Research and Prospects of Airtightness of Biological Laboratory Enclosures: Influencing Factors and Evaluation Methods

1
College of Architecture and Environment, Sichuan University, Chengdu 610065, China
2
Key Laboratory of Deep Underground Science and Engineering for Ministry of Education, College of Architecture and Environment, Sichuan University, Chengdu 610065, China
3
Failure Mechanics & Engineering Disaster Prevention and Mitigation, Key Laboratory of Sichuan Province, Sichuan University, Chengdu 610065, China
4
Southwest Construction Engineering Co., Ltd., China Construction Eighth Engineering Division Co., Ltd., Chengdu 610041, China
*
Author to whom correspondence should be addressed.
Buildings 2025, 15(13), 2314; https://doi.org/10.3390/buildings15132314
Submission received: 22 March 2025 / Revised: 15 June 2025 / Accepted: 26 June 2025 / Published: 1 July 2025
(This article belongs to the Section Building Materials, and Repair & Renovation)

Abstract

The airtightness of enclosures in biological laboratories is paramount for effective isolation between internal and external environments, ensuring containment of hazardous pathogens and mitigating accidental release risks. Consequently, studying and enhancing the airtightness of these enclosures significantly contributes to maintaining laboratory safety, safeguarding personnel health, and preventing disease. This paper examines the critical role of the enclosure structure in biological laboratories and how airtightness impacts the laboratory environment. It analyzes the current state of research on the airtightness of high-level biological laboratory enclosures, drawing on domestic and international sources. This includes exploring issues and challenges related to material properties, process methods, and evaluation methods for the airtightness of concrete structural materials as well as steel structures. The paper also studies the airtightness of enclosure structures of biological laboratories, highlighting the shortcomings in this important field of research and its future prospects.

1. Introduction

The COVID-19 pandemic, caused by the novel coronavirus SARS-CoV-2, has highlighted the critical role of biosafety laboratories in global public health. These facilities are essential for researching highly pathogenic microorganisms, developing diagnostics, and formulating vaccines. Among various biosafety levels, Biosafety Level 4 (BSL-4, or P4) laboratories represent the highest containment level, designed to handle pathogens that pose a serious threat to human health and the environment. The airtightness of these laboratory enclosures is paramount, as it ensures the isolation of hazardous pathogens from the external environment, thereby preventing accidental releases and safeguarding both personnel and the public [1].
The development of biosafety laboratories originated in the mid-20th century, pioneered by the United States. Over the decades, advancements in laboratory design and construction have been driven by the need to address emerging infectious diseases, such as SARS, MERS, and Ebola. Globally, there are currently 62 operational or planned BSL-4 laboratories across 24 countries, with Europe and North America leading in both quantity and technological maturity [2,3]. These facilities are predominantly government-owned, reflecting their strategic importance to national and global health security.
In China, the construction of high-level biosafety laboratories has accelerated in recent years, spurred by the “Plan for the Construction of High-Level Biosafety Laboratory System (2016–2025)” issued by the National Development and Reform Commission and the Ministry of Science and Technology. This plan aims to establish 5–7 BSL-4 laboratories and at least one BSL-3 laboratory in each province by 2025 [4]. Despite this progress, challenges remain, including uneven geographical distribution, gaps in management systems, and a shortage of qualified professionals [5].
The airtightness of laboratory enclosures is a critical factor in their design and operation. It involves the integration of material science, structural engineering, and advanced construction techniques to create impermeable barriers. Concrete and stainless steel are the primary materials used, each with distinct properties and challenges. For concrete structures, factors such as mixing ratios, material additives, and construction processes significantly influence airtightness [6,7]. Steel structures, particularly those employing stainless steel seam welding, offer superior airtightness and durability but require meticulous welding techniques and material selection [8].
Despite progress, gaps persist in the research on airtightness evaluation methods and standards. While international standards such as ISO 9972:2015 [9] and ASTM E779-19 [10] provide robust frameworks, China’s national standards, such as GB 19489-2008 and GB 50346-2011, still require refinement to enhance accuracy and applicability [11]. Furthermore, the interactions between material properties, structural design, and long-term operational reliability remain underexplored.
This paper aims to address these gaps through a comprehensive review of the airtightness of biological laboratory enclosures. It examines the current state of global BSL-4 laboratory construction, analyzes the material properties and construction techniques that influence airtightness, and evaluates existing testing methods and standards. By synthesizing domestic and international research, this study seeks to contribute to the development of more reliable and efficient enclosure systems, ultimately enhancing the safety and functionality of high-level biosafety laboratories.
The significance of this research extends beyond the academic realm, offering practical insights for policymakers, engineers, and laboratory operators tasked with designing, constructing, and maintaining these critical facilities. As the world faces increasing biological threats, the lessons learned from this study will be instrumental in fortifying global biosafety infrastructure.

2. Current Status of Research Worldwide and in China

2.1. Development of Biosafety Laboratories Worldwide

The establishment of biosafety laboratories dates back to the 1950s and 1960s in the United States. Subsequently, in the 1980s, China collaborated with international partners to establish its first high-level biosafety laboratory. By the 1990s, China had developed the capability to design and construct such laboratories independently. As of now, there are 62 operational and planned BSL-4 laboratories situated in 24 countries globally. Approximately 60% of these facilities are government-owned, 20% are affiliated with universities, and 20% are military establishments [2]. Table 1 summarizes the global distribution of BSL-4 laboratories, with particular emphasis on regional variations in airtightness techniques and operational challenges. A comprehensive overview of operational and planned BSL-4 laboratories worldwide, including their construction years and areas, is provided in Appendix A (Table A1). These data reveal significant disparities between developed and developing regions, informing subsequent discussions on material innovations (Section 3 and Section 4) and testing standards (Section 6).
The comparison of airtightness techniques in Table 1 reveals regional variations in material selection and their consequences. For instance, the steel/concrete hybrid structure adopted by the Wuhan Institute of Virology combines the cost-effectiveness of concrete with localized steel reinforcement at joints, achieving low leakage rates under laser welding. However, this design may face long-term micro-crack formation in concrete under cyclic pressure loads, requiring periodic sealant maintenance. In contrast, PHE’s all-stainless-steel enclosure with epoxy coatings offers superior corrosion resistance and seamless weld integrity, but at 2–3 times the material cost of hybrid designs (Section 5.1). These differences reflect the trade-off between initial investment and long-term maintenance.
In a regional context, Europe boasts the highest concentration of P4 laboratory facilities and is the earliest developed, followed by North America. In contrast, laboratories in other regions are sporadic and have been established at a later stage. Regarding individual countries, the United States has the largest number of P4 laboratories and has demonstrated maturity in constructing and operating high-level laboratories [3,12]. This distribution is illustrated in Figure 1 and Figure 2.
The global disparities in biosafety laboratory development arise from varying technical capabilities, policy frameworks, economic resources, and historical contexts. Developed countries such as the US and Europe have benefited from early technological advantages, robust regulatory systems, and substantial funding, enabling them to establish advanced facilities decades ago. Meanwhile, developing regions face challenges including technological gaps, inconsistent policies, and limited budgets, often relying on international collaborations for capacity building. The high cost of BSL-4 laboratories further limits their deployment in resource-constrained environments. Notably, defense-related research has historically driven biosafety investments in Western countries, while emerging economies like China and India are now prioritizing laboratory networks in response to recent pandemics and growing biosecurity needs. These systemic differences highlight the importance of context-specific approaches to global biosafety infrastructure development.

2.2. Research Status in China

China has achieved significant progress in biosafety laboratory development despite its later initiation compared to its global counterparts. The establishment of a key regulatory framework began with the promulgation of the “General Guidelines for Biosafety in Microbiological and Biomedical Laboratories” in 2002, marking China’s first steps toward standardized biosafety practices. A major milestone was achieved in 2018 with the operational launch of two critical facilities: the Wuhan National Biosafety (Level 4) Laboratory and the Harbin National High-Level Biosafety Laboratory for Animal Disease Control [6,7]. These achievements demonstrate China’s growing capabilities in high-containment laboratory construction and management.
The Wuhan National Biosafety Laboratory (Level 4) represents China’s most advanced high-containment facility, demonstrating exceptional airtightness performance through its stainless-steel welded enclosure system. Pressure decay tests conducted under standard operating conditions (500 Pa test pressure) showed a pressure drop of only 180 Pa over 20 min, significantly exceeding the maximum decay requirement of 250 Pa specified in GB 19489-2008 [13]. This outstanding performance is attributed to advanced laser welding techniques and stringent quality control measures for the steel/concrete hybrid structure. However, material consistency challenges, particularly in thermal expansion differentials between steel and concrete, require ongoing monitoring and adjustment in regional BSL-4 implementations. Independent evaluations, including WHO expert assessments, have confirmed the facility’s robust isolation capabilities. Biological aerosol tests using Serratia marcescens and phage ΦX174 demonstrated that the isolation efficiency at all penetration points exceeded 99.99%. However, insufficient technical staff training remains a common challenge for China’s biosafety network. The laboratory’s design incorporates multiple features, including mechanical compression doors with ultrasonic leak detection and HEPA-filtered ventilation systems, making it a benchmark for modern BSL-4 containment architecture [14,15]. These technical achievements meet international standards (ISO 9972:2015, ASTM E779-19) while also fulfilling China’s specific biosafety requirements for handling Category IV pathogens.
Since then, China has significantly expanded its biosafety infrastructure, now boasting numerous BSL-3 facilities and an increasing number of BSL-4 laboratories. This expansion has provided valuable experience in laboratory design, construction, and testing methods. Chinese national standards such as GB 19489-2008 and GB 50346-2011 have provided important guidance for laboratory construction, particularly in defining protection zones and enclosure airtightness requirements [13,16]. However, gaps remain in airtightness testing standards and research, with current studies predominantly focusing on concrete material formulations, steel structure welding techniques, and component-level performance, while paying less attention to integrated concrete/steel systems. Establishing P4 laboratories in China still faces some challenges. Notably, there are significant geographical disparities in the distribution of these laboratories, with most located in economically developed regions. Additionally, the biosafety management systems in place are far from comprehensive, and their enforcement needs to be strengthened. Financial constraints also hinder the effective operation of these laboratories. Furthermore, there is a significant shortage of qualified professionals [4].
Recent studies in China on laboratory enclosures have emphasized innovative design and efficiency assessment. Chen et al. (2022) [17] proposed a novel design for a nucleic acid testing laboratory utilizing air/membrane structures. These structures feature high airtightness and swift installation capabilities, and have been successfully applied across multiple countries, enhancing testing capacity. Wang et al. (2024) [18] suggested that intelligent building enclosures are becoming increasingly prevalent. These structures can autonomously adjust to environmental changes, thereby enhancing indoor comfort and improving energy efficiency. Concurrently, numerous scholars have rigorously assessed the performance of current building enclosures and offered viable suggestions for their enhancement.
Disparities in the development of biosafety laboratories across regions stem from the complex interplay of technological, policy, economic, and geopolitical factors. Developed countries such as the United States and European countries have leveraged their long-standing expertise in biosafety technology to establish and maintain high-level laboratories early on, supported by stringent regulatory frameworks and substantial government investments in public health infrastructure. In contrast, regions like Africa and parts of Asia face significant technological gaps and rely heavily on international collaborations to build capacity, compounded by inconsistent policies and limited funding that hinder progress. The high construction and operational costs of BSL-4 laboratories further restrict their proliferation in economically weaker regions, while developed nations prioritize biosafety as a cornerstone of national security, allocating robust budgets to sustain advanced facilities. Historically, defense-related biosafety research in the US and Europe has driven early advancements, whereas emerging economies like China and India are now accelerating their efforts in response to recent pandemics and escalating biosecurity demands. These multifaceted disparities underscore China’s need for tailored strategies to address regional imbalances in biosafety laboratory development.

3. Airtightness of Concrete Structures

3.1. Concrete Material Properties

3.1.1. Mixing Ratio Design

The enclosure structure of high-level biosafety laboratories has high requirements for the airtightness of concrete. The airtightness of concrete structures is closely related to the mixing ratio and molding of concrete materials. As a non-homogeneous material, concrete may inadvertently trap gas bubbles during production, and the evaporation of free water during hydration creates numerous air voids and capillary channels with varying morphologies. These features affect the concrete’s compactness and strength, providing pathways for gas migration. Concrete strength and airtightness are closely related to its capillary porosity. Therefore, many factors influencing concrete strength also significantly impact its permeability. According to the Borromeo formula, a lower water/cement ratio results in higher compressive strength. Tang (2017) [6] studied seven different water/cement ratio concretes. They found that a higher water/cement ratio leads to more internal pore structures, resulting in poorer airtightness. Similarly, Liu et al. (2005) [7] found that the gas permeability coefficient of concrete decreases as compressive strength increases, establishing a strong linear relationship between compressive strength and gas permeability coefficient across different water/cement ratios. Xu et al. (2022) [19] found that basalt fiber reinforcement reduces concrete gas permeability by 65.7% (from 3.5 × 10−16 m2 to 1.2 × 10−16 m2 under −500 Pa) via pore structure refinement (42% porosity reduction by SEM). Overall, as the water/cement ratio increases, so does the concrete’s gas permeability coefficient. The proportion of aggregate in concrete also affects its airtightness. It is generally accepted that adding aggregate to concrete worsens pore connectivity and increases pore tortuosity, thereby reducing its gas permeability coefficient and enhancing airtightness [20].
In summary, key factors affecting the design of the mixing ratio are the material proportioning and the molding process. The strength and airtightness of concrete are closely related to its capillary porosity. A lower water/cement ratio results in higher compressive strength; a higher water/cement ratio leads to more internal pore structure and poorer airtightness. As compressive strength rises, the gas permeability coefficient declines. Additionally, the incorporation of concrete aggregates typically also leads to a decrease in the gas permeability coefficient.

3.1.2. Material Additives

Concrete admixtures are diverse and are widely used to modify concrete properties. Adding these admixtures can lower the gas permeability coefficient, enhance the densification of the hardened concrete, and improve its resistance to salt erosion and freeze/thaw damage. This, in turn, enhances the mechanical properties and overall durability of the concrete, extending its service life. Numerous studies have examined the effects of various admixtures, with some commonly used concrete admixtures summarized in Table 2.

3.2. Construction Technology

The key technologies in concrete construction include transportation, mixing, pouring, vibration, curing, etc., each of which affects the airtightness of the enclosure structure. Among them, the mixing process, pouring method, and vibration are critical steps. The complete process of concrete construction is shown in Figure 3.
Concrete site construction must strictly follow the specified sequence of material addition and mixing time during the mixing process. Aggregate gradation should be stored in sealed containers, and moisture content must be measured before each work shift. Adjustments to water consumption and aggregate dosage should be made promptly. To ensure the airtightness of concrete, Lian (2016) [25] mentioned that a recommended way is to dry mix the admixture and fine aggregate first, then add cement along with a portion of the mixing water, and finally combine with the sequence of addition of coarse aggregate, water reducing agent, and the remaining mixing water.
Concrete pouring methods are mainly divided into full-scale pouring, segmental pouring, and inclined pouring [26]. Full-scale pouring is suitable for large-area concrete construction, requiring fast and uniform pouring to avoid prolonged surface exposure time, thereby reducing cracks and interface issues. Segmental pouring is suitable for complex structural construction projects, achieved by dividing the structure into multiple small segments for independent pouring, enhancing structural uniformity and density. Sloped pouring, including the slipform method and free-fall method, is suitable for concrete construction on slopes or inclined surfaces.
After mixing, transportation, and pouring, concrete may contain air bubbles that are formed due to entrapped air. The purpose of vibration is to discharge these bubbles, reduce the number of pores, enhance the density of concrete, and ensure the overall quality of the structure. After sufficient vibration, the trapped air is discharged, and the concrete aggregate particles are more tightly bonded. As a result, the concrete becomes dense, strong, durable, and smooth, with no honeycomb or air bubbles on the surface, making it resistant to infiltration [27].
When using concrete to cast walls, it is important to pour in layers. If the upper layer is too thick, the weight of the concrete will prevent air from being expelled from the lower layer. This trapped air forms pores in the concrete and results in inadequate vibration. The thickness of each layer depends on the selected vibrator. For example, when the length of the selected vibrating rod is 350 mm, the maximum vibrated layer thickness should be 300 mm [27]. Layers should be cast horizontally, being careful not to pile up or tilt the concrete. It is crucial to achieve a dense bond between layers to ensure that each layer of concrete is fully vibrated and compacted. When pouring the next layer, it can still be vibrated to create a dense connection between layers, thereby forming a solid, cohesive structure.

4. Airtightness of Steel Structures

4.1. Selection of Enclosure Structure and Components

Stainless steel enclosure structures are commonly used in high-level biosafety laboratories. This structure not only provides excellent airtightness, meeting the airtightness requirements of such laboratories, but also offers corrosion resistance, high-pressure resistance, and ease of disinfection and cleaning. Stainless steel plate seam-welded enclosure structures are currently the preferred situation for alterations in high-level biosafety laboratories. This solution can be implemented in existing laboratory buildings to minimize the need for extensive structural modifications, resulting in lower costs and shorter construction periods. On the other hand, color-coated steel plate enclosure structures are commonly used in biological safety laboratories where non-airborne biological factors are present. These structures can be safely operated with isolation devices. According to GB 50346-2011 “Technical Specifications for the Construction of Biosafety Laboratories”, the enclosure structures of high-level biosafety laboratories must be able to withstand air pressure loads caused by the abnormalities of the air supply fan or exhaust fan. Stainless steel enclosure structures fulfill this requirement effectively. Due to the limited pressure of color-coated steel plate enclosure structures, their airtightness is typically only tested using visual methods, such as the smoke test, to detect visible leaks in gaps. The indoor relative negative pressure should not exceed −100 Pa. When conducting airtightness testing on color-coated steel plate enclosing structures using the constant pressure method or pressure decay method, stainless steel plate seam-welded enclosure structures or epoxy-treated concrete enclosure structures are generally selected. The former is mainly suitable for new construction, renovation, expansion projects, or projects where the building structure has already been completed, while the latter is appropriate for new construction projects.
To ensure the airtightness of the stainless steel enclosure structure, structural components are made of 304 stainless steel. These components are welded and molded, then processed by aging treatment, CNC gantry milling, sandblasting, and painting. The stainless steel plates undergo laser-cutting undercutting, CNC bending, and molding [8]. In addition, the design of the enclosure structure and selection of components must consider various factors, such as seismic resistance, fire safety, waterproofing, corrosion resistance, etc. These considerations are crucial to ensuring the stability and safety of the laboratory under various extreme conditions. In the construction of high-level biosafety laboratories, these characteristics of the enclosure structure are essential not only for maintaining biological safety inside the laboratory but also for the long-term stability of laboratory operation and maintenance.

4.2. Welding Performance and Welding Materials

The welding performance of steel structures depends on the physicochemical properties and composition of the base material, the selection of welding materials, welding processes, structural design, use conditions, etc. Common physical properties that affect welding performance include the following:
(1)
Differences in melting points make heat treatment difficult. The melting of the base material cannot be synchronized; if the melting point difference is too great, it may prevent successful welding of the materials.
(2)
Differences in electromagnetic properties lead to unstable arc combustion during arc welding.
(3)
Different linear expansion coefficients can easily cause welding stress concentration or cracks, which is also one of the key reasons why welded joints may fail to meet airtightness requirements.
(4)
Differences in thermal conductivity and specific heat capacity prevent the formation of the melt pool from being synchronized. Different rates of heat transfer result in increased thermal stress.
The impact of different welding materials on the welding quality is mainly reflected in the chemical composition matching, strength, corrosion resistance, process performance of welding materials, anti-porosity, and anti-cracking ability. The chemical composition of welding materials should be matched with the welded material to ensure the strength and durability of the weld. The thermal expansion coefficient, melting point range, thermal conductivity, and mechanical properties of the welding material and the material to be welded should be similar to avoid uneven thermal and residual stresses during the welding process, which could lead to cracking or deformation problems of the weld [28]. At the same time, the strength and corrosion resistance of the welding material should meet the requirements of the operating environment. For welded structures working in corrosive environments, welding materials with good corrosion resistance should be selected. Selecting the correct welding material is critical to ensuring welding quality. The suitable welding material should be selected according to the characteristics of the base material, welding method, operating environment, and expected welded joint performance. Welding materials mainly include welding rods, wires, fluxes, shielding gases, etc. Welding rods are coated with flux for arc welding with a molten electrode, while the wire is used as a filler metal or used simultaneously to conduct the wire. The selection of welding materials needs to consider factors such as the base material, welding position, welding current, and welding environment to ensure welding quality and safety. Welding rods are usually made of metal powders, alloys, or other materials, such as carbon steel, low alloy steel, stainless steel, cast iron, copper and copper alloys, aluminum and aluminum alloys, nickel-based alloy rods, and so on. Additionally, the continuous emergence of new welding materials helps improve welding efficiency and quality while reducing problems during the welding process.

4.3. Welding Process

There are many types of welding methods, and the selection of welding methods should take into account both usability and manufacturability. Welded joints obtained by different welding methods may have different organizations and properties. The following are several commonly used welding processes.
(1)
Laser Welding.
Laser welding is a welding technology that utilizes a laser beam as a heat source. Compared to traditional welding methods, it provides faster welding speed and higher quality. The laser beam produced by the laser welding machine has extremely high energy density, which means that it can concentrate a large amount of energy in a very small area, thus achieving rapid melting and welding of materials. The size and shape of the laser beam can be precisely controlled by the optical system, allowing the welding process to be carried out with great precision, making it suitable for both small and complex welding tasks. Laser welding is widely used in industries such as automotive manufacturing, aerospace, medical devices, electronics, microelectronics, precision instrument manufacturing, and so on.
(2)
Arc Welding.
Arc welding is a method of using the high temperature generated by an electric arc to melt metal, thereby connecting metal parts. Its basic working principle involves creating an electric arc between the welding rod (usually a metal welding rod or wire) and the workpiece. The heat from the arc melts the electrode and the workpiece contact part, forming a molten pool. As the molten pool cools, it forms a weld. There are many types of arc welding, including shielded metal arc welding (SMAW), metal inert gas welding (MIG/MAG), tungsten inert gas welding (TIG), submerged arc welding (SAW), etc.
With the continuous development of technology, various new welding processes have been enhanced from the original. Gorshkova (2021) [29] introduced new techniques that have been developed, such as K-TIG welding, hybrid laser welding, dual-arc welding, and magnetron-controlled electroslag welding. These innovations have increased productivity and improved joint strength, especially in refractory steels and titanium alloys.
Welding process parameters include many aspects, such as power source, current, voltage, polarity selection, welding speed, shielding gas, electrode diameter, etc., all of which directly influence welding outcomes. Additionally, the interplay between these parameters must be considered. For example, increasing welding current increases input heat, enlarging the weld pool and expanding the heat-affected zone; increasing voltage lengthens the arc, leading to weld spatter; and welding speed affects both welding efficiency and weld pool size [30]. All these parameter effects must be considered during the welding process.

5. Evaluation of Concrete, Steel Enclosures, and Use of Other Materials

5.1. Comprehensive Evaluation of Concrete and Steel Enclosures

Case comparisons between the steel/concrete hybrid structure of the Wuhan Institute of Virology and the all-steel enclosures of PHE demonstrate that the steel/concrete hybrid structure reduces initial costs compared to PHE’s all-stainless-steel design. However, due to the mismatch in thermal expansion coefficients between concrete and steel, the steel/concrete hybrid structure requires more inspections and maintenance in the long term. PHE’s epoxy-coated stainless steel offers higher resistance to chemical disinfection, but its complex geometry results in higher welding costs. Table 3 compares the costs of enclosure structures of the Wuhan and PHE laboratories. Since detailed construction cost data for the laboratories has not been disclosed, this table is estimated based on current international market prices for construction materials, as well as relevant documents and specifications. These differences illustrate how different countries’ priorities regarding cost and durability influence their choices of building enclosures and construction techniques.
To support decision-making regarding enclosure selection, a comprehensive evaluation of the performance and economy of concrete and steel structures is necessary. Concrete structures offer high initial airtightness and long-term durability, with the potential for further enhancement through admixtures and proper construction techniques. However, they may require more maintenance to ensure joints and connections remain airtight over the long term.
Steel structures, particularly stainless steel enclosures, provide superior airtightness and pressure stability, along with corrosion resistance and ease of cleaning. The use of advanced welding techniques and high-quality materials ensures minimal leakage and long-term performance. However, steel structures may be more susceptible to damage from impacts and require careful handling during installation.
In terms of economics, concrete structures may have lower initial costs but higher maintenance costs over time. Steel structures, while potentially more expensive upfront, may have lower maintenance costs and a longer service life. When choosing between concrete and steel structures, decisions should be based on specific project requirements, including budget constraints, construction timelines, and long-term operational needs.
Regional policy frameworks and financing mechanisms further complicate the technical and economic trade-offs between enclosure types. As shown in Table 4, the selection of steel/concrete hybrids versus all-steel designs often reflects deeper institutional priorities—EU regulations prioritize seal reliability over the lifecycle by mandating the use of stainless steel, while China’s subsidy policies actively promote hybrid structures as a cost-effective solution. Table 4 systematically compares how these policy-economic factors ultimately manifest as measurable airtightness outcomes across different governance contexts.

5.2. Lifecycle Cost-Benefit Evaluation of Enclosure Systems

The selection of enclosure structures for high-level laboratories requires balancing three key dimensions: (1) initial construction feasibility, (2) long-term maintenance complexity, and (3) operational reliability requirements. While detailed cost data for individual facilities is often proprietary, comparative studies indicate that stainless steel welded structures typically offer better airtightness and longer maintenance intervals, whereas steel/concrete hybrid structures (e.g., Wuhan P4) reduce initial capital expenditures through localized material sourcing but require more frequent joint inspections due to thermal expansion differences.
The WHO Laboratory Biosafety Manual (4th edition, 2020) [33] emphasizes that high-containment facilities require comprehensive lifecycle cost management, though it does not provide specific cost ratios. The manual highlights two key principles: (1) regular maintenance is critical for maintaining isolation integrity, and (2) material selection must balance initial costs with long-term operational requirements (WHO, 2020 [33], Section 5.3).
China’s GB 50346-2011 standard specifies that steel/concrete hybrid structures require more frequent maintenance than all-steel designs, mandating comprehensive inspections every 5 years compared to 10-year intervals for welded stainless steel systems (GB 50346-2011, Clause 5.1.9). This difference stems from the need to monitor thermal expansion differentials at material interfaces. Operational data from reference facilities such as Wuhan P4 (hybrid) and PHE (steel) confirm these maintenance intervals, but actual costs vary by region due to labor and material factors.

5.3. Other Materials Applied in the BSL-4 Laboratories

In addition to concrete and steel, other advanced materials are increasingly being utilized in BSL-4 laboratories to enhance airtightness, durability, and overall safety. These materials are selected based on their unique properties, which complement the stringent requirements of high-containment facilities.
(1)
Composite Materials
Composite materials such as fiber-reinforced polymers (FRPs) are gaining attention due to their high strength/weight ratio, corrosion resistance, and adaptability in sealing joints and penetrations [34]. Their flexibility allows for seamless integration with existing structures, reducing potential leakage points [35].
(2)
Epoxy Coatings and Sealants
Epoxy coatings are widely applied to concrete and steel surfaces to fill micro-pores and cracks, further enhancing airtightness. These coatings are chemically resistant and can withstand frequent decontamination procedures, making them ideal for laboratory environments [36,37].
(3)
Glass and Acrylic Panels
For observation windows and visual access points, laminated glass or acrylic panels with airtight gaskets can be used [32]. These materials provide transparency while maintaining structural integrity and resistance to pressure differentials [38].
(4)
High-Performance Gaskets and Membranes
Specialized gaskets made from silicone, EPDM rubber, or fluoropolymers are used to seal doors, vents, and equipment penetrations. These materials exhibit excellent elasticity and longevity, ensuring airtightness under dynamic pressure conditions [39,40].
(5)
Nanotechnology-Enhanced Materials
Emerging nanomaterials, such as graphene oxide or nano-silica additives, are being explored to improve the water resistance of traditional materials like concrete and coatings [41]. These innovations aim to reduce porosity at the microscopic level [42].
(6)
Fire-Resistant and Thermal Barriers
Materials like intumescent paints and ceramic fibers are integrated into the enclosure design to meet fire safety standards without compromising airtightness. These barriers expand under heat, sealing gaps to prevent smoke or pathogen leakage in an emergency [43,44].
The selection of materials for BSL-4 laboratories extends beyond conventional choices, requiring the integration of composite materials, advanced coatings, and nanotechnology to address multifaceted challenges. Future research should focus on optimizing these materials for long-term performance under operational stresses, including thermal cycling, chemical exposure, and mechanical wear.

6. Airtightness Test Methods and Evaluation Criteria

6.1. Airtightness Test Methods

Building airtightness testing is the fundamental method for evaluating building enclosure performance. Commonly used airtightness testing methods include the pressure decay method, helium mass spectrometry leak detection method, soap liquid method, heating method, flow method, and water pressure method [45]. The introduction of each method and the recommended ratings for their use are shown in Table 5.

6.2. Airtightness Testing Standards

6.2.1. International Standards

Developed countries have prioritized research on building airtightness for decades, establishing more comprehensive building codes with stringent airtightness requirements. Building airtightness testing has been conducted extensively, with detailed technical specifications for overall building airtightness and standardized approaches that demonstrate notable regional variations. This review examines six internationally recognized standards—ISO 9972:2015 [9], EN 13829:2000 [31], ASTM E779-19 [10], JIS A 2201:2018 [46], ATTMA TS1 (2022) [47], and CAN/CGSB-149.15 (2020) [48]—comparing their technical specifications, applicability, and impact on the building enclosure performance. The assessment is presented in Table 6, focusing on five critical dimensions: regional applicability, testing protocols, quantitative metrics, calculation methods, and regulatory implementation.
The analysis demonstrates how regional building practices, climatic factors, and performance requirements have influenced the development of distinct testing frameworks. While ISO 9972 establishes an international benchmark, EN 13829 and ASTM E779 reflect European and North American regulatory approaches, respectively. Notably, JIS A 2201 incorporates Japan-specific parameters such as the C-value, while CAN/CGSB-149.15 addresses Canada’s strict climate demands. These variations highlight the necessity of adopting context-specific standards to accurately assess building enclosure performance.

6.2.2. China’s Standards

China’s research on building airtightness is still in its infancy, with most existing literature concentrated in the past decade and a lack of referenceable airtightness measurement data. In recent years, the concern for building airtightness has been rising. For concrete and stainless steel monolithic welded enclosure structures, airtightness testing methods are generally the pressure decay method test or the constant pressure method [11].
(1)
Pressure Decay Method
The pressure decay method involves testing the temperature and pressure inside a sealed enclosure at regular time intervals from the initial to the final stage. The actual leakage rate of the enclosure is calculated based on the results of temperature and pressure changes over time. Usually, the initial and final readings are used for calculation, and the remaining intermediate readings are used to control the test conditions. ISO 10648-2: 1994 “Sealed chambers Part 2: Classification of sealing and its test methods” [32] gives the formula for calculating the hourly leakage rate T f using the pressure decay method:
T f = 60 τ p n T 1 p 1 T n 1
where T f is the cavity hourly leakage rate, h−1; τ is the duration of the test, min; p n is the final reading of the absolute pressure in the room, Pa; p 1 is the initial reading of the absolute pressure in the room, Pa; T 1 is the initial reading of the temperature, K; T n is the final reading of the temperature, K.
(2)
Constant Pressure Method
The constant pressure method maintains the negative pressure in the sealed enclosure at a constant level, measures the flow rate of the discharged gas, and calculates the leakage rate based on the ratio between the leakage volume and the volume of the enclosure. As the accuracy of the cavity volume measurement directly affects the numerical calculation of the leakage rate, it is usually used to evaluate the leakage rate of sealing cavities with higher leakage rates or regular internal dimensions of the cavity. GB 19489-2008 [13] gives the formula for calculating the hourly leakage rate T f by the constant pressure method:
T f = Q / ( V 1 V 2 )
where Q is the air volume maintaining a constant pressure difference, m3/h; V 1 is the room’s spatial volume, m3; V 2 is the room’s object volume, m3.
Both the pressure decay method and the constant pressure method reflect the extent of gas leakage from the enclosure. The two methods are interchangeable in terms of their testing principles, although there are differences in their formulas [32]. Due to the presence of gaps in the building enclosure, when a pressure difference exists between the interior and exterior of the enclosure, air flows through the gaps from the high-pressure side to the low-pressure side. The volume of air flowing into or out of the room through the gap represents the leakage rate of the enclosure structure.
China’s current national standards GB 19489-2008 [13] and GB 50346-2011 [16] specify the airtightness requirements for P4 laboratories, as shown in Table 7.

7. Other Measures to Improve Airtightness

7.1. Setting the Airtight Valve and Airtight Door

7.1.1. Airtight Valve

The airtightness requirements of the enclosure structure are extremely high, and the ventilation and air conditioning piping system is the biggest risk to the enclosure structure, with many penetrating ducts, large diameters, and sealing difficulties. Installing biosafety airtight valves at key nodes of the ventilation and air conditioning duct system and ventilation and filtration equipment ducts in the building enclosure can effectively guarantee the airtightness of the enclosure structure, isolate the laboratory with biosafety protection equipment from the external environment, and realize the possibility of providing test conditions for different types of ventilation and filtration equipment to provide the possibility of test conditions [49].

7.1.2. Airtight Doors

To meet the airtightness requirements of biosafety laboratories, mechanical compression doors and inflatable airtight doors are usually used to provide safe isolation between the protected and non-protected areas of the laboratory. The mechanical compression door is mainly composed of a door frame, door panel, seal ring, mechanical compression mechanism, and access control device. Its working principle is as follows: when the door is closed, the door panel and door frame are pressed together by the seal ring through the compression mechanism, ensuring no leakage between them. After the installation of an airtight door, the ultrasonic penetration method is used for leakage detection. Mechanical compression airtight doors are durable and, unlike inflatable airtight doors, do not require inflation of the seal rings. Additionally, they do not need to be replaced regularly due to seal ring aging, thereby reducing maintenance costs [8]. Liu et al. (2025) [50] found that nano-silica epoxy coatings achieve a 90% reduction in steel joint leakage rates (0.05→0.005 m3/(h·m)) by filling micro-cracks <50 μm, which is critical for the sealing of doors and windows in BSL-4 laboratories. In addition, the study on airflow distribution in mobile BSL-4 laboratories also highlighted the importance of airtight doors in maintaining the directional airflow and preventing cross-infection [51]. The opening and closing of airtight doors can significantly affect the airflow patterns and the generation of vortices, which in turn influence the deposition and removal of bioaerosols. Therefore, the use of mechanical compression doors not only ensures airtightness but also helps in maintaining a stable and controlled airflow environment within the laboratory.

7.2. Through-Wall Equipment and Sealing Measures

High-level biosafety laboratories through-wall (floor, ceiling) equipment mainly includes airtight doors, chemical shower devices, autoclaves, transfer windows, transfer channels, high-efficiency filtration air supply and exhaust vents, airtight floor drains, etc. The airtightness of these devices themselves and the installation of the airtightness of the frame are important components of the laboratory airtightness. When installing the outer frames, stainless steel outer frames should be welded and embedded in the enclosure to ensure sealing. High-level biosafety laboratory through-wall (floor, ceiling) pipes mainly include ventilation pipes, water supply and drainage pipes, and strong and weak electric cables. The airtightness of these pipes themselves and the sealing treatment of wall penetration openings also significantly impact the laboratory’s airtightness. Overseas, specialized embedded components are often used to eliminate temporary construction openings, such as professional pipe wall penetration sealers or liquid groove seals with centralized cable trays to ensure the integrity and airtightness of laboratory walls [52]. Common sealing measures use materials such as tape, silicone strips, silicone coatings, liquid coatings, foam sealing strips, and polyurethane foam [53]. These materials can achieve good airtightness when installed perfectly. However, the performance of sealing materials is highly sensitive to construction quality, especially tape, silicone-based materials, and foam sealing strips, whose performance mainly depends on construction quality.

7.3. Adopting the Dynamic Pressure Control Design Method

The dynamic pressure control design method can effectively improve the stability of the differential pressure of the BSL-4 laboratory. The core technology of the dynamic pressure control design method involves extending the cycle of the variable air volume valve for indoor pressure measurement. By adopting a dynamic pressure control design method that combines a constant supply and variable exhaust system with parallel variable air volume valves, the stability of laboratory pressure gradients is ensured, interference resistance is enhanced, and the directionality of airflow organization is achieved [49].

7.4. Microbial Testing of Laboratory Tightness

The integrity of containment systems in high-containment laboratories, particularly those operating at BSL-4, is critical for preventing the escape of hazardous microorganisms, necessitating rigorous microbial testing of laboratory tightness. Aerosol challenge testing serves as a direct method to detect microbial leakage, involving the aerosolization of non-pathogenic tracer microorganisms such as Bacillus subtilis spores or Serratia marcescens within the lab and subsequent air sampling outside critical barriers. The acceptance criteria for this test require no viable tracer microorganisms to be detected outside containment. Complementary to this approach, particle counting tests utilize inert particles like polystyrene latex spheres to simulate microbial aerosols, with laser particle counters scanning door seals and filter housings to verify that external particle counts remain significantly lower than internal levels, typically below 0.01% leakage [54,55].
Filter integrity testing is another critical component of containment verification, particularly for HEPA/ULPA filters that serve as final barriers against microbial escape. This testing involves introducing aerosolized dioctyl phthalate (DOP) or polyalphaolefin (PAO) upstream and scanning downstream with photometers or particle counters, with permissible leakage thresholds set at ≤0.01% of upstream concentration. Smoke testing offers visual confirmation of proper airflow patterns, ensuring smoke flows inward in negative-pressure laboratories without escaping containment zones [56]. Additionally, biological indicator testing serves to verify decontamination efficacy by placing spore strips in critical areas, incubating them post-fumigation with agents like hydrogen peroxide vapor, and confirming the absence of microbial growth [57].
These diverse testing methods, when combined and aligned with rigorous regulatory standards such as those established by the WHO, CDC, or ISO 14644, create a robust system for maintaining and verifying containment integrity in BSL-4 laboratories [58]. Regular application of these tests ensures the ongoing effectiveness of containment systems, providing multiple layers of protection against accidental microbial leakage and safeguarding both laboratory personnel and the external environment from potential exposure to hazardous pathogens. The comprehensive nature of this testing regime reflects the extraordinary precautions necessary for working with the world’s most dangerous microorganisms in the highest-level containment facilities.

8. Conclusions

This paper discusses the current state of global P4 laboratory construction and the specifications for airtightness requirements. It examines the material properties, construction methods, and evaluation techniques related to the airtightness of concrete and steel structures. The analysis focuses on how various materials, structural designs, and construction methods affect the airtightness of enclosure structures. Based on these findings, construction plans to enhance airtightness are proposed, and the following conclusions are drawn.
(1)
From the operation practice of P4 laboratories, the number of high-level biosafety laboratories in China needs to be further increased, with plans to form a reasonable national network of high-level biosafety laboratories by 2025. There are still some safety loopholes in the management of P4 facilities, which need to be unified. In order to improve the accuracy and effectiveness of enclosure structure airtightness testing, relevant national standards still need to be formulated and revised. Currently, China particularly needs to accumulate information related to the long-term operational reliability of P4 facilities, including laboratory design, building materials, construction processes, construction supervision, and qualification certification. Relevant regulations and standards still need to be further improved. In the future, China can draw on the mature experiences and relevant standards of other countries in the construction of high-level biosafety laboratories to improve its national standards, laboratory management, and maintenance, providing references for the biosafety construction and application of high-level biosafety laboratories in China. Given the high requirements for the construction and management of high-level biosafety laboratories and the significant investment costs involved, it is advisable to first strengthen support for the development of key technologies and related disciplines, gradually forming and leveraging their capabilities and advantages.
(2)
The airtightness of concrete is closely related to its capillary porosity, with influencing factors including material proportions and forming processes. Admixtures significantly affect concrete airtightness. Water-reducing agents improve the airtightness of concrete specimens; defoamers refine pores and reduce concrete permeability; air-entraining agents enhance airtightness, but increased dosage leads to a temporary decrease followed by an increase in permeability coefficient; when compressive strength and permeability coefficient decrease, airtightness agent dosage increases.
(3)
Stainless steel enclosure structures are airtight, corrosion-resistant, high-pressure resistant, and easy to disinfect and clean. They are widely used in high-level biosafety laboratories. A stainless steel plate seam-welded enclosure structure is the preferred option for remodeling projects, with low cost and a short construction period. Color steel plate enclosure structures for non-airborne biological factors of the laboratory to ensure airtightness are usually made of 304 stainless steel, after welding, molding, aging treatment, CNC machining, sandblasting and painting, and other processes. The welding performance of steel structures is affected by the physical and chemical properties of the base material, chemical composition, welding material selection, process, structural design, use conditions, and other aspects. Welding material selection affects the welding quality; the chemical composition matching, strength, corrosion resistance, process performance, anti-porosity, and crack resistance need to be considered. Different welding methods to obtain the organization and properties of the welded joints include new technologies such as K-TIG welding, hybrid laser welding, dual-arc welding, and magnetron electro slag welding to improve productivity and joint strength.
(4)
Airtightness test methods include the pressure decay method, helium mass spectrometry leak detection method, soap method, heating method, flow method, water pressure method, etc., among which the pressure decay method and helium mass spectrometry leak detection method are more recommended. In developed countries, the research on the airtightness of the enclosure structure is sufficient, and the relevant building codes are more complete, with higher requirements for airtightness. China’s research on building airtightness is still in the primary stage, and the current national standards still need to be further improved.
(5)
From a holistic perspective, to systematically improve China’s biosafety laboratory infrastructure, a three-phase roadmap is proposed. In the short term, interdisciplinary training programs (e.g., biosafety engineering) should be prioritized to build technical capacity. For the mid-term, piloting regional laboratories incorporating hybrid materials could optimize cost/performance ratios. Long-term efforts should focus on establishing a centralized database for airtightness performance metrics, enabling data-driven standardization. This tiered approach balances immediate needs, incremental innovation, and sustainable governance for future biosafety challenges.

Author Contributions

Conceptualization, G.P. and X.S.; methodology, G.P. and X.S.; funding acquisition, X.S.; software, G.P.; validation, G.P.; formal analysis, G.P. and R.H.; investigation, G.P. and R.H.; resources, X.S.; data curation, G.P.; writing—original draft preparation, G.P.; writing—review and editing, G.P. and X.S.; visualization, X.W. and J.Z.; supervision, X.S., X.W. and J.Z.; project administration, X.S. All authors have read and agreed to the published version of the manuscript.

Funding

This study was funded by the Key Technologies Research Project for Concrete and Steel Enclosure Structures in P4 Biosafety Laboratory (Grant No. 21H1150) and the China Construction Eighth Engineering Division Co., Ltd.

Data Availability Statement

Data are available on request from the authors.

Conflicts of Interest

Authors Xiaoli Wang and Jinsheng Zhan were employed by the company Southwest Construction Engineering Co., Ltd., China Construction Eighth Engineering Division Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Nomenclature

The following acronyms and abbreviations are used in this manuscript:
BSL-4Biosafety Level 4
P4Physical Containment Level 4 (equivalent to BSL-4)
CNASChina National Accreditation Service for Conformity Assessment
GBGuobiao (Chinese National Standards)
ISOInternational Organization for Standardization
ASTMAmerican Society for Testing and Materials
ENEuropean Standard
JISJapanese Industrial Standards
ATTMAAir Tightness Testing & Measurement Association
CGSBCanadian General Standards Board
ACH50Air Changes per Hour at 50 Pa
ELAEquivalent Leakage Area
CFMCubic Feet per Minute

Appendix A

Table A1. Global Construction of BSL-4 Laboratories.
Table A1. Global Construction of BSL-4 Laboratories.
RegionCountryNumberName of Laboratory and OrganizationYear of ConstructionArea (m2)
EuropeUK7Centre for Emergency Preparedness and Response, Public Health England (PHE)1974105
Defence Science and Technology Laboratory (Dstl), Ministry of Defense2005335
High Containment Large Animal Facility (HCLAF), Pirbright Institute2015257
The Francis Crick Institute Containment 4 facility (formerly NIMR), The Francis Crick Institute2016298
Centre for Infections (CFL), United Kingdom Health Security Agency (UKHSA)201330
National Institute for Biological Standards and Control (NIBSC), The Medicines and Healthcare Products Regulatory Agency, Department of Health & Social Care1975118
Public Health England (PHE) Harlow, United Kingdom Health Security Agency (UKHSA)2024unknown
Germany4Institute for Virology, Philipps University of Marburg2007152
Bernhard Nocht Institute for Tropical Medicine (BNI)2014400
Centre for Biological Threats and Special Pathogens, Robert Koch Institute, Federal Ministry of Health2018330
Friedrich Loeffler Institute (FLI), Federal Research Institute for Animal Health2015405
France3DGA Maîtrise NRBC, General Directorate of Armaments (DGA)2013178
Institut de Recherche Biomédicale des Armées (IRBA), Army Health Service (SSA)2015240
Jean Mérieux-Inserm (Institut national de la santé et de la recherche médicale), French National Institute of Health and Medical Research1999400
Switzerland3Spiez Laboratory2014118
Laboratory of Virology, Geneva University Hospitalsunknown36
Institute of Medical Virology, University of Zurichunknown25
Italy2National Institute for Infectious Diseases Lazzaro Spallanzani (IRCCS)2000unknown
Laboratory of Clinical Microbiology, Virology and Bioemergencies (CLIMVIB), Luigi Sacco University Hospital, University of Milanunknownunknown
Czech Republic2Laboratory for Biological Monitoring and Protection, National Institute for Nuclear, Chemical, and Biological Protection200728
Department for Biological Defence, Military Institute of Health200750
Hungary2National Biosafety Laboratory (OKI), National Public Health Institute (former National Center for Epidemiology)2002163
Szentágothai Research Center, University of Pécs201755
Russia2State Research Center of Virology and Biotechnology (VECTOR), Russian Federal Service for Surveillance on Consumer Rights Protection and Human Wellbeing19801440
48th Central Scientific Research Institute Sergiev Posad, Ministry of Defense1979unknown
Sweden1Folkhälsomyndigheten (FOHM), Public Health Agency of Sweden2001136
North AmericaUS 11Integrated Research Facility at Rocky Mountain Lab (IRF, RML), National Institutes of Health (NIH), National Institute of Allergy and Infectious Diseases (NIAID)20081145
The Betty Slick and Lewis J. Moorman, Jr. Laboratory Complex, Texas Biomedical Research Institute1970114
Center for Biodefense and Emerging Infectious Diseases Shope Laboratory, The University of Texas Medical Branch2003186
Galveston National Laboratory, The University of Texas Medical Branch20101022
National Bio and Agro-Defense Facility (NBAF), US Department of Homeland Security, US Department of Agriculture20244084
High Containment Core (HCC) (formerly the Viral Immunology Center), Georgia State University198860
Special Pathogens Branch, Centers for Disease Control and Prevention (CDC)1988533
National Biodefense Analysis and Countermeasures Center (NBACC), US Department of Homeland Security2008980
Integrated Research Facility at Fort Detrick (IRF - Frederick), National Institutes of Health (NIH), National Institute of Allergy and Infectious Diseases (NIAID)20131305
US Army Medical Research Institute of Infectious Diseases (USAMRIID), US Army Medical Research and Materiel Command, Department of Defense19691186
National Emerging Infectious Diseases Laboratories (NEIDL), Boston University20171202
Canada2Vaccine and Infectious Disease Organization, Centre for Pandemic Research, University of Saskatchewan2024unknown
National Microbiology Laboratory (NML), Public Health Agency of Canada1999185
AsiaChina4High-Level Biosafety Primate Experimental Center, Institute of Medical Biology, Chinese Academy of Medical Sciences20193000
Wuhan Institute of Virology, Chinese Academy of Sciences2016200
Chinese Center for Disease Control and Prevention, National Health CommissionUnder construction Pending
Chinese National High Containment Facilities for Animal Diseases Control and Prevention, Harbin Veterinary Research Institute201817000
India4Microbial Containment Complex (MCC), National Institute of Virology2012848
National Institute of High-Security Animal Diseases (NIHSAD), Indian Council of Agricultural Research2000unknown
Advanced Biological Defence Research Centre (ABDRC)Under construction Pending
Rajiv Gandhi Centre for Biotechnology (RGCB)Under construction Pending
Japan2Murayama Annex, National Institute of Infectious Diseases (NIID)2015unknown
National Research Center for the Control and Prevention of Infectious Diseases, Nagasaki University2021unknown
Taiwan, China1Institute of Preventive Medical Research (IPMR), National Defense Universityunknownunknown
Korea1Osong BSL-4 Laboratory, Korea Centers for Disease Control and Prevention Agency2017300
Saudi Arabia1National Health Laboratory, Saudi Ministry of HealthPendingPending
Singapore1Defence Science Organisation (DSO) National Laboratories2025Pending
Philippines1Virology Institute of the Philippines2024Pending
AfricaSouth Africa1Special Pathogens Unit, National Institute for Communicable Diseases (NICD)1979unknown
Gabon1International Center for Medical Research of Franceville (CIRMF)2008unknown
Côte d’Ivoire1Institut Pasteur de Côte d’IvoirePendingPending
OceaniaAustralia4Australian Centre for Disease Preparedness (formerly Australian Animal Health Laboratory), Commonwealth Scientific and Industrial Research Organization (CSIRO)1985567
Emerging Infections and Biohazard Response Unit (EIBRU), Westmead Hospital200786
Queensland Health Forensic and Scientific Services (QHFSS)2007150
National High-Security Quarantine Laboratory (NHSQL), Peter Doherty Institute for Infection and Immunity201490
South AmericaBrazil1Pan American Foot and Mouth Disease Center (PANAFTOSA)2021unknown

References

  1. Lu, J.; Wang, R.; Cao, G. Protection zone and air tightness requirements for level-4 biosafety laboratories. HVAC 2018, 48, 15–20. [Google Scholar] [CrossRef]
  2. Furuyama, W.; Nanbo, A. Introduction of high containment laboratories in abroad. Uirusu 2022, 72, 139–148. [Google Scholar] [CrossRef]
  3. Song, Q.; Ding, C.; Chen, F.; Zhang, Z. Construction and development status of international biosafety level 4 laboratory and suggestions to China. World Sci. Technol. Res. Dev. 2021, 43, 169–181. [Google Scholar] [CrossRef]
  4. National Development and Reform Commission (NDRC); Ministry of Science and Technology (MOST). High-level Biosafety Laboratory System Construction Plan (2016-2025). China Pharm. Biotechnol. 2017, 12, 83. [Google Scholar]
  5. Yuan, Z. Current status and future challenges of high-level biosafety laboratories in China. J. Biosaf. Biosecur. 2019, 1, 123–127. [Google Scholar] [CrossRef]
  6. Tang, S.; Liu, W. Research on factors influencing the gas permeability of concrete. In Proceedings of the 26th National Conference on Structural Engineering, Changsha, China, 20 October 2017. [Google Scholar]
  7. Liu, Z.; Sun, W.; Zhou, X. Research on rapid testing method for gas diffusion coefficient of concrete. Concrete 2005, 11, 4–6+10. [Google Scholar] [CrossRef]
  8. Yang, J.; Liu, C.; Jiang, J. Application of stainless steel envelope to high-level bio-safety laboratories. HVAC 2021, 51, 70–72. [Google Scholar] [CrossRef]
  9. ISO 9972:2015; Thermal Performance of Buildings—Determination of Air Permeability of Buildings—Fan Pressurization Method. International Organization for Standardization: Geneva, Switzerland, 2015.
  10. ASTM E779-19; Standard Test Method for Determining Air Leakage Rate by Fan Pressurization. ASTM International: West Conshohocken, PA, USA, 2019.
  11. Li, Y.; Lu, Y.; Cao, G. Discussion and research on correlation of two air tightness testing methods in high-level biosafety laboratory envelope air tightness tests. HVAC 2023, 03, 31–36. [Google Scholar] [CrossRef]
  12. Speranza, E.; Caballero, I.; Honko, A.N.; Johnson, J.C.; Bohannon, J.K.; DeWald, L.E.; Gerhardt, D.M.; Sword, J.; Hensley, L.E.; Bennett, R.S.; et al. Previremic identification of Ebola or Marburg virus infection using integrated host-transcriptome and viral genome detection. mBio 2020, 11, e01157-20. [Google Scholar] [CrossRef]
  13. GB 19489-2008; General Requirements for Laboratory Biosafety. China National Accreditation Center for Conformity Assessment (CNAC). China CDC: Beijing, China, 2008; pp. 7–11, 23–24.
  14. China Daily. China Builds World-Class Virus Lab to Study Deadliest Pathogens. 2017. Available online: http://world.chinadaily.com.cn/2017-02/23/content_34074282.htm (accessed on 23 February 2017).
  15. Hu, L.; Jin, A.-J.; Zhang, K. Biological protection test of facilities and key equipment in BSL-4 laboratory. Chin. Med. Biotechnol. 2018, 13, 104–109. [Google Scholar] [CrossRef]
  16. GB 50346-2011; Technical Specification for Biosafety Laboratory Construction. China Academy of Building Research: Beijing, China, 2012; pp. 5–9, 32.
  17. Chen, W.; Su, Y.; Chen, Z.; Li, W.; Yin, Y.; Wen, L.; Li, R.; Chen, W. Innovative practice of key technologies in nucleic acid detection laboratory of gas membrane building structure. Sci. Discov. 2022, 10, 7–16. [Google Scholar] [CrossRef]
  18. Wang, G.; Fang, J.; Yan, C.; Huang, D.; Hu, K.; Zhou, K. Advancements in smart building envelopes: A comprehensive review. Energy Build. 2024, 312, 114190. [Google Scholar] [CrossRef]
  19. Xu, J.; Zhang, Y.; Li, W. Gas permeability and microstructure evolution of fiber-reinforced concrete under negative pressure. Build. Environ. 2022, 215, 108921. [Google Scholar] [CrossRef]
  20. Liu, M. Effect of Low Vacuum Environment on Gas Permeability of Concrete and Its Mechanism. Ph.D. Thesis, Tongfang Knowledge Network (Beijing) Technology Co., Ltd., Beijing, China, 2023. [Google Scholar] [CrossRef]
  21. Ren, S.; Zhang, X.; Che, J.; Chen, S.; Leng, B. Study on the effect of admixtures on airtightness of concrete. New Build. Mater. 2023, 50, 148–150. [Google Scholar] [CrossRef]
  22. Huang, C.; Ding, B.; Ou, Z.; Feng, R. Influence of defoamer on the properties and pore structure of cementitious grout for rebar sleeve splicing. Buildings 2023, 13, 170. [Google Scholar] [CrossRef]
  23. Cai, J. Study on the effect of defoamer and the process of “First Elimination and then Introduction” on the apparent bubbles of concrete structure. Guangdong Build. Mater. 2024, 40, 15–18. [Google Scholar] [CrossRef]
  24. Bai, G.; Li, X.; Lu, X.; Chen, X.; Liu, Y. The preparation and properties of airtight agent for concrete and its microstructure analysis. New Build. Mater. 2018, 45, 102–107. [Google Scholar] [CrossRef]
  25. Lian, X. Construction technology of gas-tightness high performance concrete with bucket-based. China Concr. Cem. Prod. 2016, 5, 80–82. [Google Scholar] [CrossRef]
  26. Yang, G. Application of concrete pouring construction technology in civil engineering construction. Brick-Tile 2024, 9, 169–171. [Google Scholar] [CrossRef]
  27. Wu, W. Pouring and vibrating of concrete. J. Liaoning Prov. Coll. Commun. 2005, 4, 14–15. [Google Scholar] [CrossRef]
  28. Zhang, G. Research on the influence of welding materials on process quality. South. Agric. Mach. 2020, 51, 157–158. [Google Scholar] [CrossRef]
  29. Gorshkova, O. New technologies in welding production. Sovrem. Naukoemkie Tekhnol. (Mod. High Technol.) 2021, 2, 14–18. [Google Scholar] [CrossRef]
  30. Liu, G.; Chen, S. A review of the welding process of dissimilar steel. China High-Tech Enterp. 2016, 25, 83–84. [Google Scholar] [CrossRef]
  31. EN 13829:2000; Thermal Performance of Buildings—Determination of Air Permeability of Buildings—Fan Pressurization Method. European Committee for Standardization (CEN): Brussels, Belgium, 2000.
  32. ISO 10648-2:1994; Containment Enclosures: Part 2: Classification According to Leak Tightness and Associated Checking Methods. International Organization for Standardization: Geneva, Switzerland, 1994.
  33. World Health Organization. Laboratory Biosafety Manual, 4th ed.; World Health Organization: Geneva, Switzerland, 2020; Available online: https://www.who.int/publications/i/item/9789240011311 (accessed on 20 December 2020).
  34. Kumar, A.P.; Singh, R.P. Bio-nanocomposites for food packaging applications. Prog. Polym. Sci. 2008, 33, 1180–1223. [Google Scholar] [CrossRef]
  35. Thakur, V.K.; Thakur, M.K. Recent advances in graft copolymerization and applications of chitosan: A review. ACS Sustain. Chem. Eng. 2014, 2, 2637–2652. [Google Scholar] [CrossRef]
  36. Panta, J.; Rider, A.N.; Wang, J.; Yang, C.H.; Hugh Stone, R.; Taylor, A.C.; Brack, N.; Cheevers, S.; Zhang, Y.X. High-performance carbon nanofiber reinforced epoxy-based nanocomposite adhesive materials modified with novel functionalization method and triblock copolymer. Compos. Part B Eng. 2023, 249, 110401. [Google Scholar] [CrossRef]
  37. Wang, Y.; Wang, J.; Huang, L.; Ding, X.; Chen, Z.; Ren, C.; Hao, W.; Ma, L.; Zhang, D. Photothermally activated self-healing coatings for corrosion protection: A review. Prog. Org. Coat. 2023, 185, 107886. [Google Scholar] [CrossRef]
  38. Kalogeras, I.M.; Hagg Lobland, H.E. The nature of the glassy state: Structure and transitions. J. Mater. Educ. 2012, 34, 69–94. [Google Scholar]
  39. Rastogi, P.; Kaushal, R. Acrylic polymers in healthcare applications. Polym. Adv. Technol. 2018, 29, 41–54. [Google Scholar] [CrossRef]
  40. Ahmed, S.; Salehi, S.; Ezeakacha, C.; Teodoriu, C. Experimental investigation of elastomers in downhole seal elements: Implications for safety. Polym. Test. 2019, 76, 350–364. [Google Scholar] [CrossRef]
  41. Yang, S.T.; Liu, Y.; Wang, Y.W.; Cao, A. Biosafety and bioapplication of nanomaterials by designing protein-nanoparticle interactions. Small 2013, 9, 1635–1653. [Google Scholar] [CrossRef] [PubMed]
  42. Nel, A.; Xia, T.; Madler, L.; Li, N. Toxic potential of materials at the nanolevel. Science 2006, 311, 622–627. [Google Scholar] [CrossRef] [PubMed]
  43. Morgan, A.B.; Wilkie, C.A. Flame Retardant Polymer Nanocomposites; Wiley: Hoboken, NJ, USA, 2014. [Google Scholar] [CrossRef]
  44. Schartel, B. Phosphorus-based flame retardancy mechanisms—Old hat or a starting point for future development? Materials 2010, 3, 4710–4745. [Google Scholar] [CrossRef]
  45. Zheng, X.; Cooper, E.; Gillott, M.; Wood, C. A practical review of alternatives to the steady pressurisation method for determining building airtightness. Renew. Sustain. Energy Rev. 2020, 132, 110049. [Google Scholar] [CrossRef] [PubMed]
  46. JIS A 2201:2018; Method for Measurement of Air Permeability of Buildings. Japanese Standards Association: Tokyo, Japan, 2018.
  47. ATTMA TS1:2022; Measuring Air Permeability of Building Envelopes (Dwellings and Non-Dwellings). Air Tightness Testing & Measurement Association: Northampton, UK, 2022.
  48. CAN/CGSB-149.15:2020; Determination of the Airtightness of Building Envelopes by the Fan Depressurization Method. Canadian General Standards Board: Ottawa, ON, Canada, 2020.
  49. Zhou, Q.; Meng, L.; Chen, Q. Case analysis of biosafety level-4 mode laboratory design. HVAC 2022, 7, 69–73. [Google Scholar] [CrossRef]
  50. Liu, W.; Song, J.; Zhao, H.; Cui, Z.; Zhang, S.; Qiao, Y.; Cao, C.; Li, W. Mechanically stable and superhydrophobic nano-SiO2@silane/silicate coating for enhanced impermeability of mortar. Constr. Build. Mater. 2025, 470, 140541. [Google Scholar] [CrossRef]
  51. Wang, Y.; Miao, J.T.; Chen, J.B.; Chai, H.Y.; Zhu, C.Y.; Tang, H.A.; Gan, Y. Study on contaminant distribution in a mobile BSL-4 laboratory based on multi-region directional airflow. Environ. Sci. Pollut. Res. 2022, 29, 12100–12114. [Google Scholar] [CrossRef] [PubMed]
  52. Cao, G.; Wang, R.; Zhai, P. Discussion on building envelope air tightness test of high-level biosafety laboratories. HVAC 2016, 12, 74–79. [Google Scholar] [CrossRef]
  53. Van Linden, S.; Van Den Bossche, N. Airtightness of sealed building joints: Comparison of performance before and after artificial ageing. Build. Environ. 2020, 180, 107010. [Google Scholar] [CrossRef]
  54. Xia, H.; Huang, Y.; Ma, H.; Liu, B.; Xie, W.; Song, D.; Yuan, W. Biosafety Level 4 Laboratory User Training Program, China. Emerg. Infect. Dis. 2019, 25, 1457–1464. [Google Scholar] [CrossRef]
  55. Richmond, J.Y.; McKinney, R.W. (Eds.) Biosafety in Microbiological and Biomedical Laboratories, 6th ed.; U.S. Department of Health and Human Services: Washington, DC, USA, 2020. Available online: https://www.cdc.gov/labs/bmbl/index.html (accessed on 20 December 2020).
  56. Le Duc, J.W.; Anderson, K.; Bloom, M.E.; Estep, J.E.; Feldmann, H.; Geisbert, J.B.; Geisbert, T.W.; Hensley, L.; Holbrook, M.; Jahrling, P.B.; et al. Framework for leadership and training of biosafety level 4 laboratory workers. Emerg. Infect. Dis. 2009, 15, e73. [Google Scholar] [CrossRef] [PubMed]
  57. Klimpel, D.; Meyer, V.; Rziha, H.-J. Testing the integrity of high-containment laboratories: Aerosol challenge studies with Bacillus atrophaeus spores. Appl. Biosaf. 2013, 18, 67–74. [Google Scholar] [CrossRef]
  58. Dimmick, R.L.; Fogl, W.F.; Chatigny, M.A. Potential for accidental microbial aerosol transmission in the biology laboratory. In Proceedings of a Conference Held at the Asilomar Conference Center, Pacific Grove, CA, USA, 22-24 Januray 1973; Hellman, A., Oxman, M.N., Pollack, R., Eds.; Biohazards in biological research; Cold Spring Harbor Laboratory: New York, NY, USA, 1973; pp. 246–266. [Google Scholar]
Figure 1. Number of BSL-4 labs by country.
Figure 1. Number of BSL-4 labs by country.
Buildings 15 02314 g001
Figure 2. Number of BSL-4 labs in each region by time of construction.
Figure 2. Number of BSL-4 labs in each region by time of construction.
Buildings 15 02314 g002
Figure 3. Concrete construction process flowchart.
Figure 3. Concrete construction process flowchart.
Buildings 15 02314 g003
Table 1. Global Distribution and Airtightness Practices of BSL-4 Laboratories.
Table 1. Global Distribution and Airtightness Practices of BSL-4 Laboratories.
RegionCountryNo.Representative FacilitiesYearArea (m2)Airtightness Standards
/Techniques
Key Challenges
EuropeUK7Public Health England (PHE)1974105ISO 9972:2015, EN 13829:2000; Stainless steel welding, Epoxy coatingsCommon: High initial costs (materials and welding);
Specific: Aging infrastructure requires specialized retrofitting.
Germany4Bernhard Nocht Institute (BNI)2014400Airtight concrete additives, Dynamic pressure control systemsCommon: High operational costs;
Specific: Stringent energy efficiency requirements increase the complexity of HVAC systems.
North AmericaUSA11NIH Integrated Research Facility (IRF)20081145ASTM E779-19; Composite materials, HEPA filtration systemsCommon: Regulatory compliance burdens;
Specific: Large facility size amplifies joint leakage risks.
AsiaChina4Wuhan Institute of Virology2016200GB 19489-2008; Steel/concrete hybrid structuresCommon: Technician training deficiencies;
Specific: Thermal expansion mismatch in hybrid structures.
India4Microbial Containment Complex (MCC)2012848ISO 10648-2; Gasket-sealed doorsCommon: Funding gaps;
Specific: Tropical climate accelerates gasket degradation.
AfricaSouth Africa1NICD Special Pathogens Unit1979N/ALimited data; Reliance on international collaborationsCommon: Resource constraints;
Specific: Outdated facilities require donor-funded upgrades.
OceaniaAustralia4Australian Centre for Disease Preparedness1985567Laser welding technology, Smart pressure monitoringCommon: High operational costs;
Specific: Geographical isolation increases parts replacement time.
Notes: “N/A” indicates unavailable data Data current as of 2024; some facilities are under construction. Regional totals include both operational and planned facilities.
Table 2. Commonly used concrete admixtures.
Table 2. Commonly used concrete admixtures.
NamePrinciple of ActionMaterial EfficacyOther
Water reducing agentA typical surfactant that adsorbs at the gas/liquid interface, effectively reducing surface tension and increasing the strength of the liquid films between foam bubbles, thereby improving foam stability.Incorporation of water-reducing agents is beneficial to improve the airtightness of concrete specimens, among which the sulfonate water-reducing agent is the most effective one [21].The uneven size and irregular shape of foam may affect the mechanical properties of concrete.
DefoamerUsing defoamers can refine the pore size and thus reduce the gas permeability of concrete.As the dosage of defoamer increases, the workability of the concrete mixture decreases. Additionally, the difference in setting time decreases, while the compressive strength ratio first increases and then decreases. The permeability coefficient of hardened concrete shows a decrease followed by an increase. Organosilicon defoamer has a notably stronger effect on enhancing concrete airtightness [21].Mercury pressure test results indicate that the defoamer increased the pore volume of the paste in the pore size range of 6–30 nm, while it decreased the pore volume in the range of 30–60 µm. However, in the pore size range of 60–300 µm, the pore volume increased at defoamer dosages of 0.0025% and 0.0075%, and the pore volume of the cement slurry first reduced and then slightly increased at defoamer dosages of 0.005% and 0.001% [22].
Air-entraining agentAdding an air-entraining agent can effectively improve the airtightness of concrete.As the dosage of the air-entraining agent increases, the permeability coefficient of the concrete specimen first decreases and then increases.Cai (2024) [23] studied the joint effects of defoamers and air-entraining agents, proposing that the process of “first elimination, then air-entraining” can effectively regulate the air content of concrete, thus controlling the apparent quality of concrete components.
Air sealing agentThe amount of air sealing agent has a greater impact on the strength and air permeability coefficient of concrete. Increasing the dosage of air sealing agent reduces the compressive strength and air permeability coefficient of concrete, while the lowest dosage of air sealing agent results in slightly poorer concrete flowability.Bai et al. (2018) [24] prepared a new type of concrete airtightness agent using the pre-emulsified seed emulsion polymerization method, which is beneficial for improving the strength and airtightness of concrete.
Table 3. Cost Comparison of PHE and Wuhan Enclosure Structures.
Table 3. Cost Comparison of PHE and Wuhan Enclosure Structures.
PHE All-Stainless-Steel EnclosureWuhan Steel/Concrete Hybrid Enclosure
Initial Construction:
Total CostUSD 950–1600/m2USD 370–600/m2
Material Cost304 Stainless steel: USD 650–900/m2
(316 L: +20–30%)
Epoxy coating: USD 50–80/m2
Structural steel (Q235/Q355): USD 150–250/m2
Concrete (C30–C50): USD 80–120/m2
Fireproofing: USD 30–50/m2
Process CostLaser welding: USD 150–200/m2
Precision joints: USD 100–150/m2
Conventional welding: USD 60–100/m2
Formwork: USD 50–80/m2
Cost Multiple2–3×1× (baseline)
Post-Construction Maintenance:
Inspection FrequencyEvery 10 yearsEvery 5 years
Maintenance CostCoating refurbishment: USD 50–80/m2/cycle
Weld inspection
Crack repair: USD 20–40/m2/cycle
Joint sealing
Notes: Data sourced from GB 50346-2011, EN 13829:2000, global market prices, relevant industry reports, etc. All cost data reflects current market conditions. Due to regional price differences, European projects may be increased by 15–20%, while Asian projects may be decreased by 10%.
Table 4. Policy/Economic Factors Driving Enclosure Structure Selection.
Table 4. Policy/Economic Factors Driving Enclosure Structure Selection.
RegionPolicy DriversFunding ProfileDominant Enclosure StructureAirtightness ImpactCost
Ratio *
EUEN 13829:2000 lifecycle requirements
Strict decontamination protocols
High public health budgets
20-year depreciation cycles
Laser-welded stainless steelUltra-low leakage
Excellent chemical resistance
1.0×
(Baseline)
USAASTM E779-19 joint testing mandates
Defense-funded biosafety priorities
Mixed federal/private funding
Emphasis on rapid deploy ability
Composite panel systemsModerate leakage
Reliant on gasket seals
0.8×
ChinaGB 19489-2008 attenuation limits
“Localized innovation” subsidies
State capital projects
5-year budget cycles
Steel/concrete hybridVariable performance
Thermal cracking risks
0.6×
IndiaISO 10648-2 compliance for aid projects
Tropical climate adaptations
International grants (e.g., WHO)
< USD 50 m project caps
Gasket-sealed color steelHigh leakage
Frequent gasket replacement
0.3×
AfricaDonor-mandated EU/US standards
Emergency outbreak response needs
>80% foreign-funded
< USD 20 m/total facility
Modular prefabricated unitsPoor long-term sealing
Reliant on silicone sealants
0.2×
* Cost ratio normalized to EU stainless steel baseline. Data synthesized from [4,9,10,13,16,31,32] and Table 1 case studies.
Table 5. Recommended ratings for airtightness test methods.
Table 5. Recommended ratings for airtightness test methods.
Method NameRecommended RatingMethod DescriptionReason for Recommendation
Pressure Decay Method★★★★★Apply a certain pressure to the product or system being tested, record the initial pressure value, then turn off the gas or liquid supply source and measure the pressure change over a period of time to determine airtightness.This method enables quantitative airtightness assessment and is the most widely adopted in BSL-4 laboratories. It is suitable for testing the airtightness of high-level biosafety laboratories, such as BSL-3 or BSL-4 laboratories.
Helium Mass Spectrometry Leak Detection Method★★★★★Apply gas around the product or test sample and use a leak detector to detect gas leakage, thereby assessing its airtightness performance.The most reliable method, offering advantages of high accuracy, fast response, locatable leaks, and environmental adaptability. However, it requires a specialized helium mass spectrometry leak detector, which is relatively expensive.
Soap Liquid Method★★★★☆Apply soap liquid to the surface of the tested component, then fill it with gas at a certain pressure. The gas will blow soap bubbles through the leakage point, thus exposing the leakage location and observing whether there are bubbles generated to determine the airtightness.Simple and easy, safe and reliable, can determine the leak location. However, the bubble formation can be influenced by leakage size and pressure difference. If the leakage volume is small, bubble formation takes longer, and bubbles may be too small or fragile to observe.
Heating Method★★★★☆Utilizing the thermal expansion and contraction properties of gas, the component is heated to expand the internal gas, then observe whether there are bubbles or water column formation to determine the airtightness.Simple to operate, no complex equipment required, and bubbles or water columns can be directly observed. However, it is unsuitable for temperature-sensitive equipment and lacks sensitivity for detecting small leaks. Often used for chemical laboratory equipment.
Flow Rate Method★★★★☆Intermittently inject gas at a certain pressure into the tested component, use a mass flowmeter or volume flowmeter to detect changes in gas flow rate, and determine whether the leakage rate of the component is within the required acceptable range.This system has a simple design, wide applicability, accurate test results, and can quantitatively assess airtightness performance. However, it can only detect overall airtightness and cannot locate the leakage position.
Water Pressure Method★★★☆☆Based on the principle of pressure, the component is submerged in water, subjected to a certain water pressure, and observed for water ingress or the formation of bubbles to determine its airtightness.This method is simple and easy to perform, enabling direct visualization of leak points. However, once water enters the component, it may cause irreparable damage, and the water must be dried, wasting manpower and resources.
Note: 5 stars—Excellent, 4 stars—Good, 3 stars—Average, 2 stars—Below average, 1 star—Poor.
Table 6. Comparative analysis of international building airtightness testing standards.
Table 6. Comparative analysis of international building airtightness testing standards.
CriteriaISO 9972:2015 [9]EN 13829:2000 [31]ASTM E779-19 [10]JIS A 2201:2018 [46]ATTMA TS1 (2022) [47]CAN/CGSB-149.15 (2020) [48]
Regional ScopeInternational benchmark standardMandatory in EU member statesMainstream in North AmericaJapan-specificUK construction standardCanadian national standard
Test MethodSingle-mode fan pressurizationDual-mode (Method A/B)Single-point/Multi-point optionsISO 9972 + Japanese adaptationResidential/Non-residential classificationSingle-zone/Multi-zone testing
MetricsQ50 (m3/h)
ACH50 (h−1)
A50 (m2)
Same as ISO 9972CFM50 (ft3/min)
ACH50 (h−1)
ELA (in2)
Q50 (m3/h)
ACH50 (h−1)
C-value (cm2/m2)
Q50 (m3/h)
ACH50 (h−1)
ELA (m2)
Q50 (m3/h)
ACH50 (h−1)
ELA (cm2)
EquationsQ = C·(ΔP)^n
ACH50 = Q50/V
A50 = Q50/(0.61·√50)
Same as ISO 9972Imperial unit adaptation
ELA = CFM50/(0.61·√50)
Same as ISO 9972
C-value = ELA/floor area
Same as ISO 9972Same as ISO 9972
Climate zone adjustments
ComplianceReferenced by other standardsIncorporated in EU regulationsUsed for US certificationJapanese Building Code referenceUK Building RegulationsCanadian National Building Code
Special NotesNoneDesign verification method BSingle point allowedMandatory C-value reportingBuilding type differentiationAdaptation to extreme climates
Abbreviations: ACH50: Air Changes per Hour at 50 Pa; ELA: Equivalent Leakage Area; C-value: Leakage area per unit floor area (Japan-specific). Unit Consistency: ISO/EN/JIS/ATTMA/CGSB use metric units (m3/h, m2); ASTM uses imperial units (CFM, in2).
Table 7. Laboratory airtightness requirements.
Table 7. Laboratory airtightness requirements.
Clause No.Airtightness Requirements
GB 194896.4.8The airtightness of the enclosure of the laboratory protection zone shall meet the following requirements: under the condition of closing all access to the test room and maintaining the temperature in the room at the upper limit of the design range, when the air pressure in the room rises to 500 Pa, the natural decay of the air pressure within 20 min shall be less than 250 Pa.
GB 5034610.1.6 No.3Level 4 biosafety laboratories shall use the primary laboratory pressure decay test method under both positive and negative pressure conditions.
3.3.2The relative negative pressure of the main laboratory room is −500 Pa, and after 20 min of natural decay, the relative negative pressure should not exceed −250 Pa.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Peng, G.; Shi, X.; Hu, R.; Wang, X.; Zhan, J. Research and Prospects of Airtightness of Biological Laboratory Enclosures: Influencing Factors and Evaluation Methods. Buildings 2025, 15, 2314. https://doi.org/10.3390/buildings15132314

AMA Style

Peng G, Shi X, Hu R, Wang X, Zhan J. Research and Prospects of Airtightness of Biological Laboratory Enclosures: Influencing Factors and Evaluation Methods. Buildings. 2025; 15(13):2314. https://doi.org/10.3390/buildings15132314

Chicago/Turabian Style

Peng, Geqing, Xiaoshuang Shi, Ruihan Hu, Xiaoli Wang, and Jinsheng Zhan. 2025. "Research and Prospects of Airtightness of Biological Laboratory Enclosures: Influencing Factors and Evaluation Methods" Buildings 15, no. 13: 2314. https://doi.org/10.3390/buildings15132314

APA Style

Peng, G., Shi, X., Hu, R., Wang, X., & Zhan, J. (2025). Research and Prospects of Airtightness of Biological Laboratory Enclosures: Influencing Factors and Evaluation Methods. Buildings, 15(13), 2314. https://doi.org/10.3390/buildings15132314

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop