Next Article in Journal
Machine Learning-Based Image Reconstruction in Wearable CC-EIT of the Thorax: Robustness to Electrode Displacement
Previous Article in Journal
The Validity and Reliability of the Force Plates and the Linear Position Transducer in Measuring Countermovement Depth and Velocity During Countermovement Jump
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers

1
Electric Power Research Institute, State Grid Ningxia Electric Power Co., Ltd., Yinchuan 750011, China
2
Wuzhong Power Supply Company, State Grid Ningxia Electric Power Co., Ltd., Wuzhong 751100, China
3
Key Laboratory of Special Motors and High Voltage Electrical Appliances, Ministry of Education, Shenyang University of Technology, Shenyang 110870, China
*
Author to whom correspondence should be addressed.
Sensors 2025, 25(21), 6528; https://doi.org/10.3390/s25216528
Submission received: 11 September 2025 / Revised: 10 October 2025 / Accepted: 18 October 2025 / Published: 23 October 2025
(This article belongs to the Section Electronic Sensors)

Abstract

The short-circuit withstanding capability of a transformer is a critical indicator for evaluating its operational reliability. This study investigates the influence of the low-voltage winding height, a key structural parameter, on the electromagnetic forces induced by short-circuit currents and the resultant short-circuit withstand capability. First, theoretical calculation formulas for the transformer leakage magnetic field and winding electromagnetic forces were derived, establishing a foundation for subsequent analysis. Subsequently, two 110 kV transformers, identical in all structural parameters except for their low-voltage winding heights, were selected as case studies. Three-dimensional finite element models were constructed to perform detailed simulations and a comparative analysis of the leakage magnetic field distribution and electromagnetic forces under short-circuit conditions. Finally, practical short-circuit tests were conducted on both transformers for experimental validation, monitoring and comparison of their short-circuit reactance variation curves. Furthermore, a CNN-LSTM model, utilizing the winding axial height of a 110 kV three-phase three-limb transformer as the characteristic parameter, is developed to detect short-circuit fault damage in such transformers with varying winding heights. Through a combined approach of theoretical analysis, simulation, and experimental verification, this study confirms that the low-voltage winding height was a crucial factor affecting the transformer’s short-circuit withstand capability of the transformer. Studies have shown that with the increase in the height of low-voltage windings, the leakage magnetic flux of the low-voltage windings increases by 36%, the radial electromagnetic force increases by 37.5%, and the axial electromagnetic force increases by 8.5%. Excessively tall windings amplify radial electromagnetic forces, compromising mechanical stability and consequently increasing the risk of damage during short-circuit faults.

1. Introduction

As the core equipment of a power system, the operational reliability of power transformers is directly related to the security and stability of the power grid [1]. However, transformers are inevitably exposed to short-circuit faults during operation, where immense short-circuit currents generate intense electromagnetic forces within the windings [2]. Weak links in the winding structural design or manufacturing process can lead to cumulative mechanical forces causing winding deformation, insulation damage, and even catastrophic failure. Consequently, in-depth research into the mechanical behavior of windings under short-circuit conditions, accurate assessment of their short-circuit withstand capability, and identification of key influential design factors are of paramount engineering importance for enhancing the intrinsic safety of equipment and grid reliability.
Currently, the assessment of a transformer’s short-circuit withstand capability relies primarily on methods such as computational analysis, numerical simulation, and testing. In computational analysis, accurately solving the leakage magnetic field distribution under short-circuit conditions is the fundamental basis for calculating the winding electromagnetic forces, as the morphology of the leakage field is intrinsically related to the geometric dimensions of the winding. In structural dynamics analysis, establishing a reasonable spring-mass model is crucial for efficiently predicting the winding displacement. Multiphysics coupling simulation technology based on the finite element method can simulate the internal electromagnetic-force coupling process in greater detail, providing critical insights for design optimization. The ultimate standard for validating a transformer’s short-circuit withstand capability is a standardized short-circuit test. Comparing the test results from identical equipment types with divergent outcomes can more precisely reveal the significant impact of minor design parameter variations on the overall performance.
In [3], during a brief period following a short-circuit fault in a transformer, the short-circuit current within the windings generates immense short-circuit impact forces under the influence of the magnetic field leakage, forces which act directly on the winding structure. The inability of windings to withstand this impact can lead to deformation or even damage, potentially resulting in grid incidents. To address the challenges of difficult feature extraction and insufficient diagnostic accuracy for converter transformer faults, ref. [4] proposed a fault diagnosis method based on time-frequency maps and a parallel CNN-LSTM network. Utilizing a 3D simulation, ref. [5] demonstrated the force characteristics of transformer windings under inrush and short-circuit currents, identified the primary failure modes induced by different stresses, and conducted short-circuit impact tests to validate the accuracy of the computational results. Reference [6] introduced a Convolutional Long Short-Term Memory (CNN-LSTM) neural network model for predicting the CO2 concentration at flue gas outlets. A calculation method for the axial resultant force at different axial heights of windings was proposed in [7], aimed at optimizing the structural design of power transformers. Reference [8] proposes a hybrid neural network load forecasting model based on CNN-LSTM-AM, which comprehensively considers the influence of load correlation factors in typical scenarios on charging load prediction. Using the finite element method, ref. [9] analyzed the forces on distribution transformer windings under the most severe three-phase symmetrical short-circuit conditions, while ref. [10] presented a finite element analysis for the comprehensive calculation and assessment of electromagnetic forces on transformer windings. The analysis in [11] primarily focused on the magnetic field distribution within the high-voltage side windings under short-circuit conditions on that side. Reference [12] proposed an evaluation method for cumulative mechanical damage in power transformer windings owing to short-circuit forces, considering the nonlinear characteristics and cumulative process of the windings, offering a novel approach for assessing the impact of these forces. Reference [13] summarized the mechanism of winding deformation and its relationship to mechanical strength under the most severe short-circuit conditions and determined the associated distribution of residual strain through calculation. An improved CNN-LSTM network-based transformer fault diagnosis model, enhanced by the Chimpanzee Optimization Algorithm (ChOA), was proposed in [14]. Reference [15] conducted experimental validation and finite element analysis of short-circuit forces in dry-type transformers, modeling high-voltage and low-voltage windings in segments to calculate the electromagnetic forces at corresponding positions under short-circuit conditions using FEM. A transformer winding fault diagnosis method based on Frequency Response Analysis (FRA) and Convolutional Neural Networks (CNN) was presented in [16]. Reference [17] investigated the generation mechanism of electromagnetic forces, solved for the distribution and magnitude of forces in various directions, analyzed the structural deformation caused by these forces, and clarified their impact on the selected transformer under study. The mechanical performance of the power transformer windings was calculated using a 2D magnetic field-structural force field coupling method [18]. Reference [19] proposed a hybrid CNN-LSTM model for fault diagnosis in mining transformers, which first employs a CNN to extract features from operational data, effectively capturing spatial characteristics, and subsequently utilizes an LSTM to perform temporal modeling on the extracted features, identifying dynamic variation patterns within the data. Reference [20] introduced an intelligent fault diagnosis and analysis technique based on a hybrid Long Short-Term Memory (LSTM) and Convolutional Neural Network (CNN) model, specifically focusing on its application for intelligent fault analysis in substation equipment. Reference [21] constructed a feature dataset comprising transformer top-oil temperature, ambient temperature and humidity, and load current, and established a CNN-LSTM network model to analyze the characteristic information within these data. Reference [22] investigated an intelligent assessment method for power transformer operating states using a CNN-BiGRU network. This involved initially constructing a CNN-BiGRU fusion model to compute feature importance scores for selecting significant data features, followed by incorporating an attention mechanism into the BiGRU for feature weighting and extracting correlated features. Reference [23] studied a data-driven optimal scheduling method for active distribution networks based on Convolutional Neural Networks (CNN) under multi-source uncertainties. Reference [24] proposed an anomaly detection method for UAV sensor data named CNN-LSTM-BF, based on CNN and LSTM. The designed CNN-LSTM-BF effectively leverages CNN’s capability for local feature extraction and LSTM’s proficiency in learning from time-series tasks, thoroughly mining and learning spatiotemporal features from the UAV data. Reference [25] employs CNN to extract spatial features from multi-source data, utilizes LSTM to capture temporal dynamics, and incorporates a Genetic Algorithm to optimize LSTM hyperparameters, thereby achieving spatiotemporal feature co-modeling. Reference [26], based on the principle of mirror images, established a dual two-dimensional simplified equivalent for the leakage magnetic field distribution in high-frequency transformers. By comprehensively considering the influence of high-frequency eddy current effects on the leakage magnetic energy within round Litz wires, an analytical model for calculating the dual two-dimensional leakage inductance of high-frequency transformers was developed. Reference [27] combined a Long Short-Term Memory (LSTM) network with a Convolutional Neural Network (CNN) to fully utilize their complementary advantages in extracting spatiotemporal features. Concurrently, the Grey Wolf Optimizer (GWO) was employed to optimize the model’s hyperparameters, further enhancing its predictive performance and stability. Reference [28] described a method for generating a full geometric model of a transformer, incorporating the complete three-dimensional geometry of the windings, core, and tank, and conducted a computational study on the magnetic field distribution.
Essentially, the difference in winding height (specifically referring to the axial height of the low-voltage windings in this study) directly induces alterations in the spatial distribution pattern and flux density amplitude of the transformer’s internal magnetic field. As the magnetic field serves as the fundamental source of electromagnetic forces acting on the windings, such magnetic field variations further lead to distinct differences in the magnitude, direction, and spatial distribution of the axial and radial electromagnetic forces borne by the windings during the transformer’s operation. It is important to note that although power transformers of different voltage levels (e.g., 35 kV, 110 kV, 220 kV) vary significantly in core design parameters, winding configuration, and rated operating conditions, the core mechanism by which winding height affects electromagnetic force generation—and the general variation law governing this relationship—remain consistent across voltage grades. That said, the rate of change in electromagnetic force magnitude (i.e., the sensitivity of electromagnetic force to unit winding height variation) differs notably among transformers of different voltage levels. This discrepancy primarily stems from differences in winding structural rigidity, insulation medium properties, and electromagnetic load level inherent to transformers of varying voltage classes. Based on this theoretical premise, this paper focuses on two 110 kV power transformers with identical rated capacity, core structure, and winding turns count, but with a predefined and controllable difference in low-voltage winding axial height. Under simulated short-circuit fault conditions, this study systematically tests and analyzes the evolutionary laws of key mechanical and electrical characteristic parameters of the two transformers—including winding axial displacement, inter-disc deformation, and short-circuit reactance. Through quantitative comparison of the test data and theoretical derivation of the electromagnetic force calculation model, this research explicitly confirms that winding height is a core factor regulating the distribution characteristics and amplitude of electromagnetic forces acting on transformers under short-circuit conditions.

2. Leakage Magnetic Field and Short-Circuit Forces in 110 kV Three-Phase Three-Limb Transformers

2.1. Analysis of Transformer Leakage Magnetic Field

To calculate the winding displacement under transformer short-circuit conditions, it is necessary to first perform a transient electromagnetic field calculation of the short-circuit process. For an axisymmetric steady magnetic field in the cylindrical coordinate system (z, r) plane, under nonlinear conditions, the boundary value problem satisfied by the vector magnetic potential A θ is governed by the Poisson equation:
Ω : z [ ν A θ z ] + r [ ν r ( r A θ ) r ] = J s θ + σ ; ( r A θ ) t S 1 : A θ = A θ 0 S 2 : ν r ( r A θ ) n = H 1 A t = t 0 = f 0 ( z , r )
The partial differential equation given above can be formally treated as being identical to that of a planar transient field. This treatment allows the direct application of the variational principle of the planar transient field to obtain the energy functional and conditional variational problem for the axisymmetric transient field used in the solution. The approach is as follows:
By multiplying both sides of the second equation in Formula (1) by r, and setting v′ = v/r in the first and third equations, Equation (1) is transformed into:
Ω : z [ ν ( r A θ ) z ] + r [ ν ( r A θ ) r ] = J s θ + σ ( r A θ ) t S 1 : r A θ = r A θ 0 S 2 : ν ( r A θ ) n = H 1 A t = t 0 = f 0 ( z , r )
where, Ω is the solution domain, S 1 is the first-class boundary, S 2 is the second-class boundary, H 1 is the tangential component of the magnetic field intensity, t0 is the initial time value of the transient field, A θ is the θ-axis component of in cylindrical coordinates, and J s θ is the θ-axis component of the excited current density J s in cylindrical coordinates, ν = ν r . σ = σ r .
Here, we use r A θ as the function to be solved, where ν is a function of coordinates. Thus, it has the same form as the boundary value problem of partial differential equations in planar transient fields. The following coordinates z and r are not rewritten as x and y, and at the same time A = r A θ , so that the conditional variational problem equivalent to Equation (3) can be obtained:
W ( A n + 1 ) = Ω ( 0 B ν B d B J s θ A n + 1 + σ A n + 1 2 A n 2 2 ) d x d y s 2 ( H t ) A n + 1 d s = min S 1 : A n + 1 = A 0 n + 1
where A n + 1 and A n are the place values of the n + 1 and n steps after time dispersion, respectively. Δ t is the time step.
The matrix equation of the above variational problem can be obtained using triangular linear element interpolation discretization and element analysis.
1 Δ t [ M ] e + [ K ] e A n + 1 e = P n + 1 e + 1 Δ t [ M ] e A n e
where A e is the upper value matrix of the three triangular nodes, P e is the vector matrix of the right end, and M e and K e are the coefficient matrices related to the media parameters and node coordinates.
Because there are ferromagnetic materials in the field studied, the saturation problem will occur, therefore, the above equation is a set of nonlinear algebraic equations. The modified Newton-Raphison iterative method was adopted to solve the problem, and the bit value A on each node in the field was obtained. The magnetic flux density at any position in the region can be obtained using the following formula B = × A :
B = A x 2 + A y 2 = 1 2 Δ b , A , + b j A j + b m A m 2 + c , A j + c j A j + c m A m 2 ( T )

2.2. Calculation of Axial Electromagnetic Forces in Transformers with Non-Equal Winding Heights

As shown in Figure 1, the following presents the schematic diagrams of transformer core structures corresponding to different core structures and different voltage levels.
As illustrated in Figure 1, the three-phase three-limb transformer core structure is applicable to voltage levels covering 10 kV, 20 kV, 35 kV, 110 kV, and 220 kV. It is primarily employed in low-voltage, medium-voltage, and high-voltage power distribution and transmission scenarios, capable of meeting the requirements for electrical energy transmission and distribution across different voltage tiers. The applicable voltage levels for wound-core transformers are concentrated at 0.4 kV, 10 kV, 20 kV, and 35 kV. Their structural characteristics dictate that their primary application domain is end-point power distribution, often deployed at the terminus of the power delivery chain to provide a stable electricity supply at the user side. The voltage ratings for toroidal transformers are confined to lower levels such as 1 kV, 3 kV, 6 kV, and 10 kV. Limited by their structural scale and magnetic circuit properties, they primarily serve applications including electronic equipment power supplies, residential electricity needs, and small-scale industrial production, catering to low-voltage, low-capacity power requirements. Despite significant differences in structural characteristics and applicable voltage levels among transformers with different core forms, the fundamental computational principles and methodologies for determining leakage magnetic fields, axial electromagnetic forces, and radial electromagnetic forces remain consistent. Variations solely arise from differences in input parameters, such as core structural details and voltage level, during specific calculations, ultimately manifesting as numerical differences in the results rather than representing inherent disparities in the underlying computational logic or methodological framework.
In transformers, if the influence of the core attraction is neglected, the ideal magnetomotive force (MMF) distribution is trapezoidal and uniform in the radial direction; a similar linear variable distribution applies to the magnetic flux density. When the effects of the flux line bending at the ends are neglected and only the flux is considered, the average value of the maximum magnetic flux density in the main duct is:
B m = 2 μ 0 N I H 12 ρ ( T )
where μ0 = 4π × 10−7 H/m is the vacuum permeability, applicable to spaces occupied by transformer insulating liquid and insulating materials; NI represents the ampere-turns of the winding; H12 is the geometric mean height (m) of the windings. ρ denotes the Rogowski coefficient, which serves to correct the magnetic flux; λ = d + a1 + a2 is the leakage magnetic field width (m). The Rogowski coefficient was calculated as follows:
ρ = 1 λ π H 12 1 e π H 12 λ
As shown in Figure 2, for a pair of windings, the outer winding is lower at its top end by δ (m) compared to the inner winding, i.e., H1 = H2 + δ, resulting in a non-uniform distribution of magnetomotive force (NI) along the winding height. Based on leakage magnetic field analysis, the winding magnetomotive force can be decomposed into axial and radial components. Consequently, the corresponding short-circuit inductance comprises an axial inductance La originating from the axial flux density and a radial inductance La originating from the radial flux density, leading to the following expression:
L k = L a + L 1 ( H )
The total axial force is
F k = F a + F 1 ( kN )
According to Equation (6), it follows that
L a = μ 0 π N 2 ρ a D 12 Δ H 1 ( H )
where the Rogowski coefficient ρ is calculated using Equation (7). Differentiating the magnetic field energy of La with respect to H1 yields:
F a = 1 2 μ 0 π ( 2 k ) 2 r 2 ( N r ) 2 ρ a Δ D 12 H 1 2 ( kN )
According to the calculation of reactance, the radial inductance is
L 1 = μ 0 π N 2 Δ D 12 3 λ ρ 1 δ 1 2 H 1 ( H )
where λ represents the transverse leakage magnetic field length, λ = d +a1 +a2; ρ1 denotes the Rogowski coefficient for the transverse leakage magnetic field. The Rogowski coefficient ρ1 is calculated as follows:
ρ 1 = 1 1 π u 1 e π u 1 0.5 e 2 π ν 1 e π u
where u = λ/h1 and v = S/h1. Here, S denotes the distance (m) from the inner winding to the core, given by S = 0.0003Dc + (D1Dc)/200, where Dc is the core diameter (m); D1 is the inner diameter (m) of the winding adjacent to the core; and h1 is the axial height (m) of the leakage magnetic field.
The axial force generated by the asymmetric leakage magnetic field distribution causes the winding to exhibit an outward thrust tendency towards the yoke. Therefore, when considering this axial force, it is necessary to differentiate the magnetic field energy within the dimensional range of λ. When the RMS value of the short-circuit current is I, according to the Lagrangian equation, we have:
F = 1 2 2 I 2 L 1 δ 1 = 1 2 2 I 2 L 1 δ 1 = μ 0 π 2 N I 2 ρ a Δ D 12 H 1 ρ 1 δ 1 3 ρ a λ ( kN )
Introducing I = krIr, then there is
F 1 = μ 0 π ( 2 k ) 2 r 2 ( N I r ) 2 ρ a Δ D 12 H 1 ρ 1 δ 1 3 ρ a λ ( kN )
Substituting the formula Fa = SL/H12Zpu × 10−2 (kN), we obtain
F 1 = F a 2 ρ 1 H 1 δ 1 3 ρ a λ Δ ( kN )
F k = F a 1 + 2 ρ 1 H 1 δ 1 3 ρ a λ Δ = F a k δ ( kN )
k δ = 1 + 2 ρ 1 H 1 δ 1 3 ρ a λ Δ ( kN )
Serves as an adjustment coefficient for non-uniform leakage magnetic field distribution.
Since the electrical force generated by the short circuit current is related to its instantaneous value, we should try to find the maximum instantaneous value of the short circuit current to the maximum instantaneous value of the short circuit after half a cycle, when f = 50   Hz , this time should be 0.01 s. The maximum instantaneous value of this short-circuit current is also called the impulse short-circuit current i ch , and its value should be;
i ch = U m Z sin ( π π 2 ) + U m Z e R L 0.01 = U m Z ( 1 + e R L 0.01 ) = U m Z K ch ( A )
where, K ch = 1 + e R L 0.01 is the impact coefficient of the short-circuit current, 2 K ch is the impact coefficient of the asymmetric short circuit current, X is the sum of the transformer’s reactance Xt and the system’s reactance Xs, R is the sum of the transformer’s resistance Rt and the system’s resistance Rs, U m is the amplitude of the supply voltage, U is the square mean root value of the supply voltage, and I d is the square mean root value of the period component of the short circuit current.
The current in the winding generates an axial leakage flux Bx, and By interacts with the current in the winding to generate radial force Fx. The radial force causes the outer winding to extend around along the radial direction, and the inner winding to compress inward along the radial direction, so the radial force will finally expand the insulation distance of the main air channel.
The radial force per unit length of cake was obtained using the Lorentz force formula.
F x = B y max i ch ( N )
where Bymax is the maximum axial magnetic induction intensity in the case of a sudden short circuit and ich is the maximum short circuit current in the case of a sudden short circuit.
The axial force per unit length can be obtained according to Lorentz force formula.
F y = B x max i ch ( N )
where, Bxmax is the maximum radial magnetic induction intensity for a sudden short circuit. ich Indicates the maximum short circuit current when a sudden short circuit occurs.
An increase in the leakage magnetic field intensity within a transformer leads to a marked rise in both axial and radial electromagnetic forces. Under conventional design and rated operating conditions, the transformer leakage magnetic field is typically maintained below 1 T; however, exceeding this 1 T threshold triggers a sharp escalation in axial and radial electromagnetic forces. Under such circumstances, the probability of structural failure or functional damage to the transformer exceeds 90%. Consequently, during the transformer design phase, it is imperative to rigorously control the leakage magnetic field intensity through technical measures such as optimizing the magnetic circuit structure and rationally configuring winding arrangements. This prevents excessive amplification, thereby ensuring the structural integrity and long-term operational reliability of the transformer.

3. Simulation and Calculation of Transformer Leakage Magnetic Field and Short-Circuit Forces Based on the Finite Element Method

This study utilized two three-phase three-limb transformers with a capacity of 50,000 kVA and a rated voltage of 110 kV. Finite element software was employed to model and simulate the windings, core, and spacers of the main transformer. The specific model types and parameters of the transformers are detailed in Table 1 and Table 2.
As detailed in Table 1 and Table 2, Transformers A and B, both three-phase three-limb types, exhibit virtually identical electrical parameters, however, they differ in their low-voltage winding heights.

3.1. Model Construction

Based on the electrical data of the transformers provided in Table 1 and Table 2, three-dimensional models of two 110 kV three-phase three-limb transformers were constructed. During model development, certain factors such as the winding method and commutation were neglected to simplify the model and enhance computational efficiency. Structural components with a minor influence on the magnetic field, including end rings, pressure plates, and lead-out terminals, were also excluded from consideration. A three-dimensional model of the 110 kV three-phase three-limb transformer is shown in Figure 3.
After the three-dimensional models of the two 110 kV three-phase three-limb transformers were constructed, simulations of the magnetic field leakage were performed, taking into account the B-H curve of the core and the stress–strain curves of the windings. The results of the leakage magnetic field simulation were subsequently imported into the structural mechanics field to calculate the mechanical characteristics of the transformers under short-circuit conditions.

3.2. Comparison of Leakage Magnetic Field Simulation Results

When the primary winding of a transformer is energized, a magnetic flux is established within the core. The main flux was generated by the excitation voltage. Leakage flux refers to the flux that closes its path through air or other non-magnetic mediums when load current flows in the windings; it directly influences the magnitude of electromagnetic forces acting on the coils. During a short-circuit fault, the short-circuit current interacts with the radial component of the leakage flux, generating axial short-circuit electromagnetic forces, which can cause mechanical damage to the winding structure.
Figure 4 shows the electromagnetic simulation results for Transformers A and B under low-voltage short-circuit conditions. Figure 4a shows the magnetic flux density nephograms of Transformer A’s windings, with a maximum leakage flux density of 0.391 T. Figure 4c shows the magnetic flux density nephograms of Transformer B’s windings, revealing a maximum leakage flux density of 0.402 T. Figure 4b,d illustrates the three-dimensional nephogram of the magnetic flux density in the core.
Figure 5 presents a comparative analysis of the axial and radial leakage magnetic field simulation results for the low-, medium-, and high-voltage windings of Transformers A and B. Considering the varying amplitudes of leakage magnetic fields inside and outside the transformer window, data collection points were set at the locations of maximum leakage flux occurrence in each winding. This approach ensures an accurate representation of the leakage magnetic field distribution in both the transformers.
As shown in Figure 5, a comparative analysis of the leakage magnetic field simulations for the two 110 kV transformers under short-circuit conditions reveals the following peak values: for Transformer A, the axial leakage flux densities are 0.018, 0.019, and 0.02 T for the low-, medium-, and high-voltage windings, respectively, while the radial leakage flux densities are 0.34 T, 0.41 T, and 0.23 T. The corresponding values for Transformer B are 0.012 T, 0.014 T, and 0.016 T (axial) and 0.25 T, 0.29 T, and 0.18 T (radial). The axial leakage magnetic field exhibits a distribution that is highest in the middle of the winding height and decreases towards both ends. This is fundamentally because the low magnetic reluctance of the core yoke creates a “short-circuit effect,” significantly weakening the magnetic field at the end regions, while the mid-section of the winding, governed by Ampère’s circuital law, exhibits the highest leakage flux intensity. The radial leakage magnetic flux densities of Transformer A are consistently greater than those of Transformer B. The radial leakage magnetic field was characterized by higher values at the ends and lower values in the middle. This occurs because the axial flux lines at the end regions are obstructed by the yoke, forcing them to bend and spread out, thereby generating a strong radial component. In the central region, the flux lines are parallel to the axial direction, causing the radial components to cancel each other out.
Owing to the difference in the low-voltage winding height, both the axial and radial leakage magnetic fields of Transformer A are greater than those of Transformer B. This is attributed to the increased magnetic conductance effect and the enhanced end region flux line bending effect caused by the taller low-voltage winding in Transformer A, resulting in a significantly stronger leakage magnetic field under short-circuit conditions compared to Transformer B.

3.3. Simulation Calculation Comparison of Electromagnetic Force for 110 kV Transformers

Figure 6 shows the simulated electromagnetic force results for Transformers A and B under short-circuit conditions. According to the analysis, the end disks of the windings exhibited a relatively minor influence from radial electromagnetic forces, whereas the middle disks experienced significantly greater effects from these forces. The end disks were subjected to substantial axial electromagnetic forces, whereas the middle disks were subjected to comparatively smaller axial electromagnetic forces.
Figure 7 presents the simulation results for the axial and radial electromagnetic forces on the low-, medium-, and high-voltage windings of the transformer. The electromagnetic force distribution nephogram was obtained through magnetic-force coupling using the leakage magnetic field as the input result. The data collection points remain consistent with those mentioned above to ensure an accurate representation of the leakage magnetic field distribution in both transformers.
As shown in Table 3, the comparative analysis of electromagnetic force simulations under short-circuit conditions for the two 110 kV transformers reveals the following peak values. For Transformer A, the axial electromagnetic force densities are 3.97 × 106 N/m3, 3.98 × 106 N/m3, and 3.76 × 106 N/m3 for the low-, medium-, and high-voltage windings, respectively, while the radial electromagnetic force densities are 2.2 × 106 N/m3, 1.7 × 106 N/m3, and 1.52 × 106 N/m3, respectively. The corresponding values for Transformer B are 3.66 × 106 N/m3, 3.73 × 106 N/m3, and 3.52 × 106 N/m3 (axial) and 1.6 × 106 N/m3, 1.25 × 106 N/m3, and 1.12 × 106 N/m3 (radial). The axial electromagnetic force distribution in 110 kV transformer windings exhibits a non-uniform characteristic over one cycle: greater forces act on the end regions, whereas smaller forces were observed in the middle section. Conversely, the radial electromagnetic forces were smaller at the ends and larger in the middle section of the windings. According to Ampère’s force law, the distribution trends of both the axial and radial forces on the windings are closely related to the radial magnetic flux and axial leakage flux density.
Owing to the difference in the low-voltage winding height, both the axial and radial leakage magnetic fields of Transformer A greater than those of Transformer B. Based on the Lorentz force law, this results in significantly larger axial and radial electromagnetic forces acting on Transformer A transformer B.

4. Field Testing and Algorithmic Prediction for 110 kV Three-Phase Three-Limb Transformers

4.1. Field Testing of 110 kV Transformers

Figure 8 presents the wiring diagram of two 110 kV transformers utilized in the short-circuit impulse test, with the connection group of these two transformers being of the YNyn0d11 type.
Factory acceptance tests were conducted on two 110 kV transformers to verify that their windings and supporting structures would not undergo permanent deformation, displacement, or damage when subjected to immense electrodynamic stresses generated by sudden short-circuit currents. Figure 9 shows the transformer configured for the factory short-circuit test.
Both transformers were operated under the conditions of high-voltage side energized and low-voltage side short-circuited. A series of 15 short-circuit impulse tests were conducted on the 110 kV transformers, and the resulting reactance variation is illustrated in Figure 10.
As shown in Figure 9, short-circuit reactance tests conducted on two 110 kV transformers showed that during the 1st impulse, Transformer A—due to its higher low-voltage winding—experienced a decrease in reactance from 104.1 Ω to 104.0 Ω, while Transformer B only saw a slight drop to 104.05 Ω. During the 2nd impulse, Transformer A’s reactance continued to decrease to 103.95 Ω, with initial terminal displacement emerging, whereas Transformer B’s reactance fell to 104.0 Ω and still maintained a rigid structure. The 3rd to 5th impulses marked the entry into the “irreversible structural compaction stage”: Transformer A’s reactance decreased sequentially to 103.9 Ω, 103.85 Ω, and 103.8 Ω, with the gap between winding discs narrowing, while Transformer B’s reactance only decreased gently to 103.98 Ω, 103.95 Ω, and 103.92 Ω, with deformation being mainly reversible. The 6th to 10th impulses entered the “deformation transition stage”: Transformer A’s reactance decreased rapidly to 103.75 Ω, 103.7 Ω, 103.65 Ω, 103.6 Ω, and 103.5 Ω, while Transformer B’s reactance decreased slowly to 103.9 Ω, 103.88 Ω, 103.85 Ω, 103.82 Ω, and 103.8 Ω, maintaining a stable attenuation rate throughout. During the 11th to 15th impulses, Transformer A—due to accumulated structural damage—saw its reactance decay rapidly to 103.4 Ω, 103.3 Ω, 103.25 Ω, 103.2 Ω, and 103.178 Ω, while Transformer B still exhibited a gentle decreasing trend, with its reactance dropping to 103.78 Ω, 103.75 Ω, 103.7 Ω, 103.5 Ω, and 103.157 Ω. Although their final reactance values were close, Transformer A exhibited the characteristic of “gentle decrease in the early stage, accelerated decrease in the middle stage, and sharp decrease in the later stage” throughout the process, attributed to the difference in electromagnetic force caused by its winding height, whereas Transformer B maintained a linear and gentle attenuation consistently. These results intuitively reflect the influence of low-voltage winding height on the structural stability and reactance variation law of transformers under short-circuit impulse conditions.
As shown in Figure 11, the two 110 kV transformers subjected to short-circuit impulses were hoisted and disassembled to examine the internal conditions of their windings.
As shown in Figure 11, the hoisting inspection results after 15 short-circuit impulses on the two 110 kV transformers reveal significant differences in the mechanical integrity of their windings. For Transformer A, a noticeable radial instability deformation occurred in the middle section of the high-voltage winding, accompanied by fragmentation of the inter-disk insulation spacers and fracture of the axial insulation support strips. The low-voltage winding exhibited overall axial displacement, with loosening traces observed on the pressure plate and pressing bolts, indicating failure of its axial compression system. In contrast, no visible deformation was observed in the high-, medium-, and low-voltage windings of Transformer B, with intact insulation structures and the absence of any structural damage. These results confirm that the winding height is a critical factor affecting the short-circuit withstand capability of the transformers. An excessive winding height significantly increases the leakage flux and corresponding electromagnetic forces, making the insulation support system more prone to failure. An optimized winding design can effectively suppress the mechanical responses under short-circuit impacts, thereby enhancing equipment reliability.

4.2. Short-Circuit Experimental Diagnosis for 110 kV Transformers Based on Dual Convolutional Neural Network-Long Short-Term Memory Architecture

4.2.1. Model Principle

Convolutional Neural Networks (CNNs) are widely employed in equipment fault diagnosis owing to their strengths in local feature extraction, parameter sharing mechanisms, and multi-kernel architectures. Compared with traditional fully connected networks, CNNs reduce the number of model parameters and enhance the training speed through feature mapping and spatial down sampling operations. The standard CNN architecture consists of an input layer and multiple alternating convolutional and pooling layers and concludes with fully connected layers to produce the output. The network structure is shown in Figure 12.
This study proposes a fault diagnosis model based on a Dual Convolutional Neural Network-Long Short-Term Memory (CNN-LSTM) architecture, utilizing the axial heights of the high-, medium-, and low-voltage windings of 110 kV transformers. The network structure is shown in Figure 13.
The CNN-LSTM evaluation model proposed in this study constructs a multi-scale spatiotemporal feature joint analysis framework by integrating the spatial feature extraction capability of convolutional neural networks with the temporal modeling advantages of long short-term memory networks. The diagnostic workflow for short-circuit tests is shown in Figure 14.
The fault diagnosis process primarily consists of four components: data augmentation, data preprocessing, neural network optimization training, and risk assessment validation. The specific evaluation procedure is as follows.
(1) Gaussian noise injection technology is employed to augment the original training samples, thereby enhancing the generalization performance of the convolutional long short-term memory hybrid neural network.
(2) Data Preprocessing: Stratified random sampling was implemented to construct the training and independent test sets. A feature matrix was built from the bushing temperature and dielectric loss signals, and the max min normalization method was applied to linearly map multidimensional features to the [0, 1] interval, eliminating the impact of dimensional differences on model learning.
(3) Network Training: Key optimization variables were identified as the learning rate, L2 regularization coefficient, number of hidden neurons, batch size, and training epochs. The Sparrow Search Algorithm (SSA) was introduced to explore this multidimensional parameter space through multi-objective optimization. This algorithm simulates the foraging-vigilance behavior mechanism of sparrow populations to achieve a global optimum search within predefined parameter boundaries. For secondary parameters such as the learning rate decay factor and its update cycle, heuristic adjustments were made based on domain prior knowledge, employing a combination of grid search and trial-and-error methods to achieve refined model performance enhancement.
(4) The CNN-LSTM diagnostic model was constructed based on the optimal hyperparameter combination output by SSA, and network training was completed using the backpropagation algorithm. After model convergence, an independent test set was used for multidimensional performance evaluation, with a focus on core metrics such as fault pattern recognition accuracy and misclassification cost. Upon completion of network training, fault diagnosis testing was performed on the network using the test set.
The hyperparameter optimization of CNN-LSTM using SSA comprises two primary steps:
(1) Parameter Initialization: Set key parameters (population size Nm, discoverer proportion PD, sentinel proportion SD, early warning threshold R2, maximum iterations Tt), generate the initial population via the initialization function, while simultaneously constructing the CNN-LSTM diagnostic model framework and defining the search ranges for hyperparameters such as learning rate, number of hidden neurons, and L2 regularization coefficient;
(2) Parameter Optimization: The preprocessed time-series data are fed into the network for end-to-end training, using the weighted classification error rate as the optimization objective function. The algorithm terminates upon reaching Tt iterations, and outputs the optimal hyperparameter combination.
The final trained network parameters through optimization using the SSA algorithm and empirical values are presented in Table 4.
To validate the effectiveness and accuracy of the algorithm, this study employed a Receiver Operating Characteristic (ROC) curve for result evaluation. The ROC curve evaluation system was based on four core metrics: True Positive Rate (TPR), True Negative Rate (TNR), False Positive Rate (FPR), and False Negative Rate (FNR). The definitions of these metrics are as follows.
True Positive Rate (TPR): The proportion of samples correctly predicted as positive out of the total number of actual positive samples, calculated as:
TPR = TP TP + FN
True Negative Rate (TNR): The proportion of samples correctly predicted as negative out of the total number of actual negative samples, calculated as:
TNR = TN TN + FP
False Positive Rate (FPR): The proportion of negative samples incorrectly predicted as positive out of the total number of actual negative samples, calculated as:
FPR = FP FP + TN
False Negative Rate (FNR): The proportion of positive samples incorrectly predicted as negative out of the total number of actual positive samples, calculated as:
FNR = FN TP + FN
Because there are five typical failure modes for high-voltage bushings (overheating due to insulation moisture, poor contact between the high-voltage bushing and the “Jiangjunmao”, poor contact between the high-voltage bushing and the raising seat, bending of the high-voltage conductive rod under force, and manufacturing defects in the high-voltage conductive rod), the True Positive Rate (TPR) and False Negative Rate (FNR) for each failure mode can be observed via a confusion matrix by monitoring these two core metrics among the five fundamental indicators.
The global fault accuracy can be calculated using the five fundamental metrics, as shown in Equation (26):
Acc = o = 1 4 ( TP o + TN o ) o = 1 4 ( TP o + FN o + FP o + TN o )
where Acc denotes the fault diagnosis accuracy, and TPo, FNo, FPo, and TNo represent the number of True Positives, False Negatives, False Positives, and True Negatives for the o-th fault category, respectively.
Based on the aforementioned analysis, the confusion matrix and accuracy (Acc) were elected as evaluation metrics for the fault diagnosis results.

4.2.2. Diagnosis Results and Analysis

The CNN-LSTM model was trained on the short-circuit experimental data of 110 kV three-phase three-limb transformers, and the variation curve of the fitness function with increasing iteration count is shown in Figure 15.
As shown in Figure 14, the fitness function converged to a stable value after 174 iterations of the algorithm. The accuracy rates of the training and test sets are shown in Figure 16.
As indicated in Figure 16, the CNN-LSTM model achieved a training set accuracy of 96.32% and a test set accuracy of 91.82%, validating its effectiveness in assessing the winding damage accuracy during short-circuit tests on 110 kV three-phase three-limb transformers.

5. Conclusions

This study establishes a comprehensive research framework integrating theoretical analysis, simulation, and experimental validation to investigate the short-circuit withstand capability of windings in two 110 kV power transformers under short-circuit conditions. The conclusions are as follows.
(1) Finite element calculations revealed distinct leakage magnetic field distributions between the two transformers. Transformer A exhibits axial leakage flux peaks of 0.018 T, 0.019 T, and 0.02 T for its low-, medium-, and high-voltage windings, respectively, with radial peaks of 0.34 T, 0.41 T, and 0.23 T. Corresponding values for Transformer B are 0.012 T, 0.014 T, and 0.016 T (axial) and 0.25 T, 0.29 T, and 0.18 T (radial). The disparity in low-voltage winding height results in Transformer A’s axial and radial leakage fields exceeding those of Transformer B. This is attributed to enhanced magnetic conductance and intensified flux line bending at the ends caused by the taller winding in Transformer A, which ultimately leads to significantly stronger leakage fields during short-circuit events.
(2) Electromagnetic-force coupling simulations under short-circuit conditions show that Transformer A experiences axial electromagnetic force densities of 3.97 × 106 N/m3, 3.98 × 106 N/m3, and 3.76 × 106 N/m3 for its low-, medium-, and high-voltage windings, respectively, with radial force densities of 2.2 × 106 N/m3, 1.7 × 106 N/m3, and 1.52 × 106 N/m3. Transformer B demonstrates values of 3.66 × 106 N/m3, 3.73 × 106 N/m3, and 3.52 × 106 N/m3 (axial) and 1.6 × 106 N/m3, 1.25 × 106 N/m3, and 1.12 × 106 N/m3 (radial). The elevated leakage magnetic fields in Transformer A, resulting from its taller low-voltage winding, generate substantially greater axial and radial electromagnetic forces than Transformer B, as governed by the Lorentz force law.
(3) Short-circuit tests monitoring reactance changes demonstrate that the transformer with shorter low-voltage windings exhibits stable, minimal reactance variations and passes the test successfully. In contrast, the transformer with taller windings showed significant reactance jumps and progressive attenuation after multiple impulses, exceeding the total change limit and indicating invisible winding deformation, which is consistent with the simulation predictions.
(4) A CNN-LSTM model utilizing the axial winding height of 110 kV three-phase three-limb transformers as a feature parameter achieved a fault diagnosis accuracy of 91.82% in detecting short-circuit damage across transformers with varying winding heights.
(5) Conventional assessments of short-circuit withstand capability primarily consider factors such as conductor type and short-circuit current magnitude [29,30], often overlooking the critical influence of winding height. This paper, based on simulation and experimental validation using two 110 kV transformers, demonstrates the significant impact of winding height on transformer short-circuit performance. Finally, a CNN-LSTM model, utilizing winding height as an input parameter, is employed for fault diagnosis in the 110 kV transformers. This research reveals that an increase in the low-voltage winding height of the 110 kV transformers leads to a 36% rise in leakage magnetic flux, a 37.5% increase in radial electromagnetic force, and an 8.5% growth in axial electromagnetic force.

Author Contributions

Conceptualization, Y.M.; methodology, X.Z.; software, X.W.; validation, T.T.; formal analysis, C.T.; investigation, D.C.; resources, Z.X.; data curation, S.W.; writing—original draft preparation, S.W.; writing—review and editing, D.C.; visualization, Z.X.; supervision, X.Z.; project administration, Y.M.; funding acquisition, X.Z. All authors have read and agreed to the published version of the manuscript.

Funding

This paper is funded by the technology project of State Grid Ningxia Electric Power Co., Ltd., project No. 5229DK24000P.

Data Availability Statement

The data presented in this study (including raw data of short-circuit impulse tests for 110 kV transformers, 3D finite element simulation datasets of leakage magnetic field and electromagnetic force, and winding deformation observation records after disassembly) are unavailable to the public due to commercial and technical confidentiality agreements with the project cooperative unit (State Grid Ningxia Electric Power Co., Ltd.). These data involve proprietary technical parameters and experimental results related to power transformer operation, which are not permitted for open release. Requests to access the datasets can be directed to the corresponding author, Dezhi Chen (email: chendezhi@sut.edu.cn), and will be considered after obtaining written approval from the cooperative unit.

Conflicts of Interest

Yukun Ma, Xiu Zhou, and Tian Tian were employed by State Grid Ningxia Electric Power Co., Ltd., Electric Power Research Institute. Xiaokang Wang and Chenfan Tai were employed by State Grid Ningxia Electric Power Co., Ltd., Wuzhong Power Supply Company. Dezhi Chen, Ziyuan Xin, and Sijun Wang were employed by the Key Laboratory of Special Motors and High Voltage Electrical Appliances, Ministry of Education, Shenyang University of Technology (a non-commercial academic institution). The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Sun, Z. Research on Cumulative Effects and Short-Circuit Strength of Transformers Under Repeated Short-Circuit Shocks. Master’s Thesis, Shenyang University of Technology, Shenyang, China, 2024. [Google Scholar]
  2. Li, P.; Sui, H.Z.; Xu, Z.Y.; Li, L.D.; Wang, K.; Wang, Z.X.; Zhang, S.Q.; Zhao, Z.G. Cumulative Effects on Transformer Windings Based on Equivalent Short-Circuit Tests. Proc. CSEE 2025, 45, 2411–2423. (In Chinese) [Google Scholar] [CrossRef]
  3. Wang, M.; Vandermaar, A.J.; Srivastava, K.D. Review of condition assessment of power transformers in service. IEEE Electr. Insul. Mag. 2002, 18, 12–25. [Google Scholar] [CrossRef]
  4. Cui, P.; Wu, M.K.; Lu, H.J.; An, Y.; Cao, Z.; Feng, X.; Feng, R. Fault Diagnosis of Converter Transformers Based on Time-Frequency Maps and Parallel CNN-LSTM. Ningxia Electr. Power 2025, 53–59+66. [Google Scholar]
  5. Guimarães, R.; Delaiba, A.C.; Rosentino, A.J., Jr.; Saraiva, E.; de Oliveira, J.C. Electromechanical stress intransformers caused by inrush and short circuit currents. J. Braz. Mech. Sci. Eng. 2015, 37, 243–253. [Google Scholar] [CrossRef]
  6. Li, Z.Y.; Meng, J.; Yang, X.D.; Ma, G.; Liu, S.J. Prediction of CO2 Concentration in Combustion Flue Gas Based on CNN-LSTM Model. J. Combust. Sci. Technol. 2025, 31, 406–414. [Google Scholar]
  7. Ahn, H.M.; Kim, S.Y.; Kim, J.K.; Oh, Y.H.; Hahn, S.C. Numerical investigation for transient electromagnetic force computation of power transformer during short-circuitcondition. Int. J. Appl. Electromagn. Mech. 2016, 52, 1141–1149. [Google Scholar] [CrossRef]
  8. Cheng, T.L.; Li, C.R.; Fu, Q.Q.; Jiang, Y.H.; Liu, J.J. Electric Vehicle Charging Load Prediction Based on CNN-LSTM-AM. Auto Electr. Parts 2025, 10, 62–64. (In Chinese) [Google Scholar] [CrossRef]
  9. Sinha, A.; Kaur, S. Analysis of short circuit electromagnetic forces in transformer with asymmetrically placed windings using Finite Element Method. In Proceedings of the 2016 Second International Innovative Applications of Computational Intelligence onPower, Energy and Controls with their Impact on Humanity (CIPECH), Ghaziabad, India, 18–19 November 2016; IEEE: New York, NY, USA, 2016; pp. 101–105. [Google Scholar]
  10. Gao, S.G.; Sun, L.; Liu, H.L. Calculation of Axial Electromagnetic Force in Transformers under Short-Circuit Conditions Based on COMSOL Multiphysics Simulation. Sci. Technol. Eng. 2022, 22, 5250–5256. [Google Scholar]
  11. Komurgoz, G.; Gundogdu, T. Effect of the tap winding configurations on the electromagnetic forces acting on the concentric transformer coils. In Proceedings of the 2013 3rd International Conference on Electric Power and Energy Conversion Systems, Istanbul, Turkey, 2–4 October 2013; IEEE: New York, NY, USA, 2013. [Google Scholar]
  12. Medeiros, L.H.; Maschio, G.; Oliveira, M.M.; Kaminski, A.M., Jr.; Bueno, D.M.; Bender, V.C.; Marchesan, T.B. Finite element analysis for calculation of total and distributed electromagnetic forces on power transformers windings arrangements. Electr. Eng. 2024, 106, 931–940. [Google Scholar] [CrossRef]
  13. Bakshi, A. An Investigation of Winding Curvature Effect on the Mechanical Strength of Transformer Windings. IEEE Trans. Power Deliv. 2015, 30, 1821–1826. [Google Scholar] [CrossRef]
  14. Liu, Y.R.; Chi, C.C. Transformer Fault Diagnosis Method Based on ChOA-CNN-LSTM. J. Shanghai Dianji Univ. 2025, 28, 142–147. [Google Scholar]
  15. Ahn, H.M.; Oh, Y.H.; Kim, J.K.; Song, J.S.; Hahn, S.C. Experimental Verification and Finite Element Analysis of Short-Circuit Electromagnetic Force for Dry-Type Transformer. IEEE Trans. Magn. 2012, 48, 819–822. [Google Scholar] [CrossRef]
  16. Qiu, S.X.; Wang, S.; Liu, Z.R.; Yu, Z.; Dong, W.; Liu, J. Research on Transformer Winding Fault Diagnosis Based on FRA Method and CNN. Large Electr. Mach. Hydraul. Turbine 2025, 108–116+122. [Google Scholar]
  17. Yadav, S.; Mehta, R.K. FEM Based Study of Short Circuit Forces on Power Transformer Windings. In Proceedings of the 2019 3rd International Conference on Recent Developments in Control, Automation & Power Engineering (RDCAPE), Noida, India, 10–11 October 2019. [Google Scholar]
  18. Chen, Q.; Wang, S.; Lin, D.; Wang, S.; Wang, S.; Yuan, D.; Li, H. Analysis of mechanical characteristics of transformer windings undershort circuit fault. In Proceedings of the 2018 12th International Conference on the Properties and Applications of Dielectric Materials (ICPADM), Xi’an, China, 20–24 May 2018; IEEE: New York, NY, USA, 2018. [Google Scholar]
  19. Sun, P.; Liu, C.R.; Ma, J.M. Fault Diagnosis of Mining Transformers Based on Convolutional Neural Network and LSTM Network. Met. Mine 2025, 168–173. [Google Scholar] [CrossRef]
  20. Jiao, X.B.; Zhang, W.F.; Chang, F.H.; Li, Q.; Ge, Q. Application Research on Intelligent Fault Diagnosis of Substation Equipment Based on LSTM-CNN Model. Home Appl. Repair 2025, 128–130. [Google Scholar]
  21. Wang, F.; Cai, Q.N. Research on Transformer Oil Temperature Prediction Based on AIoT Cloud Platform and CNN-LSTM. Transformer 2025, 62, 21–26. [Google Scholar] [CrossRef]
  22. Liu, H.R.; Cheng, H.T.; Xiao, Y.J.; Zhou, B. Intelligent Evaluation Method for Power Transformer Operation Status Based on CNN-BiGRU Network. Electr. Eng. Econ. 2024, 226–228. [Google Scholar]
  23. Ni, X.Y. CNN Data-Driven Optimal Strategy for Active Distribution Network Under Multi-Source Uncertainties. Master’s Thesis, Guangxi University, Nanning, China, 2024. [Google Scholar] [CrossRef]
  24. Wu, M.D.; Zou, P.; Zhao, Z. Anomaly Detection Model for UAV Sensor Data Based on CNN-LSTM-BF. J. Chongqing Technol. Bus. Univ. (Nat. Sci. Ed.) 2025, 1–9. Available online: https://link.cnki.net/urlid/50.1155.n.20250818.1619.006 (accessed on 9 October 2025).
  25. Wang, H.J. Reservoir Landslide Displacement Prediction Based on GA-CNN-LSTM. Shaanxi Water Resour. 2025, 10, 18–21. (In Chinese) [Google Scholar] [CrossRef]
  26. Zhang, P.N.; Li, P.Y.; Liu, Z.; Zhang, J.; Cao, Q.; Li, L. Dual Two-Dimensional Analytical Model for Leakage Inductance Calculation of High-Frequency Transformers with Round Litz Wires. High Volt. Eng. 2025, 51, 75–87. [Google Scholar] [CrossRef]
  27. Luo, W.B.; Li, L.; Zhang, Y.H.; Tong, L.; Wu, K. Time Series Prediction of Diaphragm Wall Deformation Based on GWO-LSTM-CNN. Ind. Constr. 2025, 1–10. Available online: https://link.cnki.net/urlid/11.2068.TU.20250813.1609.010 (accessed on 9 October 2025).
  28. Haack, R.W.; Girgis, S. Experimental verification of three-dimensional analysis ofleakage magnetic fields in large power transformers. IEEE Trans. Power Appar. Syst. 1983, 102, 3212–3217. [Google Scholar] [CrossRef]
  29. Wang, X.; Jing, Y.; Yu, Z.; Li, Y.; Meng, T. Evaluation Method for Anti-Short-Circuit Capacity of Power Transformers Based on Finite Element and Analytical Calculations. High Volt. Eng. 2025, 1–12. [Google Scholar] [CrossRef]
  30. Wang, Y.; Li, Y.P. Research on Measures to Enhance the Short-Circuit Resistance of Dry-Type Transformer Windings. Mech. Electr. Inf. 2025, 06, 24–27. (In Chinese) [Google Scholar] [CrossRef]
Figure 1. Schematic diagram of transformers with different core structures.
Figure 1. Schematic diagram of transformers with different core structures.
Sensors 25 06528 g001
Figure 2. Magnetomotive Force Distribution in Non-Equal Height Windings.
Figure 2. Magnetomotive Force Distribution in Non-Equal Height Windings.
Sensors 25 06528 g002
Figure 3. Three-dimensional model of 110 kV transformer.
Figure 3. Three-dimensional model of 110 kV transformer.
Sensors 25 06528 g003
Figure 4. 110 kV transformer winding and core magnetic field cloud map.
Figure 4. 110 kV transformer winding and core magnetic field cloud map.
Sensors 25 06528 g004
Figure 5. Simulation results of leakage magnetic field of 110 kV transformer comparison.
Figure 5. Simulation results of leakage magnetic field of 110 kV transformer comparison.
Sensors 25 06528 g005aSensors 25 06528 g005b
Figure 6. 110 kV Transformer Electromagnetic Force Simulation Cloud Map.
Figure 6. 110 kV Transformer Electromagnetic Force Simulation Cloud Map.
Sensors 25 06528 g006aSensors 25 06528 g006b
Figure 7. Simulation results of electromagnetic force for 110 kV transformers.
Figure 7. Simulation results of electromagnetic force for 110 kV transformers.
Sensors 25 06528 g007aSensors 25 06528 g007b
Figure 8. 110 kV transformer circuit connection scheme.
Figure 8. 110 kV transformer circuit connection scheme.
Sensors 25 06528 g008
Figure 9. 110 kV transformer for short-circuit test.
Figure 9. 110 kV transformer for short-circuit test.
Sensors 25 06528 g009
Figure 10. The impedance variation curve of the 110 kV transformer during short-circuit test.
Figure 10. The impedance variation curve of the 110 kV transformer during short-circuit test.
Sensors 25 06528 g010
Figure 11. 110 kV transformer hoisting and disassembly.
Figure 11. 110 kV transformer hoisting and disassembly.
Sensors 25 06528 g011aSensors 25 06528 g011b
Figure 12. Typical Convolutional Neural Network.
Figure 12. Typical Convolutional Neural Network.
Sensors 25 06528 g012
Figure 13. The network structure of CNN-LSTM.
Figure 13. The network structure of CNN-LSTM.
Sensors 25 06528 g013
Figure 14. CCL Fault Diagnosis Process.
Figure 14. CCL Fault Diagnosis Process.
Sensors 25 06528 g014
Figure 15. Fitness curve.
Figure 15. Fitness curve.
Sensors 25 06528 g015
Figure 16. Accuracy of the CNN-LSTM model.
Figure 16. Accuracy of the CNN-LSTM model.
Sensors 25 06528 g016aSensors 25 06528 g016b
Table 1. Electrical Specifications of Transformer A.
Table 1. Electrical Specifications of Transformer A.
Product Model110 kV Transformer
Rated Frequency/Hz50
Core StructureThree-phase three-limb
Winding ParametersH-v windingM-v windingL-v winding
Rated Capacity/kVA50,00050,00050,000
Rated Voltage/kV11038.510.5
Winding Inner Radius/mm557.5430363
Winding Outer Radius/mm645512.5408
Total Winding Height/mm9959951015
Total Winding Turns47816779
Spacer Dimensions (Length × Width)/mm87.5 × 19.1882.5 × 22.945 × 27.45
Table 2. Electrical Specifications of Transformer B.
Table 2. Electrical Specifications of Transformer B.
Product Model110 kV Transformer
Rated Frequency/Hz50
Core StructureThree-phase three-limb
Winding ParametersH-v windingM-v windingL-v winding
Rated Capacity/kVA50,00050,00050,000
Rated Voltage/kV11038.510.5
Winding Inner Radius/mm557.5430363
Winding Outer Radius/mm645512.5408
Total Winding Height/mm995995995
Total Winding Turns47816779
Spacer Dimensions (Length × Width)/mm87.5 × 19.1882.5 × 22.945 × 27.45
Table 3. Simulation calculation comparison.
Table 3. Simulation calculation comparison.
Transformer ModelTransformer ATransformer B
Winding ParametersL-V windingM-V windingH-V windingL-V windingM-V windingH-V winding
Axial magnetic flux leakage/(T)0.5320.4730.5210.4860.4530.452
Radial magnetic flux leakage/(T)0.2510.4250.3950.1870.2960.256
Axial electromagnetic force/(N/m3)3.97 × 1063.98 × 1063.76 × 1063.66 × 1063.73 × 1063.52 × 106
Radial electromagnetic force(N/m3)2.2 × 1061.7 × 1061.52 × 1061.6 × 1061.25 × 1061.12 × 106
Table 4. Parameters of CNN-LSTM Network.
Table 4. Parameters of CNN-LSTM Network.
Network ParametersNumerical Value
Fill modeSame mode
Activation functionReLU
WeightRandom normal distribution
Number of neurons in the LSTM hidden layer100
Optimize functionAdam
Learning rate1.45 × 10−3
Learning rate decay factor0.09
Learning rate decay period30
L2 regularization parameter1.45 × 10−3
Batch size21
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Ma, Y.; Zhou, X.; Wang, X.; Tian, T.; Tai, C.; Chen, D.; Xin, Z.; Wang, S. Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers. Sensors 2025, 25, 6528. https://doi.org/10.3390/s25216528

AMA Style

Ma Y, Zhou X, Wang X, Tian T, Tai C, Chen D, Xin Z, Wang S. Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers. Sensors. 2025; 25(21):6528. https://doi.org/10.3390/s25216528

Chicago/Turabian Style

Ma, Yukun, Xiu Zhou, Xiaokang Wang, Tian Tian, Chenfan Tai, Dezhi Chen, Ziyuan Xin, and Sijun Wang. 2025. "Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers" Sensors 25, no. 21: 6528. https://doi.org/10.3390/s25216528

APA Style

Ma, Y., Zhou, X., Wang, X., Tian, T., Tai, C., Chen, D., Xin, Z., & Wang, S. (2025). Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers. Sensors, 25(21), 6528. https://doi.org/10.3390/s25216528

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop