Ω | 99% |
| 1.6 kHz | 100 Ω | 99% |
| 1.6 kHz | 1000 Ω | 96% |
| 50 kHz | 100 Ω | 100% |
| 10 kHz | 100 Ω | 100% |
| 1.6 kHz | 100 Ω | 98% |
| 1.6 kHz | 1000 Ω | 95% |
Table 12.
Information on the fault simulations with noise interference.
Table 12.
Information on the fault simulations with noise interference.
| Noise Level | Fault Types | Fault Line Number | Fault Distance | Number of Faults |
|---|
| SNR = 10 dB, 20 dB, 30 dB, 40 dB | SF, IAF, CAF | L1, L4 | 5%, 50%, 95% | 144 |
| L7, L10 |
Table 13.
Location results of fault simulations under noise conditions.
Table 13.
Location results of fault simulations under noise conditions.
| Noise Level | Min Accuracy | Max Accuracy | Average Accuracy |
|---|
| 10 dB, 20 dB, 30 dB, 40 dB | 95.1% | 97.9% | 96.4% |
Table 14.
Fault location results with different cable impedance errors.
Table 14.
Fault location results with different cable impedance errors.
| Cable Impedance | Cable Impedance Errors | Fault Line Number | Fault Type | Accuracy |
|---|
| 0.34 + j1.22 Ω/km | 0 | L1, L4 | SF, IAF, CAF | 96.1% |
| ±2% | 95.9% |
| ±3% | 95.8% |
| ±4% | 95.5% |
| ±5% | 95.4% |
Table 15.
Location results with load switching.
Table 15.
Location results with load switching.
| LST | Ratio of Load Switching | Location | Rate of Misidentification |
|---|
| Single-phase | 10%, 30%, 50% | L2, L5, L8 | 0% |
| Two-phase | 10%, 30%, 50% | L2, L5, L8 | 0% |
| Three-phase | 10%, 30%, 50% | L2, L5, L8 | 0% |
Table 16.
Location success rates and current amplitudes under high-impedance faults.
Table 16.
Location success rates and current amplitudes under high-impedance faults.
| Fault Resistance (Ω) | Zero-Sequence Amplitude (A) | Grounding Wire Amplitude (A) | Accuracy |
|---|
| 1000 | 3.12 | 5.86 | 95% |
| 2000 | 1.85 | 2.92 | 94% |
| 3000 | 0.88 | 0.96 | 91% |
| 4000 | 0.35 | 0.48 | 74% |
Table 17.
Key parameters and location results under complex fault scenarios.
Table 17.
Key parameters and location results under complex fault scenarios.
| Complex Scenario | Fault Stage | Line Number | Rdc | Kdc | Ldc | Result |
|---|
| Developing fault | Initial single-phase stage | L3 | 35.24 | 0.98 | 0 | L6 |
| L6 | 38.85 | 0.10 | 1 |
| L9 | 3.28 | 0.88 | −1 |
| Evolved phase-to-phase stage | L3 | 0.05 | 0.42 | −1 | failure |
| L6 | 0.08 | 2.61 | −1 |
| L9 | 0.03 | 0.04 | −1 |
| Multi-point fault | Single-phase fault at L4 and L7 | L1 | 45.36 | 0.88 | 0 | L4, L7 |
| L4 | 51.28 | 0.12 | 1 |
| L7 | 48.33 | 0.16 | 1 |
| Single-phase fault at L1 and L7 | L1 | 68.67 | 0.15 | 1 | L1, L7 |
| L4 | 61.53 | 0.92 | 0 |
| L7 | 65.46 | 0.13 | 1 |
Table 18.
Fault section location results based on DC attenuation component under different Rset.
Table 18.
Fault section location results based on DC attenuation component under different Rset.
| Rset | Line Number | Rdc | Kdc | [Ldc1, Ldc4, Ldc7, Ldc10] | Localization Results |
|---|
| 1 | L1, L4, L7, L10 | 87.562 | 0.9574 | [0, 1, 1, 1] | L4, L7, L10 |
| 10 | 85.703 | 0.0830 | [0, 1, −1, −1] | L4 |
| 100 | 1.378 | 0.0025 | [−1, −1, −1, −1] | —— |
| 1.718 | 0.003 |
Table 19.
Comparison between the proposed method and existing methods.
Table 19.
Comparison between the proposed method and existing methods.
| Method | Main Principle | Sampling Frequency | Extra Equipment | Applicability to Arc Faults | Accuracy |
|---|
| [6] | Impedance calculation | - | No | No | 78% |
| [8] | Active signal injection | - | Yes | No | 86% |
| [12] | Traveling wave magnitudes | 1 MHz | Yes | Yes | 97% |
| [19] | Multi-timescale transient signals | 6.4 kHz | No | No | 82% |
| [25] | Data-driven | - | No | No | 84% |
| Proposed method | DC attenuation & polarity | 50 kHz | No | Yes | 99% |
Table 20.
Comparison of the proposed method with existing methods.
Table 20.
Comparison of the proposed method with existing methods.
| Methods | Minimum Sampling Frequency | Fault Types | Transition Resistance | Applicability to Arc Faults | Noise Level |
|---|
| [19] | 6.4 kHz | SF | 10 Ω | No | —— |
| [28] | 4 kHz | SF, CAF, IAF | 2000 Ω | Yes | 30 dB |
| Proposed method | 1.6 kHz | SF, IAF, CAF | 2000 Ω | Yes | 40 dB |
Table 21.
Information on the fault experiments in the RTDS platform.
Table 21.
Information on the fault experiments in the RTDS platform.
| Fault Type | Fault Line Number | Fault Angle | Fault Distance | Number of Faults |
|---|
| SF, IAF, CAF | L2, L4 | 30°, 60°, 90° | 5%, 50%, 95% | 108 |
| L6, L9 |
Table 22.
Location results of fault experiments in the RTDS platform.
Table 22.
Location results of fault experiments in the RTDS platform.
| Fault Type | Min Accuracy | Max Accuracy | Average Accuracy |
|---|
| SF, IAF, CAF | 96.3% | 99.8% | 98.1% |