Next Article in Journal
Enhancing Seismic Response of Geo-Structures Through Systematic Shaking Table Testing: A Review
Next Article in Special Issue
Stability Analysis of Coastal Slopes Based on a Semi-Diurnal Tidal Water Level Variation Model
Previous Article in Journal / Special Issue
Seismic Response of an Irregular Pile-Supported Building on Liquefiable Sand: 2D Effective-Stress Analysis and Failure-Mode Assessment
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Experimental Analysis of Kerosene’s Contamination Effect on Unit Skin Friction of Pile in Clayey Soil

1
Civil Engineering Department, American University of Sharjah, Sharjah 26666, United Arab Emirates
2
Department of Civil Engineering, Faculty of Engineering, The Hashemite University, Zarqa 13133, Jordan
*
Author to whom correspondence should be addressed.
Buildings 2026, 16(6), 1111; https://doi.org/10.3390/buildings16061111
Submission received: 12 January 2026 / Revised: 26 February 2026 / Accepted: 3 March 2026 / Published: 11 March 2026

Abstract

This study presents an experimental investigation into the effects of subsurface kerosene contamination on the behavior of model piles in clay. Three instrument piles were placed in a compacted clay bed and tested in three saturations in a two-week period: natural moisture content, water-saturated, and kerosene-flooded. The tests performed on the piles were axial compression and pullout tests, supported by unconfined compression and consolidation tests for the clay. The saturating fluid controls the pile capacity, with the water-saturated condition producing the lowest ultimate capacity and the natural condition the highest. Moreover, it was shown that kerosene contamination significantly modified the mechanical characteristics of the clay, thus leading to an order of magnitude increase in the pre-consolidation pressure and a decrease in the compression index by 50% compared to the water-saturated cases. Under pullout loading, the unit skin friction varied linearly with depth, and failure consistently occurred at the pile–soil interface. This demonstrates the applicability of geotechnical design that considers hydrocarbon contamination to significantly decrease pile capacity and substantially change the consolidation characteristics of clayey soils.

1. Introduction

The current conflict between Russia and Ukraine as well as the Middle East conflicts show that energy assets such as refineries, pump stations, and all other related components are legitimate targets and prone to bombardment. These situations may lead to hydrocarbon spill and contamination. Pile foundation behavior is governed by a multitude of factors, including installation methods, geometry (embedment length and diameter), and soil-specific mechanisms like side load transfer, residual stresses, pore water pressure dissipation, and subsequent strength gain (Dourado and Deng (2025) [1], Debnath and Singh (2025) [2], Ibrahim and Karkush (2025) [3], Gananathan et al. 2025 [4], Akbarnezhad et al. 2025 [5], Potini et al. 2025 [6]). Although the migration of hydrocarbon contaminants (e.g., kerosene) from sources like storage containers has been studied from an environmental perspective, focusing on groundwater pollution and public health risks, their geotechnical impact has been largely overlooked. This research specifically addressed this gap by investigating and quantifying the effect of kerosene contamination on the ultimate strength capacity of pile foundations. Similar performance-based geotechnical evaluations are commonly verified using field evidence (e.g., Cone Penetration Test (CPT) comparisons before and after intervention) in infrastructure projects [7].
A growing body of geotechnical research has established that hydrocarbon contamination consistently degrades the mechanical properties of soil, with critical implications for infrastructure stability on contaminated sites. This trend was demonstrated in early studies, such as those by Evgin and Das (1992) [8], who found that motor oil contamination significantly reduced the friction angle of sands. More recent research confirmed this behavior, showing that crude oil contamination leads to decreased shear strength parameters, including friction angle and cohesion, in various soil types (Saeed et al. 2024 [9], Asadi et al. 2025 [10], Awarri and West (2025) [11]). Hydrocarbon contamination directly diminishes the bearing capacity of shallow foundations. Model tests show that even low oil contents (e.g., 4–6%) can drastically reduce the ultimate bearing capacity of strip footings on sand. Finite element analyses have predicted increased settlement of flexible footings on contaminated sand due to its reduced stiffness and increased compressibility. A particularly critical design challenge arises in rigid footings, where partial contamination (e.g., from one-sided spills) can induce asymmetric horizontal displacements and foundation rotation (Evgin and Das (1992) [8]).
The detrimental effects are equally pronounced in deep foundations. For PHC piles, contamination exacerbates skin friction reduction and settlement. Pile installation in contaminated soils worsens pore pressure generation and lateral displacement, leading to significant post-installation consolidation. The driving process itself can reduce the compression modulus of the surrounding soil by up to 30%, further increasing total settlement. The root cause of this behavior lies in the alteration of the soil fabric. As Tuncan and Pamukcu (1992) [12] observed in marine clays, crude oil contamination reduces specific surface area and cation exchange capacity, promoting an open, flocculated structure. This results in soil with higher water-holding capacity but critically lower strength, stiffness, and permeability.
The geotechnical impact of hydrocarbon contamination begins at a fundamental level. Advanced insights from techniques like X-ray diffraction (XRD) reveal that hydrocarbons interact with clay minerals, altering the soil fabric and reducing the interparticle forces. These microstructural changes manifest in altered index and compaction properties; for instance, crude oil contamination in CL and CH soils typically decreases the Atterberg limits and maximum dry density while increasing the optimum moisture content. Furthermore, the viscous hydrocarbons clog soil pores, leading to a decrease in permeability. This hindered drainage can significantly prolong consolidation times, a critical factor for predicting settlement rates on contaminated sites. While direct studies on PHC piles in hydrocarbon-contaminated soils are scarce, the altered soil properties suggest a severe impact on pile capacity. Analogous research indicates that contamination reduces both shaft friction and end-bearing capacity, primarily by altering the critical pile–soil interface properties. The problem is exacerbated during construction. The driving of PHC piles in contaminated soils generates excess pore pressures and lateral soil displacements, which further compromise the soil–pile interaction and can lead to increased post-installation settlement.
These combined effects pose significant design challenges. Engineers working on contaminated sites must account for reduced soil shear parameters, increased total settlement, and the risk of differential movements. To mitigate these risks, remediation techniques such as soil mixing or grouting may be necessary to improve the in situ ground conditions before foundation construction.
Previous studies showed that hydrocarbon contaminations of soils can degrade their mechanical properties, but these studies were mostly limited to element scale laboratory tests, such as direct shear or triaxial compression. These studies detailed changes in some strength parameters but did not analyze foundation performance firsthand. Therefore, the extent to which contamination directly modifies pile load settlement response, secant stiffness, and ultimate bearing capacity is not yet available from quantitative evidence. Low viscosity fuels especially, such as kerosene, have received comparatively little foundation scale assessment, despite exhibiting higher mobility and deeper penetration in fine grained soils. The novel contribution of the current work was to move the investigation from soil element behavior to foundation scale performance with a controllable and quantifiable assessment of the interaction of pile–soil under kerosene contamination. Specifically, this work includes the following: (i) generates complete load settlement curves from instrumented model pile compression tests in compacted clayey soil, allowing direct quantification of stiffness degradation and failure capacity; (ii) determines the reduction in ultimate pile bearing capacity at defined contamination levels and formulates predictive capacity reduction relationships suitable for engineering design; (iii) investigates the combined influence of hydrocarbon contamination and pile installation disturbance on load transfer mechanisms. This study contributes to moving the field beyond qualitative confirmation of strength loss to a mechanistic and predictive model of contaminated foundation systems by converting contamination effects into measurable performance indicators and design-oriented relationships.

2. Materials and Methods

2.1. Model Soil Container Beds

Static compression and pullout tests were performed on model piles installed in compacted clay within test containers measuring 55 × 55 × 60 cm. The clay was compacted to a target density and moisture content in eleven identical layers, each 5 cm thick, across three identical containers (Figure 1a). The container dimensions were selected to minimize boundary effects. Previous research indicated that for clayey soils, a container diameter six to eight times the pile diameter is sufficient to render lateral boundary effects insignificant (Mooney et al., 1985 [13]; Davie et al., 1978 [14]). In the present setup, the lateral container dimension is more than eleven times the pile diameter, ensuring minimal influence from the side boundaries. Furthermore, the distance from the pile tip to the container base is sufficient to reduce stress interaction to less than 5%, as per elastic theory (Boussinesq, 1885 [15]; Frazee, 2021 [16]), thereby making the bottom boundary effect also negligible.

2.2. Materials

The clayey soil was collected from the eastern region of Irbid city, located northwest of Jordan. To classify the natural soil, several laboratory tests were performed. Table 1 shows the results of these tests. The soil used in this study is classified as an inorganic clay of high plasticity, fat clay, (CH). The clay beds were prepared to a target dry density of 1.42 g/cm3. Testing on undisturbed samples extruded from the prepared beds using thin-walled Shelby tubes according to ASTM D1587(2015) [17] was tested to obtain the variation of fluid/water content, dry density, and undrained shear strength with depth. The undrained shear strength was conducted according to ASTM D2166 (2016) [18]. The undrained shear strength test was performed at a strain rate of 0.75 mm/min and with all specimens trimming to have an aspect ratio (L/D) equal to 2. The tests yielded an apparent cohesion ranging from 40 to 80 kPa based on the immersion fluid used on the test containers. Furthermore, the recompression index (Cr) was 0.071, the compression index (Cc) was 0.243, and the maximum past pressure (Pm) was 520 kPa.
The fluids used in the study were tap water and kerosene. Kerosene, a major class of petroleum product, is manufactured through the fractional distillation of crude oil. It is typically obtained in a volume yield of 5 to 20 percent, depending on the crude oil source, and boils within the range of 150 to 300 °C. The raw kerosene distillate undergoes various refinery treatments tailored to its intended applications, which can be categorized as follows: (a) fuels for heating and lighting (paraffin); (b) fuels for jet engines (Britannica, 2025) [19]; (c) materials used in the manufacture of products such as printing ink, insecticides, and metal degreasers. The kerosene used in this study was a standard heating and lighting grade. It had a specific gravity of 0.790 and a hydrocarbon composition (by volume) of 58.0% paraffins, 33.0% naphthenes, and 9.0% aromatics. The selected kerosene contamination levels were chosen to represent practical conditions encountered in fuel leakage and storage tank spill scenarios. Previous field and laboratory studies reported hydrocarbon contents ranging from light surface contamination to heavily saturated conditions. Accordingly, the adopted contamination range was intended to cover low to severe exposure levels and to provide bounding cases for engineering assessment rather than a single site-specific concentration. This allows the results to be interpreted conservatively for the preliminary design of piles installed in contaminated ground.
Table 1. Physical properties for used soil.
Table 1. Physical properties for used soil.
PropertyMagnitudeStandard Used
Natural water content,30.00ASTM D4318 (2017) [20]
Liquid limit,67.00ASTM D4318 (2017) [20]
Plastic limit,32.00ASTM D4318 (2017) [20]
Plasticity index,35.00ASTM D4318 (2017) [20]
Specific gravity2.71ASTM D854 (2023) [21]
Maximum dry density (gm/cm3)1.46ASTM D698 (2012) [22]
Optimum water content,23.65ASTM D698 (2012) [22]
GradationClayey size,70.00ASTM D4318 (2017) [20]
Silt size,18.00ASTM D4318 (2017) [20]
Sand size,12.00ASTM D4318 (2017) [20]
Gravel size0.00ASTM D4318 (2017) [20]
Classification according to Unified Soil classification System (USCS)CHASTM D2487 (2017) [23]

2.3. Model Piles

The tests were conducted using three identical galvanized steel pipe piles with an outer diameter of 4.3 cm and an embedment depth of 35 cm. Each pile was welded to a pile cap, with the combined unit weighing 95 N. To measure internal strain, three electrical resistance strain guages (Micro Measurements Model CEA-06-250UW-120, 120 Ω), from Measurements Group Inc., Raleigh, NC, USA, were mounted at different locations along the embedded length of each pile, as illustrated in Figure 1b. The strain guages were installed within grooves machined on the pile’s outer surface. Each groove had a depth of 1.5 mm and a surface area of approximately 1.8 by 3.8 cm.
The model piles were installed using the static jacking method. Each pile was jacked into the compacted clay bed to an embedment depth of 35 cm at a constant penetration rate of 0.1 mm/s. The installation was accomplished using a 200 mm stroke actuator. A temporary plate, functionally similar to the final pile cap, was bolted to the pile head to interface with the jack. Three days after installation, an undisturbed soil specimen was extracted for benchmarking. Subsequently, two of the three piles were subjected to a 30-day flooding period: one with kerosene and the other with water. To maintain consistent flooding conditions, the fluid layer was visually monitored throughout testing and replenished when necessary to preserve the 2 cm depth. All tests were conducted indoors under controlled laboratory temperature with short exposure durations, which minimized evaporation effects. No noticeable reduction in fluid level was observed during individual tests. Therefore, evaporation was not expected to influence the results. Following the flooding and subsequent resting phase, all model piles were subjected to compression tests to determine their load capacity.

2.4. Equipment and Procedures

The pile tests were conducted using a Dartec Universal Testing Machine, Oldham, Greater Manchester, UK, with a maximum capacity of 100 kN (Figure 2). The setup comprised three main units (1) Loading Frame: A robust floor and portal frame system provide a large, adaptable testing area. An adjustable crosshead, bolted to the top of the columns, supports a central, double-acting, servo-controlled actuator. A load cell and a Linear Variable Differential Transformer (LVDT) are attached to the actuator’s end to measure force and displacement, respectively. The portal frames can be spaced up to 5 m apart. (2) Hydraulic Power Unit: This unit supplies hydraulic pressure to the actuator. (3) Control Unit: This unit allows for manual control of the system and includes a computer with manufacturer-supplied software for automated test execution and data acquisition. As shown in Figure 2a,b, pile displacement was measured using two LVDTs mounted on a separate reference frame on opposite sides of the pile. Strain guage readings were acquired using a switch and balance unit (SB-10) and a strain indicator. Compression tests were performed using a 10 kN load cell. To ensure the repeatability of the results, each test configuration was replicated three times. The experimental methodology is shown in Figure 3 as a flow chart.

3. Results

3.1. Soil Conditions for Pile Model

Three identical clay beds were prepared using the method previously described. The testing and sampling strategy for each bed was as follows:
For the first clay bed (Benchmark), undisturbed soil specimens were extracted three days after pile installation. Two types of samples were taken: smaller specimens (38 mm diameter) for unconfined compression tests to determine the undrained shear strength, and larger specimens (76.2 mm diameter) for consolidation tests. A permanent 2 cm layer of the corresponding fluid (water or kerosene) was maintained atop the second and third clay beds to simulate flooded conditions, starting one day post-installation. Figure 4 shows the variation of water content, dry density, and undrained strength with depth. The geotechnical properties of the soil, namely fluid content, dry density, and undrained shear strength (Cu), exhibit distinct profiles that are highly dependent on pore fluid conditions.
Regarding fluid content, benchmark beds show an increase from 20% at the surface to 25% at a depth of 82% of the pile length. In contrast, flooded samples show a decreasing trend with depth. The water-flooded beds decreased from a higher initial fluid content of 47% to 43%, while the kerosene-flooded samples decreased from 42% to 36% over the same interval. A corresponding divergence is observed in the dry density profiles. Both benchmark and water-flooded beds displayed a minor density increase from 1.40 g/cm3 to 1.42 g/cm3. The kerosene-flooded beds, however, began with a significantly lower surface density of 1.35 g/cm3 but underwent a substantial increase to 1.45 g/cm3 at the same depth.
The undrained shear strength (Cu) profiles further highlight the impact of fluid flooding. The benchmark beds showed a strength increase from 70 kPa to 80 kPa. The water-flooded beds started with a pronounced lower strength of 30 kPa at the surface, which subsequently recovered to 65 kPa. Similarly, the kerosene-flooded sample exhibited an increase in strength from 35 kPa to 50 kPa with depth.
Soil surface heave was monitored using two dial gauges positioned 12.5 cm from the pile on opposite sides. The benchmark soil beds and kerosene-flooded soil beds exhibit no heave or swell at all while the water-flooded soil beds give percent swell in the order of 13.8% as shown in Figure 5.
To comprehensively evaluate the soil bed conditions, a series of one-dimensional consolidation tests was conducted in accordance with ASTM D2435/D2435M-11 [24]. The results, as shown in Figure 6, are summarized as outlined. (a) As-Prepared Samples: The baseline specimens yielded a compression index (Cc) of 0.243, a recompression index (Cr) of 0.071, and a maximum past pressure (Pm) of 520 kPa. (b) Water-Flooded Samples: Inundation with water increased the soil’s compressibility, resulting in a higher Cc of 0.29 and a reduced Pm of 290 kPa. (c) Kerosene-Flooded Bed: A comparative analysis of two undisturbed specimens revealed the profound influence of pore fluid chemistry. The kerosene-saturated sample exhibited a low Cc of 0.23 and a very high Pm of 1000 kPa. In contrast, a companion sample saturated with water was highly compressible (Cc = 0.44) and exhibited a low Pm of 100 kPa. This stark contrast is attributed to the non-polar nature of kerosene (Fan and Zhong (2022) [25], Caffiero et al. 2024 [26], Wang et al. 2024 [27], Tang et al. 2025 [28]), which enhances interparticle electrochemical attractive forces. This strengthened soil skeleton is manifested as a substantial increase in the apparent pre-consolidation pressure.

3.2. Test Results of Axial Compression Loading

To evaluate the ultimate compressive capacity of test piles when a clear failure load is not evident from the load–settlement curve, several analytical methods are employed, predicated on the pile’s elastic properties, geometry, and the curve’s shape. This study applied four prominent methods from the literature. The Swedish Pile Commission Method (Hansen, 1963 [29], Tang et al. 2025 [30]) uses a 90% criterion, defining failure as the load causing twice the settlement observed at 90% of that load, based on a hyperbolic curve assumption. Mazurkiewicz’s Method (1972) [31] is a graphical technique where the failure load is identified as the convergence point on the load axis of a series of 45° lines projected from the intersections of arbitrary settlement lines with the load–settlement curve. Conversely, the Tangent Method (Prakash and Sharma 1991 [32], Eslami et al. 2025 [33]) determines capacity from the intersection of tangents drawn to the initial and final portions of the curve. Finally, the American Association of State Highway and Transportation Officials (AASHTO, BDS (2010) [34]) Method defines the ultimate load as that corresponding to a net settlement of 6.35 mm.
The ultimate bearing capacity was interpreted from the load–settlement curves using four established methods: Swedish Pile Commission, Mazurkiewicz, Tangent, and AASHTO. These approaches were selected because they are widely adopted in practice and are specifically developed for static compression pile load tests based on load–displacement behavior. Each method represents a different failure criterion, including settlement-based, graphical extrapolation, stiffness-change, and code-recommended interpretations. Employing multiple methods enables cross-validation of the results and reduces dependence on a single interpretation technique. Differences among the predicted capacities are expected, as each method defines the ultimate state differently (e.g., service ability-based versus theoretical failure), and similar variations are commonly reported in the pile load test literature. Therefore, the comparison enhances reliability rather than introducing uncertainty.
The axial compressive capacity of the model piles was investigated through constant rate of displacement (CRD) tests at 0.1 mm/s. Three distinct interface conditions were examined: non-flooded (dry), flooded with kerosene, and flooded with water. A summary of the ultimate load capacities is presented in Table 2, while the corresponding pile head displacements at failure for each trial are summarized in Table 3. Figure 7 provides a representative comparison from the first trial, clearly demonstrating that the pile capacity is highly dependent on the interface fluid. The non-flooded pile achieved the maximum load, with the kerosene-flooded condition exhibiting a higher capacity than the water-flooded condition. Examination of the load–displacement behavior reveals that all three curves are qualitatively similar, exhibiting a ductile failure mode without a sharp peak. The ultimate failure state was reached at displacements ranging from 2.9 mm to 6.0 mm across all tests, suggesting rather that the interface fluid primarily affects the shear strength.

3.3. Pullout Test Results

The pullout capacity of the model piles was assessed using constant rate of displacement (CRD) tests at 0.1 mm/s, conducted 24 h after the initial compression tests. The three interface conditions—non-flooded (dry), kerosene-flooded, and water-flooded—were evaluated. As summarized in Table 4 and illustrated in Figure 8, the results indicate a significant influence of the interface fluid on the ultimate pullout load. The load–displacement curves for all conditions exhibited a similar shape, featuring a sharp, distinct peak at failure. The corresponding displacements at failure ranged from 0.03 to 2.40 mm, a range consistent with previous model pile tests in clayey soils (Mochtar et al., 1988 [35], Siemaszko (2024) [36]).
To improve generality and facilitate comparison, the pullout results are also interpreted using normalized (dimensionless) parameters relative to the uncontaminated condition. Specifically, the ultimate pullout load is presented as a capacity ratio (Qpc/Qp0) and the displacement at peak load is expressed as a settlement ratio s/D, where D is the pile diameter. This normalization reduces scale dependency and highlights the relative degradation trends attributable to the flooding fluid, thereby improving the transferability of the findings to other pile dimensions and similar clayey soils.

4. Discussion

4.1. Analysis of Skin Friction and Adhesion Factors

The average unit skin friction fs under pullout loading can be derived from the force equilibrium equation:
f s = Q u l t W π B 0 L
where fs = average unit skin friction, Qult = ultimate pullout force, w = weight of the pile B0 = pile diameter and L = embedment length of the pile.
For the different test conditions, the ultimate average unit skin friction ranged from 7.1 kPa to 35.6 kPa. The adhesion factor α, defined as the ratio (α = fs/Cu), was derived from these values. Table 4 presents the calculated average unit skin friction to compare the influence of the soaking fluid. The data show that the non-flooded model exhibits a higher adhesion factor than the fluid-flooded models. The calculated adhesion factors (α) for the non-flooded piles fall within the range established by Tomlinson (1971) [37], Tomlinson, and Woodward (2007) [38]. In contrast, the values for the kerosene-flooded model lie outside the typical ranges for driven piles summarized by Poulos and Davis (1980) [39]. The average adhesion factor in this study was 0.134, which is lower than the value of 0.2 reported by Das and Seeley (1982) [40] and Basack et al. 2025 [41] for model piles in saturated soil with Cu < 27 kPa. This reduction is attributed to the prior mobilization of soil shear strength during the compression tests.

4.2. Influence of Fluid Type on Soil–Pile Adhesion

The water-flooded model yielded the lowest unit skin friction. This can be explained by the fluid’s properties: water is a wetting fluid adsorbed by clay particles due to osmotic effects (Bear, 2013 [42], Tong et al. 2025 [43]). This adsorption causes the clay to heave, increasing the diffuse double-layer thickness between particles. The resulting decrease in soil density and shear strength consequently reduces the soil–pile adhesion.
Kerosene, being a non-wetting, non-polar fluid, cannot enter the basal spacing of the clay and thus has a less detrimental effect than water. However, both fluids reduce adhesion compared to the non-flooded condition by diminishing the apparent cohesion. In the non-flooded soil, air-filled voids create surface tension between adsorbed water and air, increasing the effective stress and apparent cohesion (Al Hattamleh et al. 2021 [44], Abu-Agolah et al. 2025 [45]). This enhances the soil–pile adhesion. When either water or kerosene floods the soil, they displace the air, reducing this surface tension and the associated cohesive and adhesive strength.
Kerosene was selected as the contaminant medium because its physicochemical properties differ from heavier hydrocarbons such as diesel and crude oil in ways that directly influence soil–pile interaction. Compared with these media, kerosene has lower viscosity, higher mobility, and greater penetration capacity within fine-grained soils. As a result, it can more readily replace pore water, reduce matric suction, and introduce lubrication at particle contacts and at the pile–soil interface, potentially leading to more pronounced reductions in stiffness and bearing capacity. In contrast, heavier hydrocarbons typically exhibit slower migration and partial coating effects, resulting in different or less severe mechanical responses. Therefore, the results of this study are most directly applicable to light fuel contamination scenarios (e.g., aviation fuel or kerosene spills), while also providing conservative insight into general hydrocarbon contamination effects. This clarification defines the applicability boundaries of the findings without limiting their broader engineering relevance.

4.3. Load Transfer

It should be emphasized that the pile–soil interface behavior was not evaluated solely using average skin friction values. The strain-gauge instrumentation enabled measurement of internal axial load along the pile shaft, from which local load transfer and the distribution of unit skin friction with depth were derived. These profiles provide a direct characterization of interface shear stress mobilization and failure progression along the pile. The observed reduction and redistribution of local skin friction under kerosene flooding indicate a weakened interface and lubrication effect, confirming that contamination alters the shear transfer mechanism rather than only reducing the global capacity. Therefore, the interface response was assessed at both global (average capacity) and local (depth-dependent shear stress) scales.
Each model pile underwent axial compression calibration before installation. In this procedure, the piles were fixed and subjected to a maximum axial load of 10 kN. The corresponding strain gauge readings were plotted to generate calibration curves (see Figure 9 for an example), which were later used to derive the load transfer along the pile shaft. This pre-test calibration also served to identify and mitigate stress concentrations and prevent buckling during the main testing phase.
Figure 10 presents the variation of internal axial load with depth during the pullout test. The distribution shows that the load is maximum at the clay surface and attenuates with increasing depth. These profiles were approximated using second- or third-degree polynomials to facilitate the calculation of local unit skin friction.
Figure 11 shows the calculated local unit skin friction, which is low at the surface and increases linearly with depth during pullout. This initial low friction is due to a reduced soil–pile contact area near the surface [46], for both the dry and kerosene-flooded pile models, and the presence of a very weak soil layer at the surface for the water-flooded model.
From an engineering perspective, the results are intended to provide reduction trends and design guidance rather than direct prediction of absolute pile capacity. The experimentally derived capacity degradation ratios and load–settlement behavior can be used as modification factors or preliminary assessment tools when evaluating pile performance in contaminated sites. In practice, designers may combine these reduction factors with conventional capacity calculations to account for potential contamination-induced losses.
Moreover, the mechanisms discussed in this study are interpreted primarily from macroscopic mechanical behavior (load–settlement response, strength, and compressibility changes). Although advanced microstructural techniques such as SEM or XRD could provide direct visualization of particle arrangement and mineralogical alterations, the present work focuses on foundation-scale performance and engineering response rather than detailed physicochemical characterization. The observed degradation trends are consistent with mechanisms widely reported in the literature, including pore fluid replacement, reduction of matric suction, and lubrication at particle contacts and at the pile–soil interface. Therefore, the interpretation is supported by established soil mechanics principles, while microstructural investigation is considered a valuable direction for future research.
In Table 5, a comparative summary of representative studies addressing hydrocarbon contamination and foundation behavior is provided to clearly embed the contribution of the current investigation into prior literature. Although existing studies on index properties, shear strength degradation, or shallow foundation response have been limited, very minimal studies have explored pile behavior directly in controlled contamination conditions. The joint analysis of axial compression, pullout capacity, soil mechanical characterization, and the instrumented load transfer along the pile shaft has remained largely unexplored. This is why the study builds on existing insights from testing at a material level to testing at foundation scale performance.

4.4. Strengths, Weaknesses, Risks, and Limitations

One of the strengths of the current study is the controlled experimental design, the integration of instrumented model piles, and the coupling of mechanical soil characterization with the direct testing of pile load. The strain gauge readings allow for depth dependent load transfer measurement and thus give an insight into the interface mechanism as opposed to only viewing global capacity values. The comparison of the difference between the natural, water-saturated, and kerosene-flooded states facilitated the separation of the specific influence of pore fluid type on pile behavior. However, few limitations need to be acknowledged. Experiments were conducted at model scale, and there may be an effect of scale in stress distribution and failure mechanisms compared with full scale field conditions. The duration of contamination was short and may not allow the long-term assessment of physicochemical aging or biodegradation effects. Only one clay type and one hydrocarbon medium were analyzed, which imposes limitations on generalizability to other soil mineralogizes or contaminant compositions. Potential risks and uncertainties include inhomogeneous contaminant distribution in the soil bed, boundary effects from the testing container, and variability across local interface conditions. The above factors may result in scatter in the measured capacities and need to be considered when attempting to extrapolate results to practice. Notwithstanding these restrictions, the observed findings invariably indicated that hydrocarbon contamination causes a change in soil structure, decreases its adhesion, and changes the load transfer. Accordingly, the results offer compelling qualitative and semi-quantitative lessons for engineering in contaminated conditions.

4.5. Practical Implementation and Future Research Prospects

In this paper, the experimental results have a direct practical bearing on foundation design in hydrocarbon contaminated clay deposits. The quantified reductions in unit skin friction, adhesion factor, and ultimate pile capacity can be included in regular design practice, by using adjustment or reduction factors for classical static capacity values. At sites where light fuel pollution is suspected, i.e., storage facilities, transport corridors, and industrial sites, the resulting degradation trends may be applied for a preliminary risk assessment and conservative designing of pile foundations. This approach allows engineers the ability to accommodate contamination impacts without requiring extensive full-scale testing at each site. Although the processes for conducting the experiments have been applied to clay collected in Irbid, Jordan, for example, they are not site specific; the underlying mechanisms presented in this work are based on the basic principles of soil mechanics such as the replacement of pore fluid, abatement of matric suction, application of lubrication to the particle contact points, and the weakening of pile–soil interface as a result. These processes are the dominant ones for fine, cohesive soil all over the globe. These trends and normalized parameters of adhesion factor reduction and capacity degradation ratios can thus be extrapolated fairly readily to similar clayey soils in other regions, given that differences in mineralogy, plasticity, and contaminant type are well accounted for. It is suggested that local calibration with representative soil properties be used for wider implementation. There are, however, a few opportunities for scientific advancement in this area of research. Future work could be used to test model-scale observation results on a larger scale to confirm effects, to examine various soil species and mineral deposits, to assess heavier hydrocarbons and mixed contaminants, and to examine long-term aging and chemical interaction effects. By incorporating microstructural approaches, such as SEM or XRD investigation, there could be further visibility into the particle-scale modifications stimulated by contamination. In addition, numerical models and combined hydro-mechanical simulations may be able to generalize the results at the experimental scales and to more complicated boundary cases. In the end, the present study provides a mechanistic insight into contamination-induced degradation of pile performance characterization and quantity assessment, as well as an immediate engineering guideline, but also serves as the basis for continuing scientific progress towards the design of foundations in contaminated ground.

5. Conclusions

This study experimentally investigated the impact of subsurface kerosene contamination on the soil–pile interaction in clayey soil. The research involved testing three instrumented model piles (4.3 cm diameter, 35 cm depth) installed in a compacted clay bed under three distinct conditions: natural, water-saturated, and kerosene-flooded. A comprehensive testing program, including compression/pullout tests on the piles and unconfined compression/consolidation tests on the soil, was conducted over a two-week saturation period. The following key conclusions were drawn:
  • The ultimate compressive and pullout capacities of the piles were highly dependent on the pore fluid. The water-saturated condition resulted in the lowest capacity, while the natural (unsaturated) condition exhibited the highest. This implies that for piles in permanently saturated clays, the detrimental effect of water is the primary design concern. However, in partially saturated soils, the potential presence of hydrocarbon contaminants like kerosene necessitates a higher factor of safety to mitigate their strength-reducing effects.
  • Consolidation tests revealed that kerosene fundamentally changes the clay’s properties, leading to particle aggregation. When the pore fluid was kerosene, the pre-consolidation pressure increased more than tenfold, and the compression index decreased by approximately 50% compared to the water-saturated condition.
  • During pullout tests, the local unit skin friction demonstrated a linear relationship with depth across all tested conditions.
  • Visual inspection of the pile shafts after extraction confirmed that failure occurred at the pile–soil interface, as evidenced by the shiny, smooth surface of the adjacent clay.
This study provides a controlled experimental investigation of the response of instrumented model piles installed in compacted clay subjected to natural, water-flooded, and kerosene-flooded conditions. The results demonstrate that the saturating fluid governs pile performance and clay compressibility, with clear changes observed in load–settlement behavior, ultimate capacity, and interface response under contaminated conditions. It should also be noted that the experimental program was conducted using clay obtained from a single site; therefore, the absolute capacities reported are site-specific and the findings should be applied primarily as normalized degradation trends and design-oriented reduction guidance for clays with comparable index properties and compaction state. Although microstructural characterization and numerical or theoretical modelling could further explain particle-scale mechanisms and extend the results to field-scale parametric studies, these approaches are beyond the scope of the current work. Future research may integrate the experimentally derived capacity and stiffness degradation relationships into numerical or analytical frameworks and examine additional clay types to further generalize the conclusions [48].

Author Contributions

Conceptualization, M.A. and O.A.H.; methodology, O.A.H.; software, A.K.; validation, MA., O.A.H. and A.K.; formal analysis, O.A.H.; investigation, O.A.H.; resources, M.A.; data curation, A.K.; writing—original draft preparation, M.A.; writing—review and editing, A.K.; visualization, A.K.; supervision, M.A.; project administration, M.A.; funding acquisition, M.A. All authors have read and agreed to the published version of the manuscript.

Funding

This research was supported by the American University of Sharjah (AUS) through the Open Access Program (OAP).

Data Availability Statement

All data are available from the corresponding author upon reasonable request.

Acknowledgments

The authors would like to acknowledge the support and contributions of the American University of Sharjah (AUS) and their Civil Engineering Department staff. The work in this paper was supported, in part, by the Open Access Program from the American University of Sharjah. This paper represents the opinions of the authors and does not represent the opinions or position of the American University of Sharjah.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Dourado, J.B.D.O.L.; Deng, L. Field investigation of steel screw micropiles under axial loads in cohesionless and cohesive soils. Soils Found. 2025, 65, 101705. [Google Scholar] [CrossRef]
  2. Debnath, A.; Singh, V.P. Bearing Capacity Factors of Helical Piles Embedded in Cohesive Soils. Indian Geotech. J. 2025, 55, 500–511. [Google Scholar] [CrossRef]
  3. Ibrahim, I.W.; Karkush, M. The Axial Uplift Capacity of Screw Piles: A Review. J. Eng. 2025, 31, 105–128. [Google Scholar] [CrossRef]
  4. Gananathan, H.; Disfani, M.; Tian, Y.; Narsilio, G. A new pile-soil interface and its application in battered mini piles under monotonic lateral load in cohesive soil. Comput. Geotech. 2025, 178, 106922. [Google Scholar] [CrossRef]
  5. Akbarnezhad, S.; Ganjian, N.; Eslami, A.; Fadaee, M. Load–displacement behavior of helical conical piles in loess under dry and saturated installations. Geotech. Geol. Eng. 2025, 43, 301. [Google Scholar] [CrossRef]
  6. Potini, F.; Viggiani, G.M.; Conti, R. Interaction domains of pile groups in cohesive soils under generalised loads. Géotechnique 2025, 75, 1375–1387. [Google Scholar] [CrossRef]
  7. Khalil, A.; Khan, Z.; Attom, M.; Khalafalla, O. Evaluation of Ground Improvement with Dynamic Replacement and Rapid Impact Compaction of an Artificial Island in the UAE—A Case Study. In Proceedings of the Geo-Congress 2024: Geo-Sustainability and Resilience, Vancouver, Canada, 25–28 February 2024; American Society of Civil Engineers (ASCE): Reston, VA, USA, 2024; pp. 121–130. [Google Scholar] [CrossRef]
  8. Evgin, E.; Das, B.M. Mechanical behavior of an oil contaminated sand. In Environmental Geotechnology; Usmen, M.A., Acar, Y.B., Eds.; Balkema: Rotterdam, The Netherlands, 1992. [Google Scholar]
  9. Saeed, H.; Nalbantoglu, Z.; Uygar, E. A Comprehensive Review of Hydrocarbon Contaminated Soil Behavior, Geotechnical Properties and Potential Remediation. Soil Sediment Contam. Int. J. 2024, 34, 1023–1067. [Google Scholar] [CrossRef]
  10. Asadi, T.; Najafi, P.; Chavoshi, E.; Hoodaji, M. The Impact of oil contamination on soil hydrophobicity and physico-chemical properties around Bandar Abbas oil refinery, Hormozgan Province, Iran. Environ. Health Eng. Manag. J. 2025, 12, 1–12. [Google Scholar] [CrossRef]
  11. Awarri, A.W.; West, A.R. Geotechnical Characterization of Fuel Contaminated Clay Soil. J. Adv. Geotech. Eng. 2025, 8. [Google Scholar] [CrossRef]
  12. Tuncan, A.; Pamukcu, S. Geotechnical properties of petroleum and sludge contaminated marine sediments. In Proceedings of the International Offshore and Polar Engineering Conference (ISOPE); ISOPE: Cupertino, CA, USA, 1992. [Google Scholar]
  13. Mooney, J.S.; Adamczak, S.; Clemence, S.P. Uplift behavior of anchor foundations in soil. In Uplift Behavior of Anchor Foundations in Soil; American Society of Civil Engineers: New York, NY, USA, 1985; pp. 48–72. [Google Scholar]
  14. Davie, J.R.; Sutherland, H.B. Modeling of clay uplift resistance. J. Geotech. Eng. Div. 1978, 104, 755–760. [Google Scholar] [CrossRef]
  15. Boussinesq, J. Application of Potentials to the Study of the Equilibrium and Motion of Elastic Solids: Principally for the Calculation of Deformations and Stresses Produced in these Solids by Arbitrary Forces Applied to a Small Portion of Their Surface or Interior; Memoir Followed by Extended Notes on Various Topics in Physics, Mathematics, and Analysis; Gauthier-Villars: Paris, France, 1885; Volume 4. [Google Scholar]
  16. Frazee, G.R. New formulations of boussinesq solution for vertical and lateral stresses in soil. Pract. Period. Struct. Des. Constr. 2021, 26, 06021001. [Google Scholar] [CrossRef]
  17. ASTM D1587/D1587M-15; Standard Practice for Thin-Walled Tube Sampling of Fine-Grained Soils for Geotechnical Purposes. ASTM International: West Conshohocken, PA, USA, 2015.
  18. ASTM D2166/D2166M-16; Standard Test Method for Unconfined Compressive Strength of Cohesive Soil. ASTM International: West Conshohocken, PA, USA, 2016.
  19. Encyclopaedia Britannica. Petroleum Refining—Additional Information. 2025. Available online: https://www.britannica.com/technology/petroleum-refining/additional-info (accessed on 5 December 2025).
  20. ASTM D4318; Standard Test Methods for Liquid Limit, Plastic Limit, and Plasticity Index of Soils. ASTM International: West Conshohocken, PA, USA, 2017.
  21. ASTM D854-23; Standard Test Methods for Specific Gravity of Soil Solids by Water Pycnometer. ASTM International: West Conshohocken, PA, USA, 2023.
  22. ASTM D698; Standard Test Methods for Laboratory Compaction Characteristics of Soil Using Standard Effort (12,400 ft-lbf/ft3 (600 kN-m/m3)). ASTM International: West Conshohocken, PA, USA, 2012.
  23. ASTM D2487-17; Standard Practice for Classification of Soils for Engineering Purposes (Unified Soil Classification System). ASTM International: West Conshohocken, PA, USA, 2017.
  24. ASTM D2435/D2435M-11; Standard Test Methods for One-Dimensional Consolidation Properties of Soils Using Incremental Loading. ASTM International: West Conshohocken, PA, USA, 2011.
  25. Fan, W.; Zhong, F. Experimental study on thermal conductivity of kerosene-based nanofluids. Thermochim. Acta 2022, 712, 179229. [Google Scholar] [CrossRef]
  26. Caffiero, L.; Carlotti, S.; Maggi, F. Investigation of Hypergolic Ignition of Green Kerosene-Based Fuels with HTP. In IAF Space Propulsion Symposium (75th International Astronautical Congress); International Astronautical Federation (IAF): Paris, France, 2024; pp. 1368–1373. [Google Scholar]
  27. Wang, S.; Wei, G.; Kong, R. Flotation Purification of Spent Anode Slag with Water-Soluble Kerosene: A Comparative Study. Min. Metall. Explor. 2024, 41, 1051–1067. [Google Scholar] [CrossRef]
  28. Tang, J.; Wang, S.; Kadagala, M.R.; Wang, C. Investigation of kerosene mixed with non-ionic surfactants as potential flotation collectors for enhanced carbon recovery from coal gasification fine slag: Experimental and molecular dynamic simulations. J. Environ. Chem. Eng. 2025, 13, 119444. [Google Scholar] [CrossRef]
  29. Hansen, J.B. Discussion of “Hyperbolic stress-strain response: Cohesive soils”. J. Soil Mech. Found. Div. 1963, 89, 241–242. [Google Scholar] [CrossRef]
  30. Tang, C.; Phoon, K.-K.; Yuan, J.; Tao, Y.; Sun, H. Variability in geostructural performance predictions. ASCE-ASME J. Risk Uncertain. Eng. Syst. Part A Civ. Eng. 2025, 11, 03124003. [Google Scholar] [CrossRef]
  31. Mazurkiewicz, B.K. Test Loading of Piles According to Polish Regulations; Royal Swedish Academy of Engineering Sciences Commission on Pile Research, Report No. 35; Royal Swedish Academy of Engineering Sciences: Stockholm, Sweden, 1972. [Google Scholar]
  32. Prakash, S.; Sharma, H.D. Pile Foundations in Engineering Practice; John Wiley & Sons: Hoboken, NJ, USA, 1991. [Google Scholar]
  33. Eslami, A.; Ebrahimipour, A.; Imani, M.; Imam, R.; Mo, P. Form and load transfer aspects of foundation systems: Case-based implementation and adaptation for buildings. Deep. Undergr. Sci. Eng. 2025. [Google Scholar] [CrossRef]
  34. AASHTO. Bridge Design Specifications; AASHTO: Washington, DC, USA, 2010. [Google Scholar]
  35. Mochtar, I.B.; Edil, T.B. Shaft resistance of model pile in clay. J. Geotech. Eng. 1988, 114, 1227–1244. [Google Scholar] [CrossRef]
  36. Siemaszko, P. Pile–Soil Interaction during Static Load Test. Stud. Geotech. Mech. 2024, 46, 164–175. [Google Scholar] [CrossRef]
  37. Tomlinson, M.J. Some effects of pile driving on skin friction. In Behaviour of Piles; Thomas Telford Publishing: London, UK, 1971; pp. 107–114. [Google Scholar]
  38. Tomlinson, M.; Woodward, J. Pile Design and Construction Practice; CRC Press: Boca Raton, FL, USA, 2007. [Google Scholar]
  39. Poulos, H.G.; Davis, E.H. Pile Foundation Analysis and Design; John Wiley: New York, NY, USA, 1980. [Google Scholar]
  40. Das, B.M.; Seeley, G.R. Uplift capacity of pipe piles in saturated clay. Soils Found. 1982, 22, 91–94. [Google Scholar] [CrossRef]
  41. Basack, S.; Alkahtani, M.Q.; Islam, S. Single pile response to uplift load: Computational model and analysis. Mar. Georesources Geotechnol. 2025, 43, 2034–2056. [Google Scholar] [CrossRef]
  42. Bear, J. Dynamics of Fluids in Porous Media; Courier Corporation: North Chelmsford, MA, USA, 2013. [Google Scholar]
  43. Tong, K.-W.; Pereira, J.-M.; Huang, K.; Dai, Z.-J.; Yu, F.; Chen, S.-X.; Guo, J.-H. Experimental study on the microscopic swelling–shrinking mechanisms of clay-sand mixtures from wetting to drying. Acta Geotech. 2025, 20, 3477–3500. [Google Scholar] [CrossRef]
  44. Al Hattamleh, O.; Rababah, S.; Alawneh, A.; Alqawab’ah, A. Verification of unified effective stress theory based on the effect of moisture on mechanical properties of fiber reinforced unsaturated soil. Geotext. Geomembr. 2021, 49, 976–990. [Google Scholar] [CrossRef]
  45. Abu-Agolah, T.K.; Rabab’ah, S.; Albalasmeh, A.; Al Hattamleh, O.; Sharo, A.A.; AlGaragreh, T.J. Hydro-mechanical Properties of Micro-silica-treated Soil Using the Unified Effective Stress Equation. Geotech. Geol. Eng. 2025, 43, 158. [Google Scholar] [CrossRef]
  46. Aiban, S.A. The effect of temperature on the engineering properties of oil-contaminated sands. Environ. Int. 1998, 24, 153–161. [Google Scholar] [CrossRef]
  47. Rahman, Z.A.; Hamzah, U.; Taha, M.R.; Ithnain, N.S.; Ahmad, N. Influence of oil contamination on geotechnical properties of basaltic residual soil. Am. J. Appl. Sci. 2010, 7, 954–961. [Google Scholar] [CrossRef]
  48. Khalil, A.; Attom, M.; Khan, Z.; Astillo, P.V.; El-Kadri, O.M. Recent advancements in geothermal energy piles performance and design. Energies 2024, 17, 3386. [Google Scholar] [CrossRef]
Figure 1. The diagrammatic (a) test containers and (b) model pile configuration.
Figure 1. The diagrammatic (a) test containers and (b) model pile configuration.
Buildings 16 01111 g001
Figure 2. Testing setup (a) as sketch. (b) Photograph of the experimental setup showing the model pile container, loading frame, data acquisition system, and instrumentation layout (numbered components correspond to those described in the text).
Figure 2. Testing setup (a) as sketch. (b) Photograph of the experimental setup showing the model pile container, loading frame, data acquisition system, and instrumentation layout (numbered components correspond to those described in the text).
Buildings 16 01111 g002
Figure 3. The experimental methodology flow chart.
Figure 3. The experimental methodology flow chart.
Buildings 16 01111 g003
Figure 4. The variation of (a) fluid content, (b) dry density and (c) undrained shear strength with depth in the test containers.
Figure 4. The variation of (a) fluid content, (b) dry density and (c) undrained shear strength with depth in the test containers.
Buildings 16 01111 g004
Figure 5. Soil surface heave with elapsed time since flooding.
Figure 5. Soil surface heave with elapsed time since flooding.
Buildings 16 01111 g005
Figure 6. Compressibility curves for soil beds.
Figure 6. Compressibility curves for soil beds.
Buildings 16 01111 g006
Figure 7. Axial compressive capacity of the model piles.
Figure 7. Axial compressive capacity of the model piles.
Buildings 16 01111 g007
Figure 8. Axial pullout capacity of the model piles.
Figure 8. Axial pullout capacity of the model piles.
Buildings 16 01111 g008
Figure 9. Calibration curve for model pile from axial compression test.
Figure 9. Calibration curve for model pile from axial compression test.
Buildings 16 01111 g009
Figure 10. Internal axial load as a function of depth during pullout testing.
Figure 10. Internal axial load as a function of depth during pullout testing.
Buildings 16 01111 g010
Figure 11. Unit local unit skin friction as a function with depth during pullout test.
Figure 11. Unit local unit skin friction as a function with depth during pullout test.
Buildings 16 01111 g011
Table 2. Ultimate load in compression test.
Table 2. Ultimate load in compression test.
Beds TypeTrialsMethod of Evaluation of Failure Load
SwedishMazurkiewiczTangentAASHTOAverage (kN)
As-prepared15.806.056.06.005.97
27.808.08.07.907.99
37.407.507.057.407.33
Overall average7.07
Water-Flooded12.402.422.212.52.41
22.102.151.952.252.14
31.911.901.871.951.91
Overall average2.15
Kerosene-Flooded14.904.955.005.104.98
24.854.905.055.205.00
33.873.953.854.153.96
4.65
Table 3. Pile displacement at ultimate compression (average values).
Table 3. Pile displacement at ultimate compression (average values).
Bed TypeTrialsUltimate Displacement (mm)
As-prepared12.90
23.30
33.10
Water-Flooded15.30
25.43
36.00
Kerosene-Flooded13.45
23.50
33.52
Table 4. Ultimate pullout test results.
Table 4. Ultimate pullout test results.
Beds TypeTrialsDisplacement at Ultimate Load, s (mm)Ultimate Pullout Load, Q (kN)Qpc/Qp0(avg)s/Diameter, DfsAdhesion Factor, α
As-prepared10.101.771.000.2334.50.46
20.121.821.000.2835.60.47
30.201.731.000.4733.50.45
Water-Flooded10.070.460.260.167.50.14
20.250.450.250.587.30.13
30.150.440.250.357.10.13
Kerosene-Flooded10.111.040.590.2619.50.46
20.151.010.570.3518.70.45
30.090.980.550.2118.30.44
Table 5. Comparison between the present work to previously published literature.
Table 5. Comparison between the present work to previously published literature.
StudySoil TypeContaminantTest ScaleFoundation TypeMain FocusLimitationsDistinct Contribution of Present Study
Evgin & Das (1992) [8]SandMotor oilLaboratoryNoneShear strength reductionNo foundation behaviorDirect pile capacity evaluation
Aiban (1998) [46]ClayHydrocarbonLaboratoryNoneConsolidation effectsNo load testsPile–soil interaction studied
Rahman et al. (2010) [47]SandCrude oilModelShallow footingBearing capacityNo deep foundationsDeep foundation response assessed
Present studyClayKeroseneInstrumented modelPiles (compression and pullout)Capacity, adhesion, load transferModel scaleIntegrated foundation-scale evaluation under controlled contamination states
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Attom, M.; Al Hattamleh, O.; Khalil, A. Experimental Analysis of Kerosene’s Contamination Effect on Unit Skin Friction of Pile in Clayey Soil. Buildings 2026, 16, 1111. https://doi.org/10.3390/buildings16061111

AMA Style

Attom M, Al Hattamleh O, Khalil A. Experimental Analysis of Kerosene’s Contamination Effect on Unit Skin Friction of Pile in Clayey Soil. Buildings. 2026; 16(6):1111. https://doi.org/10.3390/buildings16061111

Chicago/Turabian Style

Attom, Mousa, Omar Al Hattamleh, and Ahmed Khalil. 2026. "Experimental Analysis of Kerosene’s Contamination Effect on Unit Skin Friction of Pile in Clayey Soil" Buildings 16, no. 6: 1111. https://doi.org/10.3390/buildings16061111

APA Style

Attom, M., Al Hattamleh, O., & Khalil, A. (2026). Experimental Analysis of Kerosene’s Contamination Effect on Unit Skin Friction of Pile in Clayey Soil. Buildings, 16(6), 1111. https://doi.org/10.3390/buildings16061111

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop