1. Introduction
As the global energy structure undergoes an accelerated low-carbon transition, the installed capacity of renewable energy, particularly wind power, continues to increase significantly. The permanent-magnet synchronous generator (PMSG)-based direct-drive wind turbine has become a prominent technology in grid-connected wind power systems [
1]. However, the large-scale integration of PMSGs into weak grids via power electronic converters intensifies interactions among the turbine control loops, filter, sampling link, and grid [
2,
3]. These interactions can readily create impedance intersections in the high-frequency range and give rise to negative damping characteristics, which in turn lead to high-frequency oscillations [
4,
5]. Such oscillations can amplify grid-connected voltage and current harmonics and degrade power quality. In severe cases, they may also compromise the safety of converters and wind turbine equipment. Therefore, investigating the mechanism of high-frequency oscillations in PMSG-based grid-connected systems and developing effective suppression strategies are critical for ensuring the secure and stable operation of power systems.
Existing methods for suppressing high-frequency oscillations in power electronics-based grid-connected systems can generally be classified into passive and active damping approaches. Passive damping methods dissipate oscillation energy within specific frequency bands by adding damping filters or modifying existing filter branches [
6,
7,
8,
9,
10,
11]. For example, Ref. [
8] introduces a passive damping filter to mitigate negative damping in the high-frequency range. Ref. [
9] considers the cable-capacitance effect in offshore wind farm collection networks and proposes a hybrid active–passive damping method based on the impedance model of the converter–network system. Further developments in bypass and C-type damping filters are presented in [
10,
11] for subsynchronous oscillation suppression, wideband oscillation mitigation, and harmonic attenuation. Although passive damping methods offer clear physical mechanisms and relatively straightforward implementation, they generally require additional hardware and may increase power losses. Their effectiveness also depends strongly on frequency-specific parameter design. Moreover, the added damping branches may alter the original power-transfer characteristics of the system.
By contrast, active damping methods reshape the output impedance of grid-connected converters by introducing additional feedback loops or virtual impedances into the converter control, thereby enhancing damping without the need for extra primary hardware [
12,
13,
14]. For instance, Ref. [
14] embeds an active filtering function into the wind turbine converter control to suppress harmonic voltage amplification in offshore wind farms. Ref. [
15] tackles high-frequency oscillations in grid-connected inverters of PMSG-based direct-drive wind turbines through a capacitor-current-feedback active damping strategy designed to improve damping in the LCL filter resonance region. Compared with passive damping approaches, active damping methods eliminate additional hardware costs and provide greater flexibility in parameter tuning. However, active damping controllers typically require additional feedback signals, filtering stages, or virtual impedance blocks, thereby increasing the structural complexity of the control system. Furthermore, their damping performance is susceptible to sampling delays, control bandwidth limitations, sensor noise, and variations in operating conditions [
16]. Parameter design may not only attenuate the original dominant oscillation peak but also induce resonance frequency shifts, increase harmonic components in non-target frequency bands, and even introduce negative damping in new frequency bands [
17,
18]. Consequently, relying solely on amplitude attenuation at the target oscillation frequency as the design criterion for active damping is insufficient; it is imperative to further evaluate the impact of impedance reshaping on the full-frequency-band stability margin and power quality.
In recent years, research has increasingly shifted toward adaptive and coordinated oscillation suppression strategies. Ref. [
19] proposes an adaptive wideband oscillation suppression control for offshore wind farm integration, addressing wideband oscillation challenges with its effectiveness validated through high-frequency case studies. From a device- and station-level coordinated optimization perspective, Ref. [
20] develops an oscillation stability control method based on supplementary dissipation compensation to enhance the system-level damping of PMSG wind farms. Although these approaches improve adaptability and system-wide coordination in oscillation suppression, they generally involve more complex system modeling, parameter identification, or multi-layer control coordination, thereby increasing implementation complexity.
In summary, existing suppression strategies still exhibit two main limitations. First, many existing methods are designed for specific converter topologies, oscillation frequencies, or nominal operating conditions. Variations in wind turbine parameters, grid impedance, or filter configuration may shift the critical impedance intersection or introduce additional negative damping regions [
21,
22,
23]. Therefore, a fixed-parameter design may require retuning when the operating condition changes. Second, active damping controllers are often designed primarily to attenuate the dominant resonance, with insufficient consideration of harmonic amplification in non-target frequency bands, sideband elevation (i.e., the elevation of high-frequency components adjacent to the dominant oscillation frequency), and total harmonic distortion (THD). Consequently, suppressing the dominant oscillation alone may not ensure simultaneous improvements in system stability and power quality after impedance reshaping.
To bridge this gap, this paper proposes a current-feedback active damping strategy for high-frequency impedance reshaping. The core idea involves incorporating a notch filter into the feedback path to reject the fundamental current component, while utilizing the remaining non-fundamental components to generate a supplementary modulation signal that reshapes the high-frequency impedance. The controller gain is determined according to the impedance-intersection margin, and the frequency-selectivity parameter is iteratively adjusted by jointly considering the dominant-resonance suppression depth, sideband-component increment, and THD. Consequently, the proposed strategy not only eliminates adverse high-frequency impedance intersections but also effectively mitigates harmonic amplification outside the target oscillation band.
The main contributions are as follows:
- (1)
Positive- and negative-sequence terminal impedance models of the PMSG-based direct-drive wind turbine are established for high-frequency stability analysis. The effects of the inner current loop, PLL, and sampling delay are incorporated, and the model accuracy is validated through frequency sweep tests.
- (2)
The high-frequency oscillation mechanism is clarified from the perspective of impedance interaction. Parameter sweep analysis identifies the filter parameters, inner-current-loop proportional gain, and sampling delay as the principal factors affecting the high-frequency impedance characteristics and demonstrates the limitations of conventional parameter retuning.
- (3)
A current-feedback active damping strategy with coordinated multi-index tuning is proposed, in which the controller gain and frequency-selectivity parameter are jointly determined using the impedance-intersection margin, dominant-resonance suppression depth, sideband-component increment, and THD. A fundamental-frequency notch filter rejects the fundamental current component from the damping channel, while the retained non-fundamental components generate a supplementary modulation signal for high-frequency impedance reshaping. Consequently, the proposed strategy eliminates adverse impedance intersections while limiting harmonic amplification in non-target frequency bands.
The remainder of this paper is organized as follows.
Section 2 establishes the positive- and negative-sequence impedance models of the PMSG-based grid-connected system.
Section 3 analyses the high-frequency stability and investigates the effects of control parameters on the high-frequency impedance characteristics through parameter sweep analysis.
Section 4 proposes a current-feedback active damping strategy for high-frequency oscillation suppression.
Section 5 presents case studies to verify the effectiveness and superiority of the proposed current-feedback active damping strategy. Finally,
Section 6 summarizes the main findings and concludes the paper.
2. Sequence-Domain GSC Output Impedance Model of PMSG Grid-Connected System
The topology of the PMSG-based grid-connected system is illustrated in
Figure 1 and can be divided into the main circuit and the control system. The main circuit is primarily composed of the machine-side converter (MSC), grid-side converter (GSC), and its associated filter, while the control system encompasses the phase-locked loop (PLL), the outer control loop, and the inner current control loop.
In a full-scale PMSG wind turbine, the MSC regulates generator torque and rotor speed for maximum power extraction, whereas the GSC maintains the DC-link voltage and controls grid-side power exchange. For the high-frequency range considered in this study, the GSC output impedance is governed primarily by the GSC inner current loop, PLL, sampling delay, and filter dynamics, while the DC-link-voltage and other outer control loops have substantially lower bandwidths and exert only a limited influence on the impedance characteristics [
24]. Moreover, when the DC link is sufficiently stiff, the machine- and grid-side dynamics can be approximately decoupled through the DC-link capacitor [
23,
25]. Accordingly, the PMSG–MSC subsystem is not explicitly modeled; instead, the DC terminal of the GSC is represented by an ideal constant-voltage source, and only the GSC and its high-frequency control dynamics are retained in the detailed impedance model [
15]. This approximation is restricted to balanced high-frequency small-signal analysis. The machine-side, DC-link, and outer-loop dynamics should be retained when analyzing sub-synchronous or medium-frequency oscillations, substantial DC-link voltage variations, or systems with limited DC-link capacitance.
The electrical quantities are defined as follows: is the DC-link voltage; is the filter inductance; and are the damping resistance and filter capacitance, respectively; and are the equivalent inductance and resistance of the grid; , , represent the three-phase grid voltages; is the grid-connected current from the wind turbine; and , , are the three-phase voltages at the point of common coupling. In the diagram, , , denote the outputs of the inner current control loop in the stationary reference frame; , , are the modulation signals; is the voltage feedforward gain; and represents the decoupling coefficient. In the subsequent analysis, the DC-link voltage fluctuation is neglected, and its value is assumed to be constant, such that the focus remains on the dynamics of the PLL and the inner current control loop.
Before deriving the impedance model, the applicability of the sequence-domain formulation is specified. Both
dq-domain and sequence-domain impedance representations have been widely used for converter-grid stability analysis, with each offering distinct practical advantages [
26,
27]. In the high-frequency range considered in this study, which is well above the PLL and outer-loop bandwidths, mirror-frequency coupling is comparatively weak under the balanced small-signal conditions considered here. Accordingly, the off-diagonal sequence-coupling terms are neglected, and the positive- and negative-sequence impedances are represented by two scalar models. This approximation is adopted specifically for balanced high-frequency small-signal analysis. When mirror-frequency coupling becomes significant, the full 2 × 2 matrix representation should be retained.
Based on the topology shown in
Figure 2, a frequency-domain small-signal modeling approach is adopted [
5].
and
represent the proportional and integral coefficients of PI controller in PLL, respectively;
and
represent the proportional and integral coefficients of PI controller in inner current control loop, respectively;
and
represent the voltage feedforward gain and decoupling coefficient, respectively. The time-domain expressions for the phase-a voltage and current can be expressed as follows:
When transformed into the frequency domain, these expressions become
where
,
,
,
,
,
.
The control equation of the PLL in the frequency domain is given by
In the above expression,
represents the transfer function of the PLL control loop. Define the following intermediate variable
:
The PLL can then be expressed as
where
denotes the voltage sampling function, which incorporates the sampling delay, the PWM delay, and the sampling low-pass filter [
28]. The expression for
is given by
The control equation of the inner current loop can be expressed as
where
denotes the transfer function of the current PI controller.
Based on the modulation relationship of the three-phase voltages, Equations (8) and (9) can be derived as follows:
By substituting the three-phase voltage and current expressions into Equation (9), the positive- and negative-sequence GSC output impedance models can be obtained as follows:
where
denotes the current sampling function, which incorporates the sampling delay, the PWM delay, and the sampling low-pass filter. The expression for
is given by
The established impedance model can be validated through frequency sweep using the parameters listed in
Appendix A Table A1, with the results shown in
Figure 3. The comparison reveals that the theoretical impedance curves closely match the simulated sweep curves in the high-frequency range, indicating that the developed sequence impedance model can accurately characterize the high-frequency impedance behavior of the wind turbine.
To quantify the agreement between the analytical model and the frequency sweep results, the mean absolute magnitude and phase errors are calculated at 50 sweep pointsover the range of 1000–5000 Hz. For the positive-sequence impedance, the mean absolute magnitude and phase errors are 0.134 dB and 1.171°, respectively. Regarding the negative-sequence impedance, the calculated magnitude and phase errors are 0.525 dB and 2.440°, respectively. These small discrepancies, together with the close overlap of the analytical and sweep curves, confirm that the derived model accurately reproduces the high-frequency terminal impedance.
It should be noted that the delay terms must be retained to accurately describe the high-frequency phase characteristic of the GSC output impedance; otherwise, the accuracy of impedance model might be degraded [
29].
3. Analysis of High-Frequency Oscillation Mechanism and Influencing Factors
3.1. Analysis of High-Frequency Oscillation Mechanism of PMSG-Based Grid-Connected System
The equivalent circuit of the grid-connected direct-drive wind power system is shown in
Figure 4. In
Figure 4,
denotes the GSC output impedance, as expressed in (10);
represents the sum of the equivalent output currents of the converters;
is the grid impedance; and
is the grid voltage.
The expression for the grid-connected current is given by
According to the Bode diagram criterion, in conjunction with Equation (12), if the magnitude–frequency characteristics of
and
intersect at a frequency
, the phase margin
of the grid-connected direct-drive wind power system can be expressed as Equation (13).
At each frequency where the magnitudes of the grid impedance and GSC output impedance are equal, the corresponding phase margin is evaluated using (13). A positive indicates that the phase difference at the impedance intersection remains below 180°, and the system satisfies the small-signal stability requirement at that frequency. By contrast, implies that the phase difference exceeds 180°, indicating negative damping and a potential oscillatory instability near . When multiple magnitude intersections exist, the phase margin should be calculated at each intersection, and the minimum value is taken as the critical stability margin. Therefore, the system stability is determined jointly by the magnitude-intersection frequencies and the phase relationship between the grid impedance and GSC output impedance.
Using the parameters listed in
Table A1 of
Appendix A as the base case, high-frequency oscillations occur in the PMSG-based grid-connected system when the system parameters are set to conditions
and
, respectively. As shown in
Figure 5, the magnitude curves of the GSC output impedance and grid impedance intersect at 1366 Hz, at which the phase difference reaches 181°. According to (13), the phase stability margin at this frequency is negative, indicating that the system provides negative damping in the vicinity of 1366 Hz and is thus prone to high-frequency oscillations.
The physical mechanism underlying this oscillatory instability can be interpreted as follows. Changes in the filter parameters cause the magnitude of the GSC output impedance to decrease in the high-frequency range, resulting in an intersection with the magnitude curve of the grid impedance. At the corresponding intersection frequency, the current-sampling delay and PLL introduce additional phase lag, causing the phase difference between and to exceed 180° in magnitude. Consequently, the magnitude and phase conditions for oscillatory instability are simultaneously satisfied, and the system exhibits negative damping at this frequency. Under such conditions, even a small disturbance may be progressively amplified, eventually giving rise to sustained high-frequency oscillations.
3.2. Analysis of the Influencing Factors of Control Parameters
Based on the above analysis of the high-frequency oscillation mechanism, it can be inferred that the occurrence of high-frequency oscillations is primarily influenced by the filter parameters, which create an intersection of the magnitude characteristics, together with the negative damping introduced by the inner current-control loop and the sampling delay. In the following, the effects of the control parameters, specifically those of the inner current-control loop, the PLL, and the sampling delay, on the GSC output impedance characteristics and high-frequency oscillations are investigated in detail through parameter sweeps.
As shown in
Figure 6a, increasing the proportional gain
of the inner current loop produces a pronounced local minimum in the impedance magnitude over the frequency range of 1000–3000 Hz. As
increases further, this minimum shifts towards higher frequencies, thereby increasing the likelihood of an intersection between the GSC output impedance and the grid impedance. Meanwhile, the phase response of the GSC output impedance develops a sharp variation in the vicinity of the corresponding frequency. The resulting phase deterioration may introduce negative damping and consequently increase the risk of high-frequency oscillations in the grid-connected system.
As illustrated in
Figure 6b, when the sampling delay varies from 40 to 60 μs, a similar local minimum emerges in the impedance magnitude within the 1000–3000 Hz range, whereas the impedance magnitude outside this frequency band remains nearly unchanged. An increase in the sampling delay also produces a sharp variation in the impedance phase near the local minimum. Therefore, both a larger inner-current-loop proportional gain and a longer sampling delay can deteriorate the high-frequency impedance characteristics and increase the susceptibility of the system to high-frequency oscillations.
By contrast, the other control parameters considered in this study exert only a limited influence on the high-frequency impedance characteristics. The proportional gain
of the PLL, presented in
Figure 6c, is included as a representative example of such parameters.
The parameter sweep results align closely with the theoretical analysis, thereby validating the mechanism of high-frequency oscillation formation in the PMSG-based grid-connected system described in the preceding section. It is also evident that only a limited number of control parameters significantly affect the high-frequency oscillations. Although these high-frequency oscillations can be mitigated to some extent by retuning the above control parameters, the feasible adjustment range is restricted by controller bandwidth, dynamic-response requirements, and system stability constraints. Moreover, excessive parameter modification may degrade steady-state and transient performance, while parameter retuning alone does not provide a systematic means of satisfying the required impedance margin under the operating condition changes. To address these limitations, a current-feedback-based active damping method is proposed in the following section to suppress high-frequency oscillations without compromising the original control parameters.
4. The Design of the Current-Feedback Active-Damping Controller
The preceding analysis indicates that high-frequency oscillations are strongly influenced by the filter parameters and delay elements. However, these parameters have limited tuning ranges in practical systems, and excessive adjustment may adversely affect system performance. Therefore, parameter tuning alone is insufficient to achieve the required oscillation suppression without compromising the original control performance.
In recent years, increasing attention has been devoted to impedance-reshaping strategies based on control modifications. Nevertheless, most existing suppression methods primarily attenuate the impedance components within the target oscillation-frequency range, while the influence of the additional controller on non-target frequency bands is not sufficiently considered. To address this issue, a grid-injected-current-feedback active damping strategy is proposed for impedance reshaping. The corresponding active damping controller modifies the GSC output impedance to avoid adverse intersections with the grid impedance while limiting its influence on non-target frequency components.
4.1. Impedance Reshaping Model
The block diagram of the wind turbine based on current-feedback active damping strategy is shown in
Figure 7.
In
Figure 7,
denotes the active damping controller, and
represents the additional modulation signal. With the incorporation of the active damping controller, the final modulation signal, denoted
, can be expressed as shown in Equation (14).
Similarly,
and
can be obtained. By substituting
,
and
into Equation (9), the positive- and negative-sequence impedance expressions of the permanent-magnet direct-drive wind turbine generator after impedance reshaping can be derived as follows:
The results indicate that the incorporation of the active damping control alters the magnitude characteristics of the positive- and negative-sequence GSC output impedances. Therefore, if the active damping control is appropriately designed, the magnitude curve of the reshaped GSC output impedance can avoid intersecting the grid-impedance magnitude curve in the high-frequency range, thereby eliminating the impedance intersection that may induce oscillations.
4.2. Design Principles for Active Damping Controller Parameters
The active damping controller is designed to reshape the high-frequency GSC output impedance while preserving the fundamental-frequency operating characteristics. Therefore, the fundamental current component should be excluded from entering the active damping channel, whereas the non-fundamental components associated with oscillations should be retained for supplementary damping control. Through the coordinated tuning of the active damping controller parameters, the proposed controller is intended to provide the required high-frequency impedance-reshaping effect while minimizing its influence on the original low- and medium-frequency control dynamics, including those associated with the PLL and outer control loops.
To achieve this objective, the active damping controller is constructed by combining the damping gain
with a fundamental-frequency notch filter
, as expressed by
The notch angular frequency is set to the fundamental angular frequency, namely . Consequently, the filter gain approaches zero at the fundamental frequency, ensuring that the fundamental current component produces almost no additional modulation signal. By contrast, the non-fundamental current components pass through the filter and are fed back with a negative sign according to (14). The resulting supplementary modulation signal therefore reshapes the high-frequency terminal impedance without materially affecting the fundamental-frequency current regulation and steady-state power transfer.
The gain
determines the magnitude of the impedance-reshaping effect, whereas the frequency-selectivity parameter
influences the frequency range and phase characteristics of the active damping channel. Both parameters are subsequently coordinated to eliminate adverse impedance intersections while limiting harmonic amplification in non-target frequency bands. The transfer function of the fundamental-frequency notch filter is given by
where
is the central angular frequency of the notch;
is the damping coefficient, taken as 0.707; and
is the frequency-selectivity parameter. When
, the magnitude-frequency and phase-frequency characteristics of the notch filter are shown in
Figure 8a,b, respectively.
It should be noted that is a continuous-domain frequency-selectivity parameter appearing in the denominator of the notch filter, rather than the closed-loop bandwidth of the grid-side converter or a frequency component to be directly reproduced by the digital controller. Therefore, its numerical value should not be directly compared with the Nyquist frequency as if it were a signal frequency. Nevertheless, its sampled-data implementation should be further evaluated through discretization and fixed-step digital simulation.
4.2.1. Gain Design Principle
The influence of the gain
on the reshaped GSC output impedance characteristics is examined by varying its magnitude.
Figure 9 presents the Bode diagrams of the positive- and negative-sequence GSC output impedances for different values of
, with
and other parameters as listed in
Appendix A,
Table A1. As can be seen, a larger gain
produces a more pronounced reshaping effect on the GSC output impedance magnitude; however, an excessively large
significantly alters the impedance characteristics in the low- and medium-frequency bands.
From Equation (15), it can be seen that after introducing active damping, the positive-sequence impedance
and the negative-sequence impedance
of the wind turbine can be uniformly expressed as
where
is the additional impedance term introduced by the active damping controller, and its expression is given by
According to the impedance-based stability criterion described above, a sufficient margin should be maintained between the magnitude of the GSC output impedance and that of the grid impedance to suppress high-frequency resonance. Let the magnitude margin coefficient be
, which is taken as 3 dB in the following. At all intersection frequencies of the wind turbine and grid impedance magnitude curves prior to impedance reshaping, the reshaped impedance magnitude relationship should satisfy:
where
denotes the intersection frequency of the impedance magnitude curves before reshaping, and
is the equivalent grid impedance. By substituting the expression into the equation, the gain
that satisfies the corresponding magnitude margin
can be determined.
Based on the above analysis, the procedure for determining the gain is summarized as follows. First, the magnitude relationship between and is swept over the entire frequency range to identify all intersection frequencies at which . Subsequently, at each intersection frequency, the gain corresponding to the specified magnitude margin is calculated using the equation. Finally, the maximum value of among all intersection frequencies is adopted as the tuning result.
It is worth noting that although the original intersection between the GSC output impedance and grid impedance curves at is eliminated after impedance reshaping, the change in alters the magnitude of the GSC output impedance, which may lead to new intersections at other frequencies. Therefore, the above solution procedure must be repeated iteratively until all intersections are eliminated.
4.2.2. Design Principle for the Frequency-Selectivity Parameter
Similarly, to investigate the influence of the frequency-selectivity parameter
on the GSC output impedance characteristics, its value is adjusted and the resulting effects are observed.
Figure 10 presents the Bode diagrams of the positive- and negative-sequence GSC output impedances for different values of
, with
and other parameters as listed in
Appendix A,
Table A1. As can be seen, the frequency-selectivity parameter
determines the transition from the fundamental-frequency rejection band to the high-frequency feedback band. A smaller
allows the filter gain to recover more rapidly outside the fundamental-frequency notch, thereby strengthening the impedance-reshaping effect over a broader high-frequency range. Conversely, excessive high-frequency feedback may amplify non-target components. By contrast, increasing
attenuates a wider range of non-fundamental components and reduces the reshaping intensity, which helps limit out-of-band harmonic amplification.
Based on the above analysis, and in order to balance the different tuning objectives of , two key evaluation indicators are proposed in accordance with the fundamental principles outlined above: the dominant resonance suppression depth and the sideband component increment .
is the change in the current magnitude at the dominant resonance frequency
before and after the introduction of active damping. It quantifies the degree of attenuation of the current magnitude at the dominant oscillation frequency and indicates the efficacy of target oscillation suppression. It is defined as
where
denotes the magnitude of the system output current at the dominant resonance frequency without active damping, and
denotes the current magnitude at the same frequency after the introduction of active damping. A negative value of
indicates that the resonance peak has been effectively attenuated.
is the change in the root mean square (RMS) value of the current in the sideband (above 55 Hz and outside the ±10% range of the dominant resonance frequency) before and after the introduction of active damping. It quantifies the overall variation of high-frequency components outside the target suppression band, and its objective is to reflect whether additional harmonic amplification has been introduced while suppressing the target oscillation. It is defined as
where
is the RMS value of the system output current in the sideband without active damping, and
is the RMS current value in the same sideband after the introduction of active damping. If
remains negative or exhibits only a small change, it indicates that no significant deterioration has occurred in the non-target frequency bands.
During the tuning process, and impose constraints on the direction of adjustment for . Specifically, if increases upon the introduction of active damping, it indicates amplitude elevation in the sideband region. Thus, should be increased to mitigate the local side effects caused by an overly narrow bandwidth. If remains negative or exhibits only a small change, it suggests that no significant deterioration has occurred in the non-target frequency bands, and can be adjusted primarily based on the trend of . Regarding , if its reduction is insufficient and shows no positive increase, it implies that the active damping has not caused notable sideband degradation but the suppression of the dominant resonance is inadequate; under these conditions, can be appropriately reduced to further enhance the impedance reshaping effect. Conversely, if decreases significantly, it indicates that the current setting can effectively suppress the dominant resonance, and may be suitably increased. In this paper, two termination criteria are imposed on the iterative tuning process of . The iteration is terminated only when the THD is below 5% and the relative change in between two successive iterations is less than 1%. Once both conditions are satisfied, the tuned values of and are obtained.
Based on the above analysis, this paper adopts a multiplicative adjustment form to describe the update relationship for the direction and magnitude of
:
where k is the iteration number, and
is the adjustment coefficient jointly determined by
,
, and the THD. The specific expression for
is given in Equation (24):
where
and
denote the normalization scales of dominant resonance suppression depth and the sideband component increment, respectively.
and THD
max represent the reference level that activates the dominant-resonance penalty and prescribed THD limit, respectively. In this study,
12 dB,
6 dB,
−3 dB, and THD
max = 5%.
,
and
are the respective weighting factors, which are set to 0.5, 0.3, and 0.2 in this paper. In addition, the adjustment coefficient
must satisfy Equation (25):
where
and
are the minimum and maximum limits of the adjustment coefficient, taken as 0.3 and 2, respectively.
It can be observed that when is positive, the corresponding adjustment coefficient tends to be greater than 1, causing to increase in order to suppress the sideband elevation; whereas when is negative, the value of is primarily adjusted according to the trend of . Similarly, when is greater than −3, the corresponding tends to be less than 1, reducing to suppress the oscillation at the dominant frequency; when is less than −3, may take a value close to 1. The iterative process for is terminated when the THD falls below 5% and the relative change in between two successive iterations is less than 1%.
4.3. Tuning Procedure
It should be clarified that the proposed multi-index tuning is not formulated as a formal multi-objective optimization problem that searches for a Pareto-optimal or globally optimal solution. Instead, it is a coordinated iterative tuning procedure in which multiple performance indices are incorporated into a hierarchical parameter-update mechanism. The resulting parameter set represents a converged feasible solution satisfying the prescribed stability and power-quality criteria, rather than a mathematically guaranteed Pareto-optimal solution.
At the
k-th outer iteration, the controller parameter vector is defined as
- (1)
Tuning criteria
For a fixed
, the inner layer determines
from the impedance-stability requirement. The positive- and negative-sequence magnitude-intersection set
is defined as
At each detected intersection, a prescribed magnitude-separation margin is imposed, allowing to be calculated by (28).
The outer layer evaluates the dominant-resonance suppression depth , the sideband-component increment , and THD.
To make the roles of the design constants explicit, we define
- (2)
Weighting factors
Weighting factors include
,
and
. These coefficients are coordination weights in the update law rather than weights of a scalarized optimization objective, which satisfy (32).
- (3)
Parameter-update rule
Accordingly, insufficient dominant-resonance attenuation tends to reduce and strengthen impedance reshaping, whereas sideband deterioration or THD violation tends to increase and reduce excessive non-target feedback.
- (4)
Stopping conditions
The final parameter pair is returned only when the inner impedance-intersection condition and both outer stopping conditions are simultaneously satisfied.
In summary, the tuning of
and
constitutes a coordinated iterative tuning procedure: the inner layer iteratively calculates
with the objective of eliminating intersections in the impedance magnitude curves, while the outer layer progressively adjusts
according to the dominant-resonance suppression depth, sideband-component increment, and THD. The flow chart summarizing this process is shown in
Figure 11, demonstrating how the two parameters are tuned alternately and in coordination, enabling the active damping controller to effectively balance the two control objectives: suppressing high-frequency oscillations and maintaining the fundamental-frequency characteristics.
In a practical wind farm, the equivalent grid impedance is location dependent because individual turbines are connected through collector cables and transformers with different electrical distances. Different turbines may therefore exhibit different impedance-intersection frequencies and may require different and values. Turbines with similar electrical characteristics may be grouped and represented by an equivalent unit, provided that the collector-network equivalence is validated. Otherwise, a multi-machine or network-level impedance representation should be retained.