Next Article in Journal
The Recent Development of Artificial Intelligence for Smart and Sustainable Energy Systems and Applications
Next Article in Special Issue
Analytical Description of Overhead Transmission Lines Loadability
Previous Article in Journal
PV Micro-Inverter Topology Using LLC Resonant Converter
Previous Article in Special Issue
Influence of DC Electric Fields on Pollution of HVDC Composite Insulator Short Samples with Different Environmental Parameters
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

CALAJOULE: An Italian Research to Lessen Joule Power Losses in Overhead Lines by Means of Innovative Conductors

1
Department of Industrial Engineering, University of Padova, 35131 Padova, Italy
2
Nuova Elettromeccanica Sud (NES) s.p.a. Campo Calabro, 89052 Reggio Calabria, Italy
3
De Angeli Prodotti S.r.l. Bagnoli di Sopra, 35023 Padova, Italy
*
Author to whom correspondence should be addressed.
Energies 2019, 12(16), 3107; https://doi.org/10.3390/en12163107
Submission received: 15 July 2019 / Revised: 26 July 2019 / Accepted: 6 August 2019 / Published: 13 August 2019
(This article belongs to the Special Issue DC and AC Overhead Transmission Lines from Low to Extra-High Voltages)

Abstract

:
The ongoing evolution of the power system to implement climate action policies is resulting in a continuous increase in the penetration of renewables and the necessity of strengthening the transmission grid to optimize the usage of those sources and contain operation costs. Reinforcing the transmission lines or building new ones is a process that is made difficult due to authorization issues related with environmental and public acceptance concerns. Developing innovative conductors for overhead lines with enhanced performances with respect to the traditional ones would bring benefits in terms of energy efficiency increases in transmission and distribution grids without requiring the substitution of the existing towers. The project CALAJOULE (the genesis of the acronym comes from the union of the Italian verb “calare”-to decrease-to the third person singular, namely “cala” i.e., decreases, and of Joule, obvious reference to the active losses), cofinanced by the Italian Ministry of Economic Development in the framework of the “Ricerca di Sistema” program, aims at proposing innovative solutions for overhead line conductors for the containment of Joule power losses. In this paper, starting from the state-of-the-art of the currently adopted conductors, the main innovative solutions resulting from the project are presented and compared with the traditional ones to evaluate the achievable reduction in Joule losses.

Graphical Abstract

1. Introduction

In recent decades, the growth and economic development of some countries has resulted in a stimulus, and consequently an increase in consumption; among these is the increase in the demand for electricity. More recently, the climate action plans worldwide are demanding for an evolution of the electricity sector, in order to contain the emissions of greenhouse gas (GHG), improve the energy efficiency and increase the share of renewables in the electricity production. At the European level, the objectives set for 2020 are on the way to being fulfilled, with a GHG reduction of 22.4% compared to 1990 levels, along with 17% of final energy usage being covered by renewable sources [1]. With the release of the “clean energy for all Europeans” package in 2016, the EU parliament defined new objectives in the climate and energy framework for the period 2021 to 2030, which aims to continue the transition started in the previous period [2]. The introduction of the new objectives in energy efficiency improvement and renewables penetration is now leading to a revision of the network code and in the reform of the electricity markets [3], pursuing a better usage of electricity and higher flexibility. The above-mentioned climate action policies are resulting in an evolution of the generation park, with the gradual substitution of traditional fossil-fuelled power plants with a high number of smaller generators, the majority of which are connected to the distribution network. To accompany this change, it is of utmost importance to have a power system infrastructure capable of hosting the geographically displaced generation and the sudden changes in the power flows, containing the formation of bottlenecks, and improving the energy efficiency of the whole system. Along with innovative network management techniques [4], aiming at exploiting the presence of distributed generators and their participation to the ancillary services market [5], it will be necessary to upgrade the infrastructure of the electricity system as increasing shares of electricity production will shift from large power plants to small generators. As it is well known, active losses in electricity systems vary considerably depending on the voltage level. Typically, active losses ranging from 2% to 10% can be assumed, passing from transmission networks (high and extra-high voltage levels, HV and EHV, respectively) to distribution networks (medium and low voltage levels, MV and LV, respectively) [6,7,8,9]. For overhead lines (OHLs), the different Joule losses values are due to the r/x ratios (ratio between the resistance r and the reactance x of the positive sequence impedance) of the transmission lines being much lower than those of the distribution networks. The reduction of Joule losses in the power system, both at transmission and distribution levels, therefore, plays a key role in increasing energy efficiency, with obvious advantages for the power system both in economic terms and in terms of reducing carbon dioxide emission into the atmosphere. This framework is extremely large, given the large extension of the power supply system and the different peculiarities of the EHV-HV and MV-LV networks. The typical Italian levels of the EHV-HV network are 380-220-150-132 kV, always with neutral solidly connected to earth. The MV network is typically operating at 20 kV with neutral grounded through Petersen’s resonant coil [10], although some parts operate at 60 kV with neutral isolated [11], while the LV network (400 V) operates with neutral solidly grounded in the secondary substation.
Improving the power system capacity leads to either the construction of new power lines or the reinforcement of the existing ones. On the one hand, building new Overhead lines (OHLs) is a difficult process that leads to issues related with the regulatory process due to environmental and public acceptance concerns. On the other hand, substituting the currently installed standard conductors with others having a larger cross-section may cause an overall weight increase, resulting in the necessity of adapting the towers, dramatically increasing the investment costs.
The project CALAJOULE, cofinanced by the Italian Ministry of Economic Development in the framework of the “Ricerca di Sistema” program, aims at proposing innovative conductor prototypes for overhead lines for the containment of Joule power losses. This paper aims at disseminating all the main findings and conclusions of the CALAJOULE project, whereas some preliminary results had already been presented in some previously published papers [12,13].
The main difference with respect to other literature contributions regarding innovative overhead conductors is that the developed solutions have been ideated not to increase current ratings and power flows but to lessen the Joule power losses. The positive economic and environmental impacts have been evaluated quantitatively for paradigmatic overhead lines. In this paper, after an overview of the state-of-the-art in currently adopted OHL conductors for the Italian transmission and distribution networks, two innovative conductor prototypes are proposed, according to the specific needs of the Italian distribution and transmission electric grids. For the novel conductor proposed for transmission and subtransmission grids, an experimental research on the core-coating material has been developed and presented in this paper for the first time in technical literature. Moreover, a procedure for the evaluation of the impact of substituting the traditional conductors with the proposed new ones is fully developed and presented, showing the potential results in containment of Joule power losses, in cost savings and in CO2 emission avoidance. Consequently, such approach allows quantitatively evaluating the positive economic and environmental impacts for paradigmatic overhead lines. In order to perform these above-mentioned evaluations of the whole benefit deriving from less power and energy losses, the research group has benefitted from some analytical tools created and invented by the Electric Energy Transmission Laboratory of the Padova Power Systems Group. In particular, the Ossanna’s formulation has been extensively applied to a stepwise duration curve forecasting the power flows of a given overhead line [14,15,16]. The CALAJOULE researchers have also benefitted from a long experience in the transmission and distribution electric grids witnessed by several papers [17,18,19,20,21]. This topic is well covered in technical literature also in international working groups and standards [22,23,24,25,26,27,28].

2. Current Solutions for Overhead Lines Conductors

This section presents an overview of the presently installed conductors for OHLs and some of the commercially available solutions. Since the scope of this project is to develop new conductors for the Italian context, the overview refers to Italian OHLs, both in the transmission (HV and EHV) and distribution (MV and LV) grids. However, a similar distribution can be assumed for other contexts given the existing standardization in the conductor typologies.

2.1. State-of-the-Art of OHL Conductors

At the time of building of most of the currently existing OHLs the electrical companies were still vertically integrated, meaning that all the entire electricity chain (from production to final delivery) was owned by the same company. This is one of the reasons why the conductors adopted in power system wiring are standardized, and typically grouped in few types, depending on the voltage level. Due to its good mechanical performances, the most used type is aluminium conductor steel reinforced (ACSR), whereas aluminium alloys (e.g., Aldrey, generally known as AAAC: All Aluminium Alloy Conductor) and copper (especially in older LV lines) may be found in the cases where the mechanical stresses are lighter, so the priority is on increasing the overall conductibility.
In Table 1, the conductors types mostly used in the Italian transmission grid are summarized with reference to the respective lengths. As it can be seen from Table 1, at EHV and HV levels (380 and 220 kV), over 95% of the lines are equipped with ACSR conductors due to the high mechanical performances required as a result of long spans and high linear weight due to a large cross-section. Furthermore, given the high capacity needed in these power lines, along with the necessity of reducing the corona effects, most of the OHLs are equipped with bundles of two or three conductors (about 50%), as can be seen in Table 2, reporting the ACSR conductors divided by the main cross-sections installed. Although a detailed analysis of all the HV Italian power system was not possible due to unavailability of data, the main conductor types adopted in the 150–132 kV system are still ACSR, but with the cross-section more likely to be about 308 mm2.
In distribution networks, as shown in Table 3, although ACSR conductors are still present in a significant share (about 16%), most of the OHLs are equipped with copper conductors, especially at LV level. A detailed distribution of OHLs conductor types is reported in Table 4, in which it can be seen that a significant share of the copper conductors has a cross-section below 25 mm2 (about 50% of the total extension, mostly LV).

2.2. Existing Conductors for Transmission OHLs

The recent evolution trend in the power systems, as mentioned in Section 1, imposes new challenges to the transmission and distribution system operators (with acronyms TSOs and DSOs, respectively), to face the higher uncertainty in the power flows and reducing the bottlenecks. Although increasing the flexibility of the power system remains a priority, reinforcing the power lines will be a necessity in the near future. The challenge is then to find conductors able to uprate the current lines (i.e., increase the thermal limit) while ensuring the same (or improved) mechanical performances. Innovation in this field has mainly concerned conductors indicated as High Temperature Low Sag (HTLS), capable of operating continuously at high temperatures (above 100 °C), but containing the sag due to elongation resulting from the high temperature [27]. The main commercially available solutions for HTLS conductors, shown in Figure 1 and whose characteristics can be found in Table 5, are as follows.
  • Aluminium Conductor Steel Reinforced, ACSR, or Aluminium Conductor Steel Supported, ACSS, composed by annealed aluminium strands (or even trapezoidal wires, in the ACSS case) over a stranded steel core: this is the most commonly adopted solution for transmission OHLs;
  • Aluminium Conductor Composite Reinforced, ACCR, typically composed by a high-temperature aluminium alloy over a composite core of aluminium fibers embedded in a pure aluminium matrix. The same structure is also used in (Z)TACIR conductors, in which the core is in INVAR (steel and nickel alloy with very low linear expansion coefficient);
  • Gap-type Aluminium Conductor Steel Reinforced, G(Z)TACSR, consisting of an external thermal-resistant aluminium alloy (with a layer of trapezoidal wires), separated from the steel core by a gap filled with grease to allow the two layers to move independently. This ensures to apply the mechanical tension on the steel core only while increasing the aluminium cross-section for a reduced electrical resistance;
  • Aluminium Conductor Composite Core, ACCC/TW, typically made of trapezoidal wires of thermal-resistant aluminium alloy over a core consisting of carbon fibers (in the inner part) surrounded by a coating of glass fibers. This configuration gathers the advantage of increased aluminium cross-section and weight lowering due to the use of a carbon fiber core.
As reported in Table 5, the four conductor types, although having similar dimensions (diameter and cross-section), present significantly different ampacities and resistance values. In particular, comparing the traditional ACSR, for which the ampacity value is reported with reference to the temperature of 75 °C assumed by the standards, with the ACCC/TW conductor, it can be noticed how, although having a lower diameter, the actual cross-section results higher, due to the trapezoidal wires and the smaller section required by the composite material core. As a result, the conductor resistance is decreased and the ampacity is higher than the ACSR.

3. Innovative Conductor for Transmission OHLs

In this section, the innovative conductor proposed for transmission OHLs is presented. The following subsections discuss about the characteristics of the proposed conductor, with a focus on the experimental research concerning the materials to realize the core shell.

3.1. Conductor Characteristics

The conductor is designed to replace the traditional bimetallic conductor (ACSR) having overall cross-section of 308 mm2 and diameter of φ = 22.8 mm, mainly employed in the 132–150 kV Italian subtransmission network. A section of the innovative conductor, denominated ACCM/TW (Aluminium Conductor Composite Multistrand-Trapeziodal Wires), is depicted in Figure 2, in which the external conductive part, the inner core and its shell are colored differently. The properties of the innovative conductor, compared to those of the traditional one, are reported in Table 6. Instead of being made of steel, the conductor core, in orange in Figure 2, is made of a composite material, mainly consisting of carbon fibers. This choice allows the same breaking load to have a conductor core with reduced section, with a significant decrease in weight and in thermal expansion respect to the traditional conductor (1/10 respect to steel). Furthermore, respect to already existing commercial options, having a single-stranded carbon fiber core, the proposed conductor presents a core divided in seven strands as it can be seen in Figure 2. Due to the thermal processes required in its manufacturing, carbon fiber composite materials tend to have a higher homogeneity in the external section, whereas the fibers assume inhomogeneous disposition in the inner parts [28].
For this reason, in this project, a stranded core is proposed, in order to contain the cross-section of each of the composite core strands, ensuring a better distribution of the mechanical stress on the core in correspondence of the clamps.
Moreover, the presence of multiple wires leads to several advantages that makes this solution much more interesting than the single wire core (i.e., ACCC-TW of Table 5), mainly from the safety point of view. Looking at the experience of other manufacturers, the single wire core (i.e., ACCC-TW of Table 5) has shown several safety problems due to the nature of carbon composite—a brittle and stiff material. Several single wire core (i.e., ACCC-TW of Table 5) breakages have been reported during the installation and also during the lifetime of the line usually within a short period after conductor installation but in some cases some years after installation. These accidents affect the carbon core, which is very sensitive to the bending external stress that can occur in the installation work. The problem is that this kind of breaks (since they affect just the carbon core and not the aluminium outer layer) are not visible from outside and cannot be detected by visually checking the conductor. For this reason the installation must be carried out with great care, avoiding excessive bending that could lead to core damage and the entire process must be constantly supervised, becoming quite complicated compared to other conductor installations. With a multiwire core the nature of the carbon composite material is not changed, but the seven-wire (multistrand) structure is much more flexible than the single carbon wire. This means that the core is much less sensitive to breakages. Another important feature of this kind of solution is that the consequences of a possible break are much less serious. In fact, if a wire breaks the other six ones guarantee the stability of the structure, leading to a much more safe transmission line. On opposite, every little damage of a single core (i.e., ACCC-TW) leads to the complete failure. Moreover, the ACCR solution has as main disadvantages the high cost and the brittleness due to the nature of the core material. Furthermore, the losses are not optimized as it can be seen from the higher electrical resistance compared to the ACCM.
The reduction of the core section and weight allows, for the same external diameter, an increase of the conductive part in aluminium. In addition, the trapezoidal strands allow a better filling factor than the traditional circular strands. In Table 6, the main characteristics of the innovative ACCM/TW conductor are reported, compared with the traditional ACSR ones. The shell, in purple in Figure 2, is realized in aluminium, as this material is the most suited to keep the core insulated from external humidity and guarantee durability for the expected OHL lifetime. A deeper discussion on this aspect is made in the following section.

3.2. Experimental Research on Core-Coating Materials

The carbon fiber composites, although offering excellent mechanical performance, are negatively affected by humidity due to the oxidation process that drastically degrades the characteristics of this material. Aiming at containing the conductor weight increase due to the coating, an important experimental part of the CalaJoule research project focused on the evaluation of the performance of polymeric materials [29,30]. The scope is to assess their suitability for realizing a shell for the core of the conductor capable of protecting it from oxidation (the area of application of the polymeric coating is highlighted in purple in Figure 2). Given the critical temperature conditions required (180–200 °C), the choice falls on thermally resistant polymers such as PEEK, PEKK, PEI, PPA and PPS. PEEK, PPS, PPA, and PEI.
The main characteristics required of the materials are the impermeability to oxygen and the preservation of the properties for long periods (at least four decades, supposed as the lifetime of an OHL). The polymeric materials to be used as coating are mainly required to be resistant to continuous exposure to high temperatures (140 °C) and to avoid the flow of oxygen in order to prevent oxidation of the carbon fiber core.
After an initial screening among the best technopolymers available on the market, those having the best performance in relation to thermal properties were identified. The classes of technopolymers analyzed are as follows [16].
  • PEEK, polyetheretherketone, is a semicrystalline thermoplastic technopolymer that can be used at high temperatures. It has high mechanical and chemical resistance, is resistant to abrasion, is not flammable, resists to high energy radiation.
  • PEKK, polyetherketoneketone, is a semicrystalline thermoplastic polymer with high heat resistance, significant mechanical strength and rigidity, combined with good chemical resistance. It is an intrinsically fireproof material with limited smoke generation and low toxicity in case of fire.
  • PEI, polyetherimide, is an amorphous technopolymer that can be used continuously at high temperatures. Its properties also include high mechanical strength and rigidity even at high temperatures, dimensional stability for low moisture absorption, and good electrical properties. It is inherently flame retardant and chemically resistant and its electrical properties are stable even under varying temperature, humidity and frequency conditions.
  • PPA, polyphthalamide, is a semicrystalline aromatic polyamide. Compared to polyamide 6.6 it is more mechanically resistant, more rigid, less sensitive to moisture, and has improved thermal properties, fatigue, and creep resistance factors that make it applicable in a wide range of sectors;
  • PPS, polyphenylene sulfide, is a semicrystalline polymer with excellent thermal resistance. This material is characterized by inherent low flammability and good chemical resistance. It has very low moisture absorption, high mechanical strength, and dimensional stability.
For a selection of these materials (shown in Figure 3), performance was assessed through the following analysis; chemical (FT-IR), physical-mechanical (hardness, density, and bending properties), thermal (TGA and DSC), and dynamic-mechanical (DMA). Creep resistance was also evaluated and oxygen permeability measured. The samples have undergone an accelerated aging test to assess their degradation according to the expected lifetime of an OHL (40 years). The approximated model in [25] has been employed to evaluate the deterioration of the material properties, applying temperatures in the range of 200 to 250 °C.
In Table 7, a list of the tested polymers is reported along with the measured oxygen permeability (considered a discriminatory property) measured according to ISO 15105-2, at 25 °C, 50% R.H.
The polymers that have shown the best performance are the polyetherimide and the polyphenylene sulfide.
However, after accelerated aging at 250 °C, the mechanical and oxygen permeability properties have shown a degradation, which leads to the conclusion that these materials cannot guarantee protection to the conductor’s core under such severe conditions (T = 140 °C) and for long periods (40 years).
The treatment of samples subjected to accelerated aging at 200 °C, following the procedure described above, takes 7.6 months to estimate 40 years of operation at 140 °C. In practice, the duration of the test was 2.5 months because already after this period all the materials considered showed clear signs of degradation, such as to prevent the measurement of oxygen permeability.
In Figure 4, the thin film samples used for the aging test are shown in the initial state and after the process. The films subjected to this aging test had the necessary geometry for the permeability tests, therefore thin films. Since the degradation of the material starts from the external surface, in contact with the air, for thin films it can affect the entire section of the film in a relatively short time. This leads to embrittlement and cracking that affects the oxygen permeability measurement.
For this reason, it has been decided to apply the aging process to thicker samples (4 mm), but with a temperature of 250 °C, in order to reduce the measurement time while assuming the same expected lifetime of 40 years. In Figure 5, the 4 mm samples are shown for three stages of the aging test: start time (1), after 2.5 h (2), and at the end of the test, after 7.2 days (3). As it can be seen, after 2.5 h the samples show a color variation and, in the case of PEI, the formation of surface swellings. At the end of the aging process, all the samples show significant color variation. In particular, the samples of PEI are partly deformed and have cavities inside.
The mechanical properties of the samples after the test have been compared with those at the start of it as reported in Table 8, where the flexural strength is reduced by 20% for PEI and by 57% for PPS (measured according to ISO 178).
In order to run an oxygen permeability test on the samples after the aging test, the thin film samples shown in Figure 6 have been obtained from the 4 mm samples in Figure 5. The visible degradation of these samples did not allow running a permeability test, since the oxygen permeability of the material was outside of the detectable range of the instrument.
The degradation of the mechanical properties and especially of the oxygen permeability, led to the conclusion that none of the tested materials (which are the techno-polymers with the best performances currently on the market) are suited to be used as core-insulation material for the innovative conductor. As a result, although leading to a higher overall weight increase, it has been decided to adopt an aluminium shell, since this material has well-known oxygen-shielding and temperature resistance properties, without suffering from the degradation detected for polymeric materials.

3.3. Clamping Equipment for the Proposed ACCM/TW Conductor

Part of the research concerned the study of innovative solutions for the clamping equipment and accessories necessary for the installation of the innovative conductors in transmission OHLs, given its constructive peculiarities. The research has focused only on the direct contact clamping because its improvement could reduce losses and exploit the innovative conductor’s full potential. By its very definition, the clamp is an element of mechanical, electrical and chemical discontinuity in the line conductor and therefore can often be a weak point. The main requirements for a good terminal block are therefore
  • having an electrical conductivity at least equal to that of the conductor with a negligible contact resistance (to reduce heating of the terminal) and
  • avoiding corrosion due to electrolytic torques deriving from contact between metals of different types.
All the parts with direct contact with the conductor have been designed using a high conductivity aluminium alloy (EN AW-1050A). In order to contain the corrosion effects, bolts, and nuts have been designed in austenitic stainless steel, whereas the suspension parts (i.e., not in direct contact with the conductive parts of the conductor) are realized in aluminium alloy EN AW-44100, having a reduced copper content.

4. Innovative Conductor for Distribution OHLs

For the distribution network, the selected solution is an All Aluminium Alloy Conductor (AAAC) with low resistivity or high conductivity (IACS), and hence the innovative conductor has been named as Super High Conductivity (AAAC-SHC). An AAAC-SHC conductor with a diameter of 17.25 mm (see Figure 7) has been developed and its characteristics are compared with the most similar traditional standard AAAC conductors used in the Italian distribution/subtransmission networks (Aldrey 185/37 and AAAC Al 3). The Aldrey 185/37 conductor, together with other commonly used conductors in the Italian distribution network is considered for the benefit analysis in Section 5. As it can be seen from Table 9, although having a reduced cross-section with reference to Aldrey 185/37, the innovative conductor presents a lower resistance and a higher ampacity due to an increased IACS (57.3% versus 53% in the traditional one). The development of the AAAC-SHC 17.25 mm conductor is the result of an accurate study of aluminium alloys properties, in terms of electrical conductivity and mechanical properties, together with a careful analysis of chemical composition and microstructure of the alloys. This research has permitted to develop a material with a higher electrical conductivity compared to the traditional aluminium alloy used for conductors (AAAC), maintaining the same tensile strength. As it can be seen in Figure 8, the conductivity increase is of several %IACS compared to the traditional aluminium alloy AL2 (%IACS = 52.5), AL3 (%IACS = 53), and AL4 (%IACS = 52.9).

5. Assessment of Benefits from the Installation of Innovative Conductors

In this section, the procedure for assessing the impact of the installation of the innovative conductors on the Italian network is outlined, and then the methodology is applied to compare the performance of the innovative conductors introduced in the previous sections with the traditional ones. The aim is to analyze the benefits resulting from the replacement of the conductors in the line sections that would not require changes in the support structures, by considering the types introduced in Section 2.

5.1. Benefit Assessment Methodology

A fully detailed representation of the national power system could be very difficult and, still, does not remove all sources of errors in building the model, given the necessity of a high detail in the information needed, not only on the network structure, but, most importantly, on the load trend over a long period. Furthermore, this effort is not necessary for the scope of this work, which is comparing the effects on the efficiency of the power lines as a whole. In this work, instead, a simplified approach to the evaluation of the operative conditions of an OHL is presented in [14] and reported in the following.
The methodology, based on the Ossanna’s theorem [14], under the hypothesis of a symmetric network and balanced loading on the phases, makes use of the single-phase OHL equivalent to analytically evaluate the operative state of a line given the complex power at its receiving end, once the voltage at the sending end is assumed.
By considering the single-phase equivalent in Figure 9a, converted to its per unit representation in Figure 9b, the current in the vector diagram in Figure 9c is obtained as in (1), as a function of the receiving end voltage u and complex power s (values in p.u., superscript * stands for complex conjugate). From (2), the relation between complex power and sending end voltage can be written as in (3), in which the angle γ results from the difference between the impedance argument ψ and the load angle φ.
i _ = s _ * u _ * = 1 u _ e j ψ
u _ * u 2 = s _ * e j ψ u e j δ u 2 s e j γ = 0
Splitting real and imaginary parts of (2) as in (3) it can be seen how, once the receiving end complex power is defined, the imaginary part of u is constant. By solving the first equation in (3), the real part is calculated as in (4), which define the two sending end voltage vectors u and u in (5), of which u’ is the most important, given the low magnitude of u”, with the constraint ξ ≥ 0, which represents the physical feasibility.
{ u x 2 + u y 2 u x + s cos γ = 0 u y + s sin γ = 0
u x = 1 2 ± 1 4 s cos γ ( s   sin γ ) 2 = 1 2 ± ξ
{ u _ = 1 2 + ξ j s sin γ u _ = 1 2 ξ j s sin γ
By considering the line representation in Figure 9a, the well-known relation (5) links the sending bus voltage and current (with subscript 1) to those at the receiving bus (with subscript 2). Under the assumption of symmetry and reciprocity of the line model (so that A = D and ADB C = 1), (6) is derived. At this point, noting that U1 = A U20, where U20 is the no-load voltage at the receiving end, and remembering that Z = B/A the current I1 can be written as in (7).
{ U _ 1 = A _ U _ 2 + B _ I _ 2 I _ 1 = C _ U _ 2 + D _ I _ 2
{ U _ 2 = A _ U _ 1 B _ I _ 1 I _ 2 = C _ U _ 1 + D _ I _ 1
I _ 1 = A _ U _ 1 U _ 2 B _ = U _ 1 U _ 2 / A _ B _ / A _ = A _ U _ 20 U _ 2 / A _ Z _
If, at this point, the base values are defined as Ub = |U20|, Sb = Ub2/|Z|, and Zb = |Z|, the per unit version of (8) is given by (9). Therefore, the complex power s1 at the sending end of the line is obtained as in (10), in which α is the argument of A.
i _ 1 = s _ * 1 A _ * = = A _ u _ 2 A _ e j ψ
s _ 1 = A 2 u _ * 2 e j 2 a e j ψ
By this approach, once the complex power is known at the receiving end and the sending end voltage is set, the receiving end voltage u2 is obtained using the first equation in (5). At this point, the power flow on a line can be analytically calculated, since the sending end complex power is given by (10). This procedure is applied in the following sections to evaluate the Joule losses of the transmission and distribution OHLs.

5.2. Transmission Grid OHLs

For this network level, the presently installed standard conductors that may be replaced by the proposed innovative conductor are those reported in Table 10. This is a selection of the OHLs in the transmission grid having higher resistance per unit length and up to the same breaking load as the innovative conductor introduced in Section 3.1.
The ampacity (hence the transmission capacity) of the potentially replaceable OHLs has been determined using the CEI 11–60 standard [31]. The current flow rates at the thermal limit, i.e., the current value for which the line can be operated for an unlimited period of time with a minimum probability of discharge and with acceptable aging of the line equipment, are defined in relation to the type of line, its position in the national territory, the seasonality and the operating conditions. Referring to Table 11, taken from [31], the current rating of the lines in Table 10 is calculated with reference to zone “A” (locations with an altitude below 800 m above sea level in central and southern Italy and the islands) and a seasonal period defined by the standard as ′′Period F′′ (cold period, between October and April). Since the reference conductor for the standard is the unified ACSR with diameter φ = 31.5 mm, it is possible to determine the flow rates for different size conductors by means of (11):
I R = ( 0.14 ϕ 2 + 30.8 ϕ 110 ) I 0 10 3
where the diameter φ is expressed in (mm) and the current I0 (deduced from Table 11) is in (A).
Table 1 shows that, among the ACSR conductors listed in Table 10, the one with higher extension on the HV and EHV networks is the 265/26 + 7. For this reason, in the following, the assessment of benefits from the substitution of traditional conductors takes into account the total extension of this type of conductor (443.3 km).
To find the value of the energies lost over the lifetime of the line, it is necessary to build the equivalent single-phase model of the line. First, the per unit length resistance of the conductor is calculated by the procedure explained in [12] and adapted to the operating temperature by means of the well-known equation
r 50 ° C = r 20 ° C [ 1 + α 20 ° C ( 50 ° C 20 ° C ) ]
where α20 °C stands for the temperature coefficient of resistance at 20 °C for aluminium in (1/°C), whereas an operating temperature of 50 °C is assumed. This is a mere assumption, since the conductor’s actual working temperature depends on the thermal regime that is established, as a result of the current flow, air temperature, and wind speed and direction with respect to the line axis.
In order to build the equivalent single-line model of the OHL, the tower type depicted in Figure 10 is considered. Along with the distances among the phases and respect to the ground, it can be noted that a maximum sag of 10 m is considered in the model. With these assumptions, the electrical parameters obtained for the OHL equipped with the traditional conductor and with the innovative one are reported in the figure as well. It should be noted that the resistance value has been increased by 3% in order to take into account the additional losses due to jumpers and clamping equipment.
Once the electrical parameters of the OHL are calculated, the methodology discussed in Section 5.1 is used to determine the Joule losses given the complex power withdrawn at the receiving end of the OHL. By assuming a duration curve of the type in Figure 11 (by hypothesis having the same trend as the national typical demand curve), the values are obtained by translating the curve according to the maximum value given by the above mentioned ampacity evaluation. In this case, as indicated in Table 10, for this conductor the maximum power is set at 422.5 MW, having assumed a thermal rating current IR of 655 A with a power factor of 0.98 (typical of the power flows on the transmission grid).
As detailed in [13], the load-duration curve can be discretized in segments having a given duration ∆τ, so that the active power loss ∆p is deduced for every load power value and the annual joule losses (AJL) energy can be calculated by just multiplying ∆p by the respective time step. At this point, by assuming a constant electricity generation cost (40 €/MWh is used in this study [32]), it is possible to have an indication of the Annual Cost of Losses (ACL), calculated as
ACL = AJL C m L   ( )
which can be actualized for each year in the OHL’s lifetime by means of a discount rate i (here assumed as 5%) as in (14):
AACL = ( 1 + i ) n 1 i ( 1 + i ) n ACL   ( )
In Table 12, the results for the transmission OHL equipped with the innovative ACCM/TW conductor are compared with those obtained with the traditional ACSR conductor. With the mentioned assumptions, if the entire extension of the ACSR 22.8 mm conductor on the HV and EHV Italian grids were replaced by the innovative conductor, the Joule power losses reduction would be of about 54.3 GWh (−18.8%). This amounts to over 2 million of euro in savings every year for reduced electricity generation needs, which results in an actualized cost (over the 40-year expected OHL lifetime) of over 37 million of euro.
From an environmental point of view, the replacement of the traditional conductor with the innovative one would result in a saving of 21.187 kt per year of carbon dioxide, which becomes 847.475 kt in the expected 40-years lifetime. These values are obtained considering an emission of 0.39 t/MWh of CO2 [32].

5.3. Distribution Network OHLs

As for the previous case, a list of potentially replaceable conductors has been identified for the distribution network context. The traditional conductors reported in Table 13 are those having higher per unit length resistance and lower breaking load with respect to the innovative conductor ones, among those listed in the state of the art. The thermal rating current IR has been calculated in a deterministic way (since the standard CEI 11–60 is not applicable to MV and LV OHLs) by means of the approach developed by Shurig and Frick in 1930 and summarized in [33]. It was decided not to consider the presence of solar irradiation (assumed equal to 1000 W/m2) in order to have a higher thermal rating in the comparison.
As already mentioned, the actual trend in electricity usage and production will require in the near future a reinforcement of the distribution network. Increasing the conductor’s cross-section would then be a solution for reducing the risk of bottlenecks in the power flow distribution. For this reason, the traditional conductors included in this study have cross-sections even below the one of the innovative one (up to 70 mm2), as the innovative conductor may be used as a reinforcement of these current OHLs.
The tower type for the distribution grid’s case study OHL is depicted in Figure 12, consisting of a three-phase line with 10.5 m tall towers. As already mentioned in Section 4, the closest match with the standard conductors presently installed, listed in Table 13, is the Aldrey 185/37 having a diameter of 17.64 mm and a cross-section of 184.5 mm2. The parameters for the single-line equivalent circuit of the OHL are reported in Figure 12 for both the reference standard conductor and the innovative one. The duration curve of the line load is reported in Figure 13, scaled according to the line thermal rating power in Table 13.
The results of the benefit analysis methodology discussed in Section 5.1 are detailed in comparison with the reference Aldrey conductor in Table 14. Replacing the total extension of the traditional Aldrey conductor would result in a Joule power losses reduction on a yearly basis of 1.17 GWh, corresponding to a decrease by 4%. The estimated cost saving is about 47 k€ per year, which corresponds to an actualized cost reduction of 804 k€ (with the same assumptions about OHL lifetime and discount rate as in the previous section). The potential CO2 emissions savings is estimated as 457 t per year.
As discussed in Section 2, the majority of Italian distribution OHLs is still equipped with copper conductors rather than with aluminium ones. By considering all the replaceable conductors in Table 13, their total extension in the distribution networks (MV and LV) in Italy is about 14% of the total 191,888 km (i.e., about 27,000 km). Table 15 reports the results of the cost analysis described in Section 5.1 for all the distribution network conductors considered in the study. Replacing these OHL conductors would lead to a containment of Joule power losses by 28.3% on a yearly basis (1354 GWh), with a possible cost reduction of about 54 M€ (AACL reduction of 929 M€) and a potential CO2 emission reduction of about 830 kt each year.

6. Conclusions

The current trend in the electricity usage and production and the expected developments in the near future will lead to reinforcements in both the transmission and distribution grids, to reduce the risk of bottlenecks and improve the energy efficiency of the power system. The CALAJOULE project, funded as part of the Italian “Ricerca di Sistema” program, has produced significant results in the development and analysis of new conductors for overhead lines at HV and MV level.
The scope of this paper is to show all the chief findings of the three-year research and chiefly the expected benefits coming from the adoption of such innovative conductors in both transmission and distribution grids, with reference to the presently installed OHL conductors. The paper shows a methodology adopted in the project to evaluate the potential benefits resulting from the usage of the innovative conductors in place of the standard ones. Under some working assumptions (i.e., 40 year OHL lifetime, fixed price of electricity, CO2 emission known, and constant per MWh), the results show a strong, positive impact on the Italian electricity system which could also be replicated, with due distinctions, for other electric grids.
The actualized cost saving for reduced Joule losses in the HV network is estimated in about 37 M€, with a corresponding CO2 avoided emission of 847 kt on yearly basis. For the distribution network, by considering a potential reinforcement of the current OHLs with conductors having cross-sections up to 70 mm2, the results have shown an actualized cost reduction of 929 M€ with a CO2 emission avoidance of 830 kt per year. It is worth noting that a mere investment cost comparison has not been investigated in this research. However, the investment cost of the distribution novel conductor is comparable with traditional Aldrey one. With regard to the transmission novel conductor, the investment cost is greater than traditional ACSR, but, as demonstrated in the paper, the return on the investment is assured by the savings obtained by less energy losses during the entire OHL lifetime. Hence, the developed prototype is more convenient than a traditional conductor in a long-term perspective.

Author Contributions

Conceptualization, R.B.; Formal analysis, R.B. and S.D.S.; Funding acquisition, R.B.; Investigation, R.B., A.C., C.G., S.D.S., D.M., M.M. and F.P.; Supervision, R.B., R.C. and L.M.; Validation, R.B.; Writing-original draft, M.C.; Writing-review & editing, R.B., C.G., S.D.S., D.M., M.M. and F.P.

Funding

This research was funded by Ministry of Economic Development in the framework of the Ricerca di Sistema Programme, grant number CCSEB_00176.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Eurostat. Smarter, greener, more inclusive? Indicators to Support the Europe 2020 Strategy; Publications Office of the European Union: Brussels, Belgium, 2018. [Google Scholar]
  2. European Commision. Clean Energy for All Europeans. Available online: https://ec.europa.eu/energy/en/topics/energy-strategy-and-energy-union/clean-energy-all-europeans (accessed on 10 November 2018).
  3. ENTSO-E. Electricity Balancing in Europe. Available online: https://www.entsoe.eu/news/2018/12/12/electricity-balancing-in-europe-entso-e-releases-an-overview-of-the-european-electricity-balancing-market-and-guideline (accessed on 20 November 2018).
  4. Bracale, A.; Caldon, R.; Coppo, M.; Canto, D.D.; Langella, R.; Petretto, G.; Pilo, F.; Pisano, G.; Proto, D.; Ruggeri, S.; et al. Active management of distribution networks with the ATLANTIDE models. In Proceedings of the 8th Mediterranean Conference on Power Generation, Transmission, Distribution and Energy Conversion (MEDPOWER 2012), Cagliari, Italy, 1–3 October 2012. [Google Scholar]
  5. Petretto, G.; Cantù, M.; Gigliucci, G.; Pilo, F.; Pisano, G.; Natale, N.; Soma, G.G.; Coppo, M.; Turri, R. Representative Distribution Network Models for Assessing the Role of Active Distribution Systems in Bulk Ancillary Services Markets. In Proceedings of the 19th Power Systems Computation Conference, Genoa, Italy, 20–24 June 2016; pp. 1–7. [Google Scholar]
  6. Kiessling, F.; Nefzger, P.; Nolasco, J.F.; Kaintzyk, U. Overhead Power Lines-Planning, Design, Construction; (Springer, Series: Power Systems); Springer-Verlag Berlin Heidelberg: Heidelberg, Gemany, 2003. [Google Scholar]
  7. Benato, R.; Capra, D.; Conti, R.; Gatto, M.; Lorenzoni, A.; Marazzi, M.; Paris, G.; Sala, F. Methodologies to Assess the Interaction of Network, Environment and Territory in Planning Transmission Lines. In Proceedings of the 2006 CIGRÉ session, Paris, France, 27 August–1 September 2006. Paper C3-208. [Google Scholar]
  8. Benato, R.; Dambone, S.S.; Guglielmi, F. Determination of Steady-State and Faulty Regimes of Overhead Lines by Means of Multiconductor Cell Analysis (MCA). Energies 2012, 5, 2771–2793. [Google Scholar] [CrossRef] [Green Version]
  9. Usman, M.; Coppo, M.; Bignucolo, F.; Turri, R.; Cerretti, A. Multi-Phase Losses Allocation Method for Active Distribution Networks based on Branch Current Decomposition. IEEE Trans. Power Syst. 2019. [Google Scholar] [CrossRef]
  10. Cerretti, A.; Di Lembo, G.; Valtorta, G. Improvement in the continuity of supply due to a large introduction of Petersen coils in HV/MV substations. In Proceedings of the CIRED 2005-18th International Conference and Exhibition on Electricity Distribution, Turin, Italy, 6–9 June 2005. [Google Scholar]
  11. Benato, R.; Dambone, S.S.; Poli, M.; Quaciari, C.; Rinzo, G. An On-Line Travelling Wave Fault Location Method for Unearthed-Operated High Voltage Overhead Line Grids. IEEE Trans. Power Deliv. 2018, 33, 2776–2785. [Google Scholar] [CrossRef]
  12. Benato, R.; Caldon, R.; Coppo, M.; Dambone, S.S.; Mimo, D.; Peroni, D.; Previatello, M. Highly Efficient Overhead Line Innovative Conductors with Reduced Joule Power Losses. In Proceedings of the 2017 AEIT International Annual Conference, Cagliari, Italy, 20–22 September 2017. [Google Scholar]
  13. Benato, R.; Caldon, R.; Coppo, M.; Dambone, S.S.; Rinzo, G.; Mimo, D. Evaluation of Joule Power Losses Reduction in Overhead Lines with Innovative Conductors. In Proceedings of the 2018 AEIT International Annual Conference, Bari, Italy, 3–5 October 2018. [Google Scholar]
  14. Benato, R.; Paolucci, A. EHV AC Undergrounding Electrical Power. Performance and Planning; (Springer, Series: Power Systems); Springer-Verlag London: London, UK, 2010; Volume 47. [Google Scholar]
  15. Benato, R.; Napolitano, D. Overall Cost Comparison Between Cable and Overhead Lines Including the Costs for Repair After Random Failures. IEEE Trans. Power Deliv. 2012, 27, 1213–1222. [Google Scholar] [CrossRef]
  16. Benato, R.; Dambone, S.S.; Guglielmi, F.; Partal, E.; Tleis, N. Zero Sequence Behaviour of a Double-Circuit Overhead Line. In Proceedings of the 2014 IEEE PES T&D Conference and Exposition, Chicago, IL, USA, 14–17 April 2014. [Google Scholar]
  17. Benato, R.; Dambone, S.S.; Guglielmi, F.; Partal, E.; Tleis, N. Ground Return Current Behaviour in High Voltage Alternating Current Insulated Cables. Energies 2014, 7, 8116–8131. [Google Scholar] [CrossRef] [Green Version]
  18. Benato, R.; Colla, L.; Dambone, S.S.; Marelli, M. Review of High Current Rating Insulated Cable Solutions. Electr. Power Syst. Res. 2016, 133, 36–41. [Google Scholar] [CrossRef]
  19. Benato, R.; Dambone, S.S.; Guizzo, L.; Rebolini, M. The Synergy of the Future: High Voltage Insulated Power Cables and Railway-Highway Infrastructures. IET Gener. Transm. Distrib. 2017, 11, 2712–2720. [Google Scholar] [CrossRef]
  20. Benato, R.; Dambone, S.S. A New Multiconductor Cell Three-Dimension Matrix-Based Analysis Applied to a Three-Core Armoured Cable. IEEE Trans. Power Deliv. 2018, 33, 1636–1646. [Google Scholar] [CrossRef]
  21. Zecchino, A.; Hu, J.; Coppo, M.; Marinelli, M. Experimental Testing and Model Validation of A Decoupled-Phase on-Load Tap-Changer Transformer in An Active network. IET Gener.Transm. Distrib. 2016, 10, 3834–3843. [Google Scholar] [CrossRef]
  22. Cigré Technical brochure n°. Alternating Current (ac) Resistance of Helically Stranded Conductors. Ecigre, Posted 2008. Available online: https://nanopdf.com/download/alternating-current-ac-resistance-of-helically_pdf (accessed on 27 June 2009).
  23. Cigré Technical brochure n°. Guide for Qualifying High Temperature Conductors for Use on Overhead Transmission Lines. Ecigre, Posted 2010. Available online: https://e-cigre.org/publication/426-guide-for-qualifying-high-temperature-conductors-for-use-on-overhead-transmission-lines (accessed on 10 October 2011).
  24. Cigré Technical brochure n°. Conductors for the Uprating of Overhead Lines. Ecigre, Posted 2004. Available online: https://e-cigre.org/publication/244-conductors-for-the-uprating-of-overhead-lines (accessed on 18 April 2006).
  25. Landwehr, G.; Marais, P. Practical Comparison of Power line Upgrading and Upgrading Result. Cigré Sci. Eng. 2016, 5. (ISSN 1286-1146). [Google Scholar]
  26. IEEE. 738-1993-IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors; IEEE: Piscataway, NJ, USA, 1993. [Google Scholar]
  27. EPRI. Demonstration of Advanced Conductors for Overhead Transmission Lines; Final Project Report; EPRI: Palo Alto, CA, USA, July 2008. [Google Scholar]
  28. Kumar, B.G.; Singh, R.P.; Nakamura, T. Degradation of Carbon Fiber-Reinforced Epoxy Composites by Ultraviolet Radiation and Condensation. J. Compos. Mater. 2012, 36, 2713–2733. [Google Scholar] [CrossRef]
  29. Fink, J.K. High Performance Polymers, 1st ed.; William Andrew: Norwich, NY, USA, 2008. [Google Scholar]
  30. Wright, D. Failure of Plastics and Rubber Products: Causes, Effects and Case Studies Involving Degradation; Smithers Rapra Press: Akron, OH, USA, 2001. [Google Scholar]
  31. CEI STANDARD 11-60. Portata al limite termico delle line elettriche aeree esterne con tensione maggiore di 100 kV; CEI: Trieste, Italy, 2002. [Google Scholar]
  32. ENEL; Rapporto Ambientale, 2013. Available online: https://www.enel.com/content/dam/enel-com/governance_pdf/reports/bilanci-annuali/2013/Enel_Rapporto_Ambientale_2013.pdf (accessed on 1 February 2014).
  33. Schurig, O.R.; Frick, C.U. Heating and Current Carrying Capacity of Bare Conductor for Outdoor Service. Gen. Electr. Rev. 1930, 33, 141–157. [Google Scholar]
Figure 1. Main types of high temperature low sag (HTLS) conductors: (a) ACSR, ACSS; (b) ACCR, (Z)TACIR; (c) G(Z)TACSR; (d) ACCC/TW.
Figure 1. Main types of high temperature low sag (HTLS) conductors: (a) ACSR, ACSS; (b) ACCR, (Z)TACIR; (c) G(Z)TACSR; (d) ACCC/TW.
Energies 12 03107 g001
Figure 2. Section of the innovative ACCM/TW conductor with diameter 22.78 mm.
Figure 2. Section of the innovative ACCM/TW conductor with diameter 22.78 mm.
Energies 12 03107 g002
Figure 3. Polymers tested in the project.
Figure 3. Polymers tested in the project.
Energies 12 03107 g003
Figure 4. Thin film samples of PEI (Top) and PPS (Bottom) before (a) and after (b) the aging process at 200 °C.
Figure 4. Thin film samples of PEI (Top) and PPS (Bottom) before (a) and after (b) the aging process at 200 °C.
Energies 12 03107 g004
Figure 5. Four millimeter samples of PEI (Top) and PPS (Bottom) before (a) and after the aging process at 250 °C; (b) after 2.5 h and (c) after 7.2 days.
Figure 5. Four millimeter samples of PEI (Top) and PPS (Bottom) before (a) and after the aging process at 250 °C; (b) after 2.5 h and (c) after 7.2 days.
Energies 12 03107 g005
Figure 6. Thin film samples obtained from the 4 mm samples of PEI (a) and PPS (b) after the aging test.
Figure 6. Thin film samples obtained from the 4 mm samples of PEI (a) and PPS (b) after the aging test.
Energies 12 03107 g006
Figure 7. Section of the AAAC-Super High Conductivity (SHC) conductor with diameter 17.25 mm.
Figure 7. Section of the AAAC-Super High Conductivity (SHC) conductor with diameter 17.25 mm.
Energies 12 03107 g007
Figure 8. Comparison between traditional alloys (AL 2, AL 3, and AL 4 in azure area) and AAAC-SHC.
Figure 8. Comparison between traditional alloys (AL 2, AL 3, and AL 4 in azure area) and AAAC-SHC.
Energies 12 03107 g008
Figure 9. (a) Single-phase equivalent of an OHL from the receiving end, (b) its equivalent per unit representation, and (c) vector diagram of the voltage.
Figure 9. (a) Single-phase equivalent of an OHL from the receiving end, (b) its equivalent per unit representation, and (c) vector diagram of the voltage.
Energies 12 03107 g009
Figure 10. HV OHL case study: tower layout and per unit length electrical parameters.
Figure 10. HV OHL case study: tower layout and per unit length electrical parameters.
Energies 12 03107 g010
Figure 11. Duration curve assumed for the HV OHL case study.
Figure 11. Duration curve assumed for the HV OHL case study.
Energies 12 03107 g011
Figure 12. MV line case study tower layout.
Figure 12. MV line case study tower layout.
Energies 12 03107 g012
Figure 13. Duration curve assumed for the distribution OHL case study.
Figure 13. Duration curve assumed for the distribution OHL case study.
Energies 12 03107 g013
Table 1. Italian extra-high voltage level (EHV) and high voltage level (HV) transmission network extension divided by main wire types in (km) and in (%) respect to the total.
Table 1. Italian extra-high voltage level (EHV) and high voltage level (HV) transmission network extension divided by main wire types in (km) and in (%) respect to the total.
ACSRCUAAAC
North9956(100.0%)0(0.0%)0(0.0%)
Central4821(88.2%)212(3.9%)435(8.0%)
South6198(94.7%)348(5.3%)32(0.5%)
Total20,975(95.5%)560(2.5%)467(2.1%)
Table 2. Detail of the Italian EHV Transmission network extension divided by cross-sections (mm2) and number of subconductors per phase of aluminium conductor steel reinforced (ACSR) conductors in (km) and in (%).
Table 2. Detail of the Italian EHV Transmission network extension divided by cross-sections (mm2) and number of subconductors per phase of aluminium conductor steel reinforced (ACSR) conductors in (km) and in (%).
Whole Cross-Section in (mm2)3084285095857087551865Total
Number of Subconductors per Phase1121123111
North31931474839571000163284320508389956
1.54%15.20%2.33%4.62%4.83%0.78%13.73%0.99%0.00%4.05%48.07%
Central1244330435935562987001534780
0.60%2.09%0.00%2.10%0.45%2.68%14.42%0.00%0.00%0.74%23.08%
South01106209631124326003475
0.00%0.05%0.00%2.99%0.46%1.50%11.74%0.03%0.00%0.00%16.78%
Islands00001480177526031502498
0.00%0.00%0.00%0.00%7.14%0.86%2.54%0.00%1.52%0.00%12.06%
Network total4443591483201226681207878821131599120,709
2.14%17.34%2.33%9.72%12.88%5.83%42.43%1.02%1.52%4.78%100.00%
Table 3. Italian distribution network (MV and LV) main wire types extension in (km) and (%) respective to the total lines extension.
Table 3. Italian distribution network (MV and LV) main wire types extension in (km) and (%) respective to the total lines extension.
ACSRAACCUAAAC
North8880(19.5%)356(0.8%)32,786(72.1%)2603(5.7%)
Central4788(7.3%)318(0.5%)59,969(91.9%)38(0.1%)
South16,420(20.2%)1331(1.6%)56,038(69.0%)6420(7.9%)
TOTAL30,090(15.7%)2005(1.0%)148,789(77.5%)9062(4.7%)
Table 4. Detail of the distribution network (MV and LV) main wire types extension in (km) and in (%) respective to the total extension.
Table 4. Detail of the distribution network (MV and LV) main wire types extension in (km) and in (%) respective to the total extension.
ACSRAACCUAAACTOT
Cross
Section
(mm2)
<100≥100≥150≤25>25≥35≤16>16>25>35≤35>35>70-
<150≤35≤25≤35≤70
North30526483117109240424914,364445097231322107720445,480
0.16%0.14%4.33%0.00%0.06%0.13%2.21%7.49%2.32%5.07%0.69%0.56%0.11%23.70%
Central2712134304264324915,42418,32318,77474481072165,236
0.14%0.11%2.24%0.01%0.02%0.13%8.04%9.55%9.78%3.88%0.01%0.00%0.01%34.00%
South420254255048625949112,65612,4895263487317914585545,365
0.22%1.32%2.87%0.04%0.13%0.26%6.60%6.51%2.74%0.25%1.66%0.76%0.03%23.64%
Islands27334273391172322583312,3474935202815541611335,809
0.14%0.18%3.82%0.00%0.09%0.17%3.04%6.43%2.57%1.06%0.81%0.08%0.01%18.66%
Network
total
1269336125,458120583130238,16257,52333,42219,68660652703293191,890
0.66%1.75%13.27%0.06%0.30%0.68%19.89%29.98%17.42%10.26%3.16%1.41%0.15%-
Table 5. Comparison of the main HTLS conductor types with ACSR.
Table 5. Comparison of the main HTLS conductor types with ACSR.
ACSRACCRG(Z)TACSRACCC/TW
Diameter (mm)22.823.922.621.79
Composition (mm)7 × 2.8 (Steel core)7 × 2.9 (Al core)7 × 2.8 (Steel core)7.11 (Core)
26 × 3.6 (Al strands)26 × 3.8 (Al strands)10 × 3.94 (Al TW)16 × 4.95 (Al TW)
19 × 3.1 (Al strands)
Cross-section (mm2)307.8338308.4355.2
Weight (kg/km)10689661098948
Rdc20 °C (Ω/km)0.10630.09450.1110.0887
Rac20 °C (Ω/km)0.10650.09710.1140.091
Ampacity (A)745133211281227
Temperature (°C)75210210180
Table 6. Main properties of the innovative conductor for transmission OHLs compared with its reference traditional conductor.
Table 6. Main properties of the innovative conductor for transmission OHLs compared with its reference traditional conductor.
ACSRACCM/TW
Diameter (mm)22.822.78
Composition (mm)7 × 2.8 (Steel core)1 × 3/6 × 2.49 (Core)
26 × 3.6 (Al strands)1 × 1 (Al shell)
-24 × 3.13 (Al layers)
Cross-section (mm)307.8345.5
Weight (kg/km)1068989
Breaking load (kN)97.52117.39
Rac20 °C (Ω/km)0.10650.0894
Ampacity (A)745994
Temperature (°C)75120
Table 7. List of the tested polymers; the highlighted ones are those with the best performance overall.
Table 7. List of the tested polymers; the highlighted ones are those with the best performance overall.
Material
Type
Permeability
(cm·cm3/(m2 24 h bar))
PEEK235
PEKK796
PPS4.2
PEI2.3
PPA9.7
Table 8. Flexural mechanical properties of the selected materials before and after the aging test.
Table 8. Flexural mechanical properties of the selected materials before and after the aging test.
MaterialFlexural Modulus (MPa)Flexural Strength (MPa)
BeforeAfterBeforeAfter
PEI3258270011089
PPS205523307030
Table 9. Main properties of the innovative conductor for distribution OHLs compared with two reference traditional conductors.
Table 9. Main properties of the innovative conductor for distribution OHLs compared with two reference traditional conductors.
Aldrey 185/37AAAC Al 3AAAC-AL-SHC
Diameter (mm)17.6415.2517.25
Composition (mm)37 × 2.5219 × 3.4519 × 3.45
Cross-section (mm2)184.5177.6177.6
Weight (kg/km)508.8488488
Breaking load (kN)52.5952.452.4
Rac20 °C (Ω/km)0.17990.18620.1724
IACS53%53%57.3%
Ampacity (A)398433450
Temperature (°C)757575
Table 10. Potentially replaceable standard ACSR conductors.
Table 10. Potentially replaceable standard ACSR conductors.
CodeCross-Section
(mm2)
External Diameter
(mm)
Breaking Load
(daN)
Electrical Resistance at 20 °C
(Ω/km)
Thermal Rating Current
IR (A)
Thermal Rating Power
PR (MW)
42/6 + 142.41916130.6766175.9113.4
68/12 + 767.6913.461950.4266322.9208.3
128/26 + 7127.615.8549090.2261407.1262.6
191/26 + 7191.219.3871220.1509531.4342.8
212/30 + 7212.02198660.1362589.6380.3
265/26 + 7264.622.897520.1090655.0422.5
Table 11. Thermal limit current for the reference conductor as for standard CEI 11-60 (Adapted with permission from [31], CEI, 2005).
Table 11. Thermal limit current for the reference conductor as for standard CEI 11-60 (Adapted with permission from [31], CEI, 2005).
Line Voltage Rating (kV)Thermal Limit Current of the Reference Conductor (A)
Zone AZone B
Period CPeriod FPeriod CPeriod F
380740985680770
220665905610710
132 ÷ 150620870575675
Table 12. Comparison between traditional and innovative conductors for HV OHLs.
Table 12. Comparison between traditional and innovative conductors for HV OHLs.
Losses ACSRACMM/TW∆%
Annual Joule Losses (AJL)(GWh)288.796234.47154.325–18.81%
Annual Cost of Losses (ACL)(M€)11.559.3792.17
Actualized Annual Cost of Losses (AACL)(M€)198.22160.93237.288
Table 13. Potentially replaceable distribution network conductors.
Table 13. Potentially replaceable distribution network conductors.
MaterialCodeCross-Section (mm2)External Diameter (mm)Breaking Load (daN)Resistance at 20 °C (Ohm/km)Thermal Rating Current IR (A)Potential Losses Reduction (%)Potential Losses Cost Savings (M€)Potential CO2 Emissions Reduction (kt)
Copper70/1968.3410.727.330.267828135.8016.820420.541
95/1994.7612.637.90.18313575.813.00075.191
Aluminium70/1968.3410.711.690.42122459.302.30022.514
95/1993.2712.515.590.308527444.401.89018.436
120/19125.5014.520.030.229233224.911.15711.282
Aldrey70/1968.3410.719.480.48420964.7010.500102.065
95/1994.7612.627.010.349125850.900.4904.758
120/19125.5014.535.770.263631034.800.3603.544
150/37147.1015.7541.930.225334423.600.2602.5285
185/37184.5017.6452.590.17973984.000.0470.457
ACSR68/12 + 767.6913.461.950.426623859.905.20050.771
128/26 + 7127.6015.8549.090.226134423.912.12118.127
Table 14. Comparison between traditional and innovative conductors for HV OHLs.
Table 14. Comparison between traditional and innovative conductors for HV OHLs.
Aldrey 185/37AAAC-SHC∆%
Annual Joule Losses (AJL)(GWh)29.31628.1461.170–4%
Annual Cost of Losses (ACL)(M€)1.1731.1260.047
Actualized Annual Cost of Losses (AACL)(M€)20.12219.3180.804
Table 15. Total cost for each traditional conductor in the study and expected benefit using the innovative one.
Table 15. Total cost for each traditional conductor in the study and expected benefit using the innovative one.
MaterialCodeAJL (GWh)ACL (M€)AACL (M€)CO2 Emissions Saving (kt)Joule Losses Potential Reduction (%)
Copper70/191174.17346.967805.900420.54135.8%
95/191294.69551.797888.60075.1915.8%
Aluminium70/1997.2833.89166.78522.51459.3%
95/19106.5524.26273.13318.43644.4%
120/19116.1314.64578.70811.28224.9%
Aldrey70/19404.60416.184277.705102.06564.7%
95/1923.9730.95916.4544.75850.9%
120/1926.1121.04417.9223.54434.8%
150/3727.4721.09918.8552.528523.6%
185/3729.3161.17320.1220.4574.0%
ACSR68/12 + 7217.3358.693149.17150.77159.9%
128/26 + 71268.93150.757870.948118.12723.9%
Total4786.577191.4713284.303830.21528.3%

Share and Cite

MDPI and ACS Style

Benato, R.; Caldon, R.; Chiarelli, A.; Coppo, M.; Garescì, C.; Dambone Sessa, S.; Mimo, D.; Modesti, M.; Mora, L.; Piovesan, F. CALAJOULE: An Italian Research to Lessen Joule Power Losses in Overhead Lines by Means of Innovative Conductors. Energies 2019, 12, 3107. https://doi.org/10.3390/en12163107

AMA Style

Benato R, Caldon R, Chiarelli A, Coppo M, Garescì C, Dambone Sessa S, Mimo D, Modesti M, Mora L, Piovesan F. CALAJOULE: An Italian Research to Lessen Joule Power Losses in Overhead Lines by Means of Innovative Conductors. Energies. 2019; 12(16):3107. https://doi.org/10.3390/en12163107

Chicago/Turabian Style

Benato, Roberto, Roberto Caldon, Antonio Chiarelli, Massimiliano Coppo, Claudio Garescì, Sebastian Dambone Sessa, Debora Mimo, Michele Modesti, Luca Mora, and Francesca Piovesan. 2019. "CALAJOULE: An Italian Research to Lessen Joule Power Losses in Overhead Lines by Means of Innovative Conductors" Energies 12, no. 16: 3107. https://doi.org/10.3390/en12163107

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop