Next Article in Journal
Study on Intelligent Identification Method of Coal Pillar Stability in Fully Mechanized Caving Face of Thick Coal Seam
Previous Article in Journal
A Charge Possibility of an Unfueled Prechamber and Its Fluctuating Phenomenon for the Spark Ignited Engine
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Propagation of Overvoltages in the Form of Impulse, Chopped and Oscillating Waveforms in Transformer Windings—Time and Frequency Domain Approach

Department of Electrical and Power Engineering, AGH University of Science and Technology, al. Mickiewicza 30, 30-059 Kraków, Poland
*
Author to whom correspondence should be addressed.
Energies 2020, 13(2), 304; https://doi.org/10.3390/en13020304
Submission received: 26 November 2019 / Revised: 2 January 2020 / Accepted: 5 January 2020 / Published: 8 January 2020
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
This paper describes a comparison of overvoltage propagation in transformer windings. Expanding and evolving electrical networks comprise various classes of transient waveforms, related to network reconfigurations, failure stages and switching phenomena, including new sources based on power electronics devices. In particular, the integration of renewable energy sources—mainly solar and wind—as well as expanding charging and energy storage infrastructure for electric cars in smart cities results in network flexibility manifested by switching phenomena and transients propagation, both impulse and oscillating. Those external transients, having a magnitude below the applied protection level may have still a considerable effect on winding electrical insulation in transformers, mainly due to internal resonance phenomena, which have been the root cause of many transformer failures. Such cases might occur if the frequency content of the incoming waveform matches the resonance zones of the winding frequency characteristic. Due to this coincidence, the measurements were performed both in time and frequency domain, applying various classes of transients, representing impulse, chopped (time to chopping from 1 µs to 50 µs) and oscillating overvoltages. An additional novelty was a superposition of a full lighting impulse with an oscillating component in the form of a modulated wavelet. The comparison of propagation of those waveforms along the winding length as well as a transfer case between high and low voltage windings were analyzed. The presented mapping of overvoltage prone zones along the winding length can contribute to transformer design optimization, development of novel diagnostic methodology, improved protection concepts and the proper design of modern networks.

Graphical Abstract

1. Introduction

Reliability of electric power systems, on both transmission and distribution levels, is an actual research topic [1,2,3,4,5,6,7,8,9,10,11,12]. Transformers play a crucial role in electrical networks and belong to the class of equipment which is not quickly replaceable. The subject of the presented research is the propagation of overvoltages in the form of impulse, chopped and oscillating waveforms in transformer windings, considered both in the time and frequency domain. The experiments were performed on a distribution transformer exposed during normal operational conditions to several surge stresses in the form of full and chopped lightning as well as switching phenomena. On the other hand, the integration of renewable energy sources, such as solar and wind, and expanding charging and energy storage infrastructure for electric cars results in network reconfiguration and the immanently related propagation of transients, both impulse and oscillating, originating in power electronics devices.
Hence, transformers are subjected to the non-standardized fast transients such as resonant oscillations, which may lead to the dangerous amplification of overvoltages inside the windings [3,13]. Proper transformer grounding should also be not neglected, which in case of lightning, may result in a higher total impedance and can lead to higher transformer terminal voltages than those computed by ideal grounding [14].
The frequency domain view allowed for the determination of the bands in the spectrum prone to resonances. If the incoming transient has a frequency content related to the resonance frequency zone, then the overvoltage amplification inside a winding might occur. Such cases are analyzed in the paper for various classes of the waveforms. The amplification or attenuation of overvoltages are analyzed along the transformer winding and also from the high voltage (HV) winding to low voltage (LV) side transfer perspective. Such tests of voltage exposure and overvoltage propagation allow a check of transformer immunity and are related to both distribution and power units. In the case of power transformers, standards [15,16,17,18,19] also require compliance with tests based on tail chopped lightning impulse. This kind of extended testing is recommended in configurations where the transformer is protected by a spark-gap or is operating in connection to a gas insulated substation. Power transformer units for a grid above 170 kV are checked routinely applying chopped lightning impulse, usually with a time delay to chopping in the range 3 µs and 10 µs [15,16,20]. Presented measurements were conducted both for a full impulse and chopped one, with the time delay to chopping from 1 µs up to 50 µs.
Another class of transient stresses is addressed by a rectangular impulse with a variable rise time, reflecting the behavior of power equipment in response to protection devices such as surge arresters. Above tests are complemented by a superimposed configuration of waveform composed of a full lighting impulse with an oscillating component, named a modulated wavelet. Such a waveform might mimic, for example, the oscillating packet appearing at the transformer terminals, propagated by the re-strikes in circuit breakers. According to the design principles, the peak values of transient overvoltages at transformer clamps are constrained by the installed protective devices to the level suggested by the insulation coordination [1,7,21,22]. Those values are much higher than the maximum nominal voltage, thus the incoming transient containing the oscillating component below the protection level may form overvoltages inside the insulation system of high voltage equipment caused by internal resonance in the windings despite the applied surge arresters. Particularly some switching transients, generated in gas insulated substations, during power making or breaking in lines supplying the transformers, ground faults or network reconfigurations, including those originated form power electronics, having oscillating character may cause high amplitude internal overvoltages. The amplitude of the overvoltage depends on the network topology, attenuation conditions and duration of the oscillating components. Transformer windings form a complex distributed resistive-inductive-capacitive (RLC) network, reflecting various internal resonances. Hence, the internal overvoltages recorded along the winding height may vary from the proportionally attenuated incoming external transients [3,23,24,25,26,27]. For this reason, study on internal transient waveforms in transformers, subjected to standard and non-standard excitations, including superimposed waveforms containing oscillating components, are important for the development of more reliable transformers.
In this context, the mapping of overvoltage prone zones along the winding length can contribute to the development of proper diagnostic methodology, improved protection concepts and the proper design of modern networks.

2. Characteristic of Voltage Waveforms Applied to Transformer Winding

In order to achieve a holistic view of test transformer response to various overvoltages, the following voltage stimulus, graphically illustrated in Table 1, have been applied:
(a)
full lighting impulse,
(b)
chopped lighting impulse,
(c)
rectangular impulse with a variable risetime,
(d)
modulated wavelet, i.e., superposition of a full lighting impulse with an oscillating component.
Special attention was paid to the propagation of those overvoltages along the high and low voltage windings as well as to the inter winding transfer case, while applying the stimulus between the winding terminal and ground.
The lightning impulse waveform Ul can be described by the following double exponential function:
U l ( t ) = U 1 [ exp ( t / τ 1 ) exp ( t / τ 2 ) ]                                                    
where τ1 and τ2 define a time constant and U1 the magnitude. For example, in high voltage testing, for the standard lightning impulse 1.2/50 µs the time constants correspond to τ1 = 0.405 µs and τ2 = 68.2 µs.
In order to design the chopped impulse Ucl (Figure 1a), the inverted and shifted lightning waveform U-ls is add (Figure 1b):
U l s ( t ) = U 2 { exp [ ( t T c ) τ 3 ] exp [ ( t T c ) τ 4 ] } for   t T c U l s ( t ) =   0 for   t < T c
Delay of chopping Tc can be tuned in a broad range—in the presented paper, up to 50 µs. In this way, a chopped lightning impulse on the front and on the tail is created. The collapse time tc is assumed to be about 0.1 µs. Thus, the chopped lightning impulse on the tail Ucl_tail, shown in Figure 1a, can be by described by equation:
U c l _ t a i l ( t ) = U l ( t ) + U l s ( t )
To design the impulse chopped on the front before reaching the prospective peak, the additional waveform Uh (Figure 1d) is needed, described by the following equation:
U h ( t ) = U 3 { exp [ ( t T c t c ) τ 5 ] exp [ ( t T c t c ) τ 6 ] } for   t T c + t c U h ( t ) = 0 for   t < T c + t c
Hence, for chopped lightning impulse on the front Ucl_front, the superposition of full lightning impulse Ul, inverted and shifted one U-ls and additional waveform Uh is performed, as presented in Figure 1c,d and given by the expression:
U c l _ f r o n t ( t ) = U l ( t ) + U l s ( t )   +   U h ( t )
When decaying oscillations Udh follow the impulse fall at the chopping point, at a time moment t = Tc + tc, the corresponding waveform component may be represented by the following expression:
U d h ( t ) = U 4 { exp [ ( t T c t c ) τ ] sin [ ω ( t T c t c ) ] } for   t T c + t c U d h ( t ) = 0 for   t < T c + t c
where U4, τα and ω are, respectively, the values of the magnitude, damping time constant and oscillation frequency.
To illustrate and to quantify the spectral density of full and chopped lightning impulses, the frequency analysis was performed (Figure 2), using the above presented methodology. It was based on two time-shifted pulses having inverted polarity to achieve voltage waveform with desired front time and delayed chopping moment.
The chopping time significantly influences the spectral content compared with the full lightning impulse voltage, i.e., the shorter the time to chopping, the spectrum is broader but simultaneously the energy spectral density lower. This effect might have a significant implication in the case of internal transients occurring along windings lengths, while performing chopped and full lightning probe.
Another applied waveform was a rectangular impulse with a variable risetime tr calculated between 10% and 90% of voltage slope magnitude U5. In the presented model, a rectangular impulse rise time is initiated at time t0 and lasts until time moment t1 with a slope β. Such a waveform can be described by the following expression:
U r ( t ) = {       0           β t           U 5 f o r     t < t 0                     f o r     t > t 0   a n d     t < t 1 f o r       t > t 1    
The last case of a stimulus waveform Ulw presented in this paper refers to the superposition of a full lighting impulse Ul with oscillating component Uw, appearing at time moment tw1 and lasting until tw2. Such a waveform with superimposed wavelet can be represented by expression:
U l w ( t ) = U l + U w = U l + U 6 exp ( ( t t w 1 ) 2 / τ w ) sin [ ω w ( t t w 1 ) ] for   t w 1   <   t   <   t w 2 U l w ( t ) = U l for   t < t w 1 and   t > t w 2
where τw and ωw are the width and frequency of the oscillating packet.

3. Measurement Setup and Test Object

The measurement on transformer windings were performed, both in time and frequency domain, in a setup presented in Figure 3. The lightning voltage pulses were generated by a lightning stroke unit with maximum amplitude 300 V. The test waveforms with oscillating component as well as the measurements in frequency domain from 20 Hz to 2 MHz were performed using programmable function generator Tektronix type AFG310 with maximum output voltage 20 V. It is important to notice that the magnitude of the generated voltage waveforms used in experiments does not have a practical impact on measurement results. The influence of the ferromagnetic transformer core in the analysis of transients is often a subject of discussion. The contentious issue concerns the cutoff frequency of transformer core impact. Usually, referring to the investigations done by Wilcox [28], in a frequency range above several dozens of kHz, the impact of the core is neglected. Hence, in this high frequency band, the windings can be treated as linear objects and the magnitudes of applied voltage stimuli do not influence the measurements. For the acquisition of the overvoltage waveforms, an oscilloscope Tektronix model 784D was used as in the configuration shown in Figure 3a. The frequency characteristics of the windings were obtained in the computer controlled configuration. The generator was programmed to yield the sweep in predefined frequency range (up to 2 MHz) and the corresponding response was acquired by an oscilloscope. Both the programmable function generator and the scope acting as a recorder were linked with a control computer by GPIB-USB. The control and analysis software was developed in LabView™ environment from National Instruments [3,10,26,29].
All experiments presented in this paper were performed on the test transformer 20 kVA 15/0.4 kV. The rated and design parameters of the experimental unit are shown in Table 2. This kind of distribution transformer was selected on purpose to test a variety of overvoltage waveforms. Such a unit can be subjected to both full lightning and chopped lightning stroke as well as to transients containing a superimposed oscillating component due to switching operations in the network. The system reconfigurations will occur increasingly frequently in the grid as a result of connected renewable generation and expanding charging and energy storage infrastructure for e-mobility.
The research was focused on the analysis of overvoltages occurring inside transformer high and low voltage windings as well as transferred from HV to LV side. The ground overvoltages were measured along the HV winding, at tap x/l denoted as follows: x/l = 0 (corresponds to the clamp of the phase L1), x/l = 0.2, x/l = 0.3, x/l = 0.7), applying various stimuli waveforms from the terminal side. The access to the internal winding structure was possible through additional taps installed inside in the winding. Due to the paper limitations, certain characteristic tap positions were selected to the visualization of the voltage distributions along the windings. For evaluation purposes, both the frequency and time relationships ko of internal overvoltages in the transformer winding are calculated using following expression:
k o = u x / l u 0 - m a x
where:
  • ux/l—measurement at tap x/l along the winding,
  • u0-max—magnitude of external stimulus applied at winding clamps (tap x/l = 0 and x/l = 1.0).
The distributions of maximum internal winding overvoltages ko-max is obtained according to the relationship:
k o - m a x = u x / l ¯ m a x u 0 - m a x
where:
  • ux/l—maximum value obtained for measurement at tap x/l along the winding,
  • u0-max—highest magnitude of external stimulus applied at winding clamps (tap x/l = 0 and x/l = 1.0).

4. Overvoltages in Frequency Domain

Determination of the winding broadband characteristics in a frequency domain allows the determination of sensitive zones and resonance frequencies [3,10,12,29]. It is well suited for analysis of the response of a transformer winding to an excitation in form of an oscillating packet of overvoltage occurring in an electrical network. The normalized frequency characteristics of overvoltages along the windings are presented in Figure 4. Depending on the excitation spectral content match with these characteristics, the stress on electrical insulation systems is obtained. From the plot one can notice characteristic frequencies, for which sinusoidal excitations are strongly amplified inside the winding. Those frequencies may fit with spectrum of incoming external overvoltages. For example (Figure 4), the overvoltage ratio in case of HV winding at frequency 12 kHz equals to 3.4 p.u. Analysis confirms, that excitation waveforms having oscillating wavelet may undergo amplification inside transformer winding because of resonance phenomena, especially if the frequencies of the applied voltage are matching the self frequencies of the transformer winding.
From the frequency characteristics of overvoltages in HV and LV experimental transformer windings (Figure 4), one can notice, that sinusoidal voltages at resonance frequencies propagated in transformer undergo amplification inside the windings. For example, in HV windings oscillating overvoltages reach maximum for following frequencies 0.65 kHz, 13.1 kHz, 36.7 kHz and 51 kHz and in LV windings for frequencies: 0.64 kHz, 8.7 kHz, 107 kHz and 0.85 MHz. If the resonant frequencies of the transformer is larger, then the probability of multiplication of internal overvoltages in transformers is greater. It was also observed that maximal values of oscillating overvoltages in windings occurs, practically for the same frequencies, for all phases.
In turn, an interesting case is a transfer characteristic i.e., stimuli on HV winding side and response measured at LV winding, as presented in Figure 5. Illustration of the HV to LV transfer characteristic of overvoltages for injecting the signal at HV terminal of phase A and recording response at LV winding phase “a” is shown in Figure 5a, while an analogous case reflecting HV-LV winding phase C-c is shown in Figure 5b.

5. Propagation of Different Waveforms in Transformer Windings in Time Domain

Overvoltages recorded in various parts of a transformer winding in response to different stimuli waveforms are presented in this section.

5.1. Full Lightning Voltage Impulse

Overvoltages measured between selected points x/l of both HV and LV winding and ground during the full lightning impulse u0(t) are presented in Figure 6a, whereas the corresponding differences of inter taps ratios are shown in Figure 6b. The magnitude of the waveform is normalized with respect to maximal value of the full lightning impulse according to formula (9). The response shapes of internal overvoltages are different comparing to the excitation applied at the external transformer clamps of one phase. For example, taking the tap at x/l = 0.3 in the HV winding, one can recalculate the magnitude of corresponding lightning impulse, which results in 1.04 p.u, and exceeds the impulse peak value.

5.2. Chopped Lightning Voltage Impulse

Overvoltages recorded in HV winding of 20 kVA transformer, excited by a lightning voltage impulse, were performed in a broad chopping time delay scope. The lightning impulse was chopped after time tu from 1 µs up to 50 µs. The waveforms measured at selected taps x/l in a HV winding in response to the tail chopped lightning voltage impulse, with various chopping time delays: 2 µs, 5 µs, and 10 µs, are shown in Figure 7A and corresponding overvoltage differences in Figure 7B. The maximal values of chopped overvoltages obtained in transformer at selected taps x/l depend on time delay to chopping tu. Increased time tu leads to amplification of inter-winding overvoltages. Thus, time delay tu has large influence on longitudinal overvoltage enhancement. In can be highlighted especially in a winding region being in a proximity to the transformer terminals.
The above measurements lead to the plot shown in Figure 8 representing overvoltages ko-max = f(x/l) between selected points and ground as well as gradients of overvoltages in HV winding of transformer excited by both full and chopped lightning voltage impulse employing time delay tu in the range from 1 µs up to 50 µs.
The chopped voltage impulse applied to the transformer winding results according to Figure 8b in the enhanced gradients, stressing the winding electrical insulation system, especially in a proximity to the transformer clamps [6,7].

5.3. Rectangular Voltage Impulse

In this part, transients measured in the transformer winding, excited by a rectangular impulse applied at HV clamp (tap x/l = 0 and x/l = 1.0) are presented in Figure 9.
Overvoltages generated inside the windings contain oscillatory components with a resonance frequency equal to 13.1 kHz. The magnitude manifests great variability, i.e., overvoltages measured at tap x/l = 0.3 along the winding are roughly 1.3 amplified comparing to the impulse crest value at the transformer clamp. Due to the relatively low self frequencies of HV windings, overvoltages are not sensitive to the rise time of the applied impulse, ranging from 10 ns to several hundred of nanoseconds. In turn, overvoltages generated inside the LV transformer windings in response to the rectangular voltage impulse strongly depend on rise time (Figure 10). It is possible to notice, for example, the overvoltage coefficient kiLV for voltage U0.5c in the LV winding of phase “c” for a rise time of 10 ns is about 3.3 but for a rise time 100 ns is about 1.6. The overvoltage coefficient kiLV of transient voltage Ua at the terminal of phase “a” for rise time 10 ns reach about 1.95 but for rise time of 100 ns is equal only to 0.7.

5.4. Lightning Voltage Impulse with Superimposed Oscilating Wavelet

Another class of stimulus is created by superimposed waveforms. Such an approach allows analysis of the internal overvoltages generated in the transformer winding, which result from the resonance phenomenon at impulse voltage with superimposed oscillating component, in the form of a wavelet. Thus the resultant waveform contains an aperiodic part as a lightning voltage surge and an oscillating wavelet. The oscillating frequency of the wavelet has been adjusted to the winding resonance frequencies obtained from frequency characteristics presented in Figure 4. An exemplary case of HV winding response to a lightning voltage impulse with superimposed oscillating wavelet tuned to 8.3 kHz, 13.1 kHz and 108 kHz is shown in Figure 11. One may notice the amplification of the oscillating components related to winding resonance frequencies (8.3 kHz and 13.1 kHz) inside the winding. Simultaneously overvoltages in HV windings have greater values than those generated during action just of the lightning impulse. However, overvoltages shown in Figure 11c, excited by the lightning impulse containing oscillating component with frequency 108 kHz are not amplified in the LV winding. The wavelet frequency in this case is not matching the sharp winding resonance peak at 107 kHz.
Similar measurement have been performed on LV winding, adjusting the wavelet frequency to the resonances in frequency characteristic (Figure 4), i.e., 107 kHz, 0.85 MHz. The results presented in Figure 12 also indicated strong amplification of the oscillating overvoltages in LV windings, for example in the case of frequency 0.85 MHz, the overvoltage coefficient for voltage U0.5c is equal to 3.4 and for voltage Ua is about 1.5. Analyzing the de-tuned case, overvoltages generated in HV winding excited by the lightning impulse containing oscillating wavelet having frequency 14.6 kHz (Figure 12c) are significantly smaller than for cases of resonance frequencies.

6. Assessment of Overvoltages in Transformer Windings

The various applied excitation have different frequency ranges, both narrow- and broad-band. Thus observed transient overvoltages manifest different responses, applying testing voltages and waveforms, which might occur during transformer operation in a network. As a reference of transformer testing, the full lightning impulse was accepted. Power grid transients were reflected by switching and oscillating waveforms. Both cases revealed relevant distinctions of maximum overvoltages along the winding. As an assessment factor the Time Domain Severity Factor (TDSF) was used. The TDSF is evaluated according to the following expression [21,22]:
T D S F = U x / l   m a x U x / l   m a x t e s t
where:
  • Ux/lmax—highest magnitude of overvoltages occurring at tap x/l during network operation,
  • Ux/lmax test—highest magnitude of overvoltages occurring at tap x/l excited by reference voltage impulse.
The TDSF obtained for the experimental transformer was evaluated taking the maximum values of overvoltages yielded by testing with the standard full lightning impulse with crest value Utest = 95 kV [15]. The protection of the unit in a grid operation was considered, assuming two models of surge arresters, having different tripping and time to disconnection parameters. In the first case, the transformer has been protected by a surge arrester model SA1 rated for continuous voltage Uc = 12 kV, whereas the latter one is protected by model SA2 working at Uc = 18 kV. Both surge arresters are applied in the distinctive network operating modes, i.e., SA1 in 15 kV topologies with automatic disconnection of short circuits current to ground, whilst the model SA2 refers to the networks without automatic ground fault clearing [21,22,30]. The rated surge arrester parameters are following: for SA1 lightning protection level is Ulp = 42 kV and switching one is Usp = 31.1 kV and for SA2 respectively Ulp = 63 kV and Usp = 46.7 kV [30]. The dependencies, of the assessment factor TDSF = f(x/l) for HV winding of experimental transformer rated 20 kVA 15/0.4 kV, were calculated and are illustrated in Figure 13.
The tabular summary of results of maximum overvoltages obtained for test transformer exposed to various stresses is presented in Table 3. One can notice, that overvoltages recorded at internal winding taps of transformer, in certain waveform cases, surpass magnitudes obtained at standard lightning voltage impulse tests. Maximum internal overvoltages are recorded for a sinusoidal oscillating component with the frequency matching the resonant frequency of transformer. For example, at the winding tap x/l = 0.7, the response to excitation of 95 kV standard lightning voltage impulse test equals to 84.6 kV.
A comparison of both cases of installed protective devices SA1 and SA2 provide quantitative illustration of transient overvoltage effects. In the case of a network equipped with SA1, with an automatic restoration after ground fault occurrence and transient excitation in the form the wavelet having the oscillating frequency 13.1 kHz (matching one of the transformer winding resonance frequencies), the measured overvoltage at the same tap was 102.6 kV. While for the experimental transformer connected to a network without automatic restoration after a ground fault occurrence, protected with SA2 device, the overvoltage at tap x/l = 0.7, in the response to excitation containing the same wavelet with transformer resonant frequency, is equal to 154.1 kV. Such an analysis reflects the transformer winding sensitive zones with respect to waveform frequency content. As an extension of the presented work, further investigations on transformers with different winding topologies and voltage levels are planned. Such an approach could lead to scalable and more general methodology for assessment of overvoltages representing impulse, chopped and oscillating waveforms.

7. Conclusions

This paper reports about propagation of various waveforms of overvoltages inside transformer winding stressing the electric insulation system. Especially highlighted are overvoltage exposures in response to a lightning voltage impulse, rectangular one and impulse containing sinusoidal oscillating component. The experiments were performed on a distribution transformer, which can be subjected in real operating conditions to such stresses in an electric network. The transformer insulation between windings and ground is exposed to the largest maximal of overvoltages during the tests with full lightning voltage impulses. The application of chopped lightning impulses, with a variable delay time to chopping does not increase the recorded transients. However, chopped lightning voltage impulses result in an enhancement of the overvoltage gradients in the electrical insulation, especially localized close to the transformer clamps. It was observed that excitation with the lightning voltage impulses chopped on tail, with a delay time above 6 µs, does not cause an increase of overvoltage impact in experimental winding. It was noticed that attention should be paid to overvoltages containing oscillating component, especially those having the frequency close to one of the winding resonance frequencies. Knowledge of these effects broadens the knowledge about transformer immunity tests and recommendations for new designs, resistant to new classes of transients and overvoltages occurring in resilient power grid.

Author Contributions

All authors cooperated fully and equally at all stages of the presented research and during the preparation of the article. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Joint Working Group A2/C4.39-CIGRE. Electrical Transient Interaction between Transformers and the Power System (Part 1-Expertise, Part 2: Case Studies); CIGRE: Paris, France, 2014. [Google Scholar]
  2. Massaro, U.; Antunes, R. Electrical transient interaction between transformers and power system–Brazilian experience. In International Conference on Power Systems Transients (IPST2009); Publisher: Kyoto, Japan, 2009; pp. 1–6. [Google Scholar]
  3. Florkowski, M.; Furgał, J. High Frequency Methods for Condition Assessment of Transformers and Electrical Machines; Publishing House AGH: Kraków, Poland, 2013; ISBN 978-83-7464-614-7. [Google Scholar]
  4. Rocha, C.A.O. Electrical Transient Interaction between Transformers and the Power System; CIGRE-Brazil Joint Working Group JWG–A2/C4-03: Paris, France, 2008; pp. 1–6. [Google Scholar]
  5. Hori, M.; Nishioka, M.; Ikeda, Y.; Naguchi, K.; Kajimura, K.; Motoyama, H.; Kawamura, T. Internal winding failure due to resonance overvoltages in distribution transformer caused by winter lightning. IEEE Trans. Power Deliv. 2006, 23, 1600–1606. [Google Scholar]
  6. Lapworth, J.A.; Wilson, A. Transformer internal overvoltages caused by remote energization. In Proceedings of the 2007 IEEE Power Engineering Society Conference and Exposition in Africa-PowerAfrica, Johannesburg, South Africa, 16–20 July 2007; pp. 1–6. [Google Scholar]
  7. Furgał, J. Analysis of overvoltages in windings of power transformers protected by use of metal oxide surge arresters. Eur. Trans. Electr. Power Eng. 2009, 19, 400–410. [Google Scholar] [CrossRef]
  8. Shipp, D.D.; Dionise, T.J.; Lorch, V.; MacFarlane, B.G. Transformer failure due to circuit-breaker-induced switching transients. IEEE Trans. Ind. Appl. 2011, 47, 707–718. [Google Scholar] [CrossRef]
  9. Holdyk, A.; Gustavsen, B. External and internal overvoltages in a 100 MVA transformer during high-frequency transients. In Proceedings of the International Conference on Power System Transmission (IPST), Cavtat, Croatia, 15–18 June 2015; pp. 1–6. [Google Scholar]
  10. Florkowski, M.; Furgał, J.; Kuniewski, M.; Pająk, P. Comparison of transformer winding responses to standard lightning impulses and operational overvoltages. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 965–974. [Google Scholar] [CrossRef]
  11. Srikanta Murthy, A.; Azis, N.; Mohd Yousof, M.F.; Jasni, J.; Othman, M.L.; Talib, M.A.; Das, B.P. Investigation on the Resonant Oscillations in an 11 kV Distribution Transformer under Standard and Chopped Lightning Impulse Overvoltages with Different Shield Placement Configurations. Energies 2019, 12, 1466. [Google Scholar] [CrossRef] [Green Version]
  12. Zhang, Z.; Gao, W.; Kari, T.; Lin, H. Identification of Power Transformer Winding Fault Types by a Hierarchical Dimension Reduction Classifier. Energies 2018, 11, 2434. [Google Scholar] [CrossRef] [Green Version]
  13. Popov, M. General Approach for accurate resonance analysis in the transformer. Electr. Power Syst. Res. 2018, 161, 45–61. [Google Scholar] [CrossRef]
  14. Popov, M.; Grcev, L.; Hoidalen, H.K.; Gustavsen, B.; Terzija, V. Investigation of the Overvoltage and Fast Transient Phenomena on Transformer Terminals by Taking into Account the Grounding Effects. IEEE Trans. Ind. Appl. 2015, 51, 5218–5227. [Google Scholar] [CrossRef]
  15. IEC 60076-3 Power Transformers–Part 3: Insulation Levels. Dielectric Tests and External Clearances in Air. Available online: https://webstore.iec.ch/publication/62880 (accessed on 8 November 2019).
  16. IEEE C57.98 Guide for Transformer Impulse Tests. IEEE Power Energy Soc. 2012. [CrossRef]
  17. Neto, E.T.W.; Lopes, G.P.; Martinez, M.L.B.; Salles, C. Chopped impulses for distribution transformers their importance for dimensioning and performance evaluation. In Proceedings of the 2014 International Conference on Lightning Protection (ICLP), Shanghai, China, 11–18 October 2014; pp. 473–478. [Google Scholar]
  18. Bhuyan, K.; Chatterjee, S. Electric stresses on transformer winding insulation under standard and non-standard impulse voltages. Electr. Power Syst. Res. 2015, 123, 40–47. [Google Scholar] [CrossRef]
  19. Florkowski, M.; Furgał, J.; Kuniewski, M. Propagation of overvoltages transferred through distribution transformers in electric networks. IET Gen. Trans. Distr. 2016, 10, 2531–2537. [Google Scholar] [CrossRef]
  20. Munshi, S.; Roy, C.K.; Biswas, J.R. Computer studies of the performance of transformer windings against chopped impulse voltages. IEE Proc. C 1992, 139, 286–294. [Google Scholar] [CrossRef]
  21. Standard EN 60071-1 Coordination of Insulation. Definitions, Principles and Rules. Available online: https://webstore.iec.ch/publication/65606 (accessed on 8 November 2019).
  22. Standard EN 60099-5 Surge Arresters. Recommendation of Selection and Use. Available online: https://webstore.iec.ch/publication/736 (accessed on 8 November 2019).
  23. Lopez-Fernandez, X.M.; Álvarez-Mariño, C. Induced transient voltage performance between transformers and VCB-severity factors and case studies. IEEE Trans. Power Deliv. 2015, 30, 1137–1144. [Google Scholar] [CrossRef]
  24. Florkowski, M.; Furgał, J.; Kuniewski, M.; Pająk, P. Investigations of transformer winding response to standard full and chopped lightning impulses. In Proceedings of the 2018 IEEE International Conference on High Voltage Engineering and Application (ICHVE), Athens, Greece, 10–13 September 2018. [Google Scholar]
  25. Rodrigues, R.B.; Mendes, V.M.F.; Catalão, J.P.S. Analysis of Transient Phenomena Due to a Direct Lightning Strike on a Wind Energy System. Energies 2012, 5, 2545–2558. [Google Scholar] [CrossRef] [Green Version]
  26. Florkowski, M.; Furgał, J.; Kuniewski, M.; Pająk, P. Propagation of lightning, oscillating and non-standard impulse waveforms in transformer windings. In The International Symposium on High Voltage Engineering; Springer: Cham, Switzerland, 2019. [Google Scholar]
  27. Xu, B.; Li, Y.; Zhao, J.; Wang, X.; Zhang, R. Simulation of propagation characteristic of ultra high frequency signals in power transformers using finite difference time domain method. In Proceedings of the 2015 5th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), Changsha, China, 26–29 November 2015; pp. 1591–1594. [Google Scholar]
  28. Wilcox, D.J.; Conlon, M.; Hurley, W.G. Calculation of self and mutual impedances for coils in ferromagnetic cores. IEE Proc. 1988, 135, 470–476. [Google Scholar] [CrossRef]
  29. Yang, Q.; Su, P.; Chen, Y. Comparison of Impulse Wave and Sweep Frequency Response Analysis Methods for Diagnosis of Transformer Winding Faults. Energies 2017, 10, 431. [Google Scholar] [CrossRef]
  30. Metal Oxide Surge Arresters Type POLIM-D, ABB Power Distribution. Available online: https://new.abb.com/high-voltage/surge-arresters/medium-voltage-arresters/distribution-systems/polim-d (accessed on 8 November 2019).
Figure 1. Illustrative formation of chopped impulse: (a) tail chopped impulse, (b) composition of component pulses for tail chopped impulse, (c) front chopped impulse, (d) composition of component pulses for front chopped impulse.
Figure 1. Illustrative formation of chopped impulse: (a) tail chopped impulse, (b) composition of component pulses for tail chopped impulse, (c) front chopped impulse, (d) composition of component pulses for front chopped impulse.
Energies 13 00304 g001
Figure 2. Spectral content of chopped and full lightning impulse (FLI). Delay time to chopping respectively: (1) 0.8 µs, (2) 2 µs, (3) 2 µs, (4) 6 µs, (5) 10 µs, (6) 20 µs, (7) FLI.
Figure 2. Spectral content of chopped and full lightning impulse (FLI). Delay time to chopping respectively: (1) 0.8 µs, (2) 2 µs, (3) 2 µs, (4) 6 µs, (5) 10 µs, (6) 20 µs, (7) FLI.
Energies 13 00304 g002
Figure 3. Measurement setup: (a) time domain measurements of overvoltages along transformer windings, (b) frequency domain and combined waveform measurements.
Figure 3. Measurement setup: (a) time domain measurements of overvoltages along transformer windings, (b) frequency domain and combined waveform measurements.
Energies 13 00304 g003
Figure 4. Frequency characteristic of terminal overvoltages and for point in half of windings and ground: (a)—HV windings, (b)—LV windings.
Figure 4. Frequency characteristic of terminal overvoltages and for point in half of windings and ground: (a)—HV windings, (b)—LV windings.
Energies 13 00304 g004
Figure 5. Transfer frequency characteristic of overvoltages at winding terminal (x = 1.00) and for point in half of windings and ground (x = 0.50): (a) injection HV windings phase A, response LV winding phase “a”, (b) injection HV winding phase C, response LV winding phase “c”.
Figure 5. Transfer frequency characteristic of overvoltages at winding terminal (x = 1.00) and for point in half of windings and ground (x = 0.50): (a) injection HV windings phase A, response LV winding phase “a”, (b) injection HV winding phase C, response LV winding phase “c”.
Energies 13 00304 g005
Figure 6. Measurement of overvoltages at tap x/l in (a) HV winding: (1) x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7 and (b) corresponding overvoltage differences: 1—u 0-0.2, 2—u 0.2-0.3, 3—u 0.3-0.7.
Figure 6. Measurement of overvoltages at tap x/l in (a) HV winding: (1) x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7 and (b) corresponding overvoltage differences: 1—u 0-0.2, 2—u 0.2-0.3, 3—u 0.3-0.7.
Energies 13 00304 g006
Figure 7. Measurement of overvoltages applying tail chopped lightning impulse (A) in HV winding at tap (1) x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7 and (B) corresponding overvoltage differences: (1) u 0-0.2, (2) u 0.2-0.3, (3) u 0.3-0.7. Time delay to chopping tu: (a) 2 µs, (b) 5 µs, (c) 10 µs.
Figure 7. Measurement of overvoltages applying tail chopped lightning impulse (A) in HV winding at tap (1) x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7 and (B) corresponding overvoltage differences: (1) u 0-0.2, (2) u 0.2-0.3, (3) u 0.3-0.7. Time delay to chopping tu: (a) 2 µs, (b) 5 µs, (c) 10 µs.
Energies 13 00304 g007
Figure 8. (a) Maximal values of overvoltages and (b) overvoltage gradient for full (FLI) and chopped lightning impulse, with time to chopping: (1) 1 µs, (2) 2 µs, (3) 4 µs, (4) 6 µs, (5) 10 µs, (6) 20 µs, (7) 30 µs, (8) 50 µs, (9) FLI.
Figure 8. (a) Maximal values of overvoltages and (b) overvoltage gradient for full (FLI) and chopped lightning impulse, with time to chopping: (1) 1 µs, (2) 2 µs, (3) 4 µs, (4) 6 µs, (5) 10 µs, (6) 20 µs, (7) 30 µs, (8) 50 µs, (9) FLI.
Energies 13 00304 g008
Figure 9. Overvoltages excited by rectangular impulse in the HV winding at tap: (1) x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7.
Figure 9. Overvoltages excited by rectangular impulse in the HV winding at tap: (1) x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7.
Energies 13 00304 g009
Figure 10. Overvoltages measured in transformer LV windings in response. to rectangular voltage impulse with different rise times: (a) 10 ns, (b) 100 ns.
Figure 10. Overvoltages measured in transformer LV windings in response. to rectangular voltage impulse with different rise times: (a) 10 ns, (b) 100 ns.
Energies 13 00304 g010
Figure 11. Response of the HV windings to lightning impulse containing oscillating components with frequency: (a) 8.3 kHz, (b) 13.1 kHz, (c) 108 kHz.
Figure 11. Response of the HV windings to lightning impulse containing oscillating components with frequency: (a) 8.3 kHz, (b) 13.1 kHz, (c) 108 kHz.
Energies 13 00304 g011
Figure 12. Response of the LV windings to lightning impulse containing oscillating wavelet. with frequency: (a) 107 kHz, (b) 0.85 MHz (c) 14.6 kHz.
Figure 12. Response of the LV windings to lightning impulse containing oscillating wavelet. with frequency: (a) 107 kHz, (b) 0.85 MHz (c) 14.6 kHz.
Energies 13 00304 g012
Figure 13. Assessment factor TDSF = f(x/l) for HV winding excited by standard full lightning impulse Utest = 95 kV of experimental transformer protected by two models of surge arresters: (a) Uc = 12 kV (SA1), (b) Uc = 18 kV (SA2); 1—standard full lightning impulse, 2—sinusoidal wavelet with resonance frequency 13.1 kHz, 3—rectangular impulse.
Figure 13. Assessment factor TDSF = f(x/l) for HV winding excited by standard full lightning impulse Utest = 95 kV of experimental transformer protected by two models of surge arresters: (a) Uc = 12 kV (SA1), (b) Uc = 18 kV (SA2); 1—standard full lightning impulse, 2—sinusoidal wavelet with resonance frequency 13.1 kHz, 3—rectangular impulse.
Energies 13 00304 g013
Table 1. Characteristic of voltage waveforms applied to transformer windings.
Table 1. Characteristic of voltage waveforms applied to transformer windings.
(a) Full lighting impulse
tf—Front time
tt—Time to half of wave tail
Energies 13 00304 i001
(b) Chopped lighting impulse
Tc—Time delay to chopping
tc—Collapse time
Energies 13 00304 i002
(c) Rectangular impulse with a variable risetime
t0—Initial time
t1—End of risetime
tr—Rise time
Energies 13 00304 i003
(d) Superposition of full lighting impulse with oscillating component
tf—Front time
tt—Time to half of wave tail
tw1, tw2—Initial and end time of oscillating packet
ωw—Frequency of oscillating packet
Energies 13 00304 i004
Table 2. Experimental transformer rated and design parameters.
Table 2. Experimental transformer rated and design parameters.
ParameterValue
Sr, (kVA)20
UrHV, (kV)15
UrLV, (kV)0.4
number of electrical phases3
Uz, (%)4.2
ΔPFe, (kW)0.11
ΔPk, (kW)0.53
I0, (%)2.8
number of turns in the coil810
number of coils4
winding height l, (mm)280
internal coil diameter do, (mm)157
externat coil diameter di, (mm)205
coil width h, (mm)25
Table 3. Comparison of an impact of various waveforms on overvoltages in transformer windings.
Table 3. Comparison of an impact of various waveforms on overvoltages in transformer windings.
Winding Position x/lReference Test OvervoltagesOvervoltages in Network Operation
Lightning Impulse 95 kVRectangular ImpulseSinusoidal Oscillating Component
duration: Tens of Microsecondsduration: Milliseconds
(kV)
Network with Automatic Fault Clearing (SA1 Uc = 12 kV)
095.042.031.1
0.1895.053.348.2
0.33102.659.278.4
0.6784.645.4102.6
Network without Automatic Fault Clearing (SA2 Uc = 18 kV)
095.0 63.046.7
0.1895.080.072.4
0.33102.688.8117.7
0.6784.668.0154.1

Share and Cite

MDPI and ACS Style

Florkowski, M.; Furgał, J.; Kuniewski, M. Propagation of Overvoltages in the Form of Impulse, Chopped and Oscillating Waveforms in Transformer Windings—Time and Frequency Domain Approach. Energies 2020, 13, 304. https://doi.org/10.3390/en13020304

AMA Style

Florkowski M, Furgał J, Kuniewski M. Propagation of Overvoltages in the Form of Impulse, Chopped and Oscillating Waveforms in Transformer Windings—Time and Frequency Domain Approach. Energies. 2020; 13(2):304. https://doi.org/10.3390/en13020304

Chicago/Turabian Style

Florkowski, Marek, Jakub Furgał, and Maciej Kuniewski. 2020. "Propagation of Overvoltages in the Form of Impulse, Chopped and Oscillating Waveforms in Transformer Windings—Time and Frequency Domain Approach" Energies 13, no. 2: 304. https://doi.org/10.3390/en13020304

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop