3.1. Analysis of the Influence of Each Window Performance Factor
The first experiment consisted in identifying the impact of each element. The change was applied to only one element, while the other two were fixed at the median value for the experiment. The experimental results of WWR 50% are presented in
Figure 2,
Figure 3 and
Figure 4.
Higher U-values lead to less cooling load and more heating load. Consequently, the sum of heating and cooling loads also increases. Higher VLTs lead to less cooling load and more heating load. The sum of heating and cooling loads shows a decrease. Finally, higher SHGCs lead to more cooling load and less heating load. The sum of cooling and heating loads also increases.
As for the changes in heating and cooling loads of each element, the U-value changed by 3.31%, VLT by 1.28%, and SHGC by 22.13%, proving that the change from SHGC is the biggest.
Table 6 shows the rates of change in each element’s cooling load, heating load, and heating and cooling loads.
The change in the sum of the U-value heating and cooling loads is relatively low, but the individual change in cooling load and heating load was high. The change in the heating load of the U-value was 165.19%, indicating a massive impact on the heating load. Conversely, for VLT, the effect on each heating and cooling load was small at 3.31%, thereby having an insignificant impact on total heating and cooling loads. SHGC shows a 22.13% change in heating and cooling loads, indicating that it has the greatest impact on all elements. The difference in cooling load was 76.37%, and the change in heating load was 55.28%, indicating that the effect on cooling load is more remarkable.
As a result, SHGC is the performance element that has the greatest influence on heating and cooling loads, followed by the U-value and VLT.
3.3. A Hierarchical Analysis of U-Value and SHGC using Window Area Ratio
The following inversion sections vary by WWR.
Figure 8 shows heating and cooling loads calculated considering the U-value and SHGC of each WWR. Here, there are the sections of inversion. Inversion occurs at SHGC = 0.7% for WWR 40%, at SHGC = 0.6% for WWR 50%, at SHGC = 0.5% for WWR 60%, and after SHGC = 0.5~0.4% for WWR 70%. Higher WWRs lead to lower SHGCs in the inversion sections. Therefore, SHGC must be considered as more when WWR is higher to reduce the load. It is necessary to select the optimal combination by considering both the U-value and SHGC of windows according to the WWR.
Figure 9 shows heating and cooling loads according to the U-value and SHGC of each WWR, as in
Figure 8. Generally, higher U-values are more disadvantageous in terms of energy efficiency. Therefore, heating and cooling loads of ‘U-value = 3.0 W/m
2K’ must be the biggest. However, as shown in
Figure 9, higher U-values were more advantageous regarding energy efficiency in high-value SHGC combinations. This was even more apparent with higher WWRs. For example, heating and cooling loads were the smallest in WWR 70% and U-value = 3.0 W/m
2K at SHGC = 0.8%, and the loads were the biggest in U-value = 0.5 W/m
2K when the thermal performance was rather good.
Table 7 presents the results of Experiment B, marking the sum of minimum heating and cooling loads at each SHGC in shading. Heating and cooling loads are increasing along with the U-value regardless of VLT, but in combination with SHGC, the loads decreased at the conversion point of SHGC and then increased again. Therefore, U-values of minimum cooling and heating loads vary depending on the SHGC. Moreover, there is a difference in the converted values of SHGC depending on the WWR. Higher WWRs lead to lower SHGCs in the inversion sections. In other words, higher WWRs indicate a greater impact on solar energy, which is why SHGC must be considered.
3.4. Sinter and Discussion
Around 60–70% of a building’s heating and cooling loads originate from the outside, with windows and doors in offices contributing up to 40% of heat loss [
24,
38]. Since office buildings have extensive areas due to designs that pursue a wide view, the increased solar heat inflow in summer causes high cooling loads and poor thermal comfort [
27,
38]. Solar radiation energy through windows has different effects on building energy consumption in winter and summer, which is why windows are a complicated design element. Previous studies are proposing strategies to reduce energy consumption by improving the envelope performance of windows [
11,
14,
16,
24]. While the effectiveness of glazing as a strategy for enhancing window performance has been verified, verification of each element’s individual performance has not been conducted [
39,
40]. Instead of analyzing individual elements, this study conducted an experiment to ascertain performance with predetermined window sets. This approach has limitations in providing objective indicators for the efficiency of each element and the application of glazing design.
The present study analyzed the impact of each glazing element—U-value, VLT, and SHGC—on window planning for energy reduction, differentiating the variable values to discern individual performances. The study distinguished itself from prior research by establishing an integrated hierarchy for each element after identifying individual performances. Further, by conducting experiments on the energy performance of glazing variables according to the WWR, a significant design element influencing energy consumption, the study holds significance by conducting a hierarchical analysis between window glass design variables. The results of this study are as follows. First, SHGC had the greatest impact on building energy loads among window performance elements, followed by the U-value and VLT. Yoon et al. [
35] also analyzed the effect of glazing performance on building energy performance and discovered that SHGC and VLT have a stronger effect than the U-value on building energy in buildings with high cooling and lighting loads. This is similar to the results of this study.
This study added the impact of WWR to the analysis. The results of analyzing the change and implications of window performance elements according to WWR are displayed in
Table 8. Higher WWRs led to less impact of the U-value and VLT, whereas the impact of SHGC increased to 93.91% in WWR 70%. The effect of VLT was insignificant. Since VLT is an element that affects glare and lighting load, the impact in terms of energy performance may have turned out to be small [
30,
35,
37].
Among the performance elements, SHGC showed the most significant change and impact in all WWRs, followed by the U-value and VLT. Therefore, the effect of SHGC was greatest in all WWRs, with higher WWRs resulting in a more pronounced impact. This result indicates that SHGC must be thoroughly considered to improve energy performance in building design.
Second, the two performance elements have different energy impacts and require opposite conditions for reducing loads. According to the change in the U-value and SHGC, the experiment showed that the U-value was disadvantageous to the cooling load and advantageous to the heating load. In contrast, SHGC was advantageous to the cooling load and disadvantageous to the heating load. This result was equally found in other studies as well.
Choi et al. [
9] conducted an energy simulation on the interactions of building envelope design factors and discovered that the infiltration air change rate (ACR) and window insulation (WDI) had a considerable influence on the heating load, and SHGC had a great impact on the cooling load. Shin et al. [
41] also analyzed that the decrease in the U-value led to a 63% decrease in office heating load and a 30% increase in cooling load, thereby reducing the total heating and cooling loads by 4%. SHGC led to a 6–18% increase in heating load and a 5–12% decrease in cooling load, thereby reducing energy by 16%. Moreover, Lee et al. [
37], Raji et al. [
42], and Zhao et al. [
43], who experimented on the impact of glazing performance according to climate features, discovered that the U-value must be considered in polar regions where heating is required, whereas SHGC must be regarded in hot climates where cooling is needed.
Finally, after examining the heating and cooling loads according to the U-value and SHGC, certain sections exhibited an inversion. As shown in
Table 7, loads are increasing along with the U-value, but in combination with SHGC, the loads decreased at the conversion point of SHGC and then increased again. In other words, in combination with SHGC and the U-value, when the U-value is lower than a certain level, it creates a greenhouse effect and increases heating and cooling loads.
Yoon et al. [
35] suggested that the U-value is inversed in 1.2 W/m
2K. However, this study additionally conducted the WWR experiment and discovered that the glazing standards vary depending on the WWR. Furthermore, an inversion occurs based on SHGC instead of the U-value. This is also proved equally by Yoon et al. [
44]. SHGC, where inversion occurs, decreases as WWR increases.
The heat causes inversion, and internal heat accumulated indoors due to solar radiation cannot escape to the outside due to the U-value, thereby increasing the cooling load [
24,
35]. Thus, more extensive window areas lead to more solar radiation inflow, which reduces the SHGC in the inversion sections and increases the impact of the SHGC. Therefore, it is necessary to consider adequate combinations of the U-value and SHGC to regulate solar radiation inflow and prevent the greenhouse effect.
One thing to note in this study is that buildings with higher WWRs are more greatly affected by SHGC and that there is a need for an optimal combination of the U-value and SHGC to increase the effect of load reduction. Lower U-values lead to less load, but the minimum cooling and heating loads appear differently in combination with SHGC. For example, in WWR 50% and SHGC = 0.5%, the load is smallest when U-value = 1.5 W/m
2K but smallest when U-value = 1.0 W/m
2K in SHGC = 0.6%. Kim et al. [
44] also revealed that building energy demand increases proportionately to SHGC, and buildings with higher WWRs show a higher rate of increase. Thus, it was found that maintaining SHGC at 0.4% or lower is beneficial for energy performance. This intention to provide the optimum SHGC is equivalent to the attempt of this study. However, this study did not limit the scope to SHGC but also revealed the complex relationship between the U-value and SHGC.
Window design is intricately related to various design variables, such as glazing, WWR, envelope area, height, scale, and volume. This study conducted experiments with only glazing and WWR and presented the interaction between SHGC and the U-value but faced limitations in clarifying the relationship between the variables. Moreover, the most energy-efficient combination of the glazing elements can be achieved by adopting a low SHGC. However, the glass becomes darker as the SHGC decreases, complicating the maintenance of views. Therefore, glazing cannot be selected solely on the basis of energy performance. Apart from energy performance, other evaluation criteria, such as indoor environment comfort and occupants’ preferences, must be considered to propose an appropriate range for glazing. Further research is currently underway, and subsequent studies will include these considerations to present a clear relationship between the variables.