Next Article in Journal
Building Information Modelling (BIM) Acceptance and Learning Experiences in Undergraduate Construction Education: A Technology Acceptance Model (TAM) Perspective—An Australian Case Study
Previous Article in Journal
Intelligent Techniques Applied in Infrastructure, Engineering, and Construction
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Anti-Freezing and Operation Optimization Design of Air-Conditioning Systems for Industrial Plants in Severely Cold Regions

1
Laboratory of Building Environment and New Energy Resources, Faculty of Infrastructure Engineering, Dalian University of Technology, Dalian 116000, China
2
School of Architecture and Art, Dalian University of Technology, Dalian 116000, China
*
Author to whom correspondence should be addressed.
Buildings 2025, 15(11), 1801; https://doi.org/10.3390/buildings15111801
Submission received: 11 April 2025 / Revised: 20 May 2025 / Accepted: 22 May 2025 / Published: 24 May 2025
(This article belongs to the Section Building Energy, Physics, Environment, and Systems)

Abstract

This study addresses the freeze-up problem in HVAC system heat exchangers of industrial buildings in severely cold regions by proposing a collaborative anti-freeze control strategy based on multi-objective optimization. Taking a diesel engine laboratory as the research case, key freezing-inducing factors were identified through system performance analysis and fault diagnosis. An innovative interlocked anti-freeze control system was developed by integrating electric heating with dynamic regulation of bypass air volume. Utilizing gray relational analysis, the optimal interlock control scheme was selected from four alternatives based on a comprehensive performance evaluation. Multi-objective optimization through the NSGA-II algorithm was performed on parameters including the set temperature, water flow rate, and fresh air volume, achieving coordinated optimization of energy consumption (11.4% reduction compared to pre-optimization) and thermal comfort. TRNSYS-based simulation verification demonstrated that the system maintains a 94.71% freeze protection time assurance rate under extreme operating conditions, effectively resolving the reliability deficiencies of traditional solutions in severely cold environments. This research provides a novel method for industrial building HVAC system anti-freeze design that harmonizes energy efficiency and comfort performance.

1. Introduction

The conflict between pollutant control and ventilation energy consumption in industrial buildings is particularly acute in cold regions, where industrial equipment and personnel generate large quantities of pollutants during their work. An experimental study by Nina Szczepanik-Scislo et al. [1] monitored the effects of radioactive radon gas (Rn-222), carbon dioxide (CO₂), and thermal comfort parameters in a typical office environment (temperature and humidity), revealing the significant effect of indoor personnel activities on the accumulation of pollutants. Indoor air purifiers have been emphasized as a method that can improve indoor air quality, especially in more polluted buildings, such as industrial buildings. Still, for industrial buildings, which are larger and have more complex pollutants, the efficiency of air purifiers is substandard and produces ozone gas problems [2]. Although the use of natural ventilation in the case of good outdoor air quality can provide relatively good air quality, in the winter, for buildings such as industrial plants, which require heating, it causes high energy consumption. Therefore, the method of mechanical ventilation, on the other hand, is currently the main method used to maintain indoor air quality and thermal comfort in most buildings located in cold regions.
Although the use of mechanical ventilation can significantly improve indoor air quality, industrial buildings have a higher demand for fresh air supply for HVAC systems due to their large space volume and the characteristics of internal pollution sources. In cold regions with persistent low temperatures in the winter, the heat exchanger of the air-conditioning system is very susceptible to freezing. The same problem is prevalent in hospitals, laboratories, and other places that require a large amount of fresh air exchange, which may result in significant economic losses. Current research mainly focuses on CFD simulation and theoretical analysis of heat exchanger tube freezing mechanisms, and the representative results include the following: M. Sugawara et al. [3] used PHOENICS code for numerical analysis and found that the beginning of freezing depends largely on the airflow temperature, velocity, and initial temperature of the water, but the rate of freezing after the beginning of freezing depends on the temperature and velocity of the airflow and is not sensitive to the water’s initial temperature. M. Tago et al. [4] investigated the effect of adiabatic insulation on pipe freezing. Wang et al. [5] proposed an air-cooled heat exchange anti-freezing prediction model, based on which the effects of the ambient temperature, airflow velocity, inlet temperature, and airflow pattern on the freezing characteristics were analyzed. However, these studies are often based on idealized assumptions and fail to fully consider the actual operating variables, such as equipment aging and environmental fluctuations, resulting in significant deviations between simulation results and actual performance.
The optimization of anti-freezing measures requires synergistic improvement of heat exchanger design and system operating parameters. There are many heat exchanger anti-freezing measures available worldwide, such as preheating outdoor air to prevent internal freezing of the heat exchanger, preventing internal freezing of the heat exchanger by using a bypass air circuit, and using an air-conditioning system defrosting mode to prevent defrosting of the heat exchanger surface. For the problem of internal heat exchanger freezing, Marek Jaszczur et al. [6] applied different ratios of fresh air to exhaust air using warm air to heat the surface of the heat exchanger. The analyzed system showed a significant decrease in system efficiency under unfavorable winter conditions. The results indicated that this type of solution should not be applied. Chen et al. [7] analyzed the operating conditions and problems of air-conditioning systems in established public buildings in cold and severe winter areas and introduced a heat exchange method to recycle the exhaust air and solve the problem of low air temperatures. Wang et al. [8] utilized a macroscopic heat exchanger model based on the balance of heat loads of the recirculating water and the ambient air. Deng et al. [9] used a deflector to mitigate the risk of freezing in a side-stream power plant, and Yan et al. [10] explored engineering solutions such as auxiliary heat exchanger configuration with forced water circulation. Andrzej Jedlikowski et al. [11] confirmed that a completely open bypass technique does not provide complete freeze protection at sub-zero outdoor air temperatures. It is worth noting that most of the existing anti-freeze strategies focus on a single technology path and lack a comprehensive assessment of scenario suitability, energy efficiency, and process compatibility.
The use of mechanical ventilation can significantly improve indoor air quality, but at the same time, it also increases the fresh air load, thus increasing the energy consumption of air-conditioning system operation. Modern industrial production processes have high requirements for the air environment, and creating a production environment with good air quality usually requires a large amount of fresh air. How to reduce the energy consumption of air-conditioning systems in industrial plants is a major challenge in the study of energy efficiency in industrial buildings. The optimization of HVAC system energy efficiency and control accuracy has been prompted to become a key research direction. Scholars have used multi-objective optimization algorithms to balance energy efficiency and comfort needs, such as Wei et al. [12], who introduced a particle swarm optimization (PSO) method to solve the multi-objective optimization problem of HVAC systems in typical office facilities. Nasruddin [13] used artificial neural networks combined with a multi-objective genetic algorithm (MOGA) to propose a combined HVAC system that includes VAVs and radiant systems simultaneously. The optimization of a dual-cooler combination HVAC system working with PPD and annual building energy consumption was selected as the objective function, and the decision variables included several parameters, such as thermostat settings, passive solar design, and cooler operation control. Li [14] et al. comprehensively analyzed the composition, working principle, and characteristics of the central air-conditioning, air-handling system and established the minimum total energy consumption of the air-handling system and the PPD values in the minimum-value multi-objective optimization model. The NSGA-II algorithm was used to optimize the established multi-objective function to obtain the optimal set of solutions that satisfy the two conditions. Sofia Yfanti et al. (2020) [15] proposed an “event-driven” framework that aims to improve building energy efficiency by monitoring and intervening in user behavior. The framework defines user behaviors as discrete “events” (e.g., inappropriate use of equipment) that are tracked, intervened, and fed back to achieve energy efficiency goals. Li [16] et al. created a back-propagation neural network (BPNN) model to quickly predict the concentration of air pollution and the degree of thermal comfort, and if these predictions using the BPNN model do not satisfy the setup requirements, then the adaptive multi-objective Particle Swarm Optimizer–Gray Wolf Optimization (AMOPSO-GWO) algorithm is used to determine the best strategy for maximizing indoor air quality, thermal comfort, and energy savings. The BPNN-based AMOPSO-GWO algorithm has high prediction accuracy (>90%). The average reduction in air pollution concentration, improvement in thermal comfort, and average energy savings were 31%, 45%, and 35%, respectively. However, most of the established studies are for residential buildings, and industrial applications require additional consideration of process flow interference and frost protection constraints, which limit the applicability of the existing models.
Current research leaves some questions about freeze protection solutions for HVAC systems in cold regions. First, existing approaches lack a comprehensive evaluation of their regional adaptability and lifecycle performance, limiting their practical implementation potential. Second, while optimization models have been well developed for civil buildings, they remain inadequate for industrial applications due to insufficient consideration of process flow impacts in retrofit designs. Most critically, current control strategies for fresh air systems during winter operations predominantly rely on oversimplified single-variable optimization approaches, while the development of multi-objective coordinated optimization methods tailored for industrial scenarios lags significantly behind actual engineering needs. These limitations collectively hinder the advancement of effective anti-freezing solutions for industrial HVAC systems in extreme cold environments.
Through in-depth analysis of an industrial building in a severely cold region and its architectural characteristics, this study innovatively constructs a comprehensive retrofit assessment framework that includes anti-freeze performance, process compatibility, and energy efficiency indicators and, for the first time, proposes an innovative electric heating–bypass duct coupling control system for anti-freeze retrofit of air-conditioning systems. At the same time, considering the thermal comfort and energy consumption of industrial buildings, a dual-objective optimization model of energy consumption and thermal comfort is established to optimize the system operating parameters. TRNSYS is also used for comparative performance simulation to quantitatively evaluate the effect of anti-freezing efficiency enhancement, which provides a theoretical basis and technical reference for anti-freezing of air-conditioning systems in buildings under extreme environments around the world.

2. Research on Anti-Freeze Retrofit Program

The project is located in Shenyang, where the winter temperature can drop to as low as −24.8 °C, and the outdoor relative humidity can reach up to 100%. Between October 1 and April 1 of the following year, there are 1075 h when the outdoor temperature is below −10 °C and 3009 h when the outdoor relative humidity exceeds 80%. Therefore, to heat the fresh air to the supply air temperature, the fresh air handling unit needs to have strong heating capabilities. Additionally, preheating should be applied to the fresh air intake to prevent water from freezing inside the heat exchanger tubes. The common fresh air treatment technologies currently available may encounter certain problems when applied in the extreme meteorological conditions of cold regions, as shown in Table 1.
It can be concluded that directly using electric heating is inefficient and costly; when an air-source heat pump directly heats the fresh air, the air temperatures on the condenser and evaporator sides are the same, preventing the heat pump system from starting. Therefore, it cannot be used directly as a heat source for heating the fresh air, and additional preheating equipment is required. The choice of heat recovery technology should be based on the specific conditions.

2.1. Propose a Program

Considering factors such as production processes, site limitations, energy structure, and policy regulations, the following four renovation schemes are proposed:
Scheme A (Original Scheme): bypass duct- and electric heating-linked control for anti-freezing protection (Figure 1): This scheme combines the electric heater preheating method and the bypass method, with both controlled in tandem by a control system. An electric auxiliary heater is installed behind the electric insulation valve at the air-conditioning system inlet. When the outdoor temperature is too low in the winter, the electric heater preheats the fresh air to 0 °C~5 °C. Additionally, a fresh air bypass is used as a double safeguard against freezing. A bypass duct is connected between the duct with the electric insulation valve and the auxiliary electric heater, with an electric regulating valve at the bypass duct inlet. When the fresh air unit detects low hot water flow through the heat exchanger, the valve on the bypass duct is opened, and the induced fan increases the bypass air volume to avoid a large amount of cold air directly contacting the heat exchanger in the air-conditioning system. The remaining fresh air is heated by the heat exchanger and then mixed with the bypassed fresh air to the supply air temperature point before being sent indoors.
Scheme B (Comparison Scheme): installing a natural gas heater for fresh air preheating: The equipment setup includes a GHP (Gas Heat Pump) gas-driven module, two water pumps (flow rate 16 m3/h, head 18 m), an electric air volume regulating valve, an anti-freezing system unit, an indoor air-conditioning box, air ducts, water pipes, and a natural gas pipeline.
Scheme C (Comparison Scheme): replacement with an electric-driven low-temperature air source heat pump with anti-freezing solution and electric preheating: The equipment setup includes two air-source heat pumps (GN-R155ML and GN-R78ML), an electric heater, two water pumps (flow rate 40 m3/h, head 18 m), an electric air volume regulating valve, an anti-freezing system unit, an anti-freezing solution (ethylene glycol + ion-softened water + anti-corrosion and anti-rust additives + anti-foaming agent + dye + stabilizer), an indoor air-conditioning box, air ducts, and water pipes.
Scheme D (Comparison Scheme): installing an air-to-air heat exchanger using flue gas waste heat for fresh air preheating. The equipment setup includes an air-to-air heat exchanger, a fan, an electric air volume regulating valve, an anti-freezing system unit, an indoor air-conditioning box, air ducts, and water pipes.
Based on the samples provided by the equipment manufacturers, the quantitative values for each scheme are shown in Table 2.

2.2. Methodology of the Assessment

The currently commonly used comprehensive evaluation method is the Multi-Level Gray System Method, which is effective in addressing the issue of multi-objective uncertain systems with small samples. After establishing the evaluation system, known information from each air-conditioning system renovation scheme can be used to extract evaluation parameters and evaluate and compare the alternative renovation schemes. The multi-level gray decision-making process flowchart is shown in Figure 2.

2.2.1. Evaluation Indicators

There is currently no universally applicable evaluation system for industrial building air-conditioning renovation schemes. By referencing the more reasonable evaluation index systems of residential building air conditioning and existing building renovation evaluation index systems, an evaluation index system for industrial building air-conditioning renovation schemes that includes both qualitative and quantitative indicators has been constructed.
The construction of an evaluation index system for the renovation of industrial building air-conditioning systems should follow these principles: (1) principle of scientific completeness; (2) principle of simplicity; (3) principle of operability; (4) principle of combining qualitative and quantitative methods; and (5) principle of suitability to local conditions. Based on the Chinese standard GB 50019-2015 “Design Code for Heating, Ventilation, and Air Conditioning in Industrial Buildings” [17], the evaluation indices for air-conditioning anti-freeze renovation are divided into target level, criterion level, and indicator level. These are further categorized into five major modules: safety and reliability, technical evaluation, economic evaluation, operational management, and environmental impact, with secondary indicators further analyzed within these five categories, as shown in Table 3

2.2.2. Judgment Matrix Construction and Eigenroot Calculation

According to the hierarchical analysis method, after constructing the evaluation hierarchy, the pairwise comparison judgment matrix should be constructed to determine the weights of the evaluation indexes at each level, using the scale method proposed by the American operations researcher Prof. T.L. Saaty (T.L. Saaty) in the early 1970s, i.e., the 1–9 scale method, through the relative scales, the indexes are compared with each other, and the indexes are evaluated according to the importance of the degree of the indexes, and ij is the result of the comparison judgment of importance of index i and index j. ij is the result of comparing the importance of indicator i and indicator j. The relative importance scale of the judgment matrix indicators is shown in Table 4.
Experienced HVAC designers, building equipment managers, and HVAC professionals were selected as survey subjects to evaluate the relative importance of each indicator in the judgment matrix. A total of 15 valid questionnaires were collected. The respondents primarily included senior engineers and individuals with master’s degrees or lower. The distribution of the survey experts is as follows: 0 in the AA category, 6 in the A category, and the remaining 9 in other categories. The expert distribution table is shown in Table 5.
The respondents evaluated the relative importance of each indicator based on their experience. After collecting the experts’ relative importance scale tables, judgment matrices for each criterion level were established, named B1, B2, B3, B4, and B5. These matrices were used to assign importance scales to each indicator, calculate their eigenvalues, and determine the weights of each indicator.

2.2.3. Consistency Test

The judgment matrices B1, B2, B3, B4, and B5 were subjected to consistency checks, and the results are shown in Table 6. The Consistency Index (CI) is used to determine the extent of inconsistency; a higher CI value indicates poorer consistency of the judgment matrix. When the CI value is 0, it signifies complete consistency. The Random Consistency Index (RI) is introduced to measure the size of CI. The value of RI is related to the order n of the judgment matrix; as n increases, the likelihood of random deviations from consistency also increases.
All judgment matrices passed the consistency check, indicating that the survey results are reliable and trustworthy. The weights were calculated and integrated into the judgment matrices, forming the quantitative values for the evaluation indicators of the air-conditioning system anti-freezing renovation in Table 7.
A comprehensive evaluation system for air-conditioning system anti-freezing renovation has been established, consisting of both qualitative and quantitative indicators. The weights for each evaluation indicator have been calculated. This evaluation system, which considers the system’s anti-freezing capability, can be used for the optimal selection of air-conditioning system renovation plans in extremely cold regions.

2.3. Program Preference

2.3.1. Gray Correlation Modeling

  • Constructing the evaluation matrix.
When the research object is a single-level model consisting of m indicators, and the research object consists of n schemes with original indicator values forming matrix X, then the m indicators of the i-th scheme form a reference sequence Xik = [Xi1, Xi2, …, Xim], where i = 1, 2, … n, and k = 1, 2, … m.
X = X 11 X 12 X 1 n X 21 X 22 X 2 n X m 1 X m 2 X m n
2.
Non-dimensional processing of evaluation indicator values.
After obtaining the original value matrix, the original data should be processed to become dimensionless, converting the original data into a unified quantitative value between [0,1] to eliminate the influence of different dimensions and magnitudes. Indicators are divided into benefit type and cost type. Benefit-type indicators are those where higher values are better, while cost-type indicators are those where lower values are better. Different dimensionless methods are applied to different evaluation indicators.
The quantitative formula for efficiency-based indicators is:
x i k = x i k x i min x i max x i min
The quantitative formula for cost-based indicators is:
x i k = x i max x i k x i max x i min
In the formula, xik represents the dimensionless value of the k-th indicator for the i-th scheme, and X i m a x and X i m i n denote the maximum evaluation value of the k-th indicator among all schemes.
3.
Calculation of the gray correlation.
The formula for calculating the gray correlation value is as follows:
φ i ( k ) = min i = 1 m min k = 1 n x i k x 0 k + η max i = 1 m max k = 1 n x i k x 0 k x i k x 0 k + η max i = 1 m max k = 1 n x i k x 0 k
In the formula, i = 1, 2, … n; k = 1, 2, … m; and η is the distinguishing coefficient, where η ∈ [0,1]. According to empirical evidence, when η > 0.5, the differences between the association coefficients are relatively small. However, when η ≤ 0.5436, the distinguishing power of the coefficient η is optimal. Therefore, in this study, η is set to 0.5.
After the results are calculated for each correlation value, a matrix of correlation coefficients L can be formed:
L = φ 1 1 φ 2 1 φ n 1 φ 1 2 φ 2 2 φ n 2 φ 1 m φ 2 m φ n m
The matrix of correlation coefficients is multiplied by the matrix of evaluation indicator weights to obtain the correlation matrix R for the evaluation program, where the correlation formula for the i-th program is as follows:
r i = k = 1 m W i k L i k = W i 1 , W i 2 , , W i m φ 1 1 φ 2 2 φ m m

2.3.2. Results

The established evaluation index table for the air-conditioning system anti-freezing modification is used as an evaluation survey form. The four schemes are rated anonymously on a scale of 10 points. The returned questionnaires are compiled into an evaluation value matrix. Based on the constructed evaluation index system, matrix calculations yield the primary index evaluation table for the four schemes. By standardizing the quantitative and qualitative indicators, a unified scale for evaluating the modification schemes is obtained, as shown in Table 8.
Based on the above calculation results, Scheme A has a correlation degree of 0.7512, Scheme B has a correlation degree of 0.7254, Scheme C has a correlation degree of 0.6760, and Scheme D has a correlation degree of 0.6774. The correlation degrees are ranked as rA > rB > rD > rC. This indicates that Scheme A is closer to the ideal solution for the air-conditioning system modification in this study. Among the four modification schemes, Scheme A is the preferred option and is recommended for adoption.

3. Operational Strategy Research

The operation of the electric heating and bypass duct interlocking control system is divided into three phases: (1) During the transition season and early winter, the electric heater is inactive; the bypass valve and heat exchanger adjust airflows to ensure the supply air meets the target temperature. (2) In winter, when the outdoor temperature is above the preheat activation threshold, the electric heater remains off, and the heat exchanger operates at maximum capacity; slight reductions in supply air temperature and indoor comfort may occur if heating is insufficient. (3) When outdoor temperatures drop below the activation threshold, the electric heater preheats the air, with the bypass valve and heat exchanger ensuring adequate mixing; the supply air temperature and comfort may still decrease slightly.
When adopting the third-stage anti-freezing air-conditioning system operation scheme, the electric heater is activated for preheating during very cold winter temperatures. This results in increased system energy consumption and a reduced indoor design temperature, leading to decreased comfort. Therefore, it is crucial to balance comfort and energy consumption within a reasonable range. Given that energy consumption and comfort cannot both be minimized simultaneously and are non-linearly related, this problem can be summarized as a multi-objective optimization issue. Consequently, it is necessary to establish a multi-objective optimization model for the anti-freezing air-conditioning system, including models for total system energy consumption and thermal comfort.
For the multi-objective optimization model, the expression is denoted as:
min f ( x ) = f 1 ( x ) , f 2 ( x ) , , f n ( x ) T s . t . h k ( x ) = 0 , k = 1 , 2 , , L g j ( x ) 0 , j = 1 , 2 , , M a i x i b i , i = 1 , 2 , , P x = x 1 , x 2 , , x P T
where x is the decision variables, and n is the total number of optimization objectives.

3.1. Modeling of Operational Energy Consumption of Anti-Freezing Air-Conditioning Systems

3.1.1. Auxiliary Electric Heaters

The energy consumption of the auxiliary electric heater consists of two parts: the energy used to heat the air and the energy lost due to dissipation. The total energy consumption of the auxiliary electric heater is calculated by summing these two components, as follows:
Q ˙ h e a t e r = m a c p f ( T s e t T h i ) + U A ( T ¯ T e n v ) 3600 η h t r
T ¯ = T h o + T h i 2
where Q ˙ h e a t e r is the auxiliary heater power, kW. ma is the fluid mass flow, kg/h. cpf is the specific heat of air, kJ/kg-K. Tset is the auxiliary heater set temperature, °C. Thi is the auxiliary heater inlet air temperature, °C. Tho is the auxiliary heater outlet air temperature, °C. T ¯ is the average temperature difference between the inlet and outlet, and °C. ηhtr is the auxiliary heater efficiency.

3.1.2. Pumps

Motors are the main energy-consuming components of frequency pumps, based on the law of similarity can be approximated that the pump energy consumption Ppumb is a third-degree polynomial of the flow rate Q, so the frequency pump energy consumption formula is as follows:
P p u m b = a 0 + a 1 m w + a 2 m w 2 + a 3 m w 3
where mw is the actual hot water flow rate, m3/s.

3.1.3. Heat Exchangers

The heat exchanger assumes the fresh air load during the winter operation of the system, and the energy change that occurs when the air is raised from the preheating temperature to the design temperature is calculated as follows:
Q ˙ e x c h a n g e r = m a c p ( T o u t T s e t ) η e x
where Q ˙ e x c h a n g e r is the heat exchanger heat transfer capacity, kW; ma is the air volume through the heat exchanger, m3/s; cp is the specific heat capacity of air; Tout is the air temperature through the heat exchanger, °C; and ηex for the efficiency of the heat exchanger.

3.1.4. Ventilator

With reference to the pump efficiency equation, the bypass fan mathematical equation can be expressed as:
P y f a n = b 0 + b 1 m s + b 2 m s 2 + b 3 m s 3
where a0~a3 and b0~b3 are the model parameters, Pyfan is the bypass fan energy consumption, kW; and ms is the actual airflow, m3/s.
Through the analysis of system operation and energy consumption and the establishment of mathematical models for each component, it is determined that the main energy-consuming equipment of the freeze-proof air-conditioning system is the auxiliary electric heater, the hot water pump, the fresh air bypass fan, and the total energy consumption of the air-conditioning system is the sum of energy consumption of each piece of equipment, so it is possible to set up the objective function of the air-conditioning system’s energy consumption model as follows:
F 1 ( x ) = min P t o t a l = min ( Q ˙ h e a t e r + P p u m p + Q ˙ e x c h a n g e r + P y f a n )
The objective function F1(x) optimization variable is:
x = T s e t , m w , m s , m a
Since it is unreasonable for electrical energy to be used to heat energy, according to the design of the operation program, the working time of the electric heater should be reduced as much as possible when the outdoor temperature is low enough to turn on the electric heating, and the heating capacity of the electric heater will be 405 kW as the electric heater working limit, so the maximum value of the energy consumption objective function constraint is 1202 kW. When the electric heater is turned off, the bypass airflow reaches the maximum, and the temperature of the supply air after mixing is in the range of the specification, the energy consumption of the system is constrained to be 597 kW as the minimum value of the energy consumption objective function.

3.2. Thermal Comfort Modeling of Personnel Activity Areas

In this paper, the Predicted Mean Valuation (PMV) and the Predicted Percentage Dissatisfaction (PPD) of thermal comfort environment were chosen to quantify the thermal comfort of a building [18,19,20,21]. PMV, proposed by Prof. Fanger of Denmark, is a comprehensive judgment index based on empirical equations, which integrates six factors of thermal comfort, namely air temperature, air relative humidity, air flow rate, average radiation temperature, human metabolic rate, and clothing thermal resistance of thermal comfort influence, representing most people to the same indoor environment thermal comfort feeling. The PMV was divided into seven evaluation levels of 3, 2, 1, 0, −1, −2, and −3, which are positive and negative values indicating hot and cold, and values close to 0 indicate higher thermal comfort. The corresponding hot and cold sensations for each level are shown in Table 9 [22].
For the selected thermal comfort evaluation indexes PMV and PPD, a comprehensive evaluation model of thermal comfort is established, and the objective function is as follows:
F 2 ( x ) = min P P D = min f ( P M V )
According to the relevant provisions of the thermal comfort evaluation of the indoor environment of industrial buildings, the evaluation index is expected to be greater than or equal to the average thermal sensation index. The PMV value should be greater than or equal to −1 and should be less than or equal to 1, and the expected percentage of unsatisfied people PPD value should be less than or equal to 27%. Therefore, the range of parameter values in the thermal comfort evaluation model is −1 ≤ PMV ≤ 1 and PPD ≤ 27%.
There are seven unknown variables in the thermal comfort evaluation model, including human energy metabolic rate M, mechanical work done by the human body W, partial pressure of water vapor around the human body Pa, indoor air temperature ta, thermal resistance of clothing Icl, average radiant temperature of the room tr, and indoor air flow rate va.
In the diesel engine factory, workers are mainly engaged in moderate labor, so the human body doing work W takes the value of 200 W. The human energy metabolic rate M when sitting quietly takes the value of 1 Met, of which 1 Met is about 58.15 W/m2. And in the light activity according to the degree of different activities, M takes the value of 2 ~ 3.4 Met between about 116 and 197 W/m2, the human body energy metabolic rate M takes 2 Met. This study is for winter conditions, so the thermal resistance of clothing is taken as 1.2 clo, with 1 clo about 0.155 (m2·°C)/W.

3.3. Bi-Objective Optimization Model for Freeze-Proof Air-Conditioning System

Through the analysis of the actual system equipment and the analysis of the heat exchange process, the energy consumption model and thermal comfort model of the air-conditioning system operation are established, the constraints of the optimization variables are determined, and the multi-objective optimization problem model, with energy consumption and thermal comfort as the objective function, is derived as follows:
F ( x ) = F 1 ( x ) = min P t o t a l = min ( P c h i l l e r + P C H W p u m p + P c f a n + P C W p u m p + P t f a n ) F 2 ( x ) = min P P D = min f ( P M V ) s . t . P P D 27 % 1 P M V 1 597 P t o t a l 1202 0 T s e t 5 0.5 m w 1.5 0 m s 1.29 14 t a 22 30 % φ R 60 %

3.4. Multi-Objective Optimization Based on NSGA-II Algorithm

The fast non-dominated sorting genetic algorithm (NSGA-II) is a kind of genetic algorithm, and the theoretical ideas are originated from the basis of evolutionary theory and the basis of genetics. Compared to the non-dominated sorting genetic algorithm (NSGA), the NSGA-II algorithm adds a new, fast non-dominated sorting algorithm, adopts an elite retention strategy, and introduces a new crowding degree and a new crowding degree comparison operator. In the optimization process, the replication probability is empirically taken to be between 0.75 and 0.95, and the crossover probability is empirically taken to be between 0.60 and 0.90 [23]. The variation probability generally takes a value between 0.01 and 0.07, with its maximum value not exceeding 0.5; it is difficult to generate a new genetic structure when the variation probability is too small, and a too-large genetic algorithm would make the variation probability become a purely random search.
According to the above method and after repeated simulations, the optimal values are obtained. MATLAB2018 is used as the platform to write the multi-objective function optimization algorithm program, setting the population size popsize as 100, the individual length popth as 14, the number of iterations as 100, the crossover probability pc as 0.9, and the mutation probability pm as 0.07.
From the optimization calculation results (Figure 3), we can see that the objective function F1(x) has a negative correlation with F2(x); that is, the air-conditioning system multi-objective optimization model of energy consumption has a negative correlation with the PPD, in line with the actual situation. When the PPD ≤ 20%, the minimum value of system energy consumption in the optimization result is 986.36 kW, and the maximum value is 1004.36 kW; the minimum value of PPD is 15.00, and the maximum value is 19.99. When the PPD ≤ 25%, the minimum value of system energy consumption in the optimization result is 852.42 kW, and the maximum value is 870.42 kW; the minimum value of PPD is 6.30, and the maximum value is 24.53. When the PPD ≤ 30%, the minimum value of system energy consumption in the optimization result is 612.00 kW, and the maximum value is 629.99 kW; the minimum value of PPD is 25.87, and the maximum value is 29.86.
After running the multi-objective optimization algorithm, the optimized values of decision parameters are obtained as Table 10.

4. TRNSYS Simulation Modeling of Electric Heating–Bypass Anti-Freezing System

In this study, TRNSYS 18 simulation software is selected to build the simulation model of the air-conditioning system.

4.1. Architectural Model Setup

According to the standard design requirements, the winter outdoor design temperature for ventilation at the diesel engine testing facility is −21.6 °C, with a winter outdoor relative humidity of 60% and an atmospheric pressure of 100,540 Pa. The engine used is a TBD234V6 medium-speed diesel engine (Henan Diesel Heavy Industry Co., Ltd., Luoyang, China), with a rated power of 222 kW and a speed of 1800 r/min. The building model is set with a length of 30 m, a width of 15 m, a height of 10 m, a roof heat transfer coefficient of 1.8 W/(m2∙K), an exterior wall heat transfer coefficient of 1.56 W/(m2∙K), and an exterior window heat transfer coefficient of 4.8 W/(m2∙K).
In the building model, the system simulation time is set from 1 November to 1 March, totaling 122 days. The working days are Monday through Friday, with operation hours from 8:00 to 20:00. On Saturdays and Sundays, the system is not activated, and only heat preservation is maintained. A schedule is set, with weekdays labeled as WEEKDAY and weekends as WEEKEND. The USE parameter is set to 1 during work hours, indicating operational status, and 0 during non-working hours. The ventilation system in the room is set up, with air temperature and humidity controlled through an external interface, calculated by the equipment module and input into the system, following the weekly schedule.
The heat source power inside the building is set at 222 kW, with the operation mode following the weekly schedule. The facility accommodates 10 people, including both staff and mobile personnel. Most staff are engaged in engine testing, debugging, and data recording, so the labor intensity is set to Mode No.2, with an average heat emission of 120 W per person. Monitoring equipment is simplified to desktop computers, with a total of 10 computers, each with a power consumption of 140 W. Lighting is simplified to fixtures with a lighting density of 5 W/m2, covering an area of 450 m2, with operation time following the weekly schedule.

4.2. Modeling

  • Heat exchanger module: In this study, the selection is made among Type52a, Type52b, Type52c, and Type5. Ultimately, the finned cross-flow heat exchanger Type5 is chosen as the heat exchanger module for this simulation.
  • Fan module: In the optimal selection of the air-conditioning system retrofit plan, two variable frequency fans are designed: a main fan and a bypass duct fan. Therefore, in TRNSYS, a variable frequency fan model is chosen, specifically the Type662 module that allows for setting the flow rate, to serve as the fan module for this simulation.
  • Pump module: For the air-conditioning system retrofit plan, the pump is replaced with a variable frequency pump. In TRNSYS, the variable speed pump model Type110 is selected to serve as the variable frequency pump model. This module works by adjusting the system pipeline resistance to change the pump flow rate. The performance parameters for the variable frequency pump, such as the design flow rate, design head, and motor heat loss rate, are set according to the provided sample. The external input parameters required for the pump module include fluid temperature and fluid flow rate. The pump module can output parameters such as pump energy consumption and pump efficiency.
  • Control module: The three-way valve is a component in the air-conditioning system responsible for diverting bypass fresh air. The fresh air is partially heated through a heat exchanger and partially bypassed. The bypass air and the air that has undergone heat and moisture treatments are mixed through a confluence valve and then input into the building module. The three-way components are chosen as Type11e and Type11g, and this module can control the proportion of bypass fresh air through external input signals, achieving system operation adjustments.
  • Auxiliary heating module: The Type6 module is used as the auxiliary electric heater model in this study, with the heating mode set to Mode 1. The maximum heating rate and auxiliary heater efficiency are set according to the sample provided by the equipment manufacturer. The heating set temperature in the input parameters serves as an operational adjustment parameter.
After establishing the equipment modules, the components are connected, and the simulation system is controlled using a calculator control module. The TRNSYS air-conditioning system simulation model is established as shown in Figure 4, and it is used for the operation simulation of the frost protection air-conditioning system.

4.3. Model Validation

To verify the accuracy of the TRNSYS model for the electric preheating–bypass frost protection system, the simulation results are compared with the measured data. The apparatus used in the experiment and its detailed parameters are shown in Figure 5 and Table 11.
The simulation start and end times are set to 6609–6618 h, with a simulation step size of 1 h. The parameters for each equipment module are set according to the measured conditions. The deviation between the simulated and experimental values is analyzed using a deviation formula. Based on the above settings, the simulation results are obtained and compared with the measured values, as shown in Figure 6.
From Figure 6, it can be observed that the deviation is significantly larger at 8:00, when the system is first started, but apart from this, the simulated values and the measured values are generally in good agreement. The maximum error in the heat exchanger’s outlet water temperature is 6.05%, and the maximum error in the indoor air temperature is 6.14%. The reasons for the deviation between the simulated and measured results can be mainly attributed to three factors. First, the modules in the TRNSYS platform are somewhat idealized, resulting in discrepancies from the actual equipment; second, the simulation’s operational control is based on direct computational results, whereas the real system’s control adjustments have a response time; third, the measuring instruments used in the actual test have a certain margin of error, and inaccuracies can also occur during data reading and recording. These reasons contribute to the deviations between the simulation and experimental results. However, since the deviation values are within the allowable range, it can be concluded that the accuracy of the established TRNSYS model is relatively high and suitable for further simulation research.

5. Optimization Results and Analysis

5.1. Analysis of Energy Consumption and Thermal Comfort Operation Effects

To analyze the effectiveness of the energy consumption–thermal comfort multi-objective optimization operation strategy, the established TRNSYS simulation model is used for system operation simulation. The optimized operating parameters are compared with those before optimization. The simulation period selected is from 9081 to 9093 h, and the time step is 1 h, specifically from 8:00 AM to 8:00 PM on 14 January. The outdoor temperature during this period is shown in Figure 7. Based on the outdoor meteorological parameters, the established multi-objective optimization model is employed to determine the optimal operating parameters for each moment, including the optimal set values for the electric heater preheating temperature, bypass air volume, and indoor design temperature, as shown in Figure 8.
The operational parameters are set for comparison between pre- and post-optimization scenarios:
Before optimization: The parameters are set to fixed values according to the design standards, with the electric heater preheating temperature set to 2 °C, the bypass air volume at 30% of the fresh air volume, and the indoor design temperature at 16 °C. These parameters are kept constant, unaffected by changes in the outdoor temperature or time.
After optimization: The parameters are set to the optimized values shown in Figure 8. These values are derived hourly based on outdoor meteorological data through multi-objective optimization, providing the optimal set points for the electric heater preheating temperature, bypass air volume, and indoor design temperature. These parameters vary over time and are not fixed.
Based on these parameter settings, a comparison is made between the energy consumption and comfort levels of the air-conditioning system before and after optimization. The results of this comparison are shown in Figure 9 and Figure 10.
System energy consumption (Figure 9): The comparison of system energy consumption before and after optimization reveals that the system’s energy consumption is significantly influenced by outdoor temperature before optimization, exhibiting an inverse relationship with the temperature fluctuations. The system’s energy consumption reaches its lowest point at around 14:00, following an overall trend of initially decreasing and then increasing, with a total daily energy consumption of 9762 kW. After the optimization, the energy consumption of the system is very stable, and it is lower than the pre-optimization level at every moment, with a total daily energy consumption of 8647 kW, which is 11.4% lower than the pre-optimization energy consumption. As the outdoor temperature decreases, the energy-saving effect of the optimized operation strategy becomes more obvious. At 8:00 a.m., when the outdoor temperature is the lowest, the energy savings of the optimized system reach its peak, with a reduction of 21.9% compared to the pre-optimized system at the same time.
Comfort level (Figure 10): The comparison of comfort levels before and after optimization shows that the pre-optimization system, which operated with constant parameters, maintains a steady indoor comfort level, with the PPD (Predicted Percentage of Dissatisfied) value remaining unchanged. When the optimized parameters are implemented, the dynamic adjustments improve the indoor comfort level most of the time. However, at specific times—8:00, 9:00, 19:00, and 20:00—when the outdoor temperature is particularly low, the PPD values are higher than those of the system running with fixed parameters. Despite this, the overall application of the optimized operation parameters to the electric heater-bypass anti-freezing air-conditioning system results in both enhanced energy efficiency and improved indoor comfort. This demonstrates that the multi-objective optimization strategy, which balances energy consumption with thermal comfort, is effective.

5.2. Analysis of the Effect of Frost Protection Operation of the System Under Different Thermal Comfort Constraints

To analyze the frost protection performance under different thermal comfort constraints, the optimized operational parameters derived for each constraint are used. The energy consumption and thermal comfort multi-objective optimization results for the air-conditioning system renovation plan are incorporated into the simulation model. The operational parameters, including the electric auxiliary heater set temperature, bypass valve flow, and indoor temperature (Figure 8), are set to their optimized values. The system performance is then evaluated for varying levels of thermal comfort, specifically for PPD ≤ 20%, PPD ≤ 25%, and PPD ≤ 30%. The simulation time is winter, i.e., from October to April, corresponding to a TRNSYS simulation time of 6674–11,688 h.
According to the simulation results (Figure 11, Figure 12 and Figure 13), it can be seen that under different PPDs, the indoor temperature volatility increases with the increase in PPD, and it is more susceptible to the influence of the outdoor air temperature. When the PPD ≤ 20%, the stability of indoor temperature is the best, and the rule of change of the PPD is the opposite of the indoor temperature; the volatility of the PPD decreases gradually, and the water supply temperature of the heat exchanger is unchanged under different working conditions.
The operation evaluation indexes of the anti-freezing limit temperature Textre, anti-freezing time guarantee rate H, and optimization result deviation value are selected to quantify the anti-freezing performance and operation stability of the system. They are defined as shown in Table 12.
According to the above three indicators, the simulation results of the operation optimization parameters obtained when the PPD limit value is 20%, 25%, and 30% are analyzed. The results obtained are shown in Table 13.
The results show that the operation optimization strategies derived from different thermal comfort constraints all have better anti-freezing effects. When the constraints are 20%, 25%, and 30%, the anti-freezing limit temperatures are −8.96 °C, −9.87 °C, and −9.90 °C, respectively, and the anti-freezing limit temperatures increase gradually with the increase in PPD, but the increase is small; the anti-freezing time guarantee rate is 94.64%, 94.37%, and 94.71%, respectively, which shows that the thermal comfort constraints have a smaller influence on the anti-freeze performance; the system anti-freeze limit temperature is the lowest when the thermal comfort constraint is the most relaxed with a PPD ≤ 30%, and the anti-freeze time guarantee rate is the lowest. It can be seen that the thermal comfort constraints have a small impact on the anti-freeze performance, and the system has the lowest anti-freeze limit temperature and the highest anti-freeze time guarantee rate when the thermal comfort constraints are the most relaxed, with a PPD ≤ 30%. In the system operation, the optimization results deviation values are 146.43, 122.02, and 293.79. The optimization results of PPD ≤ 30% run the highest degree of deviation, with a deviation value of 293.79.

6. Discussion

The electric heating–bypass interlocked control system proposed in this study achieves a 94.7% freeze protection time guarantee in TRNSYS simulation by dynamically adjusting the preheating temperature and bypass air volume. However, the heat exchanger frost protection time guarantee did not reach 100% in the results of air-conditioning system operation under three different thermal comfort conditions because of the constraints given on the energy consumption of the electric heater during multi-objective optimization. In practical engineering, the preheating set temperature tset of the electric heater can be adjusted to avoid freezing of the heat exchanger during several hours when the outdoor temperature is extremely low. Due to the short period of extremely cold outdoor temperatures throughout the winter, the increased operating costs due to electric heating are acceptable at this time. This operating strategy was applied in the test building with good results, and no freezing of the heat exchanger occurred throughout the heating season.

7. Conclusions

This study summarizes the problems of the existing air-conditioning system, analyzes the reasons for them, and puts forward the strategy of air-conditioning system anti-freeze renovation; it researches the preferred method of air-conditioning system anti-freeze renovation program, selects the evaluation indexes, constructs the evaluation index system of the air-conditioning system anti-freeze renovation program, and determines the weights of the evaluation indexes. The electric heating and bypass duct chain control anti-freeze system is determined as the optimal program, and the system energy consumption model and indoor thermal comfort model are established. The operation optimization parameters under the comfort constraints are calculated to achieve the minimum energy consumption. The TRNSYS simulation platform of an electric heating and bypass duct interlocking control anti-freeze system is established, and the anti-freeze evaluation indexes are put forward. The operation simulation of the preferred air-conditioning system retrofit scheme is carried out, and the retrofit effect in comparison with the original air-conditioning system is analyzed. The following conclusions are obtained:
  • The evaluation index system of air-conditioning system transformation is established, and the weights of the primary and secondary indexes are determined. The primary weights are safety and reliability of 0.31, technical evaluation of 0.33, economic evaluation of 0.21, operation and management of 0.11, and environmental impact of 0.04. The secondary indexes are safety of the building structure of 0.5700, safety of the firefighting of 0.2663, safety of equipment operation of 0.0732, equipment life of 0.0905, technological sophistication of 0.0443, technological maturity of 0.5190, technological complexity of 0.1177, frost effectiveness of 0.3190, initial investment of 0.0719, operation and maintenance costs of 0.2789, the system’s operational energy consumption of 0.6491, the degree of simplicity of operation and control of 0.7500, maintainability of 0.2500, the degree of environmental impact of 0.2109, the degree of vibration and noise reduction of 0.0841, and indoor thermal environment creation of 0.7049. A consistency test is conducted to ensure that the results of the calculations are usable.
  • An auxiliary electric heating and bypass duct interlocking control anti-freeze system is proposed, which combines the traditional anti-freeze method, electric heater preheating method, and bypass method to regulate the preheating amount of the fresh air and the airflow through the heat exchanger to achieve the purpose of anti-freeze. Using the gray correlation method to evaluate four air-conditioning system renovation schemes, including the electric heating–bypass renovation scheme, the correlation of the four schemes is calculated as 0.7512 for Scheme A, 0.7254 for Scheme B, 0.6760 for Scheme C, and 0.6774 for Scheme D, which results in the optimal scheme being Scheme A.
  • An energy consumption model consisting of the energy consumption of electric heaters, heat exchangers, hot water pumps, total fans, and induced fans of the bypass ducts is established for the coupled control air-conditioning system of electric heating and bypass ducts. PMV and PPD are selected as indoor thermal environment evaluation indexes from the indexes for evaluating thermal comfort, and a thermal comfort model is established with the index of the percentage of indoor personnel’s dissatisfaction with the environment, PPD, and a model of thermal comfort is established. With the PPD and the thermal comfort model, the energy consumption-thermal comfort multi-objective optimization model is established, the constraints are specified, and the multi-objective optimization calculation is carried out by using the non-dominated sorting genetic algorithm (NSGA-II), resulting in the Pareto optimal set of solutions for the system when the energy consumption is minimized and the comfort is maximized.
  • A TRNSYS simulation platform for the interlocked control of the fresh air anti-freeze system with electric heating and bypass ducts is established to simulate the operation effect after the optimization of the operating parameters, and the comparison with the system operating energy consumption and indoor thermal comfort values before optimization confirms the feasibility of the preferred solution for the air-conditioning system renovation. The operational effect of the air-conditioning system after multi-objective optimization with different thermal comfort constraints is simulated. When the thermal comfort constraints are 20%, 25%, and 30%, the guaranteed rate of anti-freezing time is 94.64%, 94.37%, and 94.71%, respectively, the limit temperatures of anti-freezing are −8.96 °C, −9.87 °C, and −9.90 °C, respectively, and the optimization results of the operation deviation values are 146.43, 122.02, and 293.79, reaching the expected goal.

Author Contributions

Methodology, B.Z. and M.L. (Ming Liu); Software, B.Z. and W.W.; Validation, B.Z. and W.W.; Formal analysis, B.Z. and M.L. (Mingxuan Liu); Investigation, W.W.; Resources, B.Z. and M.L. (Ming Liu); Data curation, W.W. and M.L. (Mingxuan Liu); Writing—original draft, B.Z.; Writing—review and editing, W.W.; Supervision, M.L. (Ming Liu); Funding acquisition, M.L. (Ming Liu); Investigation, M.L. (Mingxuan Liu). All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The datasets used and analyzed during the current study are available from the corresponding author on reasonable request.

Acknowledgments

The authors would like to thank the reviewers of the previous draft for their helpful comments.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Szczepanik-Scislo, N.; Grządziel, D.; Mazur, J.; Kozak, K.; Schnotale, J. Influence of Human Activity on Radon Concentration, Indoor Air Quality, and Thermal Comfort in Small Office Spaces. Sensors 2024, 24, 4949. [Google Scholar] [CrossRef] [PubMed]
  2. Peng, Z.; Deng, W.; Tenorio, R. An Integrated Low-Energy Ventilation System to Improve Indoor Environment Performance of School Buildings in the Cold Climate Zone of China. Build. Environ. 2020, 182, 107153. [Google Scholar] [CrossRef]
  3. Sugawara, M.; Tago, M. Freezing of Water in a Closed Vertical Tube Cooled by Air Flow. Int. J. Heat Mass Transfer 2019, 133, 800–811. [Google Scholar] [CrossRef]
  4. Sugawara, M.; Tago, M. Safe and Economical Use of Adiabatic Material and Tube Heating to Prevent Freezing of Water Cooled by Air Flow. Int. J. Heat Mass Transfer 2020, 149, 119137. [Google Scholar] [CrossRef]
  5. Wang, W.; Kong, Y.; Wang, F.; Yang, L.; Niu, Y. Anti-Freezing Prediction Model for Different Flow Patterns of Air-Cooled Heat Exchanger. Int. J. Heat Mass Transfer 2020, 153, 119656. [Google Scholar] [CrossRef]
  6. Jaszczur, M.; Kleszcz, S.; Borowski, M. Analysis of the Anti-Icing System Used in Air Handling Units with a Counterflow Heat Exchanger. E3S Web Conf. 2019, 108, 1022. [Google Scholar] [CrossRef]
  7. Chen, A.; Ran, C.; Liu, H. Application Analysis of the Recovery Fresh Air Heat Pump Units in the Public Building in the Cold and Serious Cold Regions. In Proceedings of the 2013 The International Conference on Remote Sensing, Environment and Transportation Engineering (RSETE 2013), Nanjing, China, 26–28 July 2013; Gahegan, M.N., Xiong, N., Eds.; Atlantis Press: Paris, France, 2013; Volume 31, pp. 47–50. [Google Scholar]
  8. Wang, W.; Yang, L.; Du, X.; Yang, Y. Anti-Freezing Water Flow Rates of Various Sectors for Natural Draft Dry Cooling System under Wind Conditions. Int. J. Heat Mass Transfer 2016, 102, 186–200. [Google Scholar] [CrossRef]
  9. Deng, H.; Liu, J. In-tube thermodynamic analysis on incomplete/complete condensation in finned tube condensers using a conjugate heat transfer model. Int. J. Heat Mass Transf. 2019, 137, 775–789. [Google Scholar] [CrossRef]
  10. Yan, J.; Huang, X.; Huang, W.; Yang, L.; Du, X. Auxiliary Heat Exchanger Layout for Freeze-Proofing and Performance Recovery of Natural Draft Dry Cooling System. Int. J. Heat Mass Transfer 2020, 150, 119381. [Google Scholar] [CrossRef]
  11. Jedlikowski, A.; Anisimov, S.; Danielewicz, J.; Karpuk, M.; Pandelidis, D. Frost Formation and Freeze Protection with Bypass for Counter-Flow Recuperators. Int. J. Heat Mass Transfer 2017, 108, 585–613. [Google Scholar] [CrossRef]
  12. Wei, X.; Kusiak, A.; Li, M.; Tang, F.; Zeng, Y. Multi-Objective Optimization of the HVAC (Heating, Ventilation, and Air Conditioning) System Performance. Energy 2015, 83, 294–306. [Google Scholar] [CrossRef]
  13. Shaikh, P.H.; Nor, N.B.M.; Nallagownden, P.; Elamvazuthi, I. Intelligent Multi-Objective Optimization for Building Energy and Comfort Management. J. King Saud Univ. Eng. Sci. 2018, 30, 195–204. [Google Scholar] [CrossRef]
  14. Li, X.; Li, S.; Jiao, H. Research on Multi-Objective Optimization Method of Central Air Conditioning Air Treatment System Based on NSGA-II. In Proceedings of the 2020 4th International Conference on Electrical, Automation and Mechanical Engineering, Dubai, United Arab Emirates, 28–29 November 2020; IoP Publishing Ltd.: Bristol, UK, 2020; Volume 1626, p. 012113. [Google Scholar]
  15. Yfanti, S.; Sakkas, N.; Karapidakis, E. An Event-Driven Approach for Changing User Behaviour towards an Enhanced Building’s Energy Efficiency. Buildings 2020, 10, 183. [Google Scholar] [CrossRef]
  16. Li, L.; He, Y.; Zhang, H.; Fung, J.C.H.; Lau, A.K.H. Enhancing IAQ, Thermal Comfort, and Energy Efficiency through an Adaptive Multi-Objective Particle Swarm Optimizer-Grey Wolf Optimization Algorithm for Smart Environmental Control. Build. Environ. 2023, 235, 110235. [Google Scholar] [CrossRef]
  17. GB 50019-2015; Design code for heating ventilation and air conditioning of industrial buildings. Beijing China Planning Publishing House: Beijing, China, 2015.
  18. Zhang, R. Research on Optimization Control of Indoor Comfort and Energy-Saving Environment of Buildings; Xi’an University of Architecture and Technology: Xi’an, China, 2020. [Google Scholar]
  19. Li, X. Research on Optimization Methods of Central Air Conditioning Air Handling Systems; Shenyang University of Technology: Shenyang, China, 2020. [Google Scholar]
  20. Si, Y. Research on the Methods of Intelligent Regulation and Control to the Comfortable & Energy-Saving Indoor Environment in Office Buildings; Xi’an University of Architecture and Technology: Xi’an, China, 2019. [Google Scholar]
  21. Gao, Y. Multi-Objective Optimization of Central Air-Conditioning; Shenyang University of Technology: Shenyang, China, 2019. [Google Scholar]
  22. Kim, J.T.; Lim, J.H.; Cho, S.H.; Yun, G.Y. Development of the Adaptive PMV Model for Improving Prediction Performances. Energy Build. 2015, 98, 100–105. [Google Scholar] [CrossRef]
  23. Ghaderian, M.; Veysi, F. Multi-Objective Optimization of Energy Efficiency and Thermal Comfort in an Existing Office Building Using NSGA-II with Fitness Approximation: A Case Study. J. Build. Eng. 2021, 41, 102440. [Google Scholar] [CrossRef]
Figure 1. Side ventilation duct and electric heater interlock control anti-freezing fresh air system.
Figure 1. Side ventilation duct and electric heater interlock control anti-freezing fresh air system.
Buildings 15 01801 g001
Figure 2. Multi-level gray decision flow chart.
Figure 2. Multi-level gray decision flow chart.
Buildings 15 01801 g002
Figure 3. Multi-objective optimization results with different thermal comfort constraints.
Figure 3. Multi-objective optimization results with different thermal comfort constraints.
Buildings 15 01801 g003
Figure 4. TRNSYS simulation model of electric heating and bypass interlocking control system. (solid black lines indicate parameter inputs, dashed black lines indicate data outputs, and thick solid blue lines indicate air flow).
Figure 4. TRNSYS simulation model of electric heating and bypass interlocking control system. (solid black lines indicate parameter inputs, dashed black lines indicate data outputs, and thick solid blue lines indicate air flow).
Buildings 15 01801 g004
Figure 5. Experimental measuring instruments. (a) Testo Temperature and Humidity Self-Logging Meter. (Dettol Instruments International Trading Co., Shanghai, China). (b) Thermocouple and SWP-ASR500 Paperless Recorder. (Fuzhou Changhui Automation System Co., Ltd, Fuzhou, China). (c) FLEXIM Ultrasonic Flow Meter. (Shanghai Senyi Intelligent Instrument Co., Ltd., Shanghai, China). (d) Testo Hot-Wire Anemometer. (Dettol Instruments International Trading Co., Shanghai, China).
Figure 5. Experimental measuring instruments. (a) Testo Temperature and Humidity Self-Logging Meter. (Dettol Instruments International Trading Co., Shanghai, China). (b) Thermocouple and SWP-ASR500 Paperless Recorder. (Fuzhou Changhui Automation System Co., Ltd, Fuzhou, China). (c) FLEXIM Ultrasonic Flow Meter. (Shanghai Senyi Intelligent Instrument Co., Ltd., Shanghai, China). (d) Testo Hot-Wire Anemometer. (Dettol Instruments International Trading Co., Shanghai, China).
Buildings 15 01801 g005aBuildings 15 01801 g005b
Figure 6. Comparison of heat exchanger water temperature (a) and room air temperature (b).
Figure 6. Comparison of heat exchanger water temperature (a) and room air temperature (b).
Buildings 15 01801 g006
Figure 7. Outdoor hourly temperature from 8:00 to 20:00, 14 January.
Figure 7. Outdoor hourly temperature from 8:00 to 20:00, 14 January.
Buildings 15 01801 g007
Figure 8. Optimization results of preheating setting temperature, bypass air volume, and indoor design temperature.
Figure 8. Optimization results of preheating setting temperature, bypass air volume, and indoor design temperature.
Buildings 15 01801 g008
Figure 9. Comparison of energy consumption of the air-conditioning system.
Figure 9. Comparison of energy consumption of the air-conditioning system.
Buildings 15 01801 g009
Figure 10. Comparison of indoor comfort before and after optimization.
Figure 10. Comparison of indoor comfort before and after optimization.
Buildings 15 01801 g010
Figure 11. Indoor and outdoor temperatures (a), PPD (b), and outlet water temperature when PPD ≤ 20% (c).
Figure 11. Indoor and outdoor temperatures (a), PPD (b), and outlet water temperature when PPD ≤ 20% (c).
Buildings 15 01801 g011
Figure 12. Indoor and outdoor temperatures (a), PPD (b), and outlet water temperature when PPD ≤ 25% (c).
Figure 12. Indoor and outdoor temperatures (a), PPD (b), and outlet water temperature when PPD ≤ 25% (c).
Buildings 15 01801 g012
Figure 13. Indoor and outdoor temperatures (a), PPD (b), and outlet water temperature when PPD ≤ 30% (c).
Figure 13. Indoor and outdoor temperatures (a), PPD (b), and outlet water temperature when PPD ≤ 30% (c).
Buildings 15 01801 g013
Table 1. Comparison table of existing common fresh air treatment technology.
Table 1. Comparison table of existing common fresh air treatment technology.
Fresh Air Unit TypeFresh Air Treatment MethodProblems in Application in Cold Regions
Heat exchanger heatingUse municipal hot water or boiler-generated hot water to heat fresh airHeat exchanger is prone to freezing
Electric or gas heatingElectric heaters or gas heaters preheat the fresh airInefficient energy use, high energy consumption
Fresh air preheating + low-temperature air source heat pumpFresh air is preheated and then heated by a low-temperature air-source heat pumpRequires additional fresh air preheating equipment; frequent startup and shutdown when outdoor temperature is high
Indirect heat recovery via heat exchangerFresh air exchanges heat with exhaust airHeat exchangers are prone to frosting in winter; heat recovery efficiency is affected by exhaust air volume
Exhaust air heat pump heat recoveryExhaust air serves as the heat source for the air-source heat pumpThe evaporator is prone to frosting in winter, leading to low efficiency
Intermediate heat carrier heat recoveryUse a pump and expansion tank with a heat carrier as the medium for heat recoveryHeat carrier is prone to freezing
Thermoelectric heat recoveryPhotovoltaic-powered thermoelectric recovery system preheats fresh airSolar energy utilization needs to consider specific conditions, a complex system, and high operating costs
Table 2. Comparison table of technical and economic indicators of alternative schemes.
Table 2. Comparison table of technical and economic indicators of alternative schemes.
Evaluation IndicatorsOption AOption BOption COption D
Equipment life (years)14301212
Initial investment (RMB)36.21105.4345.3338.00
Operation and maintenance costs (RMB/year)1.2941.3594.6172.300
Recovery period (years)13.9928.789.8116.52
System operation energy consumption (kW)9641203978600
Degree of environmental impact (kg/h)348502396203
Degree of anti-vibration and noise reduction (dB)53386850
Table 3. Fresh air system frost protection retrofit evaluation index.
Table 3. Fresh air system frost protection retrofit evaluation index.
Goal LevelGuideline LevelIndicator Level
Evaluation index system of air-conditioning system anti-freezing renovationSafe and reliable B1Building structural safety H1
Fire safety H2
Equipment operation safety H3
Equipment life H4
Technical evaluation B2Technological sophistication H5
Level of technological maturity H6
Technical complexity H7
Anti-freezing effectiveness H8
Economic evaluation B3Initial investment H9
Operation and maintenance cost H10
System operation energy consumption H11
Operations management B4Difficulty of operation and control H12
Maintainability H13
Environmental impact B5Degree of environmental pollution H14
Degree of vibration and noise reduction H15
Indoor thermal environment H16
Table 4. Judgment matrix index meaning and relative importance scale.
Table 4. Judgment matrix index meaning and relative importance scale.
Serial No.Importance of Factor i over Factor jRelative Importance Scale
1Equally important1
2Slightly more important3
3More pronounced importance5
4Very strong importance7
5Extremely important9
6Median of adjacent judgment levels2, 4, 6, 8
7Factor j over factor i, bj = 1/bi1, 1/2,…, 1/9
Table 5. Group distribution table.
Table 5. Group distribution table.
Research RequirementsEngineering Requirements (Unit: Persons)Total
A: Professor-Level Senior EngineerB: Senior Engineer/Associate ProfessorC: Intermediate Engineer/Assistant Engineer
A: PhDAA 0BA 2CA 02
B: graduate students and othersAB 4BB 4CB 513
Total46515
Table 6. Consistency test of judgment matrix.
Table 6. Consistency test of judgment matrix.
Judgment MatrixλmaxCIRIResults
B14.081871550.0230.0568 < 0.1Consistency check passed
B24.150168260.05010.0556 < 0.1Consistency check passed
B33.064887580.03240.0559 < 0.1Consistency check passed
B4///Consistency check passed
B53.032366610.01620.0279 < 0.1Consistency check passed
Table 7. Table of evaluation index values of anti-freezing renovation of the fresh air system.
Table 7. Table of evaluation index values of anti-freezing renovation of the fresh air system.
Goal LevelGuideline LevelGuideline Level WeightsIndicator LevelIndicator Level Weights
Evaluation index system of air-conditioning system anti-freezing renovationSafe and reliable B10.3106Building structural safety H10.5700
Fire safety H20.2663
Equipment operation safety H30.0732
Equipment life H40.0905
Technical evaluation B20.3290Technological sophistication H50.0443
Level of technological maturity H60.5190
Technical complexity H70.1177
Anti-freezing effectiveness H80.3190
Economic evaluation B30.2125Initial investment H90.0719
Operation and maintenance cost H100.2789
System operation energy consumption H110.6491
Operations management B40.1061Difficulty of operation and control H120.7500
Maintainability H130.2500
Environmental impact B50.0419Degree of environmental pollution H140.2109
Degree of vibration and noise reduction H150.0841
Indoor thermal environment H160.7049
Table 8. Unified dimension table of evaluation value of the renovation scheme.
Table 8. Unified dimension table of evaluation value of the renovation scheme.
Option AOption BOption COption D
0.09730.10280.09360.1000
0.10420.11270.09740.0930
0.12450.09910.09050.0909
0.09440.10580.10530.1022
0.10190.10500.09940.0987
0.10320.10060.09650.0981
0.10830.09760.09400.0934
0.10980.09710.09700.0962
0.09320.09640.09830.0951
0.10620.11540.08960.0933
0.10070.09610.10410.1041
0.11370.10740.10760.0995
0.10690.10730.10970.1035
0.09340.10670.10420.1045
0.10400.10930.09580.0958
0.04140.01660.00200.0101
0.75120.72540.67600.6774
Table 9. Relationship between PMV and PPD and human thermal sensation.
Table 9. Relationship between PMV and PPD and human thermal sensation.
Thermal SensationColdCoolSlightly CoolNeutralSlightly WarmWarmHot
PMV−3−2−10123
PPD (%)100%75%25%5%25%75%100%
Table 10. Part of Pareto optimal solution.
Table 10. Part of Pareto optimal solution.
Serial NumberAuxiliary Electric Heater Set Temperature TsetHot Water Flow Rate mwBypass Fresh Air Volume msIndoor Temperature taRoom Relative Humidity φRPower ConsumptionPPD
PPD ≤ 20%5.4620.430.35216.0570.4621032.71217.233
PPD ≤ 25%2.5810.3750.48414.7140.326659.36922.828
PPD ≤ 30%2.5910.320.48714.000.301625.39127.102
Table 11. Test instrument information.
Table 11. Test instrument information.
Test ParametersMeasuring InstrumentInstrument AccuracyRecording Mode
Indoor and outdoor temperature and humidityTesto Temperature and Humidity Self-Logging Meter. (Dettol Instruments International Trading Co., Shanghai, China)±0.3 °C
±3% RH
Automation
Heat exchanger inlet and outlet water temperatureThermocouple and SWP-ASR500 Paperless Recorder. (Fuzhou Changhui Automation System Co., Ltd., Fuzhou, China)±0.2 °CAutomation
Hot water inlet and outlet flowFLEXIM Ultrasonic Flow Meter. (Shanghai Senyi Intelligent Instrument Co., Ltd., Shanghai, China)±0.01 m/sManual
Duct inlet air velocityTesto Hot-Wire Anemometer. (Dettol Instruments International Trading Co., Shanghai, China)±0.01 m/sManual
Table 12. Three operational evaluation indicators.
Table 12. Three operational evaluation indicators.
IndicatorsMeaning
Anti-freezing limit temperature TextreThe lowest outdoor temperature that can be reached when the electric heater is only preheated to ensure that the heat exchanger does not freeze, which characterizes the ability of the system to resist extreme outdoor temperatures.
Anti-freezing time guarantee HThe ratio of the number of hours that the heat exchanger can be guaranteed not to freeze to the number of hours that the air-conditioning system is working in the heating season, which characterizes the effectiveness of the system to prevent freezing in the heating season.
Optimization result deviation value Optimization   value   deviation   is   defined   as   P M V P M V 0 2 + P P 0 2 , i.e., the degree of deviation between the theoretical Pareto optimization solution and the system operation results, which indicates the applicability and stability of the multi-objective optimization solution in the practical application of the system.
Table 13. Comparison of parameters under different thermal comfort constraints.
Table 13. Comparison of parameters under different thermal comfort constraints.
PPD ≤ 20%PPD ≤ 25%PPD ≤ 30%
Anti-freezing limit temperature Textre−8.96−9.87−9.90
Anti-freezing time guarantee H94.64%94.37%94.71%
Optimization result deviation value146.43122.02293.79
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Zhang, B.; Wang, W.; Liu, M.; Liu, M. Anti-Freezing and Operation Optimization Design of Air-Conditioning Systems for Industrial Plants in Severely Cold Regions. Buildings 2025, 15, 1801. https://doi.org/10.3390/buildings15111801

AMA Style

Zhang B, Wang W, Liu M, Liu M. Anti-Freezing and Operation Optimization Design of Air-Conditioning Systems for Industrial Plants in Severely Cold Regions. Buildings. 2025; 15(11):1801. https://doi.org/10.3390/buildings15111801

Chicago/Turabian Style

Zhang, Baogang, Weitao Wang, Ming Liu, and Mingxuan Liu. 2025. "Anti-Freezing and Operation Optimization Design of Air-Conditioning Systems for Industrial Plants in Severely Cold Regions" Buildings 15, no. 11: 1801. https://doi.org/10.3390/buildings15111801

APA Style

Zhang, B., Wang, W., Liu, M., & Liu, M. (2025). Anti-Freezing and Operation Optimization Design of Air-Conditioning Systems for Industrial Plants in Severely Cold Regions. Buildings, 15(11), 1801. https://doi.org/10.3390/buildings15111801

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop