Modeling Transient Waveforms of Offshore Wind Power AC/DC Transmission Faults: Unveiling Symmetry–Asymmetry Mechanisms
Abstract
1. Introduction
- ■
- First, existing offshore wind power fault simulation studies mainly focus on onshore wind power scenarios, ignoring the unique influence of submarine cable parameters on transient symmetry–asymmetry characteristics, resulting in simulated waveforms that deviate from actual offshore fault conditions.
- ■
- Second, traditional fault simulation methods only use static impedance adjustment to simulate voltage changes, failing to capture the dynamic evolution process of “symmetric steady state–fault symmetry breaking–recovery symmetry reconstruction” and are thus unable to provide accurate transient waveform support for wind turbine fault ride-through testing.
- ■
- Third, current offshore wind power grid-connection test standards lack explicit provisions for transient fault indicators, and the test indices are mainly derived from onshore wind power, which cannot adapt to the harsh fault conditions of offshore AC/DC transmission systems.
- ■
- Fourth, existing fault waveform simulation models either have high computational complexity or ignore symmetry–asymmetry constraints, making it challenging to balance simulation efficiency and precision.
- Innovative classification of offshore-specific fault scenarios and revision of test standards based on symmetry-asymmetry dynamics.
- 2.
- Quantitative analysis framework for multi-type voltage scenarios tailored to offshore wind turbine control needs.
- 3.
- Simplified RLC second-order model embedded with symmetry–asymmetry constraints for low-computing-power scenarios.
- 4.
- High-precision feature parameter solving method integrated with symmetry-constrained nonlinear least squares.
2. Simplified Circuit Model and Analytical Model of Fault Characteristics for Offshore Wind Power AC Transmission Systems
2.1. Simplified Circuit Model of Offshore Wind Power Transmission Systems
2.2. Analytical Model of the AC Transmission System
- Three-phase parameter deviation (e.g., ±5% imbalance in cable capacitance);
- Fault point grounding resistance (10–50 Ω);
- Wind turbine output fluctuation (±10% rated power).
2.3. Fault Characteristic Extraction and Influencing Factors
- Transient decay rate α (9): This is inversely proportional to Ceq/Leq; Ceq has a stronger influence (40% Ceq reduction in ↑α by ~50%, 40% Leq reduction in ↑α by ~20%) (Figure 4a).
- Transient oscillation frequency β (10): This is inversely related to Ceq/Leq; both have a similar effect (±10% variation, difference ≤ 1%) (Figure 4b).
- Transient decay peak (11): Ceq/Leq impact significantly, and Ceq is slightly stronger (Ceq positive, Leq negative correlation) (Figure 4c).
- Transient voltage peak (12): Ceq/Leq affect similarly (Ceq positive, Leq negative correlation) (Figure 4d).
2.4. Frequency-Domain and Time–Frequency Joint Indicators
- (1)
- Dominant frequency fd: Frequency corresponding to the peak of the transient signal power spectrum, reflecting the main frequency of fault oscillation;
- (2)
- Frequency band energy ratio γ: Energy ratio of 0–500 Hz band to total energy, quantifying low-frequency transient component intensity.
2.5. Fault Characteristic Analysis and Comparison of Submarine Cable and Overhead Line Transmission Systems
2.6. Comparison of Fault Characteristics Between Submarine Cable and Overhead Line Transmission Systems
3. Typical Fault Scenario Extraction and Test Index Revision for Offshore Wind AC/DC Transmission Systems
3.1. Typical Fault Scenario Extraction and Simulation Requirements for Offshore Wind Power Transmission Systems
3.2. Comparative Analysis of Voltage Types Under Different Calculation Methods
3.2.1. Instantaneous Three-Phase Voltage
3.2.2. dq Voltage Magnitude
3.2.3. RMS Value
3.3. Revision of Grid-Connection Test Indices for Offshore Wind Farms
3.3.1. Deficiencies in Current Grid-Connection Test Indices
3.3.2. Proposed Revisions to Grid-Connection Test Indices for Offshore Wind Power
4. A Rapid Simulation Method for Transient Waveforms of Typical Faults in Offshore Wind Power
4.1. Main Functions and Limitations of Power Grid Simulation Devices
- (1)
- A fault simulation circuit is established, the analytical formula of the fault waveform is constructed, and the characteristic parameters to be obtained are determined.
- (2)
- The fault waveform is preliminarily filtered by using the wavelet decomposition method to extract the main oscillation waveform and the main frequency.
- (3)
- The spectrum diagram of the fault waveform is obtained by using the fast Fourier decomposition method, and the initial values βi(0) and θi(0) of the characteristic parameters of the angular frequency and initial phase angle are calculated. The initial values Ui(0) and αi(0) of the transient voltage amplitude and attenuation coefficient are calculated by using the cubic spline interpolation method and exponential fitting.
- (4)
- The characteristic quantities of the reconstructed waveform are obtained by using the nonlinear least squares method, and the parameters of the analog circuit are further calculated based on the expression of the characteristic quantities in [32].
- (5)
- The solved circuit parameters back are substituted into the fault simulation circuit to simulate and compare the fit degree of the reproduced waveforms.
4.2. Fault Waveform Simulation Method Based on Nonlinear Least Squares Method
4.2.1. Fault Waveform Simulation Analytical Model
4.2.2. The Principle of Nonlinear Least Squares
4.2.3. Calculation of Fault Transient Characteristics
4.2.4. Calculation of Line Parameters Based on Nonlinear Least Squares Method
4.2.5. Quantifying the Adaptability of Constraints to Different Faults
4.2.6. The Sensitivity of RLC Parameters to High-Frequency Transients
- (1)
- Inductance Leq: A ±5% deviation increases the waveform fitting error by 10% in the high-frequency band (1–2 kHz);
- (2)
- Capacitance Ceq: A ±5% deviation increases the high-frequency attenuation rate error by 8%;
- (3)
- Conclusion: The deviation in Leq and Ceq is controlled to ≤3% to ensure high-frequency transient accuracy.
5. Simulation Verification
5.1. Method Foundation Test
- (1)
- A35 kV single-phase grounding fault: fd = 190 Hz, γ = 82%, Hw = 1.8 (pre-fault Hw = 0.6);
- (2)
- Conclusion: Frequency-domain/time–frequency indicators can supplement time-domain indicators for more accurate identification of fault transient characteristics.
- (1)
- Cross-validation (70% training set, 30% test set) shows test set goodness-of-fit R2 ≥ 0.91 (close to training set);
- (2)
- Error in high-frequency band (1–2 kHz) ≤ 10%, no over-fitting to training data.
5.2. Comparison with Other Methods
- (1)
- Comparison with Traditional Impedance-Voltage Divider Method
- (2)
- High-Order EMTP-RV Mode
- (3)
- Comparison with Onshore Wind Power Fault Simulation Models
5.3. Comparison of Different Voltage Levels and Fault Types
6. Conclusions
- (1)
- Mechanism exploration: The quantitative link between system parameters and symmetry–asymmetry characteristics is clarified; submarine cable capacitance reduces transient decay rate α by 58.56% and oscillation frequency β by 16.55%, while 15% inductance imbalance exacerbates three-phase waveform distortion by 20%. Core indicators α, β, and Umax are defined, with offshore Umax being 0.15–0.3 pu higher than onshore.
- (2)
- Scenario extraction and index revision: Typical faults are classified by symmetry–asymmetry evolution, adding the transient symmetry recovery time and zero-sequence voltage attenuation threshold to grid-connection indices, reducing offshore–onshore standard mismatch by 40%.
- (3)
- Simulation method innovation: An embedded RLC second-order model with symmetry-asymmetry constraints is proposed. Using wavelet decomposition, FFT, and symmetric-constrained nonlinear least squares, it reproduces the full “symmetric steady state–fault breaking–recovery” process, outperforming traditional impedance methods and high-order models.
Author Contributions
Funding
Data Availability Statement
Conflicts of Interest
References
- Prajzendanc, P.; Kreischer, C. A Review of New Technologies in the Design and Application of Wind Turbine Generators. Energies 2025, 18, 4082. [Google Scholar] [CrossRef]
- Zhang, Z.; Hui, H.; Song, Y. Response Capacity Allocation of Air Conditioners for Peak-Valley Regulation Considering Interaction with Surrounding Microclimate. IEEE Trans. Smart Grid 2024, 16, 1155–1167. [Google Scholar] [CrossRef]
- Wang, K.; Wang, C.; Yao, W.; Zhang, Z.; Liu, C.; Dong, X.; Yang, M.; Wang, Y. Embedding P2P transaction into demand response exchange: A cooperative demand response management framework for IES. Appl. Energy 2024, 367, 123319. [Google Scholar] [CrossRef]
- Si, J.L.; Ai, L.; Qiu, C. Current Situation and Prospects of Wind Power Development in China in 2023. Water Power 2024, 50, 1–4. [Google Scholar]
- Schkoda, R.F. Sliding Mode Control of a Hydraulically Actuated Load Application Unit with Application to Wind Turbine Drivetrain Testing. IEEE Trans. Control. Syst. Technol. 2015, 23, 2203–2215. [Google Scholar] [CrossRef]
- Castelló, J.; Espí, J.M.; García-Gil, R. Development Details and Performance Assessment of a Wind Turbine Emulator. Renew. Energy 2016, 86, 848–857. [Google Scholar] [CrossRef]
- Shah, S.; Koralewicz, P.; Gevorgian, V.; Wallen, R. Sequence Impedance Measurement of Utility-Scale Wind Turbines and Inverters–Reference Frame, Frequency Coupling, and MIMO/SISO Forms. IEEE Trans. Energy Convers. 2021, 37, 75–86. [Google Scholar] [CrossRef]
- Koralewicz, P.; Shah, S.; Gevorgian, V.; Wallen, R.; Jha, K.; Mashtare, D.; Gadiraju, K.V.R.; Tiwari, A. Impedance Analysis and PHIL Demonstration of Reactive Power Oscillations in a Wind Power Plant Using a 4-MW Wind Turbine. Front. Energy Res. 2020, 8, 156. [Google Scholar] [CrossRef]
- Karaagac, U.; Faried, S.O.; Mahseredjian, J.; Edris, A.-A. Coordinated Control of Wind Energy Conversion Systems for Mitigating Sub-Synchronous Interaction in DFIG-Based Wind Farms. IEEE Trans. Smart Grid 2014, 5, 2440–2449. [Google Scholar] [CrossRef]
- Sahri, Y.; Tamalouzt, S.; Hamoudi, F.; Belaid, S.L.; Bajaj, M.; Alharthi, M.M.; Alzaidi, M.S.; Ghoneim, S.S. New Intelligent Direct Power Control of DFIG-Based Wind Conversion System by Using Machine Learning Under Variations of All Operating and Compensation Modes. Energy Rep. 2021, 7, 6394–6412. [Google Scholar] [CrossRef]
- GB/T 36995-2018; Test Procedure for Fault Voltage Ride-Through Capability of Wind Turbine Generators. National Wind Machinery Standardization Technical Committee (SAC/TC 50); China Standard Press: Beijing, China, 2018.
- Chen, X.; Wang, M. WaveAtten: A Symmetry-Aware Sparse-Attention Framework for Non-Stationary Vibration Signal Processing. Symmetry 2025, 17, 1078. [Google Scholar] [CrossRef]
- Nasser, A.R.; Azar, A.T.; Humaidi, A.J.; Al-Mhdawi, A.K.; Ibraheem, I.K. Intelligent fault detection and identification approach for analog electronic circuits based on fuzzy logic classifier. Electronics 2021, 10, 2888. [Google Scholar] [CrossRef]
- Ziad, H.; Al-dujaili, A.; Humaidi, A.J. Electrical faults classification in permanent magnet synchronous motor using ResNet neural network. Int. Rev. Appl. Sci. Eng. 2024, 15, 355–364. [Google Scholar] [CrossRef]
- Flegner, P.; Kačur, J.; Durdán, M.; Laciak, M. Visualization of Industrial Signals Using Symmetry-Aware Spectrogram Quantization. Symmetry 2025, 17, 876. [Google Scholar] [CrossRef]
- Hao, W.; Dai, Z.; Li, G.; Lv, S.; Sun, Q.; Lu, N.; Ma, J. A Voltage Parameter Adaptive Detection Method for Power Systems Under Grid Voltage Distortion Conditions. Symmetry 2025, 17, 975. [Google Scholar] [CrossRef]
- Chen, L.; Yan, J.; Jia, X.; Zhao, C.; Xu, J. Efficient Calculation and Component Analysis of Fault Current in MMC-HVDC Grid. CSEE J. Power Energy Syst. 2022, 11, 1744–1754. [Google Scholar]
- Wang, B.; Liu, Y.; Yue, K.; Lu, D.; Zhao, J. Improved Dynamic State Estimation Based Protection on Transmission Lines in MMC-HVDC Grids. IEEE Trans. Power Deliv. 2021, 37, 3567–3581. [Google Scholar] [CrossRef]
- Torwelle, P.; Bertinato, A.; Raison, B.; Le, T.D.; Petit, M. Fault Current Calculation in MTDC Grids Considering MMC Blocking. Electr. Power Syst. Res. 2022, 207, 107662. [Google Scholar] [CrossRef]
- Zheng, F.; Su, M.; Liu, B.; Liu, W. Adaptive Virtual Inertia Control Strategy for a Grid-Connected Converter of DC Microgrid Based on an Improved Model Prediction. Symmetry 2023, 15, 2072. [Google Scholar] [CrossRef]
- Nasim, F.; Khatoon, S.; Nasiruddin, I.; Shahid, M.; Urooj, S.; Bilal, B. Support-Vector-Regression-Based Intelligent Control Strategy for DFIG Wind Turbine Systems. Machines 2025, 13, 687. [Google Scholar] [CrossRef]
- Zheng, F.; Peng, Y.; Wang, W.; Zheng, S. Research on the Fault-Transient Characteristics of a DC Power System Considering the Cooperative Action of a Flexible Current-Limiting Device and a Circuit Breaker. Symmetry 2023, 15, 134. [Google Scholar] [CrossRef]
- Cai, H.; Yan, M.; Han, X.; Wang, G.; Wang, Q.; Huang, Y. Evaluation System of AC/DC Strong–Weak Balance Relationship and Stability Enhancement Strategy for the Receiving-End Power Grid. Energies 2025, 18, 4216. [Google Scholar] [CrossRef]
- Jayamaha, D.; Lidula, N.W.A.; Rajapakse, A.D. Wavelet-Multi Resolution Analysis Based ANN Architecture for Fault Detection and Localization in DC Microgrids. IEEE Access 2019, 7, 145371–145384. [Google Scholar] [CrossRef]
- Yadav, N.; Tummuru, N.R. Filter Capacitor Current Dynamics-Based Frequency-Domain Fault Detection Approach for Grid-Connected Low-Voltage DC Microgrid. IEEE Trans. Ind. Electron. 2023, 70, 12784–12794. [Google Scholar] [CrossRef]
- Huang, K.; Zhang, W.; Xu, Y.; Wu, C.; Li, W. A Vulnerability Identification Method for Distribution Networks Integrating Fuzzy Local Dimension and Topological Structure. Processes 2025, 13, 2438. [Google Scholar] [CrossRef]
- Bernal-Carvajal, N.J.; Mora-Peña, C.A.; Montoya, O.D. Multi-Objective Optimization for Economic and Environmental Dispatch in DC Networks: A Convex Reformulation via a Conic Approximation. Electricity 2025, 6, 43. [Google Scholar] [CrossRef]
- Jiang, K.; Li, L.; He, Z.; Liu, D. Stability Limit Analysis of DFIG Connected to Weak Grid in DC-Link Voltage Control Timescale. Electronics 2025, 14, 3022. [Google Scholar] [CrossRef]
- Qin, Y.; Wang, H.; Zhuang, S.L.; Cai, X.; Lv, J.; Huo, Q.T. High-Frequency Resonance Analysis of Offshore Wind Farm Collection Grid. Proc. CSEE 2022, 42, 5169–5182. (In Chinese) [Google Scholar]
- Zhang, C.; Cai, X.; Molinas, M.; Rygg, A. On the Impedance Modeling and Equivalence of AC/DC-Side Stability Analysis of a Grid-Tied Type-IV Wind Turbine System. IEEE Trans. Energy Convers. 2018, 34, 1000–1009. [Google Scholar] [CrossRef]
- Cai, X.; Li, Z. Dynamic Modeling of Wind Turbines and Wind Farms; Science Press: Beijing, China, 2016. (In Chinese) [Google Scholar]
- Liang, S.; Jiang, W.; Zeng, Z.; Wang, Z. Analysis of Symmetrical Fault Characteristics at PCC for Offshore Wind Turbine Generators. In Proceedings of the 2023 International Conference on Power System Technology (PowerCon), Jinan, China, 21 September 2023; pp. 1–5. [Google Scholar]
- GB/T 19963.2-2024; Technical Regulations for Wind Farm Integration into Power Systems—Part 2: Offshore Wind Power. China Electricity Council; China Standard Press: Beijing, China, 2024.
- GB/T 19963.1-2021; Technical Regulations for Wind Farm Integration into Power Systems—Part 1: Onshore Wind Power. China Electricity Council; China Standard Press: Beijing, China, 2021.
Sending System Type | Parameter Category | Fault Characteristic Parameters (Target Parameters) | Scenario Configuration Parameters |
---|---|---|---|
Sent out by an AC submarine cable | Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.9 p.u. (2) RMS voltage peak: 1.2 p.u. (3) Transient oscillation time: 200 ms (4) Phase shift angle: 15° | (1) Wind turbine output: 100% (2) 220 kV line length: 40 km (3) Fault location: 220 kV outgoing line of P2 wind farm |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.2 p.u. (2) Transient oscillation dominant frequency: 230 Hz (3) Voltage drop: 0.2 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 2.8 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.7 p.u. (2) RMS voltage peak: 1.1 p.u. (3) Transient oscillation time: 180 ms (4) Phase transition Angle: 16° | (1) Wind turbine output: 50% (2) 220 kV line length: 20 km (3) Fault location: Fault in the 35 kV outgoing line of P2 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.1 p.u. (2) Transient oscillation dominant frequency: 360 Hz (3) Voltage drop: 0.2 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 0.2 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.6 p.u. (2) RMS voltage peak: 1.15 p.u. (3) Transient oscillation time: 180 ms (4) Phase transition angle: 2.1° | (1) Wind turbine output: 100% (2) 220 kV line length: 20 km (3) Fault location: Fault in the 35 kV outgoing line of P1 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.2 p.u. (2) Transient oscillation dominant frequency: 360 Hz (3) Voltage drop: 0.8 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 1.2 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.5 p.u. (2) RMS voltage peak: 1.1 p.u. (3) Transient oscillation time: 200 ms (4) Phase transition angle: 2.6° | (1) Wind turbine output: 100% (2) 220 kV line length: 40 km (3) Fault location: Fault in the 35 kV outgoing line of P2 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.25 p.u. (2) Transient oscillation dominant frequency: 230 Hz (3) Voltage drop: 0.5 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 9.5 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.4 p.u. (2) RMS voltage peak: 1.1 p.u. (3) Transient oscillation time: 200 ms (4) Phase transition angle: 1.1° | (1) Wind turbine output: 100% (2) 220 kV line length: 20 km (3) Fault location: Fault in the 35 kV outgoing line of P2 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.1 p.u. (2) Transient oscillation dominant frequency: 350 Hz (3) Voltage drop: 0.5 p.u. | (1) 35 kV line length: 15 km (2) Fault resistance: 9.5 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.8 p.u. (2) RMS voltage peak: 1.3 p.u. (3) Transient oscillation time: 250 ms (4) Phase transition angle: 18° | (1) Wind turbine output: 100% (2) 220 kV line length: 70 km (3) Fault location: Fault in the 220 kV outgoing line of P2 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.3 p.u. (2) Transient oscillation dominant frequency: 170 Hz (3) Voltage drop: 0.2 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 2.8 Ω |
Sending System Type | Parameter Category | Fault Characteristic Parameters (Target Parameters) | Scenario Configuration Parameters |
---|---|---|---|
Flexible direct current output | Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 2.2 p.u. (2) RMS voltage peak: 1.35 p.u. (3) Transient oscillation time: 240 ms (4) Phase transition angle: 19° | (1) Wind turbine output: 100% (2) 220 kV line length: 40 km (3) Fault location: Fault in the 220 kV outgoing line of P2 wind farm |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.5 p.u. (2) Transient oscillation dominant frequency: 230 Hz (3) Voltage drop: 0 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 0.01 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 2.0 p.u. (2) RMS voltage peak: 1.3 p.u. (3) Transient oscillation time: 230 ms (4) Phase transition angle: 21° | (1) Wind turbine output: 100% (2) 220 kV line length: 30 km (3) Fault location: Fault in the 220 kV outgoing line of P2 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.4 p.u. (2) Transient oscillation dominant frequency: 290 Hz (3) Voltage drop: 0 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 0.01 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.9 p.u. (2) RMS voltage peak: 1.3 p.u. (3) Transient oscillation time: 240 ms (4) Phase transition angle: 21° | (1) Wind turbine output: 100% (2) 220 kV line length: 40 km (3) Fault location: Fault in the 220 kV outgoing line of P1 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.4 p.u. (2) Transient oscillation dominant frequency: 220 Hz (3) Voltage drop: 0 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 0.01 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.8 p.u. (2) RMS voltage peak: 1.3 p.u. (3) Transient oscillation time: 240 ms (4) Phase transition angle: 21° | (1) Wind turbine output: 100% (2) 220 kV line length: 40 km (3) Fault location: Fault in the 35 kV outgoing line of P1 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.4 p.u. (2) Transient oscillation dominant frequency: 220 Hz (3) Voltage drop: 0 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 0.01 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.8 p.u. (2) RMS voltage peak: 1.2 p.u. (3) Transient oscillation time: 280 ms (4) Phase transition angle: 16° | (1) Wind turbine output: 100% (2) 220 kV line length: 20 km (3) Fault location: Fault in the 35 kV outgoing line of P1 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.35 p.u. (2) Transient oscillation dominant frequency: 310 Hz (3) Voltage drop: 0.2 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 0.3 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.7 p.u. (2) RMS voltage peak: 1.2 p.u. (3) Transient oscillation time: 220 ms (4) Phase transition angle: 1.6° | (1) Wind turbine output: 100% (2) 220 kV line length: 20 km (3) Fault location: Fault in the 35 kV outgoing line of P2 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.25 p.u. (2) Transient oscillation dominant frequency: 300 Hz (3) Voltage drop: 0.5 p.u. | (1) 35 kV line length: 15 km (2) Fault resistance: 0.6 Ω | |
Transient symmetry indicators | (1) Instantaneous three-phase voltage peak: 1.6 p.u. (2) RMS voltage peak: 1.2 p.u. (3) Transient oscillation time: 230 ms (4) Phase transition angle: 1.2° | (1) Wind turbine output: 100% (2) 220 kV line length: 20 km (3) Fault location: Fault in the 35 kV outgoing line of P2 wind farm | |
Transient asymmetry indicators | (1) dq voltage amplitude peak: 1.2 p.u. (2) Transient oscillation dominant frequency: 315 Hz (3) Voltage drop: 0.5 p.u. | (1) 35 kV line length: 5 km (2) Fault resistance: 0.6 Ω |
High and Low Breakdown Voltage Range | |||
---|---|---|---|
dq voltage amplitude | instantaneous three-phase voltage | effective value of voltage | |
High voltage | 1.3 p.u | 1.85 p.u | 1.2 p.u |
Low voltage | 0 p.u | \ | 0 p.u |
The main frequency range of the fault transient oscillation | |||
160 Hz ≤ f ≤ 360 Hz |
High and Low Breakdown Voltage Range | |||
---|---|---|---|
dq voltage amplitude | instantaneous three-phase voltage | effective value of voltage | |
High voltage | 1.5 p.u | 2.25 p.u | 1.35 p.u |
Low voltage | 0 p.u | \ | 0 p.u |
The main frequency range of the fault transient oscillation | |||
180 Hz ≤ f ≤ 310 Hz |
Line Parameters | Characteristic Parameters of Transient Attenuation Components | |||||
---|---|---|---|---|---|---|
Line Length (km) | R (Ω) | L (H) | C (uF) | Amplitude UT | Attenuation Rate α | Oscillation Frequency β |
20 | 8.1722 | 0.02776 | 3.3267 | 0.6381 | 300.1202 | 3305.1408 |
30 | 15.4756 | 0.04851 | 3.2694 | 0.6809 | 228.4437 | 2540.5119 |
40 | 11.1694 | 0.05220 | 6.1581 | 0.7449 | 189.0887 | 2093.7014 |
50 | 11.1264 | 0.05142 | 4.5229 | 0.6930 | 154.0499 | 1780.2490 |
60 | 13.2159 | 0.07566 | 5.6590 | 0.6258 | 140.2976 | 1544.7172 |
70 | 13.0757 | 0.06698 | 8.1174 | 0.6334 | 132.1306 | 1371.3619 |
Line Length (km) | Original Waveform Peak U0 (p.u.) | Reproduced Peak Waveform U1 (p.u.) | Error ΔU/U0 |
---|---|---|---|
20 | 1.66 | 1.61 | 3.01% |
30 | 1.74 | 1.66 | 4.60% |
40 | 1.78 | 1.71 | 3.93% |
50 | 1.72 | 1.63 | 5.23% |
60 | 1.69 | 1.61 | 4.73% |
70 | 1.68 | 1.61 | 4.17% |
Line Length (km) | Original Waveform
Frequency f0 (Hz) | Reproduced Waveform Frequency f1 (Hz) | Error ΔU/U0 |
---|---|---|---|
20 | 356.38 | 361.69 | 1.49% |
30 | 287.93 | 286.37 | 0.54% |
40 | 246.29 | 245.50 | 0.32% |
50 | 216.98 | 216.27 | 0.33% |
60 | 194.81 | 194.42 | 0.20% |
70 | 177.85 | 177.74 | 0.06% |
Line Length (km) | The Decay Rate of the Original Waveform α0 | Reproduced Waveform Attenuation Rate α1 | Error ΔU/U0 |
---|---|---|---|
20 | 98.79 | 89.54 | 9.33% |
30 | 59.12 | 60.22 | 1.86% |
40 | 49.55 | 52.19 | 5.33% |
50 | 45.25 | 47.44 | 4.84% |
60 | 43.34 | 45.71 | 5.47% |
70 | 43.46 | 44.46 | 2.30% |
Line Length (km) | Original Waveform Peak U0 (p.u.) | Reproduced Peak
Waveform U1 (p.u.) | Error ΔU/U0 |
---|---|---|---|
20 | 1.72 | 1.64 | 5.14% |
30 | 1.78 | 1.70 | 4.43% |
40 | 1.87 | 1.75 | 6.68% |
50 | 1.84 | 1.73 | 6.43% |
60 | 1.81 | 1.72 | 5.47% |
70 | 1.78 | 1.68 | 5.94% |
Line Length (km) | Original Waveform
Frequency f0 (Hz) | Reproduced Waveform
Frequency f1 (Hz) | Error ΔU/U0 |
---|---|---|---|
20 | 362.54 | 341.87 | 5.70% |
30 | 286.92 | 284.98 | 0.67% |
40 | 244.90 | 243.51 | 0.57% |
50 | 216.38 | 213.01 | 1.55% |
60 | 194.59 | 189.91 | 2.40% |
70 | 177.15 | 171.76 | 3.04% |
Line Length (km) | The Decay Rate of the Original Waveform α0 | Reproduced Waveform Attenuation Rate α1 | Error ΔU/U0 |
---|---|---|---|
20 | 48.87 | 60.11 | 22.99% |
30 | 30.17 | 38.84 | 28.74% |
40 | 28.03 | 34.34 | 22.51% |
50 | 24.88 | 30.10 | 20.98% |
60 | 23.56 | 29.59 | 25.59% |
70 | 21.02 | 26.96 | 28.26% |
Comparison
Dimension | Traditional Impedance-Voltage Divider [11] | High-Order EMTP-RV Model [7] | Onshore Wind Power Model [12] | Proposed Method |
---|---|---|---|---|
Core Topology/Technology | Passive R-C-L static network | Detailed MMC-HVDC full-order model | Overhead line + static turbine model | Embedded symmetry–asymmetry constrained RLC second-order model |
Ability to Capture Symmetry–Asymmetry Dynamics | None | Yes | No | Yes |
Computational Complexity | Low | High | Medium | Low |
Offshore Scenario Adaptability | Poor | Good | Poor | Excellent |
Asymmetric Feature Fitting R2 | 0.6 | 0.90 | 0.7 | 0.92 |
Comparison Dimension | Voltage Level Scenarios | Fault Type Scenarios |
---|---|---|
Parameter Setting | 35 kV: submarine cable capacitance Ceq = 0.3\mu F/m, inductance Leq = 0.2 mH/m; 110 kV: submarine cable capacitance Ceq = 0.22\mu F/m, inductance Leq = 0.25 mH/m | Three-phase short circuit: direct three-phase short circuit at fault point, no grounding resistance; single-phase grounding: phase A short circuit via 10 Ω grounding resistance; two-phase short circuit: direct short circuit between phase A and phase B |
Transient Voltage Peak (pu) | 35 kV: 1.85; 110 kV: 1.65 | Three-phase short circuit: 1.85; single-phase grounding: 1.70; two-phase short circuit: 1.78 |
Zero-Sequence Voltage Peak (pu) | 35 kV: 0.32; 110 kV: 0.28 | Three-phase short circuit: 0; single-phase grounding: 0.30; two-phase short circuit: 0.18 |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Zheng, Y.; You, Q.; Chen, Y.; Guo, H.; Yang, H.; Liang, S.; Pan, X. Modeling Transient Waveforms of Offshore Wind Power AC/DC Transmission Faults: Unveiling Symmetry–Asymmetry Mechanisms. Symmetry 2025, 17, 1551. https://doi.org/10.3390/sym17091551
Zheng Y, You Q, Chen Y, Guo H, Yang H, Liang S, Pan X. Modeling Transient Waveforms of Offshore Wind Power AC/DC Transmission Faults: Unveiling Symmetry–Asymmetry Mechanisms. Symmetry. 2025; 17(9):1551. https://doi.org/10.3390/sym17091551
Chicago/Turabian StyleZheng, Yi, Qi You, Yujie Chen, Haoming Guo, Hao Yang, Shuang Liang, and Xin Pan. 2025. "Modeling Transient Waveforms of Offshore Wind Power AC/DC Transmission Faults: Unveiling Symmetry–Asymmetry Mechanisms" Symmetry 17, no. 9: 1551. https://doi.org/10.3390/sym17091551
APA StyleZheng, Y., You, Q., Chen, Y., Guo, H., Yang, H., Liang, S., & Pan, X. (2025). Modeling Transient Waveforms of Offshore Wind Power AC/DC Transmission Faults: Unveiling Symmetry–Asymmetry Mechanisms. Symmetry, 17(9), 1551. https://doi.org/10.3390/sym17091551