Next Article in Journal
Evaluation of Rail Potential Based on Power Distribution in DC Traction Power Systems
Next Article in Special Issue
Marginal Generation Technology in the Chinese Power Market towards 2030 Based on Consequential Life Cycle Assessment
Previous Article in Journal
Application of a Gradient Descent Continuous Actor-Critic Algorithm for Double-Side Day-Ahead Electricity Market Modeling
Previous Article in Special Issue
Capacitor Current Feedback-Based Active Resonance Damping Strategies for Digitally-Controlled Inductive-Capacitive-Inductive-Filtered Grid-Connected Inverters
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Riding-through Technique for Seamless Transition between Islanded and Grid-Connected Modes of Droop-Controlled Inverters

1
Department of Electrical Engineering, National Sun Yat-sen University, Kaohsiung 80424, Taiwan
2
Department of Energy Technology, Aalborg University, Aalborg 9100, Denmark
*
Author to whom correspondence should be addressed.
Energies 2016, 9(9), 732; https://doi.org/10.3390/en9090732
Submission received: 31 May 2016 / Revised: 30 August 2016 / Accepted: 31 August 2016 / Published: 9 September 2016
(This article belongs to the Special Issue Microgrids 2016)

Abstract

:
This paper presents a seamless transition method for a droop-controlled inverter. The droop control is suitable to make the inverter work as a voltage source in both islanded and grid-connected modes, however, the transfer between theses modes can result in a big inrush current that may damage the system. The proposed method allows the droop-controlled inverter to improve the transient response when transferring between modes, by detecting the inrush current, activating a current control loop during transients, and then transferring back to droop-controlled mode smoothly by using a virtual inductance loop. In addition, a local phase-locked-loop (PLL) is proposed to align the inverter voltage with the grid in order to reduce the transient current during the transition. Therefore, the droop-controlled inverter is able to operate in both grid-connected and islanded modes, providing as well a smooth transition between them, requiring neither synchronization signals nor grid-side information. The control algorithm and design procedure are presented. Experimental results from a laboratory prototype validate the effectiveness of the proposed method.

Graphical Abstract

1. Introduction

Inverter-based distributed power generation systems (DPGSs) have received much attention recently due to their flexible power-control capability [1,2]. Usually, grid-connected inverters with grid-following control are used as interfaces between the grid and DPGSs. However, this control approach may suffer from voltage instabilities, frequency variations, voltage harmonics, and is not able to operate in islanded mode. Alternatively to the grid-following inverter, the grid-forming one is preferred due to its ability to provide many ancillary services defined in IEEE Std. 1547 [3], such as load regulation, reactive power compensation, and power quality improvement. However, IEEE Std. 1547 does not define the operation of distributed resources (DRs) in intentionally islanded electric power systems (EPSs).
Recently, the term “DR Island System” has been defined by IEEE Std. 1547.4 [4] in order to integrate various DRs into EPSs with the possibility of operating as a microgrid [5,6]. Four operating modes are presented: (1) area EPS-connected mode; (2) transition to island mode; (3) islanded mode and (4) reconnection mode. The first mode referred to as the DR operation described in the original IEEE Std. 1547. In the transition-to-island mode, islanded detection is necessary and then the DR system will be able to disconnect from the main grid, allowing a safe islanded operation. On the other hand, in islanded mode the DR operates without the presence of the main grid. Further, in the reconnection mode the DR should be able to reconnect to the main grid when it is present again. Since the islanding operation has been clearly defined by the IEEE Std. 1547.4, future electrical system planning should consider the paralleling issues of islanding generation [5,6,7].
In islanded mode, frequency- and voltage-droop controls are often implemented in the local control of the inverters, which are operated as voltage sources, in order to share real and reactive powers. The droop control method is based on a concept in power system. When AC generator increase output power, the frequency is drooping accordingly [8,9,10]. On the other hand, in grid-connected mode, inverters are conventionally controlled as current sources [11,12,13,14]. Consequently, a complex system is required in order to accomplish proper transition without undergoing large transient current. This transition between voltage and current source has been intensively studied in the recent years, being difficult to achieve in practice [15,16,17,18,19]. The droop-controlled voltage source inverter has been proposed to operate in both grid-connected and islanded modes without requiring a control transition between current and voltage sources [20]. The virtual inductance concept was proposed to reduce the inrush current when connecting a new voltage source inverter to an existing microgrid [21,22,23]. However, grid synchronization is also required to suppress the peak transient current of the inverter before mode transition. High inrush current may still appear in the transition from islanded to grid-connected modes due to phase error in the phase-locked-loop (PLL) system or in the voltage sensors, especially in case of low line impedance [15].
The authors have presented a droop-controlled voltage source inverter (VSI) with a seamless transition between islanded and grid-connected operation [24,25], in which riding-through control and virtual inductance concept were proposed to suppress transient current. In this paper, we further present full experimental verification and design guideline. As shown in Figure 1, various inverters and local loads are tied to the PCC (point of common coupling) [26]. The proposed droop-controlled inverter regulates the voltage and the frequency of the microgrid, whereas the other inverters are operated as current-controlled source (grid-following inverter). The solid-state transfer switch (STS) connects the microgrid to the utility through the impedance Zg, which includes both line and transformer impedances. The inrush current, due to asynchronous operation of STS, is able to be reduced by activating a current control loop. A local PLL is proposed in order to obtain the angle of the grid voltage, which is used to correct the angle of the droop controller voltage reference. In addition, a virtual inductance loop is designed in order to reduce the oscillating current due to the mode transferring between islanded and grid-connected modes. Based on this algorithm, the transient current between the inverter and the grid can be reduced to an acceptable level, without triggering protections of the system. In contrast with those presented in the state-of-the-art [15,16,17,18], this algorithm does not need to sense the grid-side voltage for phase synchronous, which may be difficult to reach if the inverter is far away from the PCC. The method could be extended to inverter-based DPGSs, in order to reduce the inrush current and to ride-through grid power-quality events, such as voltage sags and swells. The paper is organized as follows. Section 2 presents the operation principle of the proposed control approach. Section 3 shows the design methodology of the main control parameters. Section 4 presents the experimental results when the inverter transfers from islanded to grid-connected modes. Section 5 concludes the paper.

2. Operation Principle

Figure 2 shows the power stage of the three-phase three-leg inverter supplied by a dc-link, and ended by an LC filter connected to a local load (Rab, Rbc, Rac). The static transfer switch (STS) connects the local load to the main grid through the grid impedance (Zga, Zgb, Zgc). The main power stage parameters are given in Table 1. An effective algorithm is proposed in order to allow the inverter ride-through when transferring between islanded and grid-connected modes, without needing for any grid side information. This is especially interesting when the inverter is far away from the STS, so that no high-speed communication system is needed between the STS and the inverter control. Figure 3 shows the proposed overall control diagram of the inverter. Independently from being connected or disconnected to the main grid, the inverter is normally operated in droop-controlled mode (both switches SW1 and SW2 are in position 1), and it is able to switch between droop-controlled to riding-through modes in order to suppress the inrush current (thus SW1 and SW2 change from position 1 to position 2). With this order, the droop control will be operated first, followed by the riding-through algorithm.

2.1. Droop Control

As can be seen in Figure 3, inverter output voltage and current are transferred into a stationary frame where the superscripts are denoted as ‘s’. The voltage reference Edq* is determined according to both active power versus frequency (P-ω) droop and reactive power versus voltage (Q-V) droop. Both P-ω and Q-V droop equations can be expressed as follows:
ω = ω o m · ( P P o )
E = E o n · ( Q Q o )
where ωo is the nominal frequency, Po is the rated active power, Eo is the nominal voltage, Qo is the rated reactive power, m is the P-ω droop coefficient, and n is the Q-V droop coefficient.
A low-pass filter (LPF) with a cut-off frequency of 10 Hz is used to filter the ripple components when calculating P and Q. Moreover, LPF is able to help stabilize the droop control of the proposed inverter. Note that Q-V droop control is needed just for compensating possible voltage variations in the grid, thus reducing the amount of reactive power injected according to the maximum allowed voltage variations [20]. The droop control is suitable to make the inverter work as a voltage source in both islanded and grid-connected modes. However, the transition between these two modes may result in high inrush current that may damage the system. The proposed method will allow the droop-controlled inverter to improve the transient response when transferring between modes, by detecting the inrush current, activating a current control loop during the transient, and then transferring back to the droop-controlled mode smoothly by using a virtual inductance loop.
When a droop-controlled inverter operates in islanded mode, the frequency and amplitude are deviated according to the amount of active and reactive powers delivered by the inverters, as follows:
Δ ω = m · Δ P
Δ E = n · Δ Q
where Δ ω is the frequency deviation ( ω ω o ), ΔE is the amplitude deviation (EEo), ΔP is the active power deviation (PPo) and ΔQ is the reactive power deviation (QQo). On the other hand, when the inverter is operated in grid-connected mode, the frequency and amplitude are fixed by the grid, so that the delivered active and reactive powers will be Po and Qo if ωo and Eo coincide with the grid frequency and amplitude. From Equations (3) and (4), power deviations ΔP and ΔQ can be reduced by using large droop coefficients m and n.

2.2. Multi-Loop Voltage Control

In order to track the voltage reference Edq* generated by the droop control, a multi-loop voltage control is realized by using a proportional gain kp plus a voltage feedforward, as shown in Figure 3 [21]. Due to the feedforward loop, the output voltage of the inverter can be controlled within an acceptable steady-state error and a proper transient behavior. In addition, a time-derivative term of the capacitor voltage is used to reduce the resonance produced by the filter capacitor Cf. Here, a proportional gain kd is designed to accomplish a critical damped response of the inverter. Finally, the PWM is realized to produce the switching signals of the inverter. A design example of the multi-loop voltage control will be introduced in the next section.

2.3. Riding-through Algorithm

When the inverter is transferred from islanded to grid-connected modes, it may suffer from a large transient current due to the phase difference between Eabc and vg,abc. In order to obtain a seamlessly transition, we present a control algorithm able to help the inverter to ride through this transient. Figure 3 shows the proposed control method, including a local phase-lock loop (PLL) [27], a current control, and a virtual inductance loop. The applied local PLL is shown in Figure 4. The subscript ‘e’ denotes the signal under dq-frame. A PI control is used to determine the phase angle when q-axis component is controlled to zero. The frequency feedforward term ωff = 377 is to boost transient response when the inverter starts operation. A detailed flow chart is given in Figure 5 in order to illustrate the conditions required during the mode transition. If when closing the STS, the transient current is large enough being bigger than a certain threshold ITH, then the inverter control will temporarily switch to the riding-through mode (SW1 and SW2 will switch to position 2) for a time interval TRD. During this time period, the inverter is operated in current control mode with zero current command (i * = 0) and the PLL updates the reference angle of droop controller to align inverter voltage with grid voltage even though the output of droop controller is disable. This action will reduce the phase difference between the inverter and the grid due to the uncoordinated connection. Note that a short time delay TRD is required for the PLL to reach the steady state. After that, the inverter will switch back to droop-controlled mode (SW1 and SW2 switch back to position 1) with a virtual inductance that starts with a large virtual inductor value and is gradually reduced to a small final value, expressed as follows [12]:
L v = L v f ( L v i L v f ) · e t τ
V L d q s = L v d ( i q d s ) d t
where Lvf and Lvi are final and initial inductances, respectively, and τ is the time constant. Thus, an induced voltage in (6) is produced to react against the transient current. The stability of the inverter can also be improved by means of the virtual inductance loop [23].

3. Main Control Parameter Design

This section is devoted to presenting a design example in order to fix the multiple parameters of the proposed control algorithms. The discussion will include the droop coefficients, the parameters of the multi-loop voltage control, and the virtual inductance.

3.1. Droop Coefficients

According to droop Equations (1) and (2), the droop coefficients can be designed by using the root locus method [28]. Considering two inverters are connected in parallel. One is treated as grid and the other is droop-controlled inverter. The corresponding equations of the low-pass filter, droop controller and the angle of voltage are given as:
P L P F = ω c s + ω c P i n s ,   Q L P F = ω c s + ω c Q i n s
ω = ω o m ( P o P L P F ) ,   E = E o n ( Q o Q L P F )
ω d t = θ + θ o
where Pins and Qins are calculated by the measuring inverter output current and output voltage. Note that is the angle of the voltage E. Thus, the state-space equation of one inverter can be developed from small signal analysis:
X 1 ˙ = [ Δ θ 1 ˙ Δ θ 1 ¨ Δ E 1 ˙ ] = [ 0 1 0 0 ω c 0 0 0 ω c ] [ Δ θ 1 Δ θ ˙ 1 Δ E 1 ] + [ 0 0 0 0 m 1 ω c 0 0 0 n 1 ω c ] [ 0 Δ P 1 Δ Q 1 ] = A 1 · X 1 + B 1 · U 1
For two inverters, the equations can be expanded as:
X ˙ = [ A 1 0 0 A 2 ] [ X 1 X 2 ] + [ B 1 0 0 B 2 ] [ U 1 U 2 ] = A X + B U
where U is developed by the Newton-Raphson method:
U = [ Δ P 1 Δ Q 1 Δ P 2 Δ Q 2 ] = [ P 1 θ 1 P 1 E 1 P 1 θ 2 P 1 E 2 Q 1 θ 1 Q 1 E 1 Q 1 θ 2 Q 1 E 2 P 2 θ 1 P 2 E 1 P 2 θ 2 P 2 E 2 Q 2 θ 1 Q 2 E 1 Q 2 θ 2 Q 2 E 2 ] = [ 1 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 ] [ Δ θ 1 Δ θ ˙ 1 Δ E 1 Δ θ 2 Δ θ ˙ 2 Δ E 2 ] = J K X
Then the state equation of overall system can be written as:
X ˙ = A X + B J K X = M X
The droop coefficients of the inverter which represent utility are set as very small due to their stiffness. Figure 6 shows the movement of roots when varying the P-ω droop coefficient m value. Note that the grid is assumed to be a stiff voltage source. As can be seen, the two roots become complex conjugate when m increases from 0.0001 to 0.1. Note that the system is stable with a damped oscillation only. Then, we can consider parameter variation in both n and m. Figure 7 shows the roots moving to the right half-plane when increasing both coefficients. These results show that the system will become unstable for large n values. Based on the above observation, droop coefficients m and n can be chosen to achieve an acceptable transient response within the operation range.

3.2. Multi-Loop Voltage Control

Figure 8 shows the model of the multi-loop voltage control, including computational and PWM delays. The transfer function from V’(s) to E(s) and the open-loop transfer function from E*(s) to E(s) are given by (14) and (15), respectively:
E ( S ) V ( S ) = e 3 2 · s T · 1 L f C f s 2 + ( L f + k d R R L f C f ) · s + 1 L f C f = e 3 2 · s T · G L C ' ( s ) = G ( s )
E ( S ) E * ( S ) = 1 + k p G ( s )
We can design the derivative gain kd according to the quality factor with the critically damping condition of (16). As can be seen from Figure 9, the high frequency resonance may cause instability when kd = 0. In the case of kd = 0.00535 (system critically damped), the resonance is clearly suppressed and the phase lagging is improved. In case of over-damping condition (kd = 0.001064), the stability is also guaranteed, but its time response is slower than that of the critically damping case. After determining kd, the proportional gain kp can be designed according to the frequency response of the open-loop transfer function of (15). As shown in Figure 10, the crossover frequency is 790 Hz and phase margin is 59.1° for kp = 3:
Q = 1 2 ξ = L f + k d R R L f C f : { > 0.5 ,   ( u n d e r   d a m p i n g ) = 0.5 ,   ( c r i t i c a l   d a m p i n g ) < 0.5 ,   ( o v e r   d a m p i n g )

3.3. Virtual Inductance Loop

In this subsection, we will discuss the parameters design of the virtual inductance loop, including Lvf, Lvi, and τ. Figure 11 shows the equivalent circuit considering the virtual inductance loop. Similarly, the dynamic equation and the root locus are used for stability analysis purposes. Figure 12 shows the root locus when the virtual inductance Lv decreases from 5 H to 80 µH. As demonstrated, roots will be close to the real-axis as Lv increases. That means the stability of the system is improved with larger virtual inductance. However, induced voltage drop on the virtual inductance will limit the output current of the inverter, which is a compromise in determining Lvf.
When the operation of the inverter transfers back to droop-controlled mode, we assume that the same voltage amplitude exists on Lv, but with a small phase difference δ. By taking account of the phasor analysis, the voltage drop on Lv is 2Vpsin(δ/2) in Figure 11, where Vp means peak voltage value on E. Because of the assumption of a small phase difference δ, the voltage drop can be approximated as Vpδ. Thus, the maximum inrush current Ip of the inverter can be expressed as follows:
I P = 1 ω L v ( V p · 2 sin δ 2 ) V p ω L v δ
that can be used to determine Lvi based on the accepted current limitation. Note that a small Lvi value may trigger inverter protection or cause the inverter transfer to riding-through mode more than one time. On the other hand, the time constant τ determines the decay speed of the virtual inductance, which affects the dynamic behavior of the droop control and oscillating current between the inverter and the grid. We can tune the value according to the droop coefficient as well as the line impedance.

3.4. Impact on an Inverter-Dominated System

As shown in Figure 1, except for the proposed inverter, the other inverters are controlled as current sources. In this case, the mode switching of the proposed inverter does not result in stability issues due to voltage-follow characteristic of the current-controlled inverters. In an inverter-dominated power system, droop control is normally used to accomplish power sharing among multiple voltage-controlled inverters. Traditional voltages-controlled inverters may temporarily supply large currents beyond their rating due to the power mismatch. This situation probably triggers circuit protection and results in unintentional shutdowns of the inverters. However, the proposed inverter is able to switch to ride-through mode to reduce any inrush current due to system disturbances. This can improve the system stability, especially in low-voltage high impedance networks.

4. Experimental Results

A laboratory-scale prototype was built and tested in order to verify the proposed seamless transition method. The experimental setup is shown in Figure 13 and the parameters are given in Table 2. When the STS is OFF, the inverter is operated in islanded mode. The setup of the current threshold is determined based on the inverter rating. In this experiment, the current threshold is set as two times the inverter rating. Figure 14 shows steady-state voltage and current waveforms of the inverter in islanded mode. Figure 15 shows the transient response of the inverter output voltage, calculated active power, and currents when the load is increased. Obviously, the amplitude of inverter output voltage is maintained at the nominal value and the output power of the inverter increases from 1 kW to 2 kW. Notice that the calculated active power shown in Figure 15a is processed by a LPF.
This experiment can verify effectiveness of the multi-loop voltage control. Figure 16 shows that inverter voltage and grid voltage when the STS is closed at T1. At this moment, the phase difference between Eabc and vg,abc is equal to 169.9°.
As can be seen from Figure 17, the inverter current exceeds the threshold limitation at T1. Thus, subsequently the inverter controller automatically switches to the riding-through mode. The current controller of the riding through mode fixes the inverter output current to almost zero and the local PLL aligns the phase angle of the voltage command with respect to the grid at the same time. Since the proposed strategy does not use any phase synchronization, a voltage dip appears in the inverter output as shown in Figure 16 when the STS is closed. The duration of the voltage dip is less than the clear time (160 ms) in case of abnormal voltage according to IEEE 1547.2-2008 [3]. After a riding-through interval TRD, the inverter switches back to droop-controlled mode at T2, but still works in grid-connected mode. At the same time T2, the virtual inductance loop is initiated. Figure 18 shows exponentially decreasing feature of the designed virtual inductance with Lvi = 3 H, Lvf = 80 μH and τ = 0.3 s (see (5)).
Figure 17 after T2 shows that the virtual inductance can help reduce the circulating current resulting from both droop operation and phase error. It is worth mentioning that the inverter output current shows oscillation after T2 because the droop controller is trying to accomplish power sharing, and it will reach a steady-state after a few cycles. For comparison purposes, Figure 19 shows the same test result as Figure 16 without the virtual inductance loop applied. Obviously, the inverter current of Figure 19 after T2 is higher than that of Figure 17. At the steady-state of the grid-connected operation, the output power of the inverter is 1 kW as shown in Figure 20. Note that the current spikes are different at the instant T1 because Figure 17 and Figure 19 are tested in different instants.
Experimental results show that how the inrush current can be limited to an acceptable level when starting grid-connected operation. When the inverter current is larger than the threshold value, the inverter is switched to ride-through mode and temporarily operated as current mode control with zero current command to reduce the inverter current. When back to droop control mode, the inrush current no longer occurs since the angle of voltage command is updated by PLL to synchronize with the utility and virtual inductance is engaged at the same time.

5. Conclusions

This paper presents a seamless transition method for droop-controlled inverters between islanded and grid-connected modes. Thus, the inverter is able to transfer between both modes without using any grid-side information. Consequently, the approach is suitable for an IEEE 1547.4 compliant microgrid, in which the voltage source inverter responsible for both frequency and voltage regulation is located far away from the static transfer switch. For this case, an algorithm that coordinates a local PLL and a virtual inductance loop is proposed. Thus, the over-current will not occur. A control parameter design example and stability analysis are presented as well. The experimental results show that the inverter can transfer from islanded to grid-connected modes even when the inverter voltage is totally out of phase from the grid voltage.

Acknowledgments

This work was supported by Ministry of Science and Technology, TAIWAN under grant 104-2221-E-110-037.

Author Contributions

Tzung-Lin Lee, Josep M. Guerrero, Shang-Hung Hu and Chun-Yi Kuo conceived and designed the experiments; Shang-Hung Hu and Chun-Yi Kuo performed the experiments and analyzed the data; Shang-Hung Hu wrote the paper.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Blaabjerg, F.; Teodorescu, R.; Liserre, M.; Timbus, A.V. Overview of Control and Grid Synchronization for Distributed Power Generation Systems. IEEE Trans. Ind. Electron. 2006, 53, 1398–1409. [Google Scholar] [CrossRef]
  2. Pahlevani, M.; Eren, S.; Guerrero, J.M.; Jain, P. A Hybrid Estimator for Active/Reactive Power Control of Single-Phase Distributed Generation Systems with Energy Storage. IEEE Trans. Power Electron. 2015, 31, 2919–2936. [Google Scholar] [CrossRef]
  3. IEEE Std 1547.2TM-2008: IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems. Available online: http://ieeexplore.ieee.org/document/4816078/ (accessed on 6 September 2016).
  4. IEEE Std 1547.4TM-2011: IEEE Standard for Design, Operation, and Integration of Distributed Resource Island Systems with Electric Power Systems. Available online: http://grouper.ieee.org/groups/scc21/1547.4/1547.4_index.html (accessed on 6 September 2016).
  5. Lasseter, R. Microgrids. In Proceedings of the IEEE Power Engineering Society Winter Meeting, 27–31 January 2002; pp. 305–308.
  6. Katiraei, F.; Iravani, R.; Hatziargyriou, N.; Dimeas, A. Microgrids Management. IEEE Power Energy Mag. 2008, 6, 54–65. [Google Scholar] [CrossRef]
  7. Villeneuve, P.L. Concerns generated by islanding. IEEE Power Energy Mag. 2004, 2, 49–53. [Google Scholar] [CrossRef]
  8. Bergen, A.R. Power Systems Analysis; Prentice-Hall: Englewood Cliffs, NJ, USA, 1986. [Google Scholar]
  9. Han, H.; Liu, Y.; Sun, Y.; Su, M.; Guerrero, J.M. An Improved Droop Control Strategy for Reactive Power Sharing in Islanded Microgrid. IEEE Trans. Power Electron. 2014, 30, 3133–3141. [Google Scholar] [CrossRef]
  10. Yao, W.; Chen, M.; Matas, J.; Guerrero, J.M.; Qian, Z.-M. Design and Analysis of the Droop Control Method for Parallel Inverters Considering the Impact of the Complex Impedance on the Power Sharing. IEEE Trans. Ind. Electron. 2010, 58, 576–588. [Google Scholar] [CrossRef]
  11. Chandorkar, M.C.; Divan, D.M. Control of parallel connected inverters in standalone AC supply system. IEEE Trans. Ind. Appl. 1993, 29, 136–143. [Google Scholar] [CrossRef]
  12. Guerrero, J.M.; Vasquez, J.C.; Matas, J.; Castilla, M.; De Vicuna, L.G. Control strategy for flexible microgrid based on parallel line-interactive UPS systems. IEEE Trans. Ind. Electron. 2009, 56, 726–736. [Google Scholar] [CrossRef]
  13. Chandrokar, M.C.; Divan, D.M.; Banerjee, B. Control of Distributed UPS Systems. IEEE Power Eng. Soc. Gen. Meet. 1994, 1, 197–204. [Google Scholar]
  14. Guerrero, J.M.; Hang, L.; Uceda, J. Control of Distributed Uninterruptible Power Supply Systems. IEEE Trans. Ind. Electron. 2008, 55, 2845–2859. [Google Scholar] [CrossRef] [Green Version]
  15. Teodorescu, R.; Blaabjerg, F. Flexible control of small wind turbines with grid failure detection operating in stand-alone and grid-connected mode. IEEE Trans. Power Electron. 2004, 19, 1323–1332. [Google Scholar] [CrossRef]
  16. Yao, Z.; Xiao, L.; Yan, Y. Seamless Transfer of Single-Phase Grid-Interactive Inverters between Grid-Connected and Stand-Alone Modes. IEEE Trans. Power Electron. 2010, 25, 1597–1603. [Google Scholar]
  17. Gu, H.; Yang, Z.; Wang, D.; Wu, W. Research on Control Method of Double-Mode Inverter with Grid-Connection and Stand-Alone. In Proceedings of the IEEE 5th International Power Electronics and Motion Control Conference, Shanghai, China, 13–16 August 2006; Volume 1, pp. 1–5.
  18. Tirumala, R.; Mohan, N.; Henze, C. Seamless transfer of grid-connected PWM inverters between utility-interactive and stand-alone modes. In Proceedings of the Seventeenth Annual IEEE Applied Power Electronics Conference and Exposition, Dallas, TX, USA, 10–14 March 2002; Volume 2, pp. 1081–1086.
  19. Huang, H.; Kong, L.; Xu, H. Control algorithm research on seamless transfer for distributed resource with a LCL filter. In Proceedings of the Third International Conference on Electric Utility Deregulation and Restructuring and Power Technologies, Nanjing, China, 6–9 April 2008; pp. 2810–2814.
  20. Vasquez, J.C.; Mastromauro, R.A.; Guerrero, J.M.; Liserre, M. Voltage Support Provided by a Droop-Controlled Multifunctional Inverter. IEEE Trans. Ind. Electron. 2009, 56, 4510–4519. [Google Scholar] [CrossRef]
  21. Lei, Q.; Yang, S.; Peng, F.Z. Multi-loop control algorithms for seamless transition of grid-connected inverter. In Proceedings of the IEEE 25th Applied Power Electronics Conference and Exposition, Plam Springs, CA, USA, 21–25 February 2010; pp. 844–848.
  22. Guerrero, J.M.; Matas, J.; De Vicuna, L.G.; Castilla, M.; Miret, J. Wireless-Control Strategy for Parallel Operation of Distributed Generation Inverters. IEEE Trans. Ind. Electron. 2006, 53, 1461–1470. [Google Scholar] [CrossRef]
  23. Guerrero, J.M.; GarciadeVicuna, L.; Matas, J.; Castilla, M.; Miret, J. Output Impedance Design of Parallel-Connected UPS Inverters with Wireless Load-Sharing Control. IEEE Trans. Ind. Electron. 2005, 52, 1126–1135. [Google Scholar] [CrossRef]
  24. Hu, S.-H.; Kuo, C.-Y.; Lee, T.-L.; Guerrero, J.M. Droop-Controlled Inverters with Seamless Transition between Islanding and Grid-Connected Operations. In Proceedings of the IEEE Energy Conversion Congress and Exposition, Phoenix, AZ, USA, 17–22 September 2011; pp. 2196–2201.
  25. Hu, S.-H.; Kuo, C.-Y.; Lee, T.-L. Design of virtual inductance for droop-controlled inverter with seamless transition between islanded and grid-connected operations. In Proceedings of the IEEE Energy Conversion Congress and Exposition, Raleigh, NC, USA, 15–20 September 2012; pp. 4383–4387.
  26. Liang, J.; Green, T.C.; Weiss, G.; Zhong, Q.C. Hybrid Control of Multiple Inverters in an Island-Mode Distribution System. In Proceedings of the 2003 IEEE 34th Annual Power Electronics Specialist Conference, Acapulco, Mexico, 15–19 June 2003; pp. 61–66.
  27. Kaura, V.; Blasko, V. Operation of a phase locked loop system under distorted utility conditions. IEEE Trans. Ind. Electron. 1997, 33, 58–63. [Google Scholar] [CrossRef]
  28. Coelho, E.A.A.; Cortizo, P.C.; Garcia, P.F.D. Small-signal stability for parallel-connected inverters in stand-alone AC supply systems. IEEE Trans. Ind. Appl. 2002, 38, 533–542. [Google Scholar] [CrossRef]
Figure 1. The proposed droop-controlled voltage source inverter (VSI) inverter in the microgrid system.
Figure 1. The proposed droop-controlled voltage source inverter (VSI) inverter in the microgrid system.
Energies 09 00732 g001
Figure 2. Power stage of the VSI and its connection to the utility grid.
Figure 2. Power stage of the VSI and its connection to the utility grid.
Energies 09 00732 g002
Figure 3. The block diagram of the proposed controller.
Figure 3. The block diagram of the proposed controller.
Energies 09 00732 g003
Figure 4. The block diagram of the applied PLL.
Figure 4. The block diagram of the applied PLL.
Energies 09 00732 g004
Figure 5. Flow chart of the proposed control strategy.
Figure 5. Flow chart of the proposed control strategy.
Energies 09 00732 g005
Figure 6. Root locus when P-ω coefficient varies from 0.0001 to 0.1.
Figure 6. Root locus when P-ω coefficient varies from 0.0001 to 0.1.
Energies 09 00732 g006
Figure 7. Root locus when both P-ω and Q-E coefficients vary from 0.0001 to 0.1.
Figure 7. Root locus when both P-ω and Q-E coefficients vary from 0.0001 to 0.1.
Energies 09 00732 g007
Figure 8. Model of the multi-loop voltage control.
Figure 8. Model of the multi-loop voltage control.
Energies 09 00732 g008
Figure 9. Frequency responses for three different kd.
Figure 9. Frequency responses for three different kd.
Energies 09 00732 g009
Figure 10. Bode plot of the open loop for kp = 3. (Crossover frequency = 790 Hz, Phase margin = 59.1°).
Figure 10. Bode plot of the open loop for kp = 3. (Crossover frequency = 790 Hz, Phase margin = 59.1°).
Energies 09 00732 g010
Figure 11. Simplified circuit considering the virtual inductance loop.
Figure 11. Simplified circuit considering the virtual inductance loop.
Energies 09 00732 g011
Figure 12. Root locus for varying virtual inductance.
Figure 12. Root locus for varying virtual inductance.
Energies 09 00732 g012
Figure 13. Experimental setup.
Figure 13. Experimental setup.
Energies 09 00732 g013
Figure 14. Inverter voltage and current in islanded mode. (a) Inverter output voltage (200 V/div); (b) Inverter output current (2.5 A/div).
Figure 14. Inverter voltage and current in islanded mode. (a) Inverter output voltage (200 V/div); (b) Inverter output current (2.5 A/div).
Energies 09 00732 g014aEnergies 09 00732 g014b
Figure 15. Inverter voltage, measure power and current in islanded mode when load increases. (a) Inverter output voltage (eab, ebc, eca) (200 V/div); output real power (500 W/div); (b) Inverter output currents (ia, ib, ic) (5 A/div).
Figure 15. Inverter voltage, measure power and current in islanded mode when load increases. (a) Inverter output voltage (eab, ebc, eca) (200 V/div); output real power (500 W/div); (b) Inverter output currents (ia, ib, ic) (5 A/div).
Energies 09 00732 g015
Figure 16. Inverter output voltage and grid voltage (transient of inverter switching to grid-connected operation) (100 V/div).
Figure 16. Inverter output voltage and grid voltage (transient of inverter switching to grid-connected operation) (100 V/div).
Energies 09 00732 g016
Figure 17. Inverter output current with virtual inductance loop (5 A/div).
Figure 17. Inverter output current with virtual inductance loop (5 A/div).
Energies 09 00732 g017
Figure 18. The exponential virtual inductance value (1 H/div).
Figure 18. The exponential virtual inductance value (1 H/div).
Energies 09 00732 g018
Figure 19. Inverter output current without virtual inductance loop (5 A/div).
Figure 19. Inverter output current without virtual inductance loop (5 A/div).
Energies 09 00732 g019
Figure 20. Transient response of invert output power (500 W/div).
Figure 20. Transient response of invert output power (500 W/div).
Energies 09 00732 g020
Table 1. Power state parameters.
Table 1. Power state parameters.
DescriptionSymbolValueUnit
Local Load (per phase)Rload50Ω
Filter InductorLf5mH
Filter CapacitanceCf20μF
Grid impedanceZg0.2 + j1.885Ω
Table 2. Experimental Parameters.
Table 2. Experimental Parameters.
DescriptionSymbolValueUnit
Grid voltage (line-line)Vg220V
Grid frequencyfg60Hz
Nominal voltageE0174.7V
Inverter output powerPo1000W
Nominal Frequencyω0377rad/s
P-ω droopm−0.0005rad/W
Q-V droopn0V/Var
Filter cut-off frequencyωc62.8rad/s
Nominal virtual inductorLvf80μH
Initial virtual inductorLvi3H
Time constantτ0.3s
Proportional gainkp3---
Differential coefficientkd0.000532---
Riding-through periodTRD10ms
Current thresholdITH10A

Share and Cite

MDPI and ACS Style

Hu, S.-H.; Lee, T.-L.; Kuo, C.-Y.; Guerrero, J.M. A Riding-through Technique for Seamless Transition between Islanded and Grid-Connected Modes of Droop-Controlled Inverters. Energies 2016, 9, 732. https://doi.org/10.3390/en9090732

AMA Style

Hu S-H, Lee T-L, Kuo C-Y, Guerrero JM. A Riding-through Technique for Seamless Transition between Islanded and Grid-Connected Modes of Droop-Controlled Inverters. Energies. 2016; 9(9):732. https://doi.org/10.3390/en9090732

Chicago/Turabian Style

Hu, Shang-Hung, Tzung-Lin Lee, Chun-Yi Kuo, and Josep M. Guerrero. 2016. "A Riding-through Technique for Seamless Transition between Islanded and Grid-Connected Modes of Droop-Controlled Inverters" Energies 9, no. 9: 732. https://doi.org/10.3390/en9090732

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop