4.3.1. Description of CPS Standard
The North American Electric Reliability Council (NERC) proposed the CPS standard containing the CPS1 and the CPS2 to replace the A1 and A2 criterion in 1998 [
19]. Instead of requiring ACE to cross zero at least once every ten minutes, CPS1 takes a more reasonable approach based on statistical theory. First, an Expression (5) is identified which represents, quantitatively, a control area’s contribution to the reliability objective of the interconnected system to which it belongs:
where
is the clock-minute average of the ACE of area
i that is required to sample every two seconds and then take the average of thirty values,
is the CPS1 control target of the root mean square of the annual 1 min frequency average deviation of the interconnected system (0.018 Hz in the Jiangsu power grid),
is the clock-minute average of frequency deviation (in Hz) that is required to sample every one second and then take the average of sixty values, and
is the frequency bias of the control area
i (−1072.5 MW/0.1 Hz in the Jiangsu power grid).
When the value is negative, it means that the control area is over-transmitted at a low frequency (less reception) or under-transmitted at a high frequency (over-received) in one minute and the control area is helping the interconnection’s regulation requirement; when the value is positive, it means the control area is over-transmitted at a high frequency (less reception) or under-transmitted at a low frequency (over-received) in one minute and the control area is acting as a burden to the interconnection’s regulation requirement.
The statistical Formulas (6) and (7) of the CPS1 (calculated as
) for a certain period of time (such as 10 min, 1 h, …, even 1 month, 1 year) are defined as follows:
where
n is the number of minutes. The CPS1 standard requires that each control area must have no less than 100% compliance. The CPS standard is implemented in the East China power grid composed of the Jiangsu power grid, Shanghai power grid, Zhejiang power grid, Anhui power grid and Fujian power grid.
It can be seen from Equation (5) that the ideal AGC control strategy must consider simultaneously ACE and
, and keep the signs of
and
opposite; that is, CPS1 ≥ 200%. Therefore, the ideal control effect under the CPS standard is shown in
Figure 7.
As shown in
Figure 6, in order to realize the ideal control strategy under the CPS standard, it is necessary to add a component
proportional to the frequency deviation
in the ARR
, namely:
where
is the proportional component in ARR, and
is the integral component in ARR.
is the CPS component in ARR, also known as CPS regulation power, and is introduced specifically for the CPS control strategy.
is the proportional gain coefficient to ensure the ACE crosses zero, and can be directly set to 1 under the CPS control strategy.
is the filtered ACE value.
is the integral gain coefficient.
is the accumulated ACE integral value of the current assessment period (such as 10 min), in MWh.
is the frequency gain coefficient, in MW/0.1 Hz.
is the filtered frequency deviation, in Hz.
4.3.2. Allocation Strategy for Control Groups of AGC
The control group of the EESS is added to participate in the ACE regulation of Jiangsu control area together with the control groups of the coal-fired unit and gas-fired power unit. The time when the control group of the EESS participates in ACE regulation can be determined by setting the control group parameters, such as group regulation mode (normal or emergency mode), positive/negative emergency threshold and the increase/decrease priorities among the groups. The EESS participates in the ARR allocation of its affiliated group. In addition, the partitioning attribute of the EESS is added to control the power flow of transmission lines in the partitioning power network of Fangjin. The corresponding relationship among the partitioning power network, the EESS, the control group of the EESS and the control area is shown in the
Figure 8.
According to the absolute value of ARR, dividing ARR into different regulation regions, including dead band, normal regulation region, assistant emergency regulation region and emergency regulation region, can more precisely characterize the power grid operating state and the demand for the amount of frequency regulation resources. Therefore, by analyzing the relationship between the response characteristics of the EESS and the conventional units and regulation requirements, and comprehensively considering EESS capacity constraints, the operating range of the SOC and power grid frequency regulation requirements, the output contribution and intervention boundaries of EESSs participating in frequency regulation are analyzed, and thus a cooperative control strategy considering ARR regions is proposed. This strategy helps to realize the complementary advantages of EESSs and conventional units.
- (1)
Dead band
According to the classification rules of ARR regions, the variation in ACE within the dead region is small, and usually fluctuates around the zero value. Such high-frequency and low-amplitude regulation signals are very unfriendly to conventional units with time delays in response, which will increase their mechanical wear and affect their service life and economy. The EESS has a fast response speed, and the charging and discharging operating conditions of the EESS are easy to change. The regulation requirements of shallow charging and shallow discharging in the dead band of ARR are a good match for the response characteristics of the EESS. Therefore, the EESS is designed to respond to the regulation demand contributing to SOC recovery, which not only reduces the probability of the ACE continuing to expand into the normal regulation region, thereby reducing the number of actions of conventional units, but also realizes the optimal management of the SOC.
The regulation demand of the EESS control group in the dead band is calculated as follows:
- (2)
Normal regulation region
Considering that the direction of area control demand varies frequently under inconsistent power deficiency, the EESS participates in AGC during contingencies or when the regulation capacity of other units is insufficient in order to prevent the waste of EESS regulation capacity on the ARR, which stays positive or negative and constantly changes the ramp load that is mainly handled by the gas-fired power and the coal-fired units rather than the EESSs with limited capacity. The frequency regulation resources within the control area are categorized into coal-fired units, gas-fired power units and EESSs, as shown in
Table 3. These units are dispatched in a priority-based order when there is available regulation capacity, and the timing when participating in regulation is determined by the activation threshold. The “unit control mode” is the control mode normally utilized by the units. The EESSs utilize the BASER or the SCHER modes. The gas-fired power units utilize the contingency-oriented SCHEE mode due to the limited natural gas capacity. The coal-fired units utilize the AUTOR mode.
In practice, the participation of units in AGC is determined by priority, the unit control mode, and the available regulation capacity [
24]. The arrangement of different regulation resources in priority order is shown in
Figure 9. In the normal regulation region, the EESSs joined in to cooperate with the coal-fired units for regulation in order to take full advantage of their limited capacity and superior regulation performance.
The ARR-to-be-dispatched
can be formulated as follows, which is equal to the difference between the total ARR
determined in (8) and the power-to-be-regulated
of unready units and is calculated every five seconds:
where
is the current unregulated power of unit
i in the same regulated direction with ARR at the moment
t.
The priority among units is grid-side EESSs, gas-fired power units and coal-fired units.
- (a)
The total amount of to-be-dispatched
of grid-side EESSs is equal to the ARR to-be-dispatched
, which can be formulated as:
- (b)
The total amount of to-be-dispatched
of gas-fired power units is equal to the ARR to-be-dispatched
minus the actual dispatched amount
of grid-side EESSs, which can be formulated as:
- (c)
The total amount of to-be-dispatched
of coal-fired units is equal to the total amount to-be-dispatched
of gas-fired power units minus the actual dispatched amount
of gas-fired power units:
Moreover, the maximum available increasing/decreasing capacity
of EESSs is the sum of the
of each EESS. The maximum available increasing/decreasing capacity
of a single EESS is usually its regulation step per minute within the regulation range of the EESS when the EESS has regulated in place and the ARR
exceeds the dead band.
- (3)
Assistant emergency regulation/emergency regulation region
In the assistant emergency/emergency regulation region, the regulation demand is large and the duration is long. The support depth and support duration of frequency regulation resources are required to be higher. According to the grouping priority control mode of the normal regulation region, the EESS, as a resource with limited capacity, will continue to fail in response to the frequency regulation demand in the assistant emergency/emergency regulation region, thus affecting its battery characteristics and service life. Therefore, as shown in
Figure 10, in the assistant emergency/emergency regulation region, the EESS control group only participates in the tracking of high-frequency components, while the coal-fired and gas-fired power units participate in the adjustment of low-frequency components with a larger base quantity.
The original ACE value
is performed on low-pass filtering to obtain the low-frequency control component
, and the calculation method is as follows:
where
is the filter factor.
The ARR undertaken by the coal-fired unit and gas-fired power unit control group adopts the superposition of the PI control and CPS components in Equation (8). Thus the ACE low-frequency component
is substituted into Equation (8) to calculate the total amount to-be-dispatched of the coal-fired unit and gas-fired power unit control groups, and then according to the respective proportion of their adjustable capacity
and
, their respective amounts to-be-dispatched is calculated as (taking the coal-fired unit and gas-fired power unit as the same control group):
where
and
are the amounts to-be- dispatched of the coal-fired unit and gas-fired power unit, respectively.
The ARR undertaken by the EESS control group is directly calculated by the proportional controller without considering the integral component and CPS component. Therefore, based on the high-frequency component signal of ACE, the total regulation amount undertaken by the EESS control group is:
4.3.3. Optimization of Dispatching Strategy among EESSs
When the SOC is within the physical and manual limits, the regulation range of EESSs is set as the intersection of the manual operation range of the SOC, the maximum discharging power and the maximum charging power. The switching between charging and discharging will be ignored when handling the operation range of EESSs in a way similar to thermal units. If the zero values of all EESSs are set as the midpoint of the operation range, the operation margin of the EESSs can be identical and the EESSs have an equal opportunity to participate in up- or down-regulation. If the regulation range is asymmetric, the power of the EESS will keep deviating from the zero point.
Therefore, the dispatching strategy for EESSs is designed with priority based on output power and the SOC. Similar to the pumped storage power station, the dispatching strategy for EESSs with two-way regulation capability can be realized by adjusting the current charging and discharging power or switching between the charging and discharging states. The dispatching strategy is described as follows:
- (1)
When the power of EESSs is required to increase, the EESS is operated in the following order: charging, suspending and discharging regulation.
- (2)
When the power of EESSs is required to decrease, the EESS is operated in the following order: discharging, suspending and charging regulation.
After considering the status switching of the EESS, the dispatching strategy undertaking ARR among EESSs is derived as follows. The EESSs are sorted according to the value of the SOC. When the power output is required to increase, the EESSs with larger SOCs increase the discharging power first. When the power output is required to decrease, the EESSs with smaller SOCs increase the charging power first. The status switching and the SOC are considered when determining the dispatched power among EESSs. The total power considering status switching and the SOC is smaller than the regulation step of the EESS.