You are currently viewing a new version of our website. To view the old version click .
Symmetry
  • Article
  • Open Access

18 August 2022

Distributed Optimal Placement Generators in a Medium Voltage Redial Feeder

and
1
Institute of Intelligent Systems, University of Johannesburg, Johannesburg 2092, South Africa
2
Digital Transformation, Tshwane University of Technology, Pretoria West, Pretoria 0183, South Africa
*
Author to whom correspondence should be addressed.
This article belongs to the Section Engineering and Materials

Abstract

Distributed generation (DG) is an important issue for distribution networks for power loss improvement. However, the location and size of generators remain a challenge for existing techniques. This work investigates the optimal placement of a distributed generator on a medium voltage radial feeder. Simulated annealing optimisation is used to find an optimal bus of connecting a distributed generator variable-spider. The optimisation technique is then applied to a power flow Matlab program that incorporates the Newton–Raphson method. DigSilent PowerFactory simulations software is used to validate the results that are obtained from the Matlab program. The results indicate that the optimal bus for a 14-bus radial feeder loaded at 5 MVA while using a 1.5 MW DG is bus 11. This is because connecting the distributed generator at bus 11 resulted in maximum loss reduction on the feeder. The Matlab tool proposed in this study can be used to find the optimal bus where a distributed generator can be connected to a medium voltage radial feeder, thereby improving power quality and fulfilling load demand with minimal size to make the system economical.

1. Introduction

Energy resources can be classified into three categories, namely, fossil fuels, nuclear energy and renewable energy []. Fossil fuel energy is energy that is generated from the use of hydrocarbons (oil, coal and natural gas) that form from dead organisms such as plants and animals that were buried millions of years ago [,,]. Approximately 66% of electricity generated worldwide comes from fossil fuels []. Nuclear energy is energy that is released from a nuclear reaction that takes place through fission or fusion []. By the end of 2002, there were 414 nuclear power plants, which were supplying about 16% of the global electricity generated []. Nuclear energy is used as support energy in most countries []. The expansion in usage of nuclear energy relies on reactor technology innovation, which should ensure that nuclear security and proper disposal of nuclear wastes are in place []. Renewable energy is defined as energy that is generated from renewable natural resources such as wind, sunlight, geothermal heat, water and biomass [].
There are five types of renewable energy technologies, namely, biomass, hydropower, solar, wind and tidal waves. Biomass is defined as the energy generated from the combustion of organic materials. Examples of organic materials are wood chunks and debris, human and animal wastes, dedicated crops such as wheat and sugar cane and liquefied oil derived from biomass. During combustion, the organic materials are used to burn water into steam, which is used to drive a turbine that is coupled to a generator. Hydropower is considered one of the biggest renewable energy technologies [,]. In 2006, hydropower stations were contributing approximately 15% of the global electricity [,,,,].
This kind of technology converts the potential energy of water into mechanical energy. The water flows from a reservoir down a penstock using gravity. The water then hits the fins of a turbine, which is coupled to a generator, installed in the penstock. The water from the turbine is allowed to flow downstream of the dam to the river. Solar power is defined as the ability to convert sunlight into electricity [,,]. Two methods are used to convert sunlight into electricity, and they are photovoltaic (PV) cells and concentrated solar power (CSP) [,]. PV cells are known as direct because the electricity is generated by them. With CSP, mirrors and lenses concentrate the sunlight to a collector, which then transfers the heat from the sun to a heat transfer fluid. The fluid is then used for generating electricity. The heat can also be used for other industrial processing applications as well as space heating [,].
There are four types of CSP technologies: parabolic trough, fresnel reflector, central receiver and parabolic dish [,]. Currently, South Africa does not have wind farms that are commercially operational [,]. The first commercial wind farm, called Sere, is currently under construction in the Western Cape Province and is expected to be fully operational by halfway through the year 2022 and commercially available by the end of 2022. The wind farm is expected to deliver 100 MW of power []. A wind farm consists of wind turbines that are connected to give one output, e.g., 100 MW [,].
The major components of a wind turbine are the rotor, fins, low-speed and high-speed shafts, gearbox, generator, controller, anemometer, wind vane and tower [,]. When the wind blows, it hits the fins of the rotor and then the rotor rotates. The rotor is attached to the low-speed shaft, so that when the rotor rotates the shaft also rotates, causing the gearbox system to turn. The high-speed shaft is attached between the gearbox system and the generator. When the high-speed shaft rotates, the generator rotates as well, thus generating electricity [,,].
Tidal power is defined as the form of hydropower that converts the energy of ocean tides into a useful form of electrical energy [,]. The gravitational force of the moon and sun causes the motion of the ocean. Since the moon is closer to the earth than the sun is, the motion of the ocean is mostly due to the moon. When such motions occur, waves called tides are formed [,]. A Matlab-Simulink model has been used to simulate a tidal current turbine [].
There are two commercially available methods of generating tidal power, and they are tidal stream generator and tidal barrage [,]. A tidal stream generator is a generator that generates electricity due to the flow of tidal water through it [,]. These generators are mounted in the water of the ocean, and the motion of the ocean tides causes the blades of the generators to rotate, thus causing the generator to rotate and generate electricity [,]. This kind of tidal generator resembles that of a wind turbine. The tidal barrage method employs a technique that is similar to that used in a hydropower station [,]. In this method, sluice gates are opened for the tides to fill up a basin of a barrage. The water is kept in the basin until the tides have created a suitable head. The water is then released from the basin to the sea via turbines until the tides return. Electricity is then generated by the generators that are coupled to the turbines [,].
Two types of rotating generators are used for wind turbines: synchronous generators and induction generators []. The induction generators can be classified as fixed-speed and variable-speed [,]. The induction generator that is used most is a double-fed induction generator (DFIG). It is mostly used in applications such as wind turbines that require variable-speed control [].
Africa and the Middle East have the best solar irradiance []. Most areas in South Africa have an average of more than 2500 sunshine hours per year and an average solar irradiance of between 4.5 and 6.5 kWh/m2 in one day []. The annual 24-h global solar irradiance average is about 220 W/m2 for South Africa, compared to 150 W/m2 for the USA and 100 W/m2 for Europe []. According to the South African Weather Service [], there are two provinces in South Africa, namely, Eastern Cape and Western Cape, that have the most winds.
The Western Cape’s Cape Point experiences winds of about 14 m/s on annual average, with 42% of the winds having a wind speed greater than 8 m/s []. In Cape Town, winds with a speed greater than 8 m/s occur on 18.1% days of the year and the average annual speed of the wind is 1.6 m/s. In the Eastern Cape, winds of speeds of about 1.6 m/s annual average are experienced in Port Elizabeth; wind speeds higher than 8 m/s are experienced on 20.2% days of the year [].
In South Africa, the place that is considered to be very hot is Letaba in Limpopo Province. It has a mean annual temperature and average annual maximum temperature of 23.3 °C and 35 °C, respectively []. The coldest place in South Africa is Buffelsfontein in the Eastern Cape; this place has a mean annual temperature and an average annual high and low temperatures of 11.3 °C and 2.8 °C, respectively [].
Increasing usage of distributed generation by power utility companies means increasing the construction of renewable energy farms, e.g., PV farms and wind turbine farms. The community where such farms are constructed will have jobs during the construction and also during maintenance and operation []. The Sere Wind Farm that is currently under construction in the Western Cape employed about 400 people from the Matzikama community and its surroundings []. The supplier of the farm equipment will also create jobs. The persons employed due to the existence of renewable generation will also contribute to the economy of the country, South Africa in this case.
One disadvantage during the construction of renewable energy generators is that there might be traffic around the towns when the vehicles carrying site equipment pass by. Wind turbines make noise when they are operational, and this might affect surrounding communities [].
Eskom’s (a South African utility company) power generation is currently dominated by coal power []. The production of power from coal is limited to its reserves, and it is also an environmental issue. Coal is a source of carbon dioxide and other gases; carbon dioxide contributes to global warming, and the other gases lead to acid rains []. As part of the initiation by the South African government to combat carbon dioxide emissions, it was expected that 10,000 GWh of energy should be from renewable energy by the year 2013 [].
Nuclear energy is considered to have minimal negative effects on the environment, but poor disposal of its wastes can have severe consequences on the environment []. Even though renewable energy is known to be clean energy, it also affects the environment, e.g., when constructing a hydropower station, a dam is built, which then starves natural vegetation, fishes, etc. downstream of the dam []. The same is true for tidal generators, which affect the lives of animals such as fish that live in water [].
Photovoltaic (PV) cells are considered as clean without any emissions during their operation, but the chemicals that are used during their manufacturing can have severe consequences on the environment []. Proper disposal of solar panels is very important at the end of their life.
Independent power producers apply to Eskom to have their distributed generators (e.g., wind, solar) connected to the Eskom power system grid. Such connections are done both on the medium voltage (MV) network and on the low voltage (LV) network of the distribution network. Power from distributed generations depends on the availability of solar, wind, etc., and this can affect the power system stability []. The traditional power system always assumed that power flow is from generation to distribution, but with the introduction of distributed generations, power can also be generated from distribution to generation; this, therefore, changes the configuration of the power system network and so is its expected operation [].
The major contribution of this paper is an investigation of the optimal placement of a distributed generator on a medium voltage radial feeder. The research investigates the impact of connecting distributed generators to a power system to find the optimal location and sizes of such generators. This is meant to help reduce power losses while maintaining a voltage profile within acceptable limits. The research will therefore assist power utility companies, such as Eskom, Municipalities and independent power producers (IPPs) in South Africa and beyond to be aware of the impact of connecting distributed generation into their grid and to plan an optimal location for their distributed generation farms for maximum generation. This will help them to avoid building power farms where they will get minimum generation or where they will get maximum generation but are too far from a distribution network.
The remainder of the paper is organised as follows. Section 2 presents the fundamental concepts on optimal placement of distributed generators, and Section 3 explains the study methodology. Section 4 shows our experiments on large-scale real power datasets. Section 5 discusses the results of our experimentation. We draw our conclusions in Section 6.

3. Research Methodology

3.1. Analysis of a Distribution Radial Feeder

The single-line diagram in Figure 1 below shows a distribution radial feeder with N buses and N branches. S0 indicates the apparent power injected by the source at bus 0 with voltage, while V0 is the source voltage. L0, L1, …, and LN indicate the lines from the source to the bus N, respectively.
Figure 1. Single-line diagram of a distribution feeder with N buses.
The line impedance at each branch and the apparent power at each bus are given by the following general expressions:
z N 1 = r N 1 + j x N 1 S N 1 = S N + S l o s s N 1 + S D N 1 S N = S D N
where r and x are the resistance and reactance, Sloss are the losses on each line and SD is the load apparent power. The voltage at each bus is given by
V i + 1 = | V i | δ i V z i
where Vzi is the voltage drop through the impedance Zi. The power factor (pf0) at the source is given by
p f 0 = P 0 S 0
It is impractical to find the power factor on each load on a feeder; for analysis purposes, the load power factor is assumed to be the same as the source power factor, i.e.,
p f D = p f 0
The Ybus of a radial feeder is therefore computed using the diagram below, which is an updated diagram of Figure 2.
Figure 2. The schematic diagram for deriving the Ybus of a radial feeder.
From Figure 2, the admittances are given by
y 12 = 1 z 12 y 23 = 1 z 23 y ( n 1 ) n = 1 z ( n 1 ) n Y 11 = y 12 ; Y 12 = y 12 = Y 21 Y 22 = y 12 + y 23 ; Y 23 = y 23 = Y 32
Y ( n 1 ) n = y ( n 1 ) n = Y n ( n 1 )
Y n n = y ( n 1 ) n + y n ( n + 1 )
Since this is a radial feeder, some of the off-diagonal admittances ( Y i j ) are zero. The Ybus radial feeder with N buses is then found to be
Y b u s = [ Y 11 Y 21 0 0 Y 12 Y 22 Y 32 0 0 Y 23 0 0 0 0 Y ( n 1 ) ( n 1 ) Y n ( n 1 ) 0 0 0 Y ( n 1 ) n Y n n ]
Therefore, the Ybus for a radial feeder is applied to the Newton–Raphson Method to obtain the bus voltages and angles as well as the power injections to the buses and line losses.

3.2. The Objective Function and Simulated Annealing Algorithm Applied to a Distribution Feeders

  • The objective function: The main objective of optimally placing a distributed generator (DG) on a medium voltage (MV) radial feeder is to ensure that the active and reactive losses are as minimal as possible. In simple terms, the total losses on a radial MV distribution feeder must be minimised when the DG is connected at an optimal position. The minimum and maximum voltages at each bus must not be violated. The thermal ratings of the lines must also not be exceeded. The two conditions mentioned above can be written as follows:
    V min V b u s V max
In practical situations, the values of the bus minimum and maximum voltages are given as follows:
V min = 0.95 p u V max = 1.05 p u
I l i n e 0.95 I l i n e _ r a t e d
The objective function is defined as follows:
Minimise   f ( X i )
where f ( X i ) is the total feeder losses, X i indicates the design point and i the number of iterations subject to the above constraints.
2.
Defining the simulated annealing algorithm:
-
Let f indicates the feeder losses.
-
Choose a value of the starting temperature T, number of predetermined values n = N−1 (N = number of buses, n = number of bus, excluding the slack bus) and C, which is the temperature scaling factor.
-
Obtain the base losses f (X0) using the Newton–Raphson method.
-
Set p = 1 and i = 1.
-
Randomly choose the bus X1 to connect to the DG too. Compute f (X1) and
-
f = f (X1) − f (X0).
-
If ∆f ≤ 0, then accept bus X1 as the next design point (bus), else if ∆f > 0, then accept X1 as the next design point with a probability of e−Δf/kT = e−Δf/T, since k = 1 for simplicity reasons, else X1 is rejected. Note the voltage and thermal constraints should not be violated.
-
Set i = i + 1 and repeat steps 4 and 5 above. If in, then set p = p + 1, scale the temperature by C and then start in step 3.

3.3. The Case Study

In this case study, a Megawatt Park-Umngeni 11 kV feeder was used for the demonstration of the application of the simulated annealing algorithm. The feeder feeds from a substation called Megawatt Park. The feeder line data are shown in Table 1.
Table 1. Line data.
In 2015, the feeder was loaded at a maximum demand (MD) of 5000 kVA and an average power factor of 0.94. The load data of the feeder that corresponds to the MD is shown in Table 2.
Table 2. Load data.
A load flow study tool that incorporates the Newton–Raphson method was programmed using Matlab (See Figure 3). The Matlab tool is equipped with power factor and constant voltage controls and constant voltage control with reactive power compensation. The graphical user interface of the tool is shown in the figure below. The tool opens a “*.csv” file with feeder information, such as a bus number, conductor impedance and installed capacity at each bus. The data are read and then displayed under “LINE DATA” and “LOAD DATA”.
Figure 3. MATLAB TOOL GUI.
The data that are populated under “LOAD DATA” are the load bus number and the installed capacity at each bus on the feeder. The user, therefore, inputs the feeder’s electrical data such as source voltage, maximum demand (MD), power factor (pf), and the distributed generator’s (DG) proposed bus of connection, capacity, and control (voltage control with reactive power compensation and power factor). The user then presses the “CLICK TO PROCESS DATA” button to run the load flow studies. The results before and after generator connection and during generator connection at an optimal bus are generated. The studies were performed for maximum loading and maximum generation and minimum loading and maximum generation.
The feeder was then modelled in DigSilent Power Factory software, and the simulation was done for three scenarios, namely, (1) before generator connection, (2) with generator connection at a user-defined bus, (3) with generator connection at an optimal bus that was obtained from the Matlab tool. For the generator connection cases, the three control functions for generators were tested. DigSilent Power Factory was used to verify if the Matlab Tool results are precise. The generator used for these studies was a 1500 kW double-fed induction generator (DFIG).

4. Experimental Results

A snapshot of the Matlab tool showing the results of the studies with power factor control and a DG connection 6 is shown in Figure 4. To check the accuracy results, the node voltage values obtained using analytical methods and the exact ones obtained by a load flow computer program are compared. The results show the optimal bus distribution numbers for digital allocation to be bus 6, with the concentrated load method as more accurate.
Figure 4. Matlab tool results with DG connected at bus 6.
The feeder voltage profiles, with DG connected at buses 6 and 11, obtained using DigSilent Power Factory are shown in Figure 5 and Figure 6. The blue curve is the voltage profile without DG. The yellow curve correspond to the voltage profile with DG operating at different power factors. It appears that the maximum power that can be generated by the DG without violating voltage limits decreases piecewise linearly with distance from the substation.
Figure 5. Voltage profile with DG connected at bus 6.
Figure 6. Voltage profile with DG connected at bus 11.
The summary of the results including all the other scenarios that were considered is shown in Table 3 and Table 4.
Table 3. Summary of results with MD = 5000 kVA.
Table 4. Summary of Results with MD = 3000 kVA.
The siting of DGs at various locations shows a positive impact on voltage profiles. However, there is a possibility of voltage rise if the DG penetration level is too high. The rise in voltage could cause misoperation of protective devices, and therefore adjustment or changes of protective devices are required. In order to accommodate more DGs, the voltage profile along the feeder should be kept within statutory limits (voltage between ± 10% of the base voltage), and there is a need to employ intelligent devices for this purpose. The development of the smart grid allows for the use of intelligent devices and thus helps to keep the voltage level within statutory limits.

5. Discussion of Results

The Matlab tool is intended to be utilised by network planning engineers when responding to independent power producers (IPPs) inquiries for generator connection on a medium voltage distribution radial feeder. Due to the number of inquiries that might be received in a day and the amount of work that is handled by network planning engineers, the time to do proper network load flow studies, using power simulation packages, for each inquiry received might be very limited. The tool will therefore ensure that a network planning engineer can do a quick power system analysis study and be able to give feedback to an IPP or customer within a reasonable time.
Depending on where the IPP is proposing to connect their generator on the feeder, the network planning engineer can therefore advise on the optimal point of connection on the feeder, and this can also assist the customer to obtain a servitude for building their power plants closest to the optimal point of the connection while at the very same time assisting the electrical utility company in reducing the losses on the feeder.
From the results obtained using the Matlab tool, it is clear that before connecting a distributed generator the voltage drops exponentially according to the feeder distance from the source. From the studies that were performed, the losses were reduced by 52% and the minimum voltage of the feeder was improved from 99.16% to 98.71% (on power factor control), 99.91% (on constant voltage control) and 99.66% (on constant voltage control with reactive power compensation) when the distributed generator was connected to bus 6, which is the bus assumed to be where an independent power producer planned to connect their generator.
From the voltage profiles, the bus voltages at the generator’s connection bus also showed improvement. The generator reactive power that could be achieved on power factor control with a power factor of 0.94 was 544 kVAR, and this led to a generator bus voltage of 99.05%. For voltage control, the generator pumped more VARs into the network to try and regulate the voltage to 1 p.u, but the generator reactive power was limited to the maximum reactive power of 940 kVAR, which was not enough to regulate the voltage to 1 p.u. The generator bus voltage obtained from the injection of 940 kVAR was 99.25%.
For the constant voltage control scheme with reactive power compensation, the voltage improved up to 1 p.u. When connecting a distributed generator at the end of the feeder, bus 14 in this case, the feeder losses were reduced by about 57.5% and 55.8% and the minimum voltages of the feeder were improved from 99.16% to 99.996% and 99.493% on constant power factor control and constant voltage control with reactive power compensation, respectively.
The main aim of the whole study was to find an optimal point where a distributed generator can be connected to a medium voltage radial feeder. The Matlab tool created to perform the instruction of finding the optimal bus chose bus 11 as the optimum bus. The results obtained from connecting the distributed generator to bus 11 showed that the loss reduction was about 60% and the feeder minimum voltages were found to be 98.99% and 99.79% on power factor control and constant voltage control with reactive power compensation, respectively.
Minimum voltage results obtained from applying power factor and voltage control schemes indicated that the end of the feeder is the point of connection when voltage improvement is the key element to be achieved. Connecting a 1.5 MW distributed generator anywhere on a radial feeder except for the busbar at the substation will result in reduced losses and improved feeder minimum voltage on the radial feeder.
The results obtained from using DigSilent PowerFactory presented similar behaviours as those obtained from the Matlab Tool. The thermal loading of the feeder was not computed in the Matlab Tool because it is known that the feeder is not thermally constrained; however, the thermal loading was noted when performing the load flow studies using DigSilent PowerFactory. For the base case, i.e., before connecting the generator, the section of the feeder with the highest thermal loading was found to be the one closest to the source. When connecting a distributed generator to the feeder, the thermal loading of the section of the feeder closest was reduced according to the size of the generator.
The losses obtained from the two tools had maximum errors of 2.67%, 3.8% and 5.42% with a distributed generator operating under power factor control, constant voltage control and constant voltage control with reactive power compensation, respectively. It was also observed that the losses obtained from using DigSilent PowerFactory were always higher than those obtained from using the Matlab Tool.
The bus voltages had an error of less than 1%. For the constant voltage control with reactive power compensation on the PowerFactory simulation, it was observed that the reactive power compensation value required to achieve a bus-controlled voltage of 1 per unit was always about 40–100 kVAR higher than the one obtained from the Matlab Tool. This might be since the DFIG template that was used when simulating consists of a 0.4/11 kV step-up transformer, which absorbs about 100 kVAR; the Matlab Tool assumed that the generator is connected directly to the 11 kV network without the need to use the step-up transformer. It was observed that the value of reactive power compensation that was required to achieve a voltage of 1 p.u. at a point connection dropped as the connection point moved away from the source.
Connecting a generator at bus 11 will result in a saving of 38.21 − 14.94 = 23.27 kW. An RDP (Reconstruction and Development Programme) house in South Africa has a notified maximum demand (NMD) of about 2.5 kW. The number of RDP houses that can be supplied from the saved losses is 9. If each kilowatt-hour of electricity costs R1.35, then the total cost that can be recovered from the losses is about 1.35 * 9 * 24 = R291.60 per day, which translates to R106 434 per annum assuming that the generator is running for 24 h per day. The more generators are optimally connected on more than one radial feeder, the more losses can be reduced on the medium voltage network and the more houses without power can be electrified.
The Matlab Tool was also used to perform studies when the feeder load was considered to be light, i.e., 60% of the maximum demand of 5000 kVA = 3000 kVA, with an assumption that the results obtained would be very similar to when simulating with DigSilent PowerFactory. The tool indicated that bus 10 was the optimal bus for connecting a distributed generator when using power factor control. In this case, the losses before connecting the generator were sitting at 13.8 kW, and after connecting the generator at the optimal bus, the losses were reduced to 2.58 kW with a feeder minimum voltage of 99.62%. The generator bus voltage was sitting at 99.685%. When comparing the results of the heavy-loaded feeder and light-loaded feeder, it is clear that when a load of a feeder is light, then the bus voltages will rise.
Environmentally, this Matlab tool will not have any environmental impacts and it will not put the public in any danger. However, it should be stressed that renewable energy generators such as wind farms and solar and tidal waves do have an impact on the environment. As discussed in the introduction, they can cause traffic during their construction, noise when they are operating and air pollution during their manufacturing.
Simulated annealing optimisation was used because it relates well to the problem at hand. The coding of the optimisation method in Matlab was not complex, but setting up the code to the point where the optimisation could be coded was a bit of a challenge, especially for one not familiar with the Matlab programming language. The limitation with this optimisation method is that it cannot tell that it has found the optimal point, and one used additional functionality to determine the exact optimal point. Another disadvantage is that there os a trade-off between the quality of the result and the time taken for the algorithm to run.

6. Remarks and Conclusions

The objective of the study was to investigate the optimal placement of a distributed generator on a medium voltage radial feeder. Simulated annealing optimisation was used to find an optimal bus for connecting a distributed generator to a radial feeder.
A Matlab tool for performing load flow studies on medium voltage radial feeders with distributed generation was developed. The tool incorporates a simulated annealing optimisation algorithm to identify an optimal bus for distributed generator connection.
For a radial feeder, the voltage drops according to the distance from the source, i.e., the further away from the source, the more voltage drops on the feeder. The section of the feeder that carries most of the load was the one closest to the source. We have also shown that a connection of a 1.5 MW distributed generator anywhere, except the source busbar, on a radial feeder loaded at 5 MVA results in reduced losses, and connecting a distributed generator at an optimal position results in maximum loss reduction.
The optimal point of connecting a distributed generator depends on the loading of the feeder and the control function of the distributed generator. A distributed generator operating on a feeder with reduced load demand leads to a voltage rise. The generation might need to be reduced to ensure that maximum voltage constraints are not violated. Furthermore, the results showed less reactive power compensation as required when the generator connection moves away from the source.
The Matlab tool created in this research can be used to perform load flow studies in cases where the time available is very limited, provided the feeder information such as conductor type, section length and installed capacity is available and well tabulated in excel.
The study has shown how DigSilent PowerFactory can be used to perform load flow studies on medium voltage radial feeders with distributed generators. Future work will include investigating a feeder with multiple branches, taking into consideration fault levels when connecting a distributed generator and also ensuring that the basics of optimisation mathematics are covered to avoid delays, and further optimise the Matlab program for easy troubleshooting.

Author Contributions

Conceptualization, T.L. and B.T.; methodology, T.L. and B.T.; software, T.L. and B.T.; validation, T.L. and B.T.; formal analysis, T.L. and B.T.; investigation, T.L. and B.T.; resources, T.L. and B.T.; data curation, T.L. and B.T.; writing—original draft preparation, T.L. and B.T.; writing—review and editing, B.T.; visualization, T.L. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Acknowledgments

This research was supported by the University of Johannesburg in South Africa. We thank our colleagues from the Institute for Intelligent Systems who provided useful insights when the research was conducted; their comments and suggestions are invaluable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Manzamo-Agugliaro, F.; Alcayde, A.; Montoya, F.G. Scientific production of renewable energies worldwide: An overview. Renew. Sustain. Energy Rev. 2013, 18, 134–143. [Google Scholar] [CrossRef]
  2. Fossil Fuel. Available online: http://www.sciencedaily.com/articles/f/fossil_fuel.htm (accessed on 20 April 2022).
  3. Fossil Fuel. Available online: http://en.wikipedia.org/wiki/Fossil_fuel (accessed on 20 April 2022).
  4. Impact of Fossil Fuel. Available online: http://geoscience.wisc.edu/~chuck/Geo106/lect24.html (accessed on 20 April 2022).
  5. Pazheri, F.R.; Al-Arainy, A.A.; Othman, M.F.; Malik, N.H. Global renewable electricity potential. In Proceedings of the GCC Conference and Exhibition (GCC), Doha, Qatar, 17–20 November 2013; pp. 59–63. [Google Scholar]
  6. Williams, A. Role of fossil fuels in electricity generation and their environmental impact. IEE Proc. A Sci. Meas. Technol. 1993, 140, 8–12. [Google Scholar] [CrossRef]
  7. Turner, W.; Western, J. Nuclear energy’s role in a more sustainable future. In Proceedings of the Opportunities and Advances in International Electric Power Generation, International Conference, Orlando, FL, USA, 18–20 March 1996; Volume 1, pp. 81–86. [Google Scholar]
  8. Rashad, S.M. Nuclear Power and the Environment Prospects and Challenges. In Proceedings of the Radio Science Conference, Proceedings of the Twenty Third National, Menouf, Egypt, 14–16 March 2006; pp. 1–32. [Google Scholar]
  9. Available online: http://www.empr.gov.bc.ca/EAED/AEPB/Documents/CleanEnergyJune.pdf (accessed on 20 April 2022).
  10. Mohibullah, M.; Radzi, A.M.; Hakim, M.I.A. Basic design aspects of micro hydro power plant and its potential development in Malaysia. In Proceedings of the Power and Energy Conference Proceedings, Kuala Lumpur, Malaysia, 29–30 November 2004; pp. 220–223. [Google Scholar]
  11. Sriram, N.; Shahidehpour, M. Renewable biomass energy. In Proceedings of the Power Engineering Society General Meeting, San Francisco, CA, USA, 12–16 June 2005; Volume 1, pp. 612–617. [Google Scholar]
  12. Kellas, A. Biomass and electrical energy. In Proceedings of the 7th Mediterranean Conference and Exhibition on Power Generation, Transmission, Distribution and Energy Conversion, Ayia Napa, Cyprus, 7–10 November 2010; pp. 1–7. [Google Scholar]
  13. Biomess Energy. Available online: http://www.northblythproject.co.uk/biomass-energy/ (accessed on 25 March 2022).
  14. Renewable Energy. Available online: http://www.window.state.tx.us/specialrpt/energy/renewable/ (accessed on 25 March 2022).
  15. Solar Systems. Available online: www.kids.esdb.bg/solar.html (accessed on 24 April 2022).
  16. Solar Power Systems. Available online: http://en.wikipedia.org/wiki/Concentrated_solar_power (accessed on 30 March 2022).
  17. Freris, L.; Infield, D. Renewable Energy in Power Systems; John Wiley and Sons: Hoboken, NJ, USA, 2020. [Google Scholar]
  18. PowerFactory Training Notes. Introduction to Renewable Energy Generation; DigSilent Buyisa: Centurion, South Africa, 2019. [Google Scholar]
  19. Available online: http://www.irena.org (accessed on 30 March 2022).
  20. Siraj, K.; Siraj, H.; Nasir, M. Modeling and control of a doubly fed induction generator for grid integrated wind turbine. In Proceedings of the 2022 16th International Power Electronics and Motion Control Conference and Exposition (PEMC), Antalya, Turkey, 21–24 September 2014; pp. 901–906. [Google Scholar]
  21. Available online: http://en.wikipedia.org/wiki/Photovoltaic_power_station (accessed on 3 April 2022).
  22. Available online: www.eskom.co.za (accessed on 30 March 2022).
  23. Sharma, V.V.; Chawla, H. Integrated renewable systems. In Proceedings of the Power, Control and Embedded Systems (ICPCES), 2nd International Conference, Allahabad, India, 17–19 December 2012; pp. 1–6. [Google Scholar]
  24. Wind Turbine Foundations. Available online: http://wind-turbine.tripod.com (accessed on 15 March 2022).
  25. Energy Systems. Available online: http://www.esru.strath.ac.uk (accessed on 20 March 2022).
  26. Matlab. Available online: www.mathworks.com (accessed on 25 March 2022).
  27. Department of Mineral Resources and Energy. Available online: www.energy.gov.za (accessed on 15 March 2022).
  28. South African Weather Services. Available online: www.weathersa.co.za (accessed on 15 March 2022).
  29. Renewable Energy World. Available online: http://www.renewableenergyworld.com (accessed on 27 April 2022).
  30. Global Warming 101. Available online: www.nrdc.org/globalwarming/ (accessed on 27 January 2022).
  31. Radioactive Waster. Available online: http://en.wikipedia.org/wiki/Radioactive_waste (accessed on 15 March 2022).
  32. Hydropower Industry. Available online: http://www.internationalrivers.org/environmental-impacts-of-dams (accessed on 17 March 2022).
  33. Available online: http://www.oregon.gov/ODOT/HWY/OIPP/docs/ (accessed on 17 March 2022).
  34. Khani, D.; Yazdankhah, A.S.; Kojabadi, H.M. Impacts of distributed generations on power system transient and voltage stability. Int. J. Electr. Power Energy Syst. 2012, 43, 488–500. [Google Scholar] [CrossRef]
  35. Rao, S.S. Engineering Optimization: Theory and Practice, 4th ed.; Wiley: Hoboken, NJ, USA, 2009. [Google Scholar]
  36. Walsh, G.R. Methods of Optimization, 1st ed.; John Wiley and Sons: Hoboken, NJ, USA, 1975. [Google Scholar]
  37. Nemhauser, G.L.; Rinnooy, K.A.H.G.; Todd, M.J. Optimization, Handbooks in Operations Research and Management Science; Elsevier Science: North-Holland, The Netherlands, 1989; Volume 1. [Google Scholar]
  38. Raghavjee, R.; Pillay, N. A Comparison of Genetic Algorithms and Genetic Programming in Solving the School Timetabling Problem. In Proceedings of the Fourth World Congress on Nature and Biologically Inspired Computing (NaBIC), Mexico City, Mexico, 5–9 November 2012; pp. 98–103. [Google Scholar]
  39. Sickel, K.; Hornegger, J. Genetic Programming for Expert Systems. In Proceedings of the IEEE Congress on Evolutionary Computation, Barcelona, Spain, 18–23 July 2010; pp. 1–8. [Google Scholar]
  40. Filho, J.L.R.; Treleaven, P.C.; Alippi, C. Genetic-algorithm programming environments. Computer 1994, 27, 28–43. [Google Scholar] [CrossRef]
  41. del Valle, Y.; Venayagamoorthy, G.K.; Mohagheghi, S.; Hernandez, J.C.; Harley, R.G. Particle Swarm Optimization: Basic Concepts, Variants and Applications in Power Systems. IEEE Trans. Evol. Comput. 2008, 12, 171–195. [Google Scholar] [CrossRef]
  42. Dorigo, M.; Birattari, M.; Stutzle, T. Ant colony optimization. IEEE Comput. Intell. Mag. 2006, 1, 28–39. [Google Scholar] [CrossRef]
  43. Alkandari, A.M.; Soliman, S.A.; Mantwy, A.H. Simulated annealing optimization algorithm for electric power systems quality analysis: Harmonics and voltage flickers. In Proceedings of the 2008 12th International Middle East Power System Conference—MEPCON, Aswan, Egypt, 12–15 March 2008; pp. 287–293. [Google Scholar]
  44. Li, Y.; Czarkowski, D.; de Leon, F. Optimal Distributed Voltage Regulation for Secondary Networks with DGs. IEEE Trans. Smart Grid 2012, 3, 959–967. [Google Scholar]
  45. Lee, S.H.; Park, J. Optimal Placement and Sizing of Multiple DGs in a Practical Distribution System by Considering Power Loss. IEEE Trans. Ind. Appl. 2013, 49, 2262–2270. [Google Scholar] [CrossRef]
  46. Foster, J.; Berry, A.M.; Boland, N.; Waterer, H. Comparison of Mixed-Integer Programming and Genetic Algorithm Methods for Distributed Generation Planning. IEEE Trans. Power Syst. 2022, 29, 833–843. [Google Scholar] [CrossRef]
  47. Duong, Q.H.; Mithulananthan, N. Multiple Distributed Generator Placement in Primary Distribution Networks for Loss Reduction. IEEE Trans. Ind. Electron. 2013, 60, 1700–1708. [Google Scholar]
  48. Kashem, M.A.; Ganapathy, V.; Jasmon, G.B.; Buhari, M.I. A novel method for loss minimization in distribution networks. In Proceedings of the International Conference on Electric Utility Deregulation and Restructuring and Power Technologies, London, UK, 4–7 April 2000; pp. 251–256. [Google Scholar]
  49. George, S.P.; Ashok, S.; Bandyopadhyay, M.N. Impact of distributed generation on protective relays. In Proceedings of the 2013 International Conference on Renewable Energy and Sustainable Energy (ICRESE), Coimbatore, India, 5–6 December 2013; pp. 157–161. [Google Scholar]
  50. National Energy Regulator of South Africa. Grid Connection Code for Renewable Power Plants (RPPs) Connected to the Electricity Transmission System (TS) or Distribution System (DS) in South Africa; National Energy Regulator of South Africa: Pretoria, South Africa, 2022.
  51. Azmy, A.M.; Erlich, I. Impact of distributed generation on the stability of electrical power system. In Proceedings of the IEEE Power Engineering Society General Meeting, San Francisco, CA, USA, 12–16 June 2005; Volume 2, pp. 1056–1063. [Google Scholar]
  52. Slootweg, J.G.; Kling, W.L. Impacts of distributed generation on power system transient stability. In Proceedings of the Power Engineering Society Summer Meeting, Chicago, IL, USA, 21–25 July 2002; Volume 2, pp. 862–867. [Google Scholar]
  53. Camilo, L.; Cebrian, J.C.; Kagan, N.; Matsuo, N.M. Impact of distributed generation units on the sensitivity of customers to voltage sags. In Proceedings of the 8th International Conference and Exhibition on Electricity Distribution (CIRED 2005), Turin, Italy, 6–9 June 2005; pp. 1–4. [Google Scholar]
  54. Caples, D.; Boljevic, S.; Conlon, M.F. Impact of distributed generation on voltage profile in 38kV distribution system. In Proceedings of the 2011 8th International Conference on the European Energy Market (EEM), Zagreb, Croatia, 25–27 May 2011; pp. 532–536. [Google Scholar]
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.