1. Introduction
Since 1990, there has been a more than threefold increase in the demand for space cooling in buildings. Space cooling contributed with the emission of 1 Gt CO
2 and around 8.5% of global electricity consumption, according to the 2019 global energy report [
1]. Some reasons are: the improvement in environmental comfort, urban growth, and climatic changes that cause drastic variations in temperatures. Following the same trend over the years, cooling demand growth rates will continue in the next decade. China has positioned itself as the world leader, with 40% of the market in the purchase of cooling equipment [
1]. It has been recorded that global refrigeration consumption is the cause of 15% of electricity demand peaks, and for days of intense heat, it can be responsible for more than 50% of electricity demand peaks in the residential sector [
2].
Absorption cooling systems are being used worldwide to save electricity, with chillers driven by waste heat, district heat, or solar heat. The evidence that the peak cooling demand is linked with increased solar radiation presents an optimal development opportunity for solar thermal refrigeration technologies. An example of experimental absorption equipment is a system, whose components, i.e., the heat exchangers, the expansion valve, and the thermal compressor, are connected by means of pipes and valves, which provoke strong non-linearities, a high dependency unit, and a high thermal inertia. Thus, the dynamic modelling and control of such systems is not trivial [
3].
Various types of absorption systems, research on working fluids, practical achievements, and the most promising developments are discussed by Ziegler [
4,
5,
6], Labus et al. [
7], Azher et al. [
8], and Pongsid et al. [
9]. Absorption cycles are modelled and compared with experiments by Dincer et al. [
10,
11] and Ng et al. [
12], for different heat exchange technologies, e.g., with plate exchangers such as those proposed by Sterner and Sunden [
13] and Goodarzi et al. [
14].
A useful tool in the analysis of the heat and mass transfer processes, particularly during the operation set up, is the use of dynamic models [
15,
16,
17]; Kim and Ferreira [
18] achieved an analysis simulation of an ammonia–water absorption chiller. Weihua et al. [
19], Viswanathan et al. [
20], and Martinho et al. [
21] described the dynamic model in detail regarding the heat and mass balances, whereas Iranmanesh and Mehrabian [
22], Ochoa et al. [
23], and Kohlenbach and Ziegler [
24] describe LiBr/H
2O systems, where the latter further includes performance analysis, sensitivity checks, and comparison to experimental data. Puig et al. [
25] compared approaches to the characteristic equation method and concluded that the method developed by Albers et al. [
26,
27] is the simplest and that it provides better accuracy. An object-oriented simulation using parallel processing for foretelling the transient behavior of absorption chillers with arbitrary configuration has been explained by Matsushima et al. [
28]. Other modeling methods such as state-space, graph-theory, structure-matrix, and combined forecasting have been employed for modeling air-conditioning systems by Yao et al. [
29], Omar and Micallef [
30], and Wen et al. [
31].
An advantage of the absorption refrigeration systems over mechanical compression is the energy source; the latter require high-quality energy for their operation, but absorption refrigeration systems can use low quality thermal energy. This means that heat source temperatures do not need to be high (80–150 °C). Therefore, the waste heat from many industrial processes or, as in the actual analysis, a solar collector system would be sufficient to supply the power required in these machines, which are frequently controlled by on–off or proportional–integral control strategies. Fernández and Vázquez [
32], Rêgo et al. [
33], and Jeong et al. [
34] propose a parametric model control action that is based on generator heat flux modulation and the level of a high temperature generator that provides the maximum system performance. Hüls et al. [
35] shows applications with an intelligent control algorithm, in which absorption chillers are advantageous because of synergies within the rest of the energy supply system, such as a solar cooling system. The control of absorption commercial chillers is conventionally done by temperature control of the driving heat input. In order to understand this behavior, it is important to realize that an absorption chiller is a device that is totally governed by heat transfer processes. This gives rise to the possibility of reducing the complex response to the characteristic temperature equation model [
36]. Nienborg et al. [
37] contested variants of control in diverse system arrangement with a dynamic system simulation. By the optimization of key parts, they achieved electricity savings of up to 25%. Sabbagh and Gómez [
38] established an optimal control strategy to run an absorption refrigeration chiller.
Some researchers have already worked with the proportional integral derivative (PID) controller [
39,
40,
41], even using fuzzy logic [
42], to tune PID parameters (Kp, Ki, and Kd) of variable speed pumps for the purpose of improving the solar fraction and the system energy consumption [
43]. Lima et al. [
44] proposed a technique for varying the speed of the pump and, therefore, ensured the range of flow for absorption chillers, with the pair LiBr-H
2O, implementing a PID controller action system, which allowed flow control testing. Vinther et al. [
45] simulated decentralized control structures in terms of PI feedback loops for absorption cycle heat pumps using the dynamic nonlinear model of a single-effect LiBr-H
2O absorption system.
Previous work experience and promising results achieved in solar absorption systems motivate us to continue improving the systems and the models that describe them for the implementation of optimal controls. The main purpose of this work is to propose a PID controller in a plate heat exchanger solar absorption cooling system (SACS), designed and built by Jimenez-García and Rivera [
46]. The system works with the ammonia–water pair (NH
3–H
2O), it was built using five vertical plate heat exchangers and is designed to operate with solar energy or some other cheap heat source. Suggested adjustments were made to improve efficiency; in addition, a cascade PID control is tested. The controlled variables are the outlet temperature of the cold water and the mass balance in the thermal compressor, while the solution returning to the absorber and the refrigerant volumetric flow are the manipulated variables. The test facility was located at the Refrigeration and Heat Pump Laboratory of the Renewable Energy Institute (IER), National Autonomous University of Mexico (UNAM) in Temixco, Morelos.
2. Absorption Cooling System ACS
2.1. Main System
Figure 1 shows the most important components of the refrigerant (NH
3) circuit: the compression heat pump, the condenser CO, the refrigerant throttling valve Vr, and the evaporator EV; heat exchangers have 20 plates each. To replace the compressor in a conventional refrigeration system, the absorber AB is used, together with a heat exchanger HX and the desorber DE (also called generator elsewhere), with 40 plates each; a solution pump P and throttling solution valve Vs are also required. In this inner circuit, a solution of the refrigerant and absorbent is recirculated. Two tanks are used, one mixing chamber in the absorber and another for vapor separation flow at DE exit. The system operation is continuous, with simultaneous refrigerant generation and absorption operations; the real experimental equipment is shown in
Figure 2. Therefore, there are two circuits in the system, one for the solution (1–6) and another one for the refrigerant (7–10). External fluids are streams of water supplied to different components so that the operation of the cooling system is carried out.
In the evaporator EV, the liquid refrigerant is vaporized at low pressure by absorbing heat Q
0 from the chamber to be cooled. The refrigerant vapor (10) is then absorbed by a refrigerant-depleted weak (1) solution in the absorber. The resulting strong (6) solution enriched by the absorption of refrigerant is pumped by the solution pump into DE (5), which is at the condenser pressure. The mechanical work supplied to the solution pump is relatively low, a very low percentage of the heat supplied to the desorber [
5].
The pumped solution flows through HX, (4) before it enters DE, increasing its temperature as a consequence of the heat transferred by the solution returning from the desorber to the absorber. In DE, the strong solution is boiled by the driving heat Q2 at the highest temperature, whereby the refrigerant absorbed in AB is expelled from the solution (3). The refrigerant is condensed in CO (7). The condensate is then expanded in Vr (8) to the evaporator pressure (9). This closes the working medium circuit. At DE, the solution changes from high refrigerant concentration to low refrigerant concentration by the supply of heat from an external source, Q2. This weak solution flows into the solution heat exchanger HX, and then, it is expanded by the expansion valve Vs to the evaporator pressure and passes back into the absorber AB, where it can absorb refrigerant again. This closes the solution cycle.
The refrigeration cycle can be considered as a reverse thermal machine. Carnot efficiency can be defined for the refrigeration cycle as Equation (1),
It represents the maximum theoretical value of efficiency that can be obtained in a refrigeration cycle. In practice, the efficiencies obtained are much lower due to the irreversibilities in the system. As the analysis of the Carnot cycle gives the maximum coefficient of performance (COP)
max for a mechanical vapor compression system, it is convenient to find the COP achievable in an absorption system. The heating medium of the DE supplies the heat
QDE (Q
2) to the system, the pump supplies the work
Wp, and the cooled solution in the evaporator supplies the heat
QEV. The system delivers heat to the environment (cooling water) in the absorber
QAB and condenser
QCO. The sum is the heat dissipated
Q0:
From the first law of thermodynamics:
Supposing that mean heating temperature in the desorber
TDE, a mean chilled solution temperature in the evaporator
TEV, and that ambient temperature
T0 are constant.
if
Wp is assumed to be negligible,
and for a reversible system:
2.2. Experimental System
Figure 2a shows a diagram of the main mechanical components of the experimental SACS. Its support structure’s dimensions are length 1 m, width 0.8 m, and height 1 m, including the instrumentation for measurement and analysis. All components, including the pipes, valves, and accessories, are made of stainless steel to prevent corrosion. Five high efficiency plate heat exchangers were used, all of them oriented vertically; with 40 plates for DE, HX, and AB and 20 plates for CO and EV.
Figure 2b shows a photograph of the experimental system.
In order to modify the solution load within the cooling system, two storage tanks of 4 L each were incorporated. The separation tank is placed at the outlet of DE; it allows that ammonia vapor to flow towards CO through the rectifier and the weak liquid solution to return to AB; the mixing tank receives the weak solution and the ammonia vapor from EV. Since the SACS is operated with the NH3-H2O working mixture, the rectifier used was a finned stainless steel tube, with a length of 40 cm and a nominal diameter of 1/2 inch, installed with 30° of inclination. To operate the equipment, a diaphragm, intermittent flow, or pulse pump was used, and a pulse damper had to be adapted, a small spherical chamber, and a membrane with nitrogen gas confined to the discharge pressure of the pump. There are two pressure levels (high and low) separated by two expansion valves. The first Vr was on the line from EV–CO, and the second on the line from DE–AB, both are unidirectional and made from stainless steel. Both are coupled to NEMA 17 DC stepper motors and allow us to maintain the position without using encoders.
For the experimental evaluation, a data acquisition system and external flow systems (a heating system, a cooling system, and a circuit of water to be chilled) were used. The auxiliary water heating system that the refrigeration system requires for its operation is installed on the roof of the Refrigeration and Heat Pumps Laboratory at IER-UNAM. It consists of a bank of evacuated tube collectors (18 modules divided into 3 sections connected in parallel) with a collection area of 30 m2. The system has a vertical storage tank and an auxiliary heater. The heated water is sent to the cooling system by means of a 0.33 HP pump. The cooling water for AB and CO is obtained from a cooling chiller (26–30 °C). For the analysis of the cooling power, water is circulated through the evaporator at constant temperature controlled by an electrical resistance.
To evaluate the behavior of the SACS, it was necessary to measure some thermodynamic variables such as temperature, pressure, and mass flow of the weak and strong solution, cooling water (AB, CO), heating water (DE), and chilled water (EV). The variables were measured using electronic instruments: 20 RTD temperature sensors (PT1000) to register the flow temperatures at the inlet and outlet of each heat exchanger, 4 piezoelectric pressure transducers placed at the outputs of the DE, CO, EV, and AB; 3 Coriolis flowmeters, the first between the HX and AB heat exchanger for the weak solution, the second between the desorber and heat exchanger for the strong solution, the third between CO and EV and 4 rotameter-turbine flowmeters, at the inlets of external pressure flows. The location of each sensor in the SACS is shown in
Figure 3.
Table 1 describes the accuracy of the sensors. For the data acquisition, a program was developed in which all the calibrated temperature, pressure, and mass flow sensors that were utilized in the system are included. The information is stored every twenty seconds in a database. A DAC 34972A with a multiplexer card and an input and output control card were used, the latter for the implementation of the PID. In Vr and Vs, the speed of both stepper motors can be controlled by means of a PMW signal and their direction with a digital signal using the micro-stepping motor driver A3967 and the Agilent card.
2.3. Dynamic System
The dynamic model of a refrigeration system proposed by Wen et al. [
31] allows the comparison between the performance of an experimental control and the numerical simulations using MATLAB. The system basically contains 8 interconnected units: evaporator, absorber, desorber, condenser, heat exchanger, rectifier, pump, two throttle valves; two pressure levels were considered. For completeness, the main aspects of this model are here explained.
For each element of the system, pressure, temperature, and concentration are described, through a concentrated parameters approximation: according to the law of energy and conservation of mass; taking into account that the ammonia–water mixture phase changes throughout the cycle and the transfer of heat and mass are time-varying in the system; other assumptions are listed below:
Only two pressures are considered: high (desorber–condenser) and low (absorber-evaporator);
The thermal storage of the plates heat exchanger are neglected;
There is no pressure loss in the pipes;
The throttling process is isenthalpic;
Heat transfer to and from the surroundings are ignored;
The amount of work given to the pump is negligible;
The fluid leaves each component at the component temperature;
Constant heat exchanger efficiency.
The model in state space is as follows:
where
is the cumulative mass in the absorber, including the mass of refrigerant vapor and NH
3 solution;
,
and
are the mass flow rates of the weak solution, refrigerant vapor, and strong solution, respectively. The mass traces and heat of the refrigerant vapor are imperceptible compared to those of the NH
3 solution within the margin of error.
Therefore, can approximately represent the mass of the NH3 solution in AB. is the specific enthalpy of the solution at the AB outlet, is the specific enthalpy at the inlet of AB, is the specific enthalpy of the heated refrigerant vapor in AB, and is the heat transfer rate from AB to the cooling water. is the average temperature, and is the specific heat capacity of the solution in the case side of AB. is the cumulative mass of the liquid refrigerant in the evaporator. is the average temperature in EV, is the heat transfer rate from the chilled water to the evaporator, and is the specific enthalpy of the liquid refrigerant under evaporating pressure.
If the volumes inside the pipes that join all parts of the system are neglected, the mass conservation equation of AB and the mass conservation equation in the whole system can be resolved as:
The effectiveness of the heat exchanger given as [
3]:
The energy balance, therefore, leads to:
The heat transfer rate can be calculated by taking the desorber as an example:
Connecting Equations (16) and (17), the heat transfer rate in the DE and the hot water outlet temperature can be estimated:
Analogous results can also be concluded for the other main components.
The mass flow rate of the strong solution from AB is defined by the solution pump, and it can be defined as:
where the coefficient
k is particular to the pump;
is the strong solution density;
is the frequency driving the solution pump;
is the internal volume of the pump. The valves Vr and Vs are adiabatic devices. The mass flow rate can be calculated as:
where
is the valve flow coefficient;
is the pressure difference between the connected components;
g is the gravitational acceleration;
is the density. By controlling the valve aperture, the cross-section area
can be set, and this can be used as a manipulated variable for controlling the mass flow rates in the SACS [
47,
48].
The state of the SACS can be described by six variables: the cumulative mass in AB , the average temperature in AB (), the concentration of the strong solution in AB (, the cumulative mass in EV (), the average temperature in DE (), and the concentration of the weak solution in DE (.
SACS model can be written in state-space form
with the following state vector:
The input vector for the model is:
where
are the external water circuits mass flow rates and inlet temperatures.
is an internal variables vector that depends on the state, and p is a constant value parameters vector.
5. Discussion
Several experimental tests were carried out to validate the repeatability of the parametric evaluation, at the beginning, for a non-controlled system. The operating conditions and the solution flow influence determined the following methodology for stability control: first, it was developed an object oriented program through a data acquisition system, then, some test runs were carried out to finally be able to validate the proposed controller. The maximum cooling capacity obtained was 3.86 kW external and 4.87 kW internal; this was obtained at 95 °C hot water, 86 °C solution temperature at DE, and 26 °C cooling water in CO. As expected, the best cooling capacity was achieved at the lowest cooling water temperatures in the condenser, and the best COP achieved was 0.67 with an average of 0.58.
The validation of the dynamic simplified model was implemented in MATLAB/Simulink, and its accuracy was verified. The thermodynamic properties for the ammonia–water solution with an ammonia concentration of 40% for the temperatures, at which the system was operated, were obtained by the Tillner-Roth [
51] equations. The comparison results shown in
Figure 8 show good agreement between the simulated and experimental data, which is a good reference to validate the experimental PID controllers proposed in the system.
The feasibility of the PID control for the SACS began with local experimental tests of the behavior of the equipment operated with a PID tuning with known techniques from Ziegler and Nichols; then, a linearized model was used to compare the practical results. The hypothesis was that the control of the refrigerant and diluted solution mass flows, in addition to maintaining the levels in the mixing and separation tanks, could achieve the stability and control of the system. It was then possible to improve other parameters such as evaporator cooling capacity and COP. Response time, beyond the inherent advantages of automation, has been reduced; once the transitory part is reached, the range of the control objective is maintained indefinitely. The operation proposal of cascaded PID’s was also verified. The simulation results show good agreement with the experimental data, except for parts of the initial transient response.
On the validation of the control proposal, the adaptation of the dynamic model exposed in state space is proposed. The thermodynamic and control results in the SACS were analyzed with MATLAB and compared to the experimental results in the real SACS, considering an NH3-H2O mixture with a strong concentration of 0.40. The traditional PID controller action is augmented with a version of two cascaded PID’s, which overcomes several issues of previous formulations. There are linear alternatives that attempt to approximate the behavior of non-linear techniques but reduce their complexity. As PID control strategies, in this type of control, the main purpose is to simplify controllers designed for specific operation points and some rules that allow switching between them or operated in parallel. Except for the transitory behavior data, the model simulated data in the settlement time and the experimental results were concurrent with a variation of ±2%.
6. Conclusions
This investigation aims to present a proposal for automatic control in the SACS resulting from a black box analysis from which the tuning of the PID controller gain follows. This study has made it possible to advance in the operation of the system, improving the performance of the equipment operating without control, achieving, on average, cooling powers of 3.8 kW, external COP of 0.58, and −4.1 ° C evaporator cooling temperature at a desorber temperature of 86 °C and condenser temperature of 26 °C. Furthermore, shorter transient times are obtained, compared to the usual response of 3–5 min, as well as longer stand-alone stable times, which is desirable in this sort of cooling systems.
A theoretical model was developed to reproduce the theoretical behavior of an ideal cascade PID controller of the SACS, for the evaporation temperature variable, manipulating the variables of mass flow of weak solution (PID1) and mass flow of refrigerant (PID2), operating in parallel; this was validated with data from experimental tests. Obtaining an average difference between 8% for the solution case and 10% for the refrigerant case.
The transient response time to reach the steady state and the SP of the PID was 2 min for the weak solution flow and 5 min for the refrigerant flow. The temperature objective was reached in 11 min. Once the settling time had been reached, the coupled PID controllers maintained the conditions with a variation error of ±2% during the entire operating time of the system. The system fulfilled what was expected, so it is concluded that it is a viable technical and economic proposal for absorption systems of various capacities.