An Occupant-Oriented Calculation Method of Building Interior Cooling Load Design

1
School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China
2
Key Laboratory of Efficient Utilization of Low and Medium Grade Energy, MOE, Tianjin University, Tianjin 300072, China
*
Author to whom correspondence should be addressed.
Received: 2 May 2018 / Revised: 25 May 2018 / Accepted: 29 May 2018 / Published: 31 May 2018
(This article belongs to the Collection Sustainable Built Environment)
Full-Text   |   PDF [9767 KB, uploaded 31 May 2018]   |  

Abstract

Given continued improvement in the thermal performance of building envelopes, interior disturbances caused by occupant behavior now have the greatest impact on building loads and energy consumption. The accurate calculation of interior load during design stage was emphasized in this paper, and a new method was proposed. Indoor occupants were considered as the core of interior disturbances, and the relationship with other interior disturbances was explored. The interior heat release was arbitrarily combined with the representative cooling load to be utilized in building cooling load calculation. Field surveys were conducted in three typical university buildings: an office building, a teaching building, and a library, located in a university in Tianjin, China. The oversized chillers supplying cooling for the buildings resulted from the over-estimating of the indoor occupant number and the power density of electric appliances. Through quantitative analysis, it was observed that the maximum representative interior loads were 196.43, 329.94, and 402.58 W/person, respectively, for the case buildings, at least 50% less than the empirical design data. Compared to the measured cooling load during the testing period, the accuracy of the modified cooling load was greater than 90%. This research is intended to serve as a reference for calculating and optimizing the design loads of cooling systems. View Full-Text
Keywords: load disturbances; representative interior load; consistency check; university buildings load disturbances; representative interior load; consistency check; university buildings
Figures

Figure 1

This is an open access article distributed under the Creative Commons Attribution License which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited (CC BY 4.0).
SciFeed

Share & Cite This Article

MDPI and ACS Style

Wang, Z.; Ding, Y.; Deng, H.; Yang, F.; Zhu, N. An Occupant-Oriented Calculation Method of Building Interior Cooling Load Design. Sustainability 2018, 10, 1821.

Show more citation formats Show less citations formats

Note that from the first issue of 2016, MDPI journals use article numbers instead of page numbers. See further details here.

Related Articles

Article Metrics

Article Access Statistics

1

Comments

[Return to top]
Sustainability EISSN 2071-1050 Published by MDPI AG, Basel, Switzerland RSS E-Mail Table of Contents Alert
Back to Top