2. Simultaneous Fault Analysis by the University of Padova (SFPD): The Theoretical Background of This Open Matrix Algorithm
With regard to multiconductor electric lines, the modeling approach underlying the SFPD is Multiconductor Cell Analysis (generally known by its acronym MCA). It provides the possibility of obtaining the admittance matrix in the phase frame of reference of any electric line (in single or double circuit). It has been applied and experimentally validated by means of some real land ICs [
33,
34,
35], of OHLs [
36,
37], of submarine three-core armored cables [
38,
39], and of GILs [
40].
Even if each line typology has its own MCA representation (for which the readers can refer to the copious bibliography [
33,
34,
35,
36,
37,
38,
39,
40]), the basic idea for deriving its power frequency admittance matrix is to divide the entire length
d of the line into cells of suitable length Δ (with Δ <<
d). The number
n of conductors, both active and passive ones, varies for each line typology: for a single-circuit OHL with two earth wires, it is
n = 3 + 2 = 5; for a double-circuit OHL with one earth wire, it is
n = 3 + 3 + 1 = 7; for a single-circuit land (unarmored) IC, it is
n = 3 + 3 = 6 (three phases and three metallic screens); for a double-circuit IC, it is
n = 6 + 6 = 12; for a three-core armored submarine IC, it is
n = 3 + 3 + 1 = 7 (three phases, three metallic screens, and one armor). The admittance matrix is the equivalent matrix of the cascade connection of
z elementary cells where the number of cells is simply given by:
For OHLs, Δ can be equal to the average span (e.g., for EHV OHLs, it can be equal to 400 m); in contrast, for ICs, Δ can range between 10 m and 100 m.
Due to the small length Δ of each cell in comparison with the entire length of the multiconductor system
d, each cell can be represented by means of a nominal multiconductor π-circuit consisting of one series block of longitudinal elements and two shunt blocks of transverse elements lumped at the sending-end (
S) and receiving-end (
R) of the cell. For the same abovementioned reason (i.e., Δ <<
d), it is possible to lump the distributed shunt admittances at the ends of the cell, thus allowing the separate study of longitudinal elements whose model is lumped in the series block. This is similar to what is usually done for the nominal π-circuit of short single-phase lines.
Figure 1 shows the nominal multiconductor π-circuit of one elementary cell
i for both a single-circuit OHL and a three-core submarine cable. At
S and
R, voltage vectors
uS and
uR and current vectors
iS and
iR can be defined. These vectors contain all the voltages and currents of both active conductors (phase conductors) and passive ones (OHL earth wires, IC screens, IC armors, GIL enclosures).
With regard to the longitudinal block of an OHL, the admittance matrix YL (2n × 2n) is defined by exploiting the Carson–Clem formulation, which is a set of formulae to determine the self and mutual impedances of longitudinal conductors which account for the earth return currents. Alternatively, the complete Carson formulae can be used with Carson’s corrections in terms of series. It has been widely demonstrated in the technical literature that at power frequency (50 or 60 Hz), the Carson–Clem formulae are very precise, and consequently, they give the same results as the complete Carson ones. For IC, the matrix Zca can be derived by means of Schelkunoff/Pollaczek or Wedepohl theories.
The matrix
YL (2
n × 2
n) is the admittance matrix of the longitudinal block circuit formed by the
n parallel conductors seen from the two ends, and it is given by:
With regard to the transverse or shunt elements, it is possible to lump a set of shunt admittances at the ends of the cell, so that each end can be modelled by means of two admittance matrices
YSST (
n ×
n) and
YRRT (
n ×
n). Typically,
YSST =
YRRT (since the admittances of Δ/2 are lumped at each end), and these two matrices are defined by computing the capacitive and conductive links between the conductors of the multiconductor system. The vectors of the shunt currents at both ends of the cell are linked to the voltage vectors by means of Equation (3); i.e.,
where
YT of order (2
n × 2
n) is the transverse admittance matrix of the entire cell, and it is a block diagonal matrix where each block is represented by the sending-end transverse admittance matrix and the receiving-end one. Matrix Equation (3) links the sending-end transverse or shunt current vectors
iST and the receiving-end one
iRT.From
Figure 1, it is evident that the superimposition of
YL and
YT represents the admittance matrix of the steady-state regime of the elementary cell
YCel (2
n × 2
n), so
YCel =
YT +
YL, and:
where
u is the vector of the cell voltages, and
i is the vector of the currents entering in the cell.
2.1. The Admittance Matrix Representing the Faults
Once the admittance matrix
YC of one cell is computed, it is necessary to make the cascade connection with all the other cells. Let us suppose that the fault location is along the line, at the position
k (see
Figure 2); the matrix
Ycelf considers the type of fault. Its structure is shown in
Figure 3: by means of this structure, it is straightforward to consider any type of short circuit at the sending or receiving end and any type of open conductor. The faulted cell admittance matrix
Ycelf is given by:
For instance, the open conductor of phase 1 can be considered by means of the following matrix:
where
G2 is a very high-value conductance representing the galvanic continuity, e.g., 10
6 S;
G1 is a very small-value conductance representing the open conductor, e.g., 10
−6 S; and the other elements are zeros. Any other open conductors can be easily considered, such as the open conductors of passive conductors like an earth wire breaking in an OHL or a screen fracture in an IC.
Differently, if a short circuit occurs at the sending end of a given cell, the elements of the
YSC_Sen are expressed by:
where Equation (7) expresses the self-admittances and Equation (8) the mutual ones. If a short circuit occurs between phase 1 and the earth wire
n in a single-circuit OHL, it is sufficient to set:
With the systematic use of admittance matrices, it is possible to consider any type of fault and any number of these along the lines or at the busbars. The case of a short circuit at a busbar is not shown, since it simply employs a matrix like
YSC. Moreover, the case of an arc resistance or, more generally, a fault impedance
zf, can be easily modelled by (always with reference to a line-to-earth wire short circuit):
With regard to the arc resistance, its value depends upon the short-circuit current magnitude. For short-circuit current magnitudes ranging between 10 kA and 60 kA, arc resistance ranges between 16 mΩ and 3.5 mΩ. Therefore, it is often neglected.
In contrast, the fault impedances of short circuits involving OHLs are much greater than the arc resistance. In regard to orders of magnitude, refer to
Table 1, derived from 70 measured actual faults [
41]. In the table, the fault impedance is considered to be wholly of a resistive nature (i.e.,
Zf = R
f).
According to the structure described below, several simultaneous faults can be implemented, adding multiple cells
Ycelf inside the matrix structure of
Figure 3. Then, the cascade connection of the faulted cells with the rest of the line cells allows the derivation of the equivalent admittance matrix
Yeq of the entire line.
2.2. The Bus Admittance Matrix, Including the Network, Faults, Loads, and Generators
The multiconductor network admittance matrix in phase (namely
ABC) frame of reference
and its formation have been thoroughly exposed in [
42]. It encompasses the multiconductor structure of all the elements belonging to the grid, i.e., OHLs, ICs, GILs, two-winding transformers, three-winding transformers, and special transformers, e.g., PSTs, shunt reactors, capacitor banks, excluding loads, and synchronous generators. It is worth highlighting that after having located and characterized the faults according to
Section 2.1, this matrix also includes the faults and becomes the matrix
(see
Figure 4). In
Figure 4, the indexes
G″ and
G refer to the internal and external generator nodes, whereas the index
L refers to load nodes and intermediate nodes.
The synchronous generators must be considered during their behavior in a faulted regime, which means that they must be modelled by its sub-transient positive, negative, and zero sequence impedances. In order to correctly consider their influence on the faulted regime, new fictious busbars must be added to the network busbars, i.e., the internal busbars of the synchronous generators which are named as
G″ (see
Figure 4).
All the synchronous generator admittance matrices (
for the generic
g generator) in the phase frame of reference (obtainable by means of the Fortescue transformations, i.e., the use of matrix
F [
42] as in
Figure 5) find their suitable locations on the matrix
YSincr of
Figure 4.
The presence of the loads (balanced or unbalanced) is considered by knowing the complex power absorbed by each phase
A,
B,
C (see
Figure 6).
It is worth noting that the admittance
yA,
yB, and
yC modeling the load on each phase are computed by knowing the pre-fault regime solved by the multiconductor power flow PFPD_MCA, which gives all the busbar voltage phasors (e.g.,
ul,A,
ul,B,
ul,C for the generic load
l). Therefore, the loads are correctly modelled by their equivalent admittance and not by their nominal one (i.e., with voltage magnitudes assumed to be 1 p.u.). Once computed
for each load, these matrices must be located inside the block diagonal of the admittance matrix
of
Figure 4.
3. The Steady-State Regime of the Faulted Power System
By considering the partition of
in
Figure 4, it is possible to write the following matrix relation:
Since both faults and generators + loads are considered by their admittance matrices in phase frame of reference, their injected currents are zeroed, i.e.,
. Therefore, Equation (11) can be re-written in the following form:
By considering the second equation of the system (12), the vector
EGL can be derived:
and substituted in the first equation of the system (12), it yields:
Equation (14) represents the current vector injected by the synchronous generators due to simultaneous faults occurring in the network. The voltage vector
can be derived by the knowledge of the pre-fault steady-state regime which is performed by the power flow solution of PFPD_MCA.
Figure 7 shows the positive-sequence sub-transient circuit of a generic synchronous generator.
The voltage behind sub-transient impedance can be easily derived by means of the second Kirchhoff law applied to the positive-sequence equivalent circuit and given by:
If consideration is given to all the synchronous machines in the network, Equation (15) must be re-written in matrix form by means of Equation (16), i.e.,
whose fully matrix representation is shown in
Figure 8.
Once the fault regime is solved, it is possible to focus on a specific element of the network (usually on the transmission lines) to investigate the behavior of the electric quantities along the element itself. In order to achieve these further analyses, it is possible to use the SPLIT procedures. It was developed in [
42] by the first author and reported again in
Appendix A.
5. Application of SFPD to the HV/EHV Italian Network
SFPD can represent a powerful tool for any transmission system operator that aims at deepening detailed analyses of its large-scale grid.
For example, the increasing generation by renewable sources decreases the fault levels, i.e., the three-phase short-circuit powers. SFPD could be used to foresee the decreasing trend in fault levels by connecting more and more grid-tied inverters delivering renewable power. In other words, this open algorithm can be used in the control room in order to provide evidence of the actual direction in which the national transmission grid is heading in terms of robustness and rotating power in service.
Another important application of SFPD towards large-scale grids, presented in this paper, deals with the neutral point treatment.
It is well known that the star points of the autotransformers of the transmission network are solidly earthed. In contrast, the distribution transformers (HV/MV step-down transformers) in the primary substation are an exception: the primary HV winding is unearthed. This is due to the fact that it is necessary to avoid high values of the line-to-earth short-circuit current which can give rise to high earth potential rises; in fact, the earthing grid resistances have values greater than those of transmission substations due to the fact that the former cannot benefit from the great extension of the latter. The synchronous generator star points are always connected to earth via a sufficiently high impedance.
There are two fundamental parameters in the neutral point treatment.
The first is
a or the ratio between the line-to-earth (single-phase) short-circuit current and the line-to-line-to-line (three-phase) short-circuit current at a given busbar, i.e.:
If |a| > 1, then the single-phase short-circuit current is greater than the three-phase one. In general, the higher the values of a, the higher the earth potential rise of the faulted substation.
The second is indicated with
k, and it is given by the ratio between the maximum overvoltage in p.u. of the two healthy phases
B,
C during a line-to-earth short circuit on phase
A and the phase-to-earth rated voltage. It can be expressed as in the following:
If k is too high, this could provoke another short circuit in another location of the grid. Therefore, it is convenient to keep k sufficiently low.
It is worth recalling the following IEC definition of directly earthed system: “a system in which in case of ground contact of a phase, the voltage to earth of healthy phases, excluding the transient period, does not exceed 80% of the nominal phase-to-phase voltage at any point”. It means that if |k| ≤ 0.8· ≅ 1.4 p.u., the system is a directly earthed one.
Moreover, not all the star points of the transmission transformers should be earthed: according to neutral point treatment theory, it is well known that the greater the number of star points earthed, the lower the zero-sequence impedance seen from any node and, therefore, the greater the single-phase short-circuit current than those three-phase, i.e., the greater the |a| parameter. Conversely, the greater the number of star points earthed, the lower the parameter |k| in order to have low overvoltages facilitating the insulation co-ordination. Hence, there are two conflicting requirements. Therefore, it is possible to identify an optimal number of the transmission transformer star points earthed. The other star points (distribution transformers and synchronous generator star points) cannot be varied as explained above.
In order to show the applicability of SFPD to real-world power networks and to find the above-mentioned optimum, SFPD is extensively applied to the ITG [
44]. The Italian grid (see
Figure 24) is meshed and has the data reported in
Table 9. The available scenario is off-peak during the winter of the year 2022.
The Italian network data available to the authors deal with a given scenario where the 132/150 kV busbars were originally represented by simple P and Q nodes. In order to consider the real configuration of the primary substations and chiefly to analyze the difference between the isolated and earthed neutral of their transformers, it has been necessary to add one or more HV/MV transformers of a suitable size (depending upon the absorbed apparent power). As already mentioned, in Italy, the primary winding of these transformers is always unearthed. In order to demonstrate the importance and technical soundness of this choice,
Figure 25 and
Figure 26 show the
a and
k parameters, respectively. In each of the 5498 EHV/HV nodes (see
Table 9), a single-phase
k1 and three-phase
k3 short circuits are computed (collectively, 10,996 short circuits!). Both types of short circuit are computed with the two different connections of the neutral point of the HV winding of the primary substation transformers: earthed (indicated with empty squares) and isolated (indicated with black dots). From
Figure 25, it can be deduced that it is convenient not to connect to earth the HV windings of the transformers in the primary substations in order to reduce the single-phase short-circuit currents which impact on the earth potential rise of the substations.
Figure 26 shows that
k for almost all the 5498 busbars is always lower than 1.4 p.u.; i.e., this proves that the Italian grid is a
directly earthed system.
The two zooms of
Figure 27 (between busbars 1500 and 1600, i.e., for 100 busbars) show that the choice to keep the star points (black dots in
Figure 27) of the distribution transformers isolated produces lower values for parameter
a (see
Figure 27a) where the black dots are always equal to (or lower than) the corresponding squares and higher values of parameter
k (see
Figure 27b) where the black dots are always equal to (or greater than) the corresponding squares.
By changing the focus on transmission transformers in the substations, in order to find the optimum percentage of their isolated star points, it is possible to vary the neutral state of those transformers. The percentage of isolated neutrals is varied stepwise according to the values of
Table 10, starting from the actual situation with 0% transformers with an isolated neutral. In order to vary the neutral status of EHV/HV substations uniformly across the Italian territory, the subdivision of these nodes is performed according to Terna’s territorial areas, headed by the following provincial capitals: Turin, Milan, Venice, Florence, Rome, Naples, and Palermo. Within each individual territorial area, in order to ensure a uniform distribution of the isolated neutral transformers, a “random” function is used, taking care to ensure that the mutual distances are not too concentrated at certain values. For each configuration of
Table 10, the
a and
k parameters are computed for each EHV/HV busbar (collectively 5498), and two average values are computed. Their values are shown in
Figure 28 as a function of the isolated neutrals of the transmission transformers reported in
Table 10.
The optimum is given by the intersection of the two lines: it occurs when the 58.03% of the star points of the transmission transformers are isolated (or the 41.97% of the star points of the transmission transformers are solidly earthed).
In the Italian network, this research achievement (only possible by means of the power of SFPD) is not taken into account since TERNA (the Italian TSO) prefers to connect to earth all the transmission transformer star points. In this way, TERNA achieves lower values of k (i.e., lower overvoltages during single-phase short circuits) but accepts greater values of a (i.e., of Ik1) by trusting in the effectiveness of the earthing grid at the substations, which lowers the earth potential rise at the faulted bus.
In any case, SFPD allows TSOs to choose whether to deepen such issues. This demonstrates the great possibilities of power system analysis by this open algorithm, namely SFPD.