1. Introduction
Climate impacts associated with global warming have led to increasing global concern over carbon emissions. On 15 October 2016, the Kigali Amendment to the Montreal Protocol was adopted in Kigali, Rwanda, extending the regulatory scope of the Montreal Protocol on Substances that Deplete the Ozone Layer to include hydrofluorocarbon (HFC) refrigerants [
1]. This amendment entered into force in China on 15 September 2021. As a developing country, China is obligated to phase down the consumption of all HFC refrigerants by 2030 [
2,
3]. Currently, the majority of air-conditioning units in rail vehicles in China utilize R407C as the refrigerant. With a 100-year global warming potential (GWP
100) of 1620, R407C presents a substantial risk of atmospheric warming if released through leakage or inadequate disposal after equipment decommissioning, and is listed among the six primary greenhouse gases restricted by the Kyoto Protocol [
4].
China’s high-speed rail technology is world-leading; however, rail vehicle air-conditioning technology still lags significantly behind that of developed countries. The European Union mandates that refrigerants used in rail vehicle air-conditioning systems must have a GWP
100 not exceeding 750 [
5], yet China currently utilizes R22, R407C, and R134a—all of which far exceed this threshold. Statistics indicate that [
6], by the end of 2024, China operated 81,000 passenger rail vehicles, including 38,448 electric multiple units, marking a 3.7% increase compared to 2023. Taking the KLR30YTH rail vehicle air-conditioning unit as an example, each unit is charged with 8 kg of R407C, corresponding to a total national charge of approximately 6.48 × 105 kg in 2024. By reducing the refrigerant’s GWP
100 from 1620 to 750, the resulting decrease in carbon-dioxide equivalent (CO2
e) emissions would amount to 5.64 × 10
5 tons.
Compared with residential and automotive air-conditioning systems, rail vehicle air-conditioning units require a substantially larger refrigerant charge, operate at higher speeds in more demanding thermal environments, and must function within confined car-body spaces with high passenger densities [
7]. These factors impose stringent safety requirements on rail vehicle air-conditioning refrigerants, particularly concerning flammability and toxicity. Single-component refrigerants rarely provide both excellent thermodynamic performance and environmental safety along with favorable transport properties, whereas refrigerant mixtures can capitalize on the complementary advantages of their individual constituents. Moreover, the temperature glide inherent in refrigerant mixtures enables the cycle to more closely approximate the Lorenz cycle, thereby reducing irreversible losses associated with heat-transfer temperature differences and improving overall system performance.
With increasing emphasis on refrigerant environmental performance, global research investment in refrigerant mixtures has intensified. The constituent components of these mixtures have evolved from traditional refrigerants such as R22 and R152a to include compounds beyond conventional refrigerants, encompassing substances originally developed for other applications. Trifluoroiodomethane (R13I1), initially used as a fire suppressant and stabilizer, was considered in the 1990s as a principal constituent for next-generation, long-lasting, environmentally friendly refrigerant blends and was listed by the United Nations Environment Programme as a promising alternative refrigerant [
8]. Although R13I1 has clear potential as a refrigerant, early limitations in synthesis technology, such as production challenges and high costs, prevented its widespread adoption. However, with continuous improvements in preparation techniques in recent years [
9,
10,
11], R13I1 has once again attracted attention owing to its outstanding environmental performance. Duan [
12,
13] measured the saturated vapor-pressure data, saturated liquid and vapor densities, gas-phase p-v-T data, and critical parameters of CF3I with high accuracy, and developed comprehensive correlation equations that show excellent agreement with REFPROP 10.0 data. Based on these correlations, Wang [
14] conducted theoretical cycle simulations of CF
3I and its mixtures with R290 under nominal refrigerator conditions, demonstrating that R13I1/R290 mixtures with CF
3I molar fractions between 50% and 65% can be directly charged into refrigerators as R12 replacement refrigerants. Chabot et al. [
15] compared the COP and stability of 167 candidate fluids in heat-pump systems, identifying R161, R40, CF
3I, R435a, and R510a as the most promising refrigerants. Sun et al. [
16] experimentally determined the flammability limits of multiple mixtures containing CF
3I or CF
4, and found that the fully halogenated hydrocarbons CF
3I and CF
4 suppress the flammability of combustible refrigerants more effectively than inert gases such as N
2 and CO
2 or hydrogenated halocarbons like R134, R134a, and R125, while also raising the lower flammability limits of these mixtures. Wu [
17] blended R13I1 as a flame-retardant additive with the flammable refrigerants R1243zf and RE170 to investigate the lower flammability limits and critical extinguishing concentrations of the mixtures at various compositions. Ye [
18] utilized R13I1 as the base component to develop a MATLAB-based (R2017a) cycle model, conducted both simulations and experimental tests to evaluate system performance when directly charging the new refrigerant in place of R134a, and found that the R290/R13I1 (0.6/0.4) mixture demonstrates significant potential as an alternative to R134a in automotive air-conditioning systems. Zhang et al. [
19] proposed a novel refrigerant blend, R13I1/R152a (0.35/0.65), for replacing R134a in automotive air-conditioning. A thermodynamic property model for R13I1/R152a was established, and the results indicate that the application of R13I1/R152a in automotive air-conditioning systems is technically feasible. Recent developments have improved the practicality of R13I1 (CF
3I) for engineering deployment. Commercial suppliers now provide industrial-grade CF
3I in cylinder packages with ton-scale availability, and public B2B quotes indicate bulk prices in the USD 300–1000/kg range depending on purity (99–99.999%) and order size, whereas small reagent bottles remain much more expensive. In parallel, patents and recent studies have reported gas-phase/one-step catalytic routes that support scale-up and cost reduction compared with early laboratory syntheses [
20]. While pricing is volatile and specification-dependent, these supply-chain signals suggest that CF
3I is increasingly obtainable for large-scale blending and testing.
To investigate the feasibility of replacing the existing refrigerant R407C with an R13I1-based refrigerant mixture in rail vehicle air-conditioning systems, a theoretical cycle model for rail vehicle air-conditioning was developed and its accuracy validated experimentally. Following a comparative analysis of refrigerant properties, the constituent components and their proportions for the refrigerant mixture were selected. Finally, the performance of the mixture and R407C under varying operating conditions was evaluated using the theoretical cycle model, and an LCCP assessment was conducted, thereby providing both theoretical and experimental foundations for refrigerant selection and substitution in rail vehicle air-conditioning systems.
4. Theoretical Analysis
The basic thermophysical properties and environmental performance parameters of ZT01 and R407C are presented in
Table 7.
Table 7 indicates that, compared to R407C, ZT01 has a critical temperature that is 9.45 °C lower, a critical pressure that is 19.6 % higher, and a critical specific volume that is 26.7 % lower. These properties not only satisfy the operating temperature range of rail vehicle air-conditioning systems but also enable a more compact unit design, albeit with increased pressure-containment requirements. Furthermore, the polyolester (POE) lubricant used in R407C-charged units is fully compatible with ZT01, indicating good compatibility with POE lubricants used in R407C units; field verification of oil miscibility and return is still required, and oil conversion is not typically necessary when POE is already in use.
In practical applications, the operating conditions of refrigerants are not constant. For rail vehicles, the air-conditioning system’s operating conditions are influenced by environmental factors. During the actual cycle, to prevent the refrigerant from fully evaporating into gas within the evaporator, which could result in liquid refrigerant entering the compressor and causing a phenomenon known as “liquid slugging,” it is common practice to allow the refrigerant to evaporate and continue to absorb heat until it reaches a superheated gas state before entering the compressor. Moreover, to improve the refrigerant’s cycle performance, the refrigerant is typically in a subcooled liquid state at the condenser outlet. However, different refrigerants have varying degrees of tolerance to superheat, and the impact of subcooling on cycle performance also differs. In order to analyze the replacement performance of ZT1, this chapter investigates the effects of condensing temperature, evaporating temperature, superheating, and subcooling on the operating performance of the refrigerant mixture, comparing it with the theoretical performance of R407C.
4.1. Variable Condensation Temperature Working Conditions
The calculation conditions were set with a condensing temperature range of 30~60 °C in 5 °C increments, an evaporating temperature of 5 °C, and both subcooling and superheating of 5 °C. Theoretical cycle calculations yield
Figure 10, which illustrates the effects of condensing-temperature variation on volumetric cooling capacity, specific cooling capacity, specific compressor work, COP, pressure ratio, discharge temperature, mass flow rate, and gas flow rate.
With rising condensing temperature, both volumetric cooling capacity and specific cooling capacity show a marked decline for the tested refrigerants, reflecting the combined effects of increasing condenser pressure and diminishing enthalpy difference across the evaporator. Across the entire temperature range, ZT01 delivers 45.73–49.75% higher volumetric cooling capacity than R407C, even though its specific cooling capacity is 15.48–17.75% lower. The reason is that ZT01 provides higher suction-vapor density and more effective volumetric throughput, so more refrigerant mass is processed per unit swept volume, and the cooling delivered per unit compressor displacement rises by roughly 45–50%. As a result, the same duty can be achieved with a smaller-displacement compressor or by operating the existing machine at a lower speed, which is especially attractive where compressor size or installation space is constrained and can also reduce unit cost. Notably, this volumetric advantage becomes increasingly prominent at elevated condensing temperatures, where the relative performance gap widens. Consequently, ZT01 is particularly well-suited for compact system configurations or high-temperature refrigeration environments where maximizing cooling output within constrained volumetric and mechanical limits is a priority.
The superior volumetric capacity of ZT01 is accompanied by a markedly higher refrigerant mass flow rate, with values exceeding those of R407C by 21.5–26.4% across the investigated condensing temperature range. This elevated mass flow rate offers a practical pathway to offset the reduction in specific cooling capacity, as a greater refrigerant mass can be circulated through the system—achieved, for example, by a modest increase in expansion valve opening—without necessitating an increase in the total refrigerant charge. This approach not only avoids excessive charge inventory, thereby reducing leakage risk, but also helps sustain overall cooling output. In parallel, ZT01 exhibits a lower volumetric flow rate at the compressor suction compared with R407C, implying that a smaller suction volume is required to process the same cooling load. This characteristic directly translates into reduced compressor displacement requirements, which can facilitate the adoption of smaller, lighter, and potentially more cost-effective compressor designs. Such a combination of higher mass flow and reduced volumetric demand positions ZT01 as a promising candidate for system configurations where both footprint and mechanical capacity are constrained, without compromising on total cooling performance.
With increasing condensing temperature, the COP of both refrigerants exhibits a gradual decline, whereas their specific compressor work rises steadily. This behavior is primarily attributed to the elevation of condenser pressure, which increases the compression ratio and consequently the work input required for vapor compression, while simultaneously reducing the enthalpy difference across the evaporator and thereby diminishing the refrigeration effect. Despite these adverse thermodynamic shifts, the COP of ZT01 remains consistently close to that of R407C, with a deviation not exceeding 5% over the entire investigated temperature range. Notably, ZT01 requires 13.19–19.81% less specific compressor work compared with R407C. This substantial reduction in compression energy demand implies that, under equal refrigerant charge and operating conditions, a system charged with ZT01 can deliver an equivalent cooling capacity while consuming less electrical power. Such energy-saving potential, combined with the previously discussed volumetric advantages, underscores ZT01’s suitability for high-efficiency system designs, particularly in applications where energy cost and operational sustainability are of critical concern.
ZT01 exhibits a pressure ratio that is 8.83–11.53% lower than that of R407C under the same operating conditions. A lower pressure ratio reduces valve impact, bearing and thrust loads, shaft-seal differential pressure, and pressure pulsations; thermodynamically, it also enhances compressor volumetric efficiency and curbs internal leakage. Together, these effects lessen mechanical stress on moving components and are favorable for long-term compressor reliability, durability, and service life. In contrast, ZT01’s discharge temperature is approximately 17.5% higher than that of R407C, with the maximum observed value reaching 125.94 °C. While this temperature remains within the acceptable operational limits for most commercial compressors, elevated discharge temperatures can accelerate lubricant degradation, increase thermal loading on valves and seals, and heighten the risk of material fatigue in high-temperature components. ZT01’s higher discharge temperature requires attention to the compressor operating envelope and control settings. To avoid power/COP penalties, practical measures such as liquid injection or economizer operation, condenser-fan curve optimization, and superheat returning should be adopted; oil-cooling and enhanced heat rejection can be considered when necessary. By addressing these considerations, ZT01’s lower pressure ratio advantage can be fully leveraged without compromising system reliability and durability in long-term operation.
4.2. Variable Evaporation Temperature Working Conditions
The calculation conditions were set with an evaporating temperature range of −10 °C to 20 °C in 5 °C increments, a condensing temperature of 45 °C, and both subcooling and superheat of 5 °C. Theoretical cycle calculations yield
Figure 11, which depicts the effects of varying the evaporating temperature on volumetric cooling capacity, specific cooling capacity, specific compressor work, COP, pressure ratio, discharge temperature, mass flow rate, and gas flow rate.
With increasing evaporating temperature, both volumetric cooling capacity and specific cooling capacity exhibit a clear and sustained upward trend. Across the investigated range, ZT01 delivers an average 47.87% improvement in volumetric cooling capacity relative to R407C, while its specific cooling capacity remains 16.67% lower. This performance profile indicates that, although ZT01 requires a greater mass flow rate to achieve the same cooling effect per unit mass, it can provide substantially higher total refrigeration output per unit of compressor displacement. Such an advantage in volumetric performance allows for more effective utilization of compressor capacity and may enable the selection of smaller, more cost-efficient compressors without compromising overall cooling output.
Analysis of mass flow characteristics further underscores ZT01’s volumetric advantage. Across the full evaporating temperature spectrum, ZT01 consistently achieves mass flow rates approximately 20% higher than those of R407C. Notably, despite this higher mass flow, ZT01 exhibits markedly lower gas volumetric flow rates—on average, about 35% less than R407C—reflecting its higher vapor density. This reduced volumetric demand on the compressor directly contributes to improved volumetric efficiency, lower suction volume requirements, and a reduction in specific compression work.
As the evaporating temperature increases, the COP rises while the specific compressor work decreases, reflecting both the thermodynamic benefits of reduced compression ratios and the improved enthalpy difference across the evaporator. Within this context, ZT01 demonstrates a 12.64–21.08% reduction in specific compressor work compared to R407C. Although ZT01’s lower specific cooling capacity translates into a marginally reduced COP, the difference remains within 4% across all tested conditions, indicating that the two refrigerants exhibit comparable overall energy efficiency.
The narrowing temperature difference between the evaporator and condenser at higher evaporating temperatures results in a decreasing pressure ratio and a reduction in discharge temperature for both refrigerants. ZT01 maintains a pressure ratio 7.88–13.20% lower than that of R407C, which enhances compressor mechanical efficiency, reduces operating stress, and can extend equipment service life. However, ZT01’s discharge temperature is, on average, 17.44 °C higher than that of R407C. While this temperature remains within the safe operating range for most commercial compressors, it may require attention to thermal management strategies—such as enhanced discharge-side cooling or optimized oil return design—to ensure long-term operational reliability under elevated-temperature conditions.
4.3. Variable Superheat Working Conditions
The calculation conditions were set with a superheat range of 0 °C to 12 °C in 2 °C increments, a condensing temperature of 45 °C, an evaporating temperature of 5 °C, and subcooling of 5 °C. Theoretical cycle calculations yield
Figure 12, which depicts the effects of varying the superheat on volumetric cooling capacity, specific cooling capacity, specific compressor work, COP, pressure ratio, discharge temperature, mass flow rate, and gas flow rate.
The results indicate that the trends in cycle performance parameters for R407C and ZT01 under varying superheat are generally consistent. With increasing superheat, volumetric cooling capacity remains essentially constant, whereas specific cooling capacity, specific compressor work, discharge temperature, and gas flow rate all increase, while mass flow rate decreases. A key difference lies in COP behavior: for R407C, COP remains nearly unchanged across the superheat range, whereas for ZT01, COP shows a slight decline with increasing superheat.
In terms of volumetric cooling capacity, ZT01 maintains a significant advantage over R407C throughout the 0–12 °C superheat range, with an average increase of approximately 47.5%. This indicates that, for the same compressor displacement, ZT01 can deliver a higher cooling capacity. However, ZT01 exhibits a 15–17% lower specific cooling capacity compared to R407C, implying weaker cooling performance per unit mass flow. From a system design perspective, these characteristics suggest that ZT01 is more suitable for applications where compressor displacement is the limiting factor, whereas, in systems constrained by mass flow, its cooling efficiency may be somewhat restricted.
The specific compressor work for both refrigerants increases with superheat, with R407C consistently higher than ZT01 by approximately 13–20%. This demonstrates that, for equivalent cooling capacity, ZT01 requires lower compressor power input, contributing to reduced operating energy consumption. In terms of COP, R407C exhibits slightly higher values than ZT01, with differences remaining below 4% across the entire superheat range. The relatively small variation in COP with superheat indicates that superheat has a less pronounced effect on overall system efficiency compared to changes in condensing or evaporating temperature. Overall, ZT01 offers advantages in reducing compressor power consumption, although its slightly lower specific cooling capacity limits COP improvement. At a constant compression ratio, higher compressor suction temperatures lead to greater specific work. As superheat increases from 0 °C to 12 °C, the specific compressor work of R407C and ZT01 increases by 7.45% and 7.9%, respectively, with only minor differences between the two. While R407C’s higher specific cooling capacity contributes to a marginally higher COP, its specific compressor work remains consistently above that of ZT01.
Discharge temperature for both refrigerants rises with increasing superheat, with ZT01 maintaining an average discharge temperature approximately 17% higher than R407C. The relative difference is about 21%, decreasing slightly with superheat. Higher discharge temperatures can impose greater thermal loads on compressor valves, lubricating oil, and sealing components, potentially challenging long-term operational stability. Therefore, systems using ZT01 may require enhanced discharge-side cooling or optimized lubrication management to mitigate potential thermal failure risks. Nevertheless, the maximum discharge temperature of ZT01 remains below the widely accepted commercial compressor limit of 130 °C, ensuring safe operation under proper management.
Mass flow rate for both refrigerants declines as superheat increases, primarily due to the rise in suction specific volume, which reduces refrigerant mass intake at constant displacement. ZT01 consistently achieves mass flow rates 18–20% higher than R407C, largely due to its higher density characteristics. In contrast, R407C exhibits significantly higher gas flow rates, which gradually decline with increasing superheat. This suggests that, for the same displacement, ZT01’s higher mass flow partially offsets its lower specific cooling capacity. Furthermore, the lower gas flow rate helps reduce compressor volumetric load and improve volumetric efficiency.
4.4. Variable Subcooling Working Conditions
The calculation conditions were set with a subcooling range of 0 °C to 12 °C in 2 °C increments, a condensing temperature of 45 °C, an evaporating temperature of 5 °C, and superheating of 5 °C. Theoretical cycle calculations yield
Figure 13, which depicts the effects of varying the superheat on volumetric cooling capacity, specific cooling capacity, COP, specific compressor work, pressure ratio, discharge temperature, mass flow rate, and gas flow rate.
The subcooling increases from 0 °C to 12 °C, and the specific cooling capacity of both refrigerants exhibits a steady upward trend. This improvement is attributed to the reduction in refrigerant enthalpy prior to entering the evaporator, which enables greater heat absorption during the evaporation process and consequently enhances the cooling effect per unit mass. Across the entire subcooling range, R407C consistently demonstrates a 14–16% higher specific cooling capacity than ZT01, indicating superior cooling capability per unit mass flow. In contrast, ZT01 maintains a 16–20% higher mass flow rate than R407C over the same range. This difference primarily stems from ZT01’s higher density and lower specific volume under identical operating conditions, allowing a greater mass of refrigerant to be delivered at the same compressor displacement. From a system design perspective, R407C offers an advantage in specific cooling efficiency, whereas ZT01 can partially offset its lower specific cooling capacity by achieving higher mass flow rates, thereby sustaining substantial cooling output even when compressor displacement is limited.
Figure 13b illustrates the variation in COP with subcooling and the relative difference between the two refrigerants. As subcooling increases, the COP of both R407C and ZT01 rises, primarily due to the enhancement in specific cooling capacity while the specific compressor work remains nearly constant, leading to improved system energy efficiency. Across the entire subcooling range, the COP of R407C remains slightly higher than that of ZT01, with a gap of approximately 3–4%, and the relative difference decreases with increasing subcooling. This suggests that under high subcooling conditions, the energy efficiency of ZT01 approaches that of R407C, thereby narrowing their performance disparity. It is noteworthy that the magnitude of COP improvement is relatively modest, indicating that subcooling has a more pronounced effect on cooling capacity than on overall energy efficiency. Nevertheless, its role in reducing the performance gap between different refrigerants is non-negligible.
Overall, increasing subcooling simultaneously enhances the specific cooling capacity and COP of both R407C and ZT01. R407C maintains an advantage in cooling efficiency per unit mass, while ZT01 leverages its higher mass flow rate to boost total cooling output and narrows the COP gap with R407C under high subcooling conditions.
4.5. Life-Cycle Climate Performance (LCCP) Analysis
To further evaluate the feasibility of replacing R407C with ZT01 from an environmental perspective, this study introduces the Life-Cycle Climate Performance (LCCP) metric to quantify the total carbon emissions of the two refrigerants over the full service life of a rail vehicle air-conditioning system. LCCP accounts for both direct greenhouse-gas emissions from refrigerant leakage and indirect carbon emissions resulting from energy consumption during operation. The calculation formula is as follows:
where
ED is direct emissions and
EI is indirect emissions. Direct emissions are closely related to the refrigerant’s GWP, the charge amount, and the system leakage rate; indirect emissions depend primarily on the system’s energy consumption and the local electricity carbon-emission factor.
In this section, the analysis is based on the TTK7G-6.0GD air-conditioning unit, for which R407C has a rated charge of 1.6 kg, a rated cooling capacity of 6 kW, and a rated input power of 4 kW. Annual operating time is assumed to be 1500 h, with an average annual leakage rate of 15% [
31] and a service life of 15 years. Theoretical calculations indicate that the ZT01 charge amount is approximately 1.9 kg. The calculation results are shown in
Table 8.
The results show that ZT01’s direct emissions are 22.6% of those of R407C, a reduction of about 77.4%, so its low GWP substantially mitigates lifecycle leakage; because ZT01’s COP is about 4% lower, indirect emissions rise by roughly 4%, yet the large cut in direct emissions more than compensates, yielding an overall LCCP decrease of about 6.88%. Although the ZT01 charge is 1.9 kg versus 1.6 kg for R407C, this difference mainly reflects hold-up in the present rig rather than an intrinsic penalty, and vehicle-level safety will follow the applicable requirements for the selected safety class A1 or A2L, including charge-concentration limits and leak detection or ventilation when required by the operator or the standard. Charge can be minimized without changing system function by adopting lower hold-up heat exchangers such as microchannel designs, reducing receiver and liquid-line volumes, shortening piping, right-sizing the accumulator, and returning subcooling and superheat via the electronic expansion valve to the minimum stable settings; for new designs, the higher volumetric capacity of ZT01 enables smaller internal volumes and compressor displacement, which helps offset charge. Further optimization of the ZT01 system design and control could deliver even greater LCCP improvements.
It is worth noting that the LCCP assessment is sensitive to assumptions regarding the carbon emission factor of the electricity grid and the annual refrigerant leakage rate. A higher emission factor, as observed in coal-dominated grids, would increase indirect emissions and thus reduce the relative benefit of efficiency improvements. Conversely, cleaner grids with lower emission factors amplify the advantage of low-GWP refrigerants by lowering the indirect component of LCCP. Similarly, an increase in leakage rate would proportionally increase direct emissions, whereas improved maintenance practices and leak-tight system design could further enhance the environmental benefit of ZT01. These factors indicate that while absolute LCCP values may vary by region and operational conditions, the comparative advantage of ZT01 over R407C remains consistent.
5. Conclusions
This study addresses the environmental issues associated with the widespread use of the high-GWP refrigerant R407C in rail vehicle air-conditioning systems by proposing a novel refrigerant blend, ZT01 (R13I1/R32, 0.6/0.4), as an alternative. Through theoretical thermodynamic cycle analysis, the feasibility of applying ZT01 in rail vehicle air-conditioning systems was systematically evaluated. The main conclusions are as follows:
- (1)
The thermodynamic performance of ZT01 meets the cooling requirements of rail vehicle air-conditioning. Compared with R407C, ZT01 delivers 45–49% higher volumetric cooling capacity, although its specific cooling capacity is 15–18% lower. Under equivalent cooling output, a smaller-displacement compressor can be used to reduce system cost. The COP of ZT01 differs by no more than 5% from that of R407C, demonstrating excellent energy-efficiency compatibility.
- (2)
ZT01 exhibits superior operational characteristics. Across varying condensing and evaporating temperatures, ZT01 consistently delivers an 8–13% lower pressure ratio and a 13–21% lower specific work compared to R407C, thereby enhancing compressor volumetric efficiency and extending system lifespan. Although its discharge temperature is higher than that of R407C, it remains within the safe operating range of standard compressors, and thermal management can be achieved by optimizing the cooling and lubrication systems.
- (3)
Under typical operating conditions, its GWP100 is only 308, far below R407C’s 1620. LCCP analysis indicates that ZT01 reduces direct greenhouse-gas emissions by approximately 77.4%. Although its slightly higher energy consumption yields a 4% increase in indirect emissions, the net effect is a 6.88% reduction in total LCCP compared with R407C. In the context of carbon-peak and carbon-neutrality goals, ZT01 thus presents a clear advantage.
- (4)
ZT01 demonstrates practical engineering feasibility and strong substitution potential. Its environmental performance and safety characteristics meet the rail-transportation requirement for low-toxicity, non-flammable, low-GWP refrigerants, and are compatible with POE lubricants used in many R407C units; however, integration should follow a retrofit with a limited adjustments pathway rather than a drop-in claim, with oil miscibility/return verified in practice. This provides a reliable technical pathway for the green, low-carbon upgrade of rail vehicle air-conditioning systems. While ZT01 is classified as A1 under laboratory conditions, vehicle-level confined-space leakage behavior and interactions with other substances will be verified in forthcoming prototype and in-service trials, with results reported in a follow-up study.
- (5)
For zeotropic blends such as ZT01 and R407C, long-term leaks influence performance through two coupled mechanisms: progressive charge loss reduces evaporator wetting, raises suction superheat, lowers suction density, and degrades capacity and COP; composition shift due to preferential loss of the more volatile component alters mixture properties, further reducing volumetric capacity and control stability until the nominal composition and charge are restored. Chronic undercharge can also narrow protection margins and increase cycling. To manage these risks in rail HVAC service, we recommend the following: fixed leak detection in equipment bays with periodic functional checks; trend monitoring of superheat, subcooling, capacity, and power to flag early undercharge; no top-off after a leak, but full recovery, evacuation and weigh-in recharge to the nominal composition and charge, followed by verification of expansion-device settings and superheat; timely replacement of filter-driers and adherence to deep-vacuum and dehydration practices; design-for-tightness measures that reduce joints and permeation, favor-brazed connections and minimized hold-up volumes in receivers and liquid lines; scheduled leak inspections during maintenance intervals; and documentation plus technician training specific to zeotropic blends. These steps limit performance drift, shorten downtime, and help preserve both energy efficiency and component integrity over the service life.
- (6)
Based on the theoretical assessment, ZT01 is not a strict drop-in but a retrofit-ready candidate requiring limited adjustments. Given its differences from R407C in discharge temperature, mass flow, and pressure, implementation should include expansion-device retuning, updates to control and protection settings, charge determination and minimization, compressor-envelope verification, and vehicle-level safety conformity. We will conduct prototype and in-service trials following this process to confirm equivalence in performance, reliability, and safety. In addition, prior to fleet deployment, materials and lubricant compatibility should be verified (elastomers/seals, polymers, metals, desiccants) and POE miscibility and oil return confirmed; where a non-POE oil is installed, conversion to POE should follow standard procedures.
This study systematically analyzed the thermodynamic performance and cycle characteristics of R407C and the low-GWP mixture ZT01 under various operating conditions, and partially validated the theoretical model with experimental data. The results indicate that the model can reasonably capture the performance trends of the refrigerants. However, the experimental validation was conducted over a relatively limited range of operating conditions, which may not fully represent the complex scenarios encountered by rail vehicle air-conditioning systems under diverse climates and operational modes. Furthermore, the analysis primarily focused on steady-state conditions, without fully accounting for load fluctuations, part-load performance of components, and non-ideal heat and mass transfer effects during actual operation. In addition, key engineering issues such as the long-term stability of the mixture, composition glide, and lubricant compatibility remain insufficiently addressed.
Economic considerations: Beyond climate impact, the economic feasibility of an R407C→ZT01 retrofit depends on fleet- and region-specific drivers: (i) refrigerant price and required charge; (ii) conversion scope and outage cost (retuning controls/expansion device, possible seal/valve replacements, safety conformity items); (iii) electricity cost over the duty cycle given the observed small COP difference and local tariffs; (iv) maintenance and reliability effects associated with the lower pressure ratio (spares, labor, unplanned downtime); (v) carbon pricing/fees and phase-down-related price/availability risks for R407C; (vi) leak management and detection costs; (vii) end-of-life recovery/reclamation; and (viii) documentation and staff training. An economic advantage is expected when the present value of items (iii)–(viii) outweighs items (i)–(ii). For new designs, ZT01’s higher volumetric capacity can reduce compressor displacement and internal hold-up volumes, further improving lifecycle costs.
Future research should expand the scope of experimental validation to cover a wider range of operating conditions and environments; investigate the long-term property variations and system compatibility of ZT01; incorporate variable-condition experiments and dynamic simulations to evaluate performance stability under realistic operation; explore optimized compressor, heat exchanger, and control strategies tailored to ZT01; and conduct full life-cycle environmental and economic assessments. In addition, it will be essential to validate ZT01 under real rail vehicle operating conditions, where complex thermal environments, varying passenger loads, and dynamic duty cycles may influence refrigerant behavior. Long-term stability tests should also be carried out to evaluate potential composition changes, lubricant compatibility, and material interactions during extended operation. Such efforts will provide more comprehensive and reliable technical support for the adoption of low-GWP refrigerants in rail vehicle air-conditioning systems.
In summary, ZT01 is a low-GWP refrigerant mixture that balances thermodynamic performance, environmental friendliness, and system compatibility. It demonstrates both technical feasibility and environmental superiority for replacing R407C in rail vehicle air-conditioning applications, and offers strong prospects for engineering deployment.