Next Article in Journal
Identification of Both Distortion and Imbalance Sources in Electrical Installations: A Comparative Assessment
Previous Article in Journal
Integrated Underground Analyses as a Key for Seasonal Heat Storage and Smart Urban Areas
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Localization of Dual Partial Discharge in Transformer Windings Using Fabry–Pérot Optical Fiber Sensor Array

1
School of Electrical and Electronic Engineering, North China Electric Power University, Beijing 102206, China
2
State Grid Beijing Electric Power Company, Beijing 100031, China
*
Author to whom correspondence should be addressed.
Energies 2024, 17(11), 2537; https://doi.org/10.3390/en17112537
Submission received: 29 April 2024 / Revised: 18 May 2024 / Accepted: 22 May 2024 / Published: 24 May 2024

Abstract

:
The power transformer is one of the most critical core devices for energy exchange in power systems, and its safe and stable operation is directly related to the reliability of the power grid. Partial discharge is the main cause of insulation degradation and failure of high-voltage electrical equipment. Online monitoring and accurate localization of partial discharge can provide information on the aging of power equipment, which is of great value for improving the safe operation and maintenance of the power grid. Internal dual partial discharge in transformer windings is a more complex type of fault. Since it is located inside the windings, the signal is attenuated and distorted, making it difficult for traditional monitoring methods to capture such partial discharge signal The Fabry–Perot optical fiber sensor is an ultrasonic detection method that can be built into the transformer interior. This sensor has high sensitivity and a small size, enabling flexible placement at different locations inside the transformer for precise partial discharge detection. Especially for the narrow space inside the high and low voltage windings, F–P sensors can form an array, utilizing the array’s directivity to locate the fault points. In this study, an ultrasonic detection system based on the F–P optical fiber sensor array was developed. The system utilizes a directional cross-localization algorithm based on the multiple signal classification (MUSIC) algorithm to accurately locate dual partial discharge sources. This partial discharge detection system was applied to a 35 kV single-phase transformer, enabling the localization of dual partial discharge sources within the high and low voltage windings. Combined with experimental results, this method exhibits high localization accuracy and is particularly suitable for detecting partial discharge phenomena that occur within or between transformer windings.

1. Introduction

The transformer is crucial primary equipment in the power system, and its stable operation is closely related to the reliability of the power grid. Typically, failures in power transformers can be classified into insulation failures, mechanical failures, and conductor failures. According to statistical results, insulation failures account for the highest proportion of transformer failures among these three categories [1]. Partial discharge (PD) refers to the phenomenon where a localized discharge occurs in the insulation part of electrical equipment under the action of a strong enough electric field. This often occurs at defects. such as cracks, bubbles, and metallic impurities within the insulation medium [2]. PD is accompanied by the generation of a series of gases and chemicals, as well as local temperature rises and insulation corrosion, which can accelerate insulation deterioration at the defects, and even lead to severe damage to the entire electrical equipment due to a vicious cycle. Partial discharge testing can effectively assess the degree of insulation aging and evaluate the health status of transformers [3]. In large-capacity transformers with compact internal structures, partial discharge situations are more complex, with discharge energy, discharge types, discharge locations, and the number of discharges all closely related to the degree of insulation degradation [4]. Therefore, timely detection, identification, and accurate localization of complex partial discharges that occur during actual operation and production are of great significance for production maintenance, troubleshooting, reducing power outages, and shortening maintenance cycles.
For power transformers with complex structures, the probability of partial discharge occurring in the windings is the highest, and the associated hazards are the most significant. Equipment maintenance personnel detected two consecutive discharge pulse signals through the pulse current method but were unable to locate them accurately. Although traditional ultrasonic detection methods can be used for localization, they are greatly affected by environmental interference and are unable to detect two accurate discharge waveforms. The missed detection of PD sources can result in ineffective maintenance, and repeated repairs can increase transformer maintenance costs. In summary, the multi-point detection and localization of partial discharge within transformer windings are crucial for the safe operation of power systems and the optimization of maintenance plans. The localization of dual partial discharge sources can help improve the accuracy and efficiency of fault detection. Traditional fault detection methods often rely on manual inspections and empirical judgments, which are not only time-consuming and labor-intensive but also susceptible to human factors. However, through research on dual partial discharge source localization technology, automatic identification and localization of fault points can be achieved, significantly improving the accuracy and efficiency of fault detection.
Partial discharge is accompanied by electromagnetic pulses, sound, light, and other phenomena, which can be used to characterize the occurrence and intensity of partial discharge. Through processing and analysis of relevant algorithms, information, such as the location and magnitude of partial discharge, can be determined. Reference [5] employs the optical signal generated by partial discharge for online monitoring of power equipment with partial discharge. Reference [6] utilizes ultrasonic methods to inspect gas-insulated switchgear and implements the detection of weak partial discharge signals through noise reduction algorithms. Currently, transformer partial discharge localization methods mainly focus on electrical methods, ultra-high-frequency methods, and acoustic methods. As an effective and accurate localization methodology, acoustic methods have been widely used in industry [7].
The general acoustic localization method involves the use of piezoelectric transducers (PZTs) that are magnetically attached to the metal shell of the transformer tank [8]. The position of the partial discharge source is inferred by utilizing the time difference between the arrival of ultrasonic signals generated by partial discharge at different piezoelectric transducers [4,9,10,11,12,13]. However, this method has several drawbacks. Firstly, ultrasonic waves undergo attenuation and distortion after refraction and reflection through windings and tank walls. Secondly, transformers operate in environments with numerous interference signals, resulting in low signal-to-noise ratios (SNR) for the signals measured by the sensors and large localization errors. Especially for partial discharge signals occurring within transformer windings, even in ideal environments, PZT can experience difficulty capturing this type of discharge signal [1,14,15,16,17]. With the increasing application of optical technology in partial discharge detection, fiber-optic ultrasonic sensors have emerged as a novel method for detecting partial discharges. Reference [18] fabricated a single Fabry–Perot (F–P) sensor and detected the partial discharge waveforms inside transformers, but further applied research was not conducted. Reference [19] arranged F–P sensors in a square array and installed them outside the transformer windings, achieving localization of a single partial discharge source in the oil and on the surface of the outer windings. However, the issue of localizing dual partial discharge sources occurring within the high and low voltage windings was not addressed.
To address the issue of localizing dual partial discharge sources within transformer windings, this paper proposes the deployment of a regular tetrahedron structured F–P sensor array above the oil gallery between the high and low voltage windings of the transformer, with adjacent arrays arranged at 90° intervals. Utilizing the PD positioning system established, in combination with the proposed cross-localization algorithm based on the MUSIC direction-finding principle, only four sensor arrays are required to localize dual partial discharge sources in both the high and low voltage windings of the transformer. This localization system was tested in a 35 kV single-phase transformer, with experiments conducted separately in the high and low voltage windings. The results demonstrate that the localization error is within 18 cm, indicating high positioning accuracy. This method provides a novel approach and solution for locating dual partial discharge sources within transformer windings.

2. F–P Optical Fiber Sensor Array

The F–P fiber optic sensor is composed of single mode fiber, silica tube and silica diaphragm. The end face of the fiber and the silica diaphragm constitute two reflecting surfaces of the F–P interference cavity. The schematic diagram of the F–P optical fiber ultrasonic detection system is shown in Figure 1.
The laser source produces a light, which is divided into eight laser signals through a beam splitter. Each optical signal reaches the sensor probe through an optical path. At the interface between air and glass at the end of the fiber end face, approximately 4% of the light is first reflected back into the fiber, while the remaining 96% of the light passes through the air in the F–P cavity and undergoes a second reflection on the inner surface of the silicon diaphragm [20]. By adjusting the reflectivity of the silicon diaphragm, approximately 4% of the light can be reflected back into the fiber for the second time. These two reflected beams return along the same fiber, causing interference. The expression for the intensity of the interference light is as follows:
I r ( λ ) = R 1 + R 2 2 R 1 R 2 cos φ 1 + R 1 R 2 2 R 1 R 2 cos φ I 0 ( λ )
I0(λ) represents the incident light intensity; λ is the wavelength of the light source; R1 is the reflectivity of the fiber end face; R2 is the reflectivity of the inner surface of the silica diaphragm; φ is the optical path difference between the two reflecting surfaces. φ = 4πl/λ, l represents the length of the F–P cavity. It is evident from Equation (1) that, after interference, the intensity of the light reflected back into the fiber only depends on the length of the F–P cavity. Ultrasonic signals generated by partial discharges cause vibrations in the silica diaphragm of the sensor probe, thereby affecting the length of the F–P cavity and producing a fringe interference phenomenon. By detecting the intensity of the interfered light, converting it into an electrical signal, and further amplifying it through a photodetector, the ultrasonic signal can be converted into a pulsed electrical signal. Laser light serves as the intermediate medium for the exchange of these two types of signals, therefore this detection system does not produce electromagnetic interference to the detection equipment. Coupled with the compactness of the sensor probe, it can be flexibly arranged inside the transformer.
The frequency range of ultrasonic signals generated by partial discharges in transformer oil is between 20–2000 kHz. Through studying the impact of diaphragm thickness and diameter on the central frequency of the sensor, in order to obtain a good signal-to-noise ratio, the final design of the sensor probe has a central frequency of 30 kHz. At a distance of 2 m from the PD source, the sensor can detect a minimum discharge capacity of 100 pC. The output waveform corresponding to the ultrasonic signal from dual partial discharge sources measured by a single sensor is shown in Figure 2.
As can be seen from the waveform diagram, the designed sensor can accurately distinguish the discharge waveforms from two partial discharge sources. Based on verifying the performance of a single F–P fiber-optic sensor, this paper also designs a sensor array for partial discharge localization. According to the phased array theory, when designing the array structure, in order to avoid grating lobes, the array element spacing d should satisfy the condition that dλ/2, where λ represents the wavelength of the target to be measured. Under the condition of a fixed number of array elements, it is desired that the array has as large an aperture as possible, namely, d = λ/2. In our research, the propagation speed of ultrasonic waves is 1420 m/s, and the central frequency is 30 kHz, so the λ ≈ 4.73 cm. Additionally, to ensure the consistency of ultrasonic signals received by each array element and prevent significant waveform differences among the signals from different channels, through multiple experimental results, the spacing between adjacent sensor elements was set to 20 mm, and a regular tetrahedron structure is adopted. The array structure is shown in Figure 3, where θ and φ represent the azimuth angle and pitch angle, respectively. The establishment of the 3D rectangular coordinate system is shown in Figure 3, and all subsequent discussions in this paper are based on this.

3. Dual Partial Discharge Localization Algorithm

The MUSIC algorithm is a high-resolution spectral estimation method used for signal processing and array processing. Based on the orthogonality principle of signal subspace and noise subspace, it determines the direction of the signal by searching for the peak of the spatial spectrum [21,22,23]. It is particularly suitable for parameter estimation of multi-source signals in noisy environments. However, there are some difficulties in applying the MUSIC algorithm to partial discharge ultrasonic detection. Firstly, the ultrasonic signal generated by partial discharge is a broadband signal, which contains components of different frequencies within a certain range. In addition, the traditional piezoelectric transducers generally has a bandwidth of 30–150 kHz, and the collected ultrasonic signal is also a broadband signal. For the MUSIC algorithm, the signal subspaces of broadband signals at different frequencies are different, which is not suitable for direct directional measurement of traditional piezoelectric transducers. However, the F–P optical fiber sensor designed in this paper has a central frequency and peak sensitivity at around 30 kHz, and the measured signal is a narrowband signal, which can be directly used with the MUSIC algorithm for directional measurement of partial discharge sources. In summary, the F–P optical fiber sensor developed in this paper has certain advantages in design compared with the traditional piezoelectric transducers.

3.1. The Principle of Direction Finding Using MUSIC Algorithm

Based on the principle of spatial spectrum estimation, assuming X(t) represents the array received signal, we compute its covariance matrix:
R = E X t X t H = A ( φ , θ ) R S A H ( φ , θ ) + R N
R represents the covariance matrix of the array signal. A(φ,θ) is the steering vector, which encodes the DOA of the sound source. Specifically, θ denotes the azimuth angle of the sound source, and φ represents the pitch angle, as illustrated in Figure 3. Additionally, RS and RN are the signal covariance matrix and noise covariance matrix, respectively. By performing eigenvalue decomposition on the array signal covariance matrix R, we can obtain the results:
R = U S Σ S U S   H + U N Σ N U N   H
US represents the signal subspace, UN represents the noise subspace, and ∑S and ∑N are the corresponding diagonal matrices for each subspace, respectively. Based on the properties of the signal subspace, it can be deduced that the steering vector A(φ,θ) of the signal is orthogonal to the noise subspace UN. It can be described as follows:
A H ( θ , φ ) U N = 0
Due to the finite length of the array signal, the maximum likelihood estimation of R is
R ^ = 1 L n = 1 L X X H
In the equation, L represents the acquisition length of the array signal, R ^ denotes the maximum likelihood estimation of the covariance matrix R, and n stands for the number of sampling points in the array signal. By performing eigenvalue decomposition on R ^ , we obtain the noise subspace U ^ N . Since background noise is always present, the steering vector A(φ, θ) and the noise subspace U ^ N are not completely orthogonal. In practical calculations, the estimation of the DOA is achieved through a minimum optimization search, it can be expressed as follows:
( φ ^ , θ ^ ) = arg min A H φ , θ U N U N H A φ , θ
This formula represents the solution to minimization problems. By utilizing the inverse relation, (6) can be transformed as follows:
P m u s i c = 1 A H φ , θ U N U N H A φ , θ
Pmusic represents the spatial spectrum, which is a calculation formula related to energy. The energy value of ultrasonic signals at the location of partial discharge is significantly higher than that at other locations where only acoustic wave reflections and refractions occur without partial discharge sources. In the case of a single PD source, after searching the entire spatial spectrum, the MUSIC algorithm identifies the peak with the highest energy. The values of φ and θ corresponding to this peak can indicate the directional information of the partial discharge source, namely the azimuth and pitch angles. This is the basis for direction finding using the MUSIC algorithm. Even in the case of continuous discharge at a single point, the position of the energy extremum in the spatial spectrum remains unchanged, with only one peak representing the direction of the partial discharge source. In the case of dual PD sources, the spatial spectrum function exhibits two energy extrema. By searching for the directional information of the first and second extrema, the directional information of both partial discharge sources can be obtained.
The MUSIC algorithm, by constructing a spatial spectrum function, achieves the estimation of signal direction of arrival. Compared to traditional beamforming methods, it offers superior resolution. Based on this advantage, it can simultaneously perform direction finding for multiple partial discharge source signals.

3.2. Direction Finding Cross-Localization Algorithm

The fundamental principle of the direction finding cross-localization algorithm involves two sensor arrays or direction-finding stations measuring the DOA of signals from the same target. Based on the spatial geometric relationship, the target’s coordinate position is then calculated. A schematic diagram of this principle is shown in Figure 4.
Considering the measurement error in the actual situation, the space straight lines are not intersecting straight lines, but spatially anisotropic straight lines; for this reason, we choose the midpoints of two spatially anisotropic straight lines’ common perpendicular segments as the coordinates of the localization source.

4. Experimental Test Results and Analysis

The dual partial discharge sources localization test platform in transformer oil consists of a transformer oil tank, F–P fiber optic sensor array, a Marx high-voltage pulse generator, and a needle-plate electrode that generates partial discharge. The transformer oil tank has dimensions of 200 cm × 100 cm × 150 cm and is filled with 25# transformer oil. The outer shell of the oil tank is grounded. The experimental transformer model is a 35 kV single-phase transformer with a height of 0.6 m, an outer diameter of 0.24 m and an inner diameter of 0.2 m for the high-voltage windings, and an outer diameter of 0.13 m and an inner diameter of 0.1 m for the low-voltage windings. The transformer core has a height of 0.6 m and a radius of 0.1 m. The turn-to-turn spacing of the windings is 0.6 cm. The actual scene image of the transformer is shown in Figure 5.
Based on past experience, two serially connected needle-plate electrodes can simultaneously undergo partial discharge under a high-voltage pulse of 20 kV. The sensor array is arranged at a 90° interval above the oil channel between the high and low voltage windings of the transformer, approximately 5 cm apart. According to the cross-localization principle, only four sensor arrays are required to localize dual partial discharge sources in the entire high and low voltage windings of the transformer. However, due to experimental limitations, this study employs two sensor arrays to detect and locate partial discharge sources within a quarter of the winding range. The experimental setup is illustrated in Figure 6.
Based on the 3D rectangular coordinate system established for the array in Figure 3, the spatial angles measured in the experiment include azimuth and elevation angles, which can be obtained from the line connecting the PD source and the origin of the coordinate system. In comparing similarity, the distance between the theoretical PD source position and the estimated position can be treated as the distance error.

4.1. Dual PD Sources Localization Test Results in Low-Voltage Winding

In the first experiment, two PD sources were placed at (11 cm, 40 cm, 10 cm) and (5 cm, 40 cm, 6 cm), within the low-voltage winding. After the occurrence of partial discharge, the signals captured by the F–P sensor array were processed through a localization algorithm, resulting in estimated positions of (10.9 cm, 51.2 cm, 11.4 cm) and (4.3 cm, 32.5 cm, 17.6 cm). According to the previous definition, the distance error was 11.3 cm. Subsequently, similar to the first experiment, the two PD sources were placed at three additional positions with different heights and deviation angles to evaluate the overall stability of the localization system. The experimental setup is illustrated in Figure 7, and the experimental results are presented in Table 1 (No. 2–4 group data).
Analysis of the data in the Table 1 reveals that the average localization error of this method in the low-voltage windings is approximately 13.3 cm. Moreover, when the dual partial discharge sources occur on the same depth coil, the localization accuracy is slightly higher compared to two sources at different depths, as observed in the experimental data of Group 1 and Group 2. This is because, when the two PD sources are far apart, the time interval between the arrival of ultrasonic waves at the sensor array is larger, resulting in more refraction and reflection waveforms that can interfere with localization accuracy. For two PD sources located on the same layer of the coil, the deeper the position, the better the localization effect, as seen in data 1 and 4. This is due to the fact that, as the distance from the PD sources increases, the directivity of the F–P sensor array improves and, as the distance decreases, the error increases. Additionally, the cross-directional measurement algorithm itself has blind zones. Although placing it 5 cm above the oil duct can reduce the impact of blind zones, the localization error for the upper windings near the sensor array is slightly higher. Overall, the low-voltage windings have relatively fewer coil turns, resulting in less interference during ultrasonic wave propagation. Therefore, this method exhibits good accuracy in the localization of dual partial discharge sources in low-voltage windings.

4.2. Dual PD Sources Localization Test Results in High-Voltage Winding

Based on the working principle of transformers, the number of turns in the high-voltage winding is higher than that in the low-voltage winding. Structurally, this manifests as the high-voltage winding being wider than the low-voltage winding. Therefore, five representative discharge positions were selected to verify the reliability of the localization algorithm. Similar to the localization research method for low-voltage winding, five test points with different depths and deviations were chosen on the side of the high-voltage winding of a 35 kV transformer. A schematic diagram of the experimental setup is shown in Figure 8, and the localization results are presented in Table 2.
Experimental results indicate that the average localization error of the double partial discharge sources in the high-voltage winding is 14.2 cm, which is higher than that of the low-voltage winding. This is due to the fact that the number of turns in the high-voltage winding is higher than that for the low-voltage winding. When ultrasonic waves pass through the windings to reach the sensor array, they encounter more reflections and refractions, which result in increased interference and localization errors. The deeper the partial discharge source, the more windings the ultrasonic signals have to pass through to reach the sensor array, and the more interference the signals encounter, leading to slightly higher localization errors. This can be observed from the data of No. 1 and No. 5, which show the impact of the depth of the partial discharge source on localization errors. However, the MUSIC algorithm has a high peak resolution, which reduces the impact of these interferences on localization accuracy. As can be seen from No. 3 and No. 6, although the partial discharge source 5 is located in the middle of the winding, its ultrasonic signals theoretically should encounter more interference from the windings, but the impact seems to be insignificant. This may be related to the randomness and contingency of the experiment. To reduce the localization distance error and minimize the interference from obstacles such as windings, further exploration is needed in optimizing the localization algorithm and the arrangement of the sensor array.

5. Conclusions

This paper develops a dual partial discharge source detection system for transformer windings based on the Fabry–Perot sensor array. By using the cross-localization algorithm based on the MUSIC algorithm proposed in this paper, fault localization within the windings can be achieved. Compared to traditional piezoelectric transducers, the tetrahedral-structured F–P sensor array designed in this study is compact, sensitive, strongly resistant to electromagnetic interference on-site, and possesses a high insulation rating. These arrays are capable of operating in the high-temperature and high-pressure environment inside transformers, adapting to various typical environmental characteristics within power transformers. Therefore, during the manufacturing process of power transformers, the sensors can be installed in proximity to the windings, such as above the oil duct between the high-voltage and low-voltage windings, to detect inter-turn partial discharge signals within the windings. The MUSIC algorithm enables high-resolution spatial spectrum estimation for dual partial discharge sources. Using the azimuth angles and pitch angles obtained, the proposed directional cross-localization algorithm can achieve localization of dual partial discharge sources within the windings using a relatively small number of sensor arrays. This system represents a significant step forward in improving the reliability and accuracy of partial discharge detection in power transformers.
Utilizing the dual PD localization system proposed in this paper, validation experiments were conducted separately on the high-voltage and low-voltage windings of a 35 kV single-phase transformer. Combined with the proposed dual PD localization algorithm, the localization errors meet the requirements for engineering applications. However, due to the complex conditions within transformer windings, further optimization of the sensor array placement positions is necessary. Additionally, novel signal processing methods should be employed to reduce the interference caused by the winding structure on ultrasonic signals, thereby enhancing the localization accuracy. These efforts will pave the way for more reliable and precise partial discharge detection in power transformers.

Author Contributions

Conceptualization, W.W.; methodology, J.D. and F.L.; validation, J.D., F.L., Y.S. and S.Z.; writing—original draft preparation, F.L.; writing—review and editing, W.W. and F.L.; funding acquisition, W.W. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by National Natural Science Foundation of China, grant number 51577063.

Data Availability Statement

The original contributions presented in the study are included in the article; further inquiries can be directed to the corresponding authors.

Conflicts of Interest

Author Jian Du was employed by the State Grid Beijing Electric Power Company. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Fuhr, J.; Aschwanden, T. Identification and localization of PD-sources in power-transformers and power-generators. IEEE Trans. Dielectr. Electr. Insul. 2017, 24, 17–30. [Google Scholar] [CrossRef]
  2. Lu, S.; Chai, H.; Sahoo, A.; Phung, B.T. Condition Monitoring Based on Partial Discharge Diagnostics Using Machine Learning Methods: A Comprehensive State-of-the-Art Review. IEEE Trans. Dielectr. Electr. Insul. Publ. IEEE Dielectr. Electr. Insul. Soc. 2020, 27, 1861–1888. [Google Scholar] [CrossRef]
  3. Shang, H.; Li, Y.; Xu, J.; Qi, B.; Yin, J. A Novel Hybrid Approach for Partial Discharge Signal Detection Based on Complete Ensemble Empirical Mode Decomposition with Adaptive Noise and Approximate Entropy. Entropy 2020, 22, 1039. [Google Scholar] [CrossRef]
  4. Lu, L.; Ichimura, S.; Rokunohe, T. Interaction Between Partial Discharge and Generated Bubbles Under Repeated Lightning Impulses in Transformers Using a Complex Structure Model. IEEE Trans. Dielectr. Electr. Insul. 2021, 28, 727–735. [Google Scholar] [CrossRef]
  5. Xia, C.; Ren, M.; Chen, R.; Yu, J.; Li, C.; Chen, L.; Chen, Y.; Wang, K.; Wang, S.; Dong, M. Multispectral Optical Partial Discharge Detection, Recognition, and Assessment. IEEE Trans. Instrum. Meas. 2022, 71, 7002911. [Google Scholar] [CrossRef]
  6. Lin, Q.; Lyu, F.; Yu, S.; Xiao, H.; Li, X. Optimized Denoising Method for Weak Acoustic Emission Signal in Partial Discharge Detection. IEEE Trans. Dielectr. Electr. Insul. 2022, 29, 1409–1416. [Google Scholar] [CrossRef]
  7. Wang, Y.-B.; Chang, D.-G.; Qin, S.-R.; Fan, Y.-H.; Mu, H.-B.; Zhang, G.-J. Separating Multi-Source Partial Discharge Signals Using Linear Prediction Analysis and Isolation Forest Algorithm. IEEE Trans. Instrum. Meas. 2020, 69, 2734–2742. [Google Scholar] [CrossRef]
  8. Binotto, A.; Castro, B.A.d.; Santos, V.V.d.; Rey, J.A.A.; Andreoli, A.L. A Comparison between Piezoelectric Sensors Applied to Multiple Partial Discharge Detection by Advanced Signal Processing Analysis. Eng. Proc. 2020, 2, 55. [Google Scholar] [CrossRef]
  9. Jalil, M.A.A.; Rosmi, A.S.; Rohani, M.N.K.H.; Isa, M.; Mohammad, W.N.A.W.; Abdullah, A.Z.; Mustafa, W.A. Piezoelectric Sensor using PZT Material for Partial Discharge Detection on Power Transformer. IOP Conf. Ser. Mater. Sci. Eng. 2020, 864, 012204. [Google Scholar] [CrossRef]
  10. Meitei, S.N. Partial Discharge Detection Using Piezoelectric Sensors on Power Transformer: A Review. IEEE Sens. J. 2024, 24, 13730–13742. [Google Scholar] [CrossRef]
  11. Sikorski, W.; Wielewski, A. Low-Cost Online Partial Discharge Monitoring System for Power Transformers. Sensors 2023, 23, 3405. [Google Scholar] [CrossRef] [PubMed]
  12. Rathod, V.B.; Kumbhar, G.B.; Bhalja, B.R. Partial Discharge Detection and Localization in Power Transformers based on Acoustic Emission: Theory, Methods, and Recent Trends. IETE Technol. Rev. 2021, 39, 540–552. [Google Scholar] [CrossRef]
  13. Korzec, D.; Hoppenthaler, F.; Nettesheim, S. Piezoelectric Direct Discharge: Devices and Applications. Plasma 2021, 4, 1–41. [Google Scholar] [CrossRef]
  14. Chan, J.Q.; Raymond, W.J.K.; Illias, H.A.; Othman, M. Partial Discharge Localization Techniques: A Review of Recent Progress. Energies 2023, 16, 2863. [Google Scholar] [CrossRef]
  15. Yan, J.; Chen, C.; Wu, Z.; Ding, X.; Lou, L. An Acoustic Localization Sensor Based on MEMS Microphone Array for Partial Discharge. Sensors 2023, 23, 1077. [Google Scholar] [CrossRef] [PubMed]
  16. Al-Masri, W.; Wadi, A.; Abdel-Hafez, M.F.; Hashim, H.A.; El-Hag, A.H. Partial Discharge Localization in Power Transformers Using Invariant Extended Kalman Filter. IEEE Trans. Instrum. Meas. 2023, 72, 1002110. [Google Scholar] [CrossRef]
  17. Hashim, A.H.M.; Azis, N.; Jasni, J.; Radzi, M.A.M.; Kozako, M.; Jamil, M.K.M.; Yaakub, Z. Application of ANFIS and ANN for Partial Discharge Localization in Oil Through Acoustic Emission. IEEE Trans. Dielectr. Electr. Insul. 2023, 30, 1247–1254. [Google Scholar] [CrossRef]
  18. Wang, K.; Tong, X.; Zhu, X. Transformer partial discharge monitoring based on optical fiber sensing. Photon. Sens. 2014, 4, 137–141. [Google Scholar] [CrossRef]
  19. Gao, C.; Wang, W.; Song, S.; Wang, S.; Yu, L.; Wang, Y. Localization of partial discharge in transformer oil using Fabry-Pérot optical fiber sensor array. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 2279–2286. [Google Scholar] [CrossRef]
  20. Huang, Y.W.; Tao, J.; Huang, X.G. Research Progress on F-P Interference—Based Fiber-Optic Sensors. Sensors 2016, 16, 1424. [Google Scholar] [CrossRef]
  21. Ma, T.; Xiao, Y.; Lei, X. Channel Reconstruction-Aided MUSIC Algorithms for Joint AoA&AoD Estimation in MIMO Systems. IEEE Wirel. Commun. Lett. 2023, 12, 322–326. [Google Scholar]
  22. Wang, X.; Amin, M.; Ahmad, F.; Aboutanios, E. Interference DOA estimation and suppression for GNSS receivers using fully augmentable arrays. IET Radar Sonar Navig. 2017, 11, 474–480. [Google Scholar] [CrossRef]
  23. Merkofer, J.P.; Revach, G.; Shlezinger, N.; Routtenberg, T.; Van Sloun, R.J.G. DA-MUSIC: Data-Driven DoA Estimation via Deep Augmented MUSIC Algorithm. IEEE Trans. Veh. Technol. 2024, 73, 2771–2785. [Google Scholar] [CrossRef]
Figure 1. Structure of the F–P optical fiber ultrasonic detection system.
Figure 1. Structure of the F–P optical fiber ultrasonic detection system.
Energies 17 02537 g001
Figure 2. Ultrasonic signals measured by F–P optical fiber sensor in transformer oil.
Figure 2. Ultrasonic signals measured by F–P optical fiber sensor in transformer oil.
Energies 17 02537 g002
Figure 3. Coordination of F–P optical fiber sensor array.
Figure 3. Coordination of F–P optical fiber sensor array.
Energies 17 02537 g003
Figure 4. Schematic diagram of cross-localization for direction finding of dual PD sources.
Figure 4. Schematic diagram of cross-localization for direction finding of dual PD sources.
Energies 17 02537 g004
Figure 5. Single-phase winding model of 35 kV transformer.
Figure 5. Single-phase winding model of 35 kV transformer.
Energies 17 02537 g005
Figure 6. Dual PD localization test using a real 35 kV single-phase transformer winding.
Figure 6. Dual PD localization test using a real 35 kV single-phase transformer winding.
Energies 17 02537 g006
Figure 7. Localization Test for Dual PD Sources in Low-Voltage Winding.
Figure 7. Localization Test for Dual PD Sources in Low-Voltage Winding.
Energies 17 02537 g007
Figure 8. Localization Test for Dual PD Sources in High-Voltage Winding.
Figure 8. Localization Test for Dual PD Sources in High-Voltage Winding.
Energies 17 02537 g008
Table 1. Results of dual PD source localization in low-voltage winding.
Table 1. Results of dual PD source localization in low-voltage winding.
NumberPD Source
Coordinates/cm
Localization
Results/cm
Distance
Error/cm
11 (11.0, 40.0, 10.0)(10.9, 51.2, 11.4)11.3
2 (5.0, 40.0, 6.0)(4.3, 32.5, 17.6)13.8
21 (11.0, 40.0, 10.0)(16.1, 26.9, 5.3)14.8
4 (3.0, 20.0, 4.0)(6.7, 30.8, 10.4)13.1
33 (9.0, 20.0, 8.0)(5.3, 9.5, 13.4)12.4
2 (5.0, 40.0, 6.0)(10.1, 53.2, 11.2)15.1
43 (9.0, 20.0, 8.0)(13.9, 32.8, 5.0)14.0
4 (3, 20.0, 4.0)(5.5, 10.7, 11.4)12.1
Table 2. Results of dual PD source localization in high-voltage winding.
Table 2. Results of dual PD source localization in high-voltage winding.
NumberPD Source
Coordinates/cm
Localization
Results/cm
Distance
Error/cm
11 (20.0, 40.0, 16.0)(14.3, 51.6, 18.9)13.3
3 (4.0, 40.0, −5.0)(8.3, 56.2, −2.6)17.2
21 (20.0, 40.0, 16.0)(25.4, 27.2, 21.8)15.0
4 (0, 20.0, −5.0)(3.7, 32.5, −8.8)13.6
31 (20.0, 40.0, 16.0)(17.6, 52.3, 11.8)13.2
5 (0, 20.0, −7.0)(6.4, 10.7, −1.6)12.5
42 (19.0, 20.0, 13.0)(15.1, 32.4, 8.6)13.7
3 (4.0, 40.0, −5.0)(6.9, 55.6, −10.4)16.8
52 (19.0, 20.0, 13.0)(13.3, 10.2, 4.9)13.9
4 (0, 20.0, −5.0)(6.0, 32.1, −3.7)13.6
62 (19.0, 20.0, 13.0)(14.4, 32.5, 9.8)13.7
5 (0, 20.0, −7.0)(4.3, 33.1, −2.5)14.5
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Liu, F.; Du, J.; Shi, Y.; Zhang, S.; Wang, W. Localization of Dual Partial Discharge in Transformer Windings Using Fabry–Pérot Optical Fiber Sensor Array. Energies 2024, 17, 2537. https://doi.org/10.3390/en17112537

AMA Style

Liu F, Du J, Shi Y, Zhang S, Wang W. Localization of Dual Partial Discharge in Transformer Windings Using Fabry–Pérot Optical Fiber Sensor Array. Energies. 2024; 17(11):2537. https://doi.org/10.3390/en17112537

Chicago/Turabian Style

Liu, Feng, Jian Du, Yansheng Shi, Shuainan Zhang, and Wei Wang. 2024. "Localization of Dual Partial Discharge in Transformer Windings Using Fabry–Pérot Optical Fiber Sensor Array" Energies 17, no. 11: 2537. https://doi.org/10.3390/en17112537

APA Style

Liu, F., Du, J., Shi, Y., Zhang, S., & Wang, W. (2024). Localization of Dual Partial Discharge in Transformer Windings Using Fabry–Pérot Optical Fiber Sensor Array. Energies, 17(11), 2537. https://doi.org/10.3390/en17112537

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop