Thermo-Hydraulic Optimization of Parallel-Channel Cold Plates Using CFD: A Comparative Study of Cylindrical and Fin-Type Baffles for Battery Thermal Management

1
School of Mechanical Engineering, Hanoi University of Science and Technology, Hanoi 100000, Vietnam
2
Department of Electrical Engineering, Chang Gung University, Taoyuan 33302, Taiwan
3
Department of Electrical Engineering, Ming Chi University of Technology, New Taipei City 24301, Taiwan
4
Center for Reliability Engineering, Ming Chi University of Technology, New Taipei City 24301, Taiwan
*
Author to whom correspondence should be addressed.
Batteries 2026, 12(5), 183; https://doi.org/10.3390/batteries12050183
Submission received: 17 April 2026 / Revised: 17 May 2026 / Accepted: 19 May 2026 / Published: 20 May 2026

Abstract

This study proposes two enhanced configurations for a parallel-channel cold plate in battery thermal management systems to improve thermo-hydraulic performance through the introduction of cylindrical and fin-type baffles. A three-dimensional computational fluid dynamics (CFD) model was developed in ANSYS to simulate fluid flow and heat transfer within the cold plate. A Poly-Hexcore meshing strategy with local refinement and near-wall inflation layers was employed to ensure numerical accuracy while maintaining computational efficiency. A parametric investigation involving 150 cases was conducted to identify the optimal channel configuration. The results indicate that, among the investigated configurations and under the present numerical operating conditions, the fin-type baffle exhibits the most balanced thermo-hydraulic behavior by achieving an effective balance between heat-transfer enhancement and pressure-drop penalty. The present study provides a CFD-based framework for the design and optimization of parallel-channel cold plates for battery thermal management applications.

1. Introduction

The rapid development of electric vehicles (EVs), renewable energy storage systems, and portable electronic devices has significantly increased the demand for high-performance lithium-ion batteries. Despite their advantages, including high energy density, excellent efficiency, and long lifespan, lithium-ion batteries are highly sensitive to thermal conditions. Elevated operating temperatures and non-uniform temperature distributions can accelerate degradation, reduce capacity, shorten service life, and may even trigger thermal runaway. Therefore, an efficient and reliable battery thermal management system (BTMS) is essential to ensure safety, performance, and durability [1,2,3,4,5,6].
BTMS technologies mainly include air cooling, liquid cooling, phase change materials (PCM), heat pipes, and hybrid systems [1,2,3,4,5,6,7,8,9]. Among these, liquid cooling has emerged as the most effective solution for high-power and high-energy-density battery applications, particularly in electric vehicles, due to its superior heat dissipation capability and excellent temperature uniformity [5,6,7,9,10]. Within liquid-cooling technologies, cold plates are widely adopted because of their compact structure, high efficiency, and ease of integration with battery modules [6,11,12,13,14,15,16,17,18,19,20,21,22,23,24,25,26,27,28,29,30,31].
The thermal and hydraulic performance of cold plates is strongly influenced by channel configuration [11,12,13,16,19,20,24,25,26,28,30]. Parallel-channel cold plates are especially attractive due to their simple structure, low pressure drop, and uniform flow distribution [11,13,20,25,30]. However, their heat transfer performance is often limited by boundary layer development and insufficient fluid mixing [11,16,20,26,28]. To overcome these limitations, passive heat transfer enhancement techniques such as ribs, pin fins, vortex generators, grooves, and baffles have been extensively investigated to improve thermo-hydraulic performance without additional energy consumption [16,29,32,33,34,35,36,37,38].
Previous studies have explored a wide range of channel configurations and passive enhancement strategies to improve the thermo-hydraulic performance of battery cold plates and compact liquid-cooled structures. Among channel-layout modifications, serpentine and multi-channel configurations are among the most widely used because of their compactness and effective cooling capability [11,12,13,20,25,26,30]. For example, Mahmoud et al. [34] performed combined numerical and experimental investigations on serpentine and multi-mini-channel heat sinks with ribs, grooves, and pin fins, and showed that pin-fin-and-groove structures can improve heat dissipation compared with conventional rib-based designs, although with higher pressure drop. In battery cold plates, Tesla-valve-type channels have been proposed to enhance flow mixing through flow splitting [16,33], while cross-linked cold plates were developed to reduce pumping power and improve temperature uniformity [25]. In addition, zig-zag serpentine channel layouts have also been investigated to increase coolant contact area and improve cooling effectiveness [26]. These studies indicate that channel-layout modification is a way to improve cooling performance, although the associated hydraulic penalty remains an important concern [16,20,24,25,26,30,33].
In parallel with channel-layout modifications, many studies have introduced passive internal flow-disturbing structures into cooling channels to enhance convective heat transfer [14,15,16,19,20,23,24,25,26,27,28,29,30,32,33,34,35,36,37,39,40]. Mahmoud et al. [34] demonstrated that pin-fin-based structures can intensify heat transfer by disrupting the thermal boundary layer and promoting fluid mixing. In battery cold plates, Zhao et al. [32] reported that optimized internal structures can substantially improve cooling performance and temperature uniformity, while Han et al. [36] showed that fin-based enhancements can intensify fluid mixing and thermal performance with acceptable hydraulic penalties. More broadly, previous studies have confirmed that passive enhancement structures such as ribs, fins, pin fins, grooves, and baffles can effectively improve thermo-hydraulic performance, but they also highlight the persistent trade-off between heat-transfer enhancement and hydraulic loss.
Despite these advances, several research gaps remain. First, most previous studies have focused on either a single enhancement concept or a limited number of design cases, while systematic and fair comparisons between cylindrical-type and fin-type baffles within the same parallel-channel cold plate and under identical operating conditions remain limited [16,20,23,24,25,26,30,32,33,34,35,36]. Second, many earlier investigations considered only a relatively small design space and therefore could not fully capture the overall performance trends across the geometric parameter space [16,19,23,24,25,26,30,33,35]. Third, thermo-hydraulic evaluation criteria such as REF or PEC have not always been used as a consistent optimization basis in battery cold-plate studies [16,20,24,30,32,35,36]. Therefore, a more systematic thermo-hydraulic investigation is still needed, one that simultaneously considers heat-transfer enhancement and pressure-drop penalty during design optimization.
Motivated by these research gaps, the present study investigates two enhanced configurations, namely cylindrical-type and fin-type baffles, for a liquid-cooled parallel-channel cold plate in battery thermal management. The main contributions of this work are summarized as follows: (i) a validation-driven CFD-based optimization framework is developed to enable a systematic comparison between the two baffle concepts under identical operating conditions within the same cold-plate platform; (ii) a large-scale parametric study involving 150 configurations is conducted to explore the design space and clarify the thermo-hydraulic trends associated with geometric variation; and (iii) the optimal geometry for each baffle concept is identified using REF as a consistent thermo-hydraulic evaluation criterion, thereby providing a rational basis for design-oriented cold-plate development.
The remainder of this paper is organized as follows. Section 2 presents the model development, including the physical configurations of the baseline and enhanced cold plates, the governing equations, boundary conditions, and the numerical method with grid independence analysis. Section 3 describes the model validation process, including the validation setup, evaluation metrics such as the Nusselt number and pressure drop, and detailed comparisons between numerical and experimental results. Section 4 focuses on the optimization of baffle configurations, including the definition of parametric cases and evaluation criteria, followed by the optimization of cylindrical and fin-type baffles. Section 5 presents the investigation and evaluation of the optimized model performance, where the thermo-hydraulic characteristics of the baseline, optimized cylindrical-baffle, and optimized fin-type-baffle designs are systematically compared and analyzed. Finally, Section 6 summarizes the main findings and presents the conclusions of this study.

2. Model Development

2.1. Physical Model

Figure 1 illustrates the geometric configuration of the baseline battery thermal management system (BTMS) investigated in this study. The primary component of the system is a cold plate positioned beneath the battery module. The internal structure of the cold plate consists of seven parallel channels. As shown in Figure 1, the coolant flows from a single inlet to a single outlet, both having identical dimensions of 10 mm × 10 mm, through long, straight, and uninterrupted parallel channels. These channels facilitate the distribution of the coolant and connect the cold plate to the external coolant supply and circulation system. The geometric parameters of the baseline model, along with those of the enhanced configurations, are summarized in Table 1.
The cold plate is assumed to be fabricated from aluminum, while water is selected as the working coolant. The coolant enters the cold plate through the inlet at a temperature of 293 K and exits through the outlet. The thermophysical properties and key specifications of both the cold plate and the coolant are summarized in Table 2.
In this study, two enhanced cooling configurations are proposed and analyzed, as illustrated in Figure 2. The selection of these configurations is guided by the underlying physical mechanisms of thermo-fluid enhancement. Specifically, cylindrical and fin-type baffles are introduced to induce local flow disturbances and flow obstruction within the channels, thereby enhancing fluid mixing and disrupting the thermal boundary layer.
In addition to the physical rationale, the choice of these two baffle geometries is also motivated by their geometric simplicity and practical applicability. These structures are fundamentally simple, easy to manufacture, and can be readily implemented in real-world designs without introducing significant fabrication complexity. Moreover, such simple geometries facilitate efficient mesh generation and ensure stable numerical convergence, which is particularly important for large-scale parametric studies. As a result, they enable computationally efficient optimization analyses. The baseline configuration is hereafter referred to as Module 1, while the two enhanced configurations are designated as Module 2 and Module 3 for subsequent analysis.

2.2. Governing Equations and Boundary Conditions

A three-dimensional conjugate heat transfer model was developed to characterize the flow and heat transfer behavior within the liquid-cooled cold plate. In this study, several assumptions were adopted to simplify the numerical model: (a) The fluid is incompressible and exhibits Newtonian behavior. (b) The flow is single-phase, laminar, steady, and satisfies the no-slip condition at the solid–fluid interface. (c) The effects of gravity and thermal radiation are neglected, and viscous dissipation is neglected in the energy equation. However, viscous effects are fully retained in the momentum equations; therefore, the pressure drop is directly resolved from the computed pressure field. (d) A constant heat flux is applied at the bottom surface to represent the heat generation from the battery.
In the present study, the flow is assumed to be laminar and steady-state. The laminar flow assumption was selected based on the investigated Reynolds-number range and will be discussed further in Section 4. Regarding the steady-state assumption, the steady-state model was adopted based on several previous studies on microchannels with flow-disturbing structures [41,42]. Although local recirculation regions and flow separation were still observed in these studies, laminar steady-state models were successfully used and showed good agreement with experimental data. This indicates that the steady-state assumption is still capable of reasonably describing the thermo-hydraulic characteristics of cooling channels under laminar flow conditions. Therefore, the laminar steady-state assumption is considered appropriate for the present study.
Based on these assumptions, the governing equations for the fluid domain include the continuity, momentum, and energy equations, while the solid domain is described by the steady-state heat conduction equation, as presented in the reference research [34].
ρ L v = 0
ρ L ( v ) v = P + μ L 2 v
ρ L C p L ( v T L ) = k L 2 T L
where is the vector differential operator, 2 is the Laplace operator. In addition, ρ L is the fluid density, v is the velocity vector, P is the pressure, μ L is the dynamic viscosity, C p L is the specific heat capacity, T L is the liquid temperature, and k L is the thermal conductivity of the liquid.
For the solid domain, heat transfer is governed by the steady heat conduction equation:
k s 2 T s = 0
where T s is the solid temperature and k s is the thermal conductivity of the solid. The subscripts L and S denote the liquid and solid domains, respectively.
The thermal and hydraulic boundary conditions employed in the present simulation are summarized in Table 3 and can be described as follows: (a) At the channel inlet of the cold plate, a constant velocity inlet condition was imposed, and the coolant inlet temperature was fixed at T L = T i ; (b) at the channel outlet, a pressure outlet condition was specified with the outlet pressure set to the ambient pressure P = P atm ; (c) at the fluid–solid interface, conjugate heat transfer was applied between the coolant and the cold-plate wall; (d) for the solid domain, a uniform heat flux was imposed at the heat-flux wall to represent the heat input from the battery, while adiabatic boundary conditions were applied to the remaining walls.

2.3. Numerical Method and Grid Independence

The three-dimensional conjugate heat transfer model was solved using ANSYS 2024R2, a commercial CFD software package. In the present study, the computational domains of all investigated modules were discretized using a Poly-Hexcore mesh to achieve a suitable balance between numerical accuracy and computational efficiency. The use of this mesh type allowed the core flow region to be resolved efficiently while maintaining sufficient refinement near the walls and in geometrically complex regions.
During the mesh generation process, local refinement was applied in several critical regions, including the heat-conducting walls, the solid–fluid interface, and the near-wall regions of the channels, where significant gradients of temperature and velocity are expected. In addition, the mesh was further refined in regions containing flow-disturbing structures to more accurately capture local variations in the flow and thermal fields. To enhance near-wall resolution, inflation layers were generated adjacent to solid boundaries to properly resolve both velocity and thermal boundary layers. The residual criteria for the continuity equation were set to 10−6, while those for the momentum and energy equations were set to 10−7. The resulting mesh structure for a representative case is shown in Figure 3, along with enlarged views of the near-wall regions and locally refined zones.
A grid independence test was conducted to ensure numerical accuracy with minimal computational cost. Eight mesh configurations were evaluated to examine the effects of mesh density on surface temperature and pressure drop. As shown in Figure 4 for the baseline model at m = 0.0045 kg/s and q = 20,000 W/m2, the deviations in heat transfer and pressure drop decrease with increasing cell number and become negligible at approximately 1,550,000 cells, beyond which the results remain nearly unchanged. The enhanced models exhibit different mesh sizes due to their higher geometric complexity.

3. Validation

3.1. Validation Model Description

To assess the accuracy of the numerical method and verify the applicability of the adopted meshing strategy to the present CFD model, a benchmark-based validation study was conducted using the experimentally validated rectangular multi-mini-channel heat sink (MMCHS) reported by Mahmoud et al. [34]. Although the validation model has different dimensions from the cold-plate configurations investigated in this study, the two problems remain physically comparable because: (i) both employ rectangular parallel-channel cooling structures and belong to the class of forced-convection flow in confined channels; (ii) both involve laminar forced flow of liquid coolant through compact mini-channels; and (iii) both are governed by similar heat-transfer mechanisms, including boundary-layer development, conjugate heat transfer between solid and fluid, and heat-transfer enhancement associated with flow obstruction. Therefore, this benchmark is considered appropriate to validate the solver, the meshing strategy, and the overall numerical framework adopted in the present study.
The geometric configuration and operating conditions were established consistently with the reference study, as shown in Figure 5 and Table 4, where the cold plate material was set to copper, and the coolant was water. The mass flow rate and heat flux were specified as m = 0.0045 kg/s and q = 20,000 W/m2, respectively. It should be noted that the meshing strategy applied to the validation model is consistent with that described in Section 2.3. The computational mesh of the MMCHS model, along with the local mesh refinement in critical regions, is illustrated in Figure 6. The model consists of approximately 265,407 cells, which significantly reduces the computational cost while maintaining the reliability and accuracy of the simulation results.

3.2. Validation Metrics

In forced-convection cooling systems, evaluating heat-transfer enhancement alone is insufficient for comprehensively assessing the effectiveness of baffle configurations, since improvements in heat transfer are often accompanied by increased pressure drop and pumping-power consumption. In particular, a configuration with a high Nusselt number does not necessarily provide the best overall operating performance if the hydraulic penalty becomes excessively large. Therefore, thermo-hydraulic performance should be evaluated based on both heat-transfer enhancement capability and the corresponding pressure-drop penalty during operation. To quantitatively reflect this trade-off in a consistent manner, the thermo-hydraulic performance factor (REF) is adopted in the present study as the primary evaluation criterion for identifying the most balanced thermal–hydraulic configuration under the same flow-rate condition [34]. The REF is defined as follows:
REF = Nu / Nu 0 Δ P / Δ P 0 1 / 3
where Nu and Δ P represent the average Nusselt number and pressure drop of the enhanced configuration, respectively, while Nu 0 and Δ P 0 denote the corresponding values of the baseline model. A larger REF value indicates a more effective balance between heat-transfer enhancement and hydraulic cost. In particular, REF > 1 demonstrates that the enhanced configuration provides superior overall thermo-hydraulic performance compared with the baseline configuration.
In addition to the REF, several other thermal and hydraulic parameters are employed to provide a detailed analysis of the thermo-fluid characteristics of the investigated configurations, including the heat-transfer rate, logarithmic mean temperature difference, average Nusselt number, thermal resistance, and pressure drop. The heat absorbed by the coolant is determined based on the energy balance between the inlet and outlet of the fluid flow, which can be expressed as:
Q = m L C p L Δ T L = h ahtc A hta LMTD
where m L is the mass flow rate of the coolant, C p L is the specific heat capacity of the fluid, Δ T L is the temperature rise in the coolant, h ahtc is the average convective heat-transfer coefficient, and A hta is the effective heat-transfer area.
The logarithmic mean temperature difference (LMTD) between the heated surface and the coolant is calculated and presented below [34]:
LMTD = T wall T L , in T wall T L , out ln T wall T L , in T wall T L , out
where T wall is the average temperature of the heat-transfer surface, while T L , in and T L , out are the coolant temperatures at the inlet and outlet, respectively.
Based on the calculated heat-transfer rate, the average Nusselt number is used to characterize the convective heat-transfer capability of the cold plate as follows [34]:
Nu = Q D A hta LMTD k L
where D is the hydraulic diameter of the channel and k L is the thermal conductivity of the coolant. The hydraulic diameter was determined by:
D = 4 A B
where A is the effective cross-sectional flow area, and B is the wetted perimeter. In the present study, A was evaluated on a cross-sectional plane perpendicular to the flow direction and included the influence of internal structures such as cylindrical baffles or fin-type baffles. Therefore, it represents the actual flow area available to the coolant after excluding the solid region occupied by the internal obstructions.
To evaluate the overall heat-dissipation capability of the cold plate, the thermal resistance is defined as summarized below [34]:
R = LMTD Q
A lower thermal resistance indicates a stronger overall heat dissipation capability. In addition, the temperature uniformity of the cold-plate surface was assessed using the surface temperature difference:
Δ T = T max T min
where T max and T min are the maximum and minimum temperatures on the cold-plate surface, respectively. A smaller value of Δ T indicates better temperature uniformity.
The inlet and outlet pressures used to calculate the pressure drop were obtained directly from the CFD-predicted pressure field. The hydraulic performance was evaluated through the pressure drop across the channel, which was calculated as:
Δ P = P in P out
where P in and P out are the inlet and outlet pressures, respectively. In the following sections, these parameters are used to compare the thermal and hydraulic behaviors of all investigated channel configurations under different operating conditions.
In this study, the Reynolds number (Re) is also employed to characterize the flow regime inside the parallel-channel system. The Reynolds number is determined based on the nominal average mass flow rate through each channel and is calculated as follows:
Re = m channel . D A . μ L
where m channel is the nominal average mass flow rate of the coolant through each channel, and μ L is the dynamic viscosity of the coolant.

3.3. Validation Results and Discussion

Figure 7 presents the validation of the numerical model through a direct comparison between the reference experimental data (Figure 7a) and the numerical results obtained in the present study (Figure 7b) for the MMCHS. As shown in Figure 7a, the reference data from Mahmoud et al. [34] provide the experimental trends of the Nusselt number (Nu) and pressure drop ( Δ P ), while Figure 7b illustrates the corresponding results predicted by the present model under identical conditions. To further quantify the agreement, Table 5 summarizes the quantitative discrepancies between the reference experimental data and the present numerical predictions at each investigated mass flow rate for both the Nusselt number and pressure drop. The revised comparison shows that the present model reproduces the benchmark trends well. The deviations are in the ranges of 2.43–8.29% for Nu and 1.94–8.52% for ΔP, indicating good quantitative agreement with the experimental benchmark. Therefore, the present agreement is considered sufficient to support the reliability of the solver, boundary-condition implementation, and meshing strategy adopted in this study.
Importantly, this agreement demonstrates that the proposed meshing strategy, despite employing a reduced number of computational cells, is capable of maintaining high accuracy and reliability in capturing the thermo-hydraulic behavior of the system. The reduced mesh size decreases computational cost while maintaining sufficient numerical accuracy.
Therefore, the validation confirms that the developed numerical framework, including the mesh generation approach and boundary condition implementation, is sufficiently accurate and robust for subsequent simulations of the baseline configuration and the enhanced models considered in this study.

4. Optimization of Baffle Configurations

4.1. Parametric Cases and Evaluation Criteria

To systematically investigate the influence of baffle geometry on the thermo-hydraulic performance of the cold plate, a structured parametric study was conducted under fixed operating conditions. Specifically, the mass flow rate was maintained at 0.06 kg/s, the applied heat flux to the heat transfer surface was set to q = 20,000 W/m2, and the inlet coolant temperature was fixed at 293 K. These operating conditions were selected as a reference baseline to isolate the effect of geometric parameters and to ensure a fair and consistent comparison among all investigated configurations during the optimization process.
For the cylindrical baffles (Module 2) and the fin-type baffles (Module 3), the key geometric parameters were systematically varied to construct the parametric design space. The detailed definitions of the geometric variables, along with their corresponding ranges and increments, are summarized in Table 6.
A total of 150 configurations were generated for both modules by systematically combining the selected parameter ranges and increments. This structured design space enables a detailed yet computationally manageable evaluation of the effects of baffle geometry on the thermo-hydraulic performance of the cold plate. Figure 8 illustrates the investigated geometric parameters and their corresponding minimum–maximum ranges for the enhanced configurations. The selected ranges were based on manufacturing feasibility, mechanical strength, and the geometric limits of the cooling channel. The lower bounds were set to avoid very small features that are difficult to machine accurately in aluminum, are mechanically less robust, and are ineffective in disturbing the flow. The upper bounds were limited by the channel dimensions and by the need to prevent excessive flow blockage and pressure-drop increase. Thus, the adopted ranges provide a practical yet sufficiently wide basis for evaluating the thermo-hydraulic effects of baffle geometry. The spacing, number, and positions of the baffles were kept fixed. This setup enables a clearer and more consistent evaluation of the primary size parameters ( d 2 , h 2 , l 3 , h 3 ) while also keeping the parametric design space at a manageable scale. In addition, the present study focuses on the analysis and optimization of baffle shape and size under controlled conditions, to clarify the role of these enhancement structures in the thermo-hydraulic behavior of the cold plate. The simultaneous optimization of spacing, number, and position will be considered in future work.
To comprehensively evaluate the performance of all configurations, both thermal and hydraulic criteria were employed, including the average surface temperature ( T wall ), pressure drop ( Δ P ), average Nusselt number (Nu), thermal resistance (R), and the thermo-hydraulic performance factor (REF). These parameters enable a simultaneous assessment of heat transfer enhancement, flow resistance, and the overall system performance.

4.2. Optimization of Cylindrical-Type Baffles

During the parametric investigation of cylindrical baffle geometry, the two design variables d2 and h2 were found to play a dominant role in governing the thermal performance of the cold plate. Increasing these parameters leads to a noticeable improvement in the cooling capability of the system.
As illustrated in Figure 9a, the average temperature of the heat-transfer surface decreases significantly with increasing d2 and h2, particularly within the ranges of d2 = 1–3 mm and h2 = 1–5 mm. However, beyond these ranges, the rate of temperature reduction gradually diminishes, indicating a saturation trend in heat-transfer enhancement. At relatively small baffle sizes, the flow disturbance generated by the obstacles effectively disrupts the thermal boundary layer and promotes boundary-layer redevelopment. In contrast, further increases in baffle size provide only limited additional enhancement to the heat-transfer process.
The variation in the Nusselt number (Figure 9b) reveals the existence of high-performance regions within the design space. Specifically, the minimum Nu value is observed at d2 = 1 mm and h2 = 2 mm, after which Nu increases rapidly and forms a region of high heat transfer performance within d2 = 3–5 mm and h2 = 3–6 mm, where relatively high and stable values are maintained. Although the maximum Nu occurs at the upper boundary of the design space (d2 = 6 mm and h2 = 10 mm), the overall distribution shows non-uniformity with local decreases, indicating that heat transfer enhancement does not increase proportionally with geometric size.
The thermal resistance (Figure 9c) decreases with increasing d2 and h2, indicating an improvement in the overall heat dissipation capability. However, the regions of extreme values for R and Nu do not coincide. This reflects the fundamental difference between local convective heat transfer and global thermal performance. While Nu is governed by convective intensity, R is influenced by the overall heat transfer process within the system.
In addition to thermal behavior, the geometric parameters d2 and h2 also strongly affect the hydraulic characteristics. As shown in Figure 10a, the pressure drop increases significantly with increasing d2 and h2, particularly in the region where h2 > 5 mm and h2 > 7 mm. This increase is caused by the reduction in effective flow area and the increased flow obstruction, leading to higher local velocities, greater frictional losses, and the formation of strong recirculation zones.
The interaction between heat-transfer enhancement and hydraulic penalty is reflected by the thermo-hydraulic performance factor (REF), as presented in Figure 10b. The maximum REF value is obtained at d2 = 4 mm and h2 = 3 mm, while a relatively stable high-performance region is observed within d2 = 3–5 mm and h2 = 2–5 mm. Within this region, the enhancement in convective heat transfer remains significant while the pressure-drop increase is still moderate, resulting in an effective balance between thermal and hydraulic performance. In contrast, although larger baffle dimensions further improve heat transfer, the REF value decreases noticeably because the hydraulic penalty increases more rapidly than the thermal benefit. This result indicates that optimal thermo-hydraulic performance cannot be achieved by maximizing heat transfer alone, but rather through a balanced compromise between thermal enhancement and flow resistance.
The Reynolds-number distribution shown in Figure 10c further indicates that all investigated cases remain within the laminar-flow regime. Although the Reynolds number varies with changes in d2 and h2 due to the modification of the local flow field and hydraulic diameter, the calculated values remain below the typical transition threshold for mini-channel flow. This supports the applicability of the laminar-flow assumption adopted in the present numerical model.
Therefore, the optimal configuration of Module 2 is identified at d2 = 4 mm and h2 = 3 mm, where the maximum REF value is achieved while maintaining favorable thermal characteristics and a moderate hydraulic penalty. Under this condition, the cooling performance remains effective without causing an excessive increase in pressure drop, resulting in a favorable balance between thermal enhancement and hydraulic penalty.

4.3. Optimization of Fin-Type Baffles

Following the analysis of cylindrical baffles in Section 4.2, the geometric parameters l3 and h3 of Module 3 are further investigated to evaluate the performance of the fin-type baffle structure.
As shown in Figure 11a, the average surface temperature of the heat-transfer plate decreases with increasing l3 and h3, indicating an enhancement in the cooling capability of the system. Lower temperatures are mainly observed in the large-geometry region, whereas relatively high temperatures remain in the small-size region. Compared with Module 2, Module 3 exhibits a more pronounced temperature reduction as the geometric dimensions increase. This behavior can be attributed to the more continuous flow-guiding effect of the fin-type structure, which promotes stronger near-wall flow redistribution and more effective thermal-boundary-layer redevelopment.
The Nusselt-number distribution shown in Figure 11b indicates that the baffle height h3 plays a dominant role in heat-transfer enhancement. As h3 increases, the Nusselt number rises significantly due to stronger flow disturbance and improved disruption of the thermal boundary layer. In contrast, the influence of the baffle length l3 is non-monotonic. An optimal heat-transfer region is observed within l3 = 4–6 mm, where relatively high Nu values are maintained. At small l3 values, the induced flow disturbance is insufficient to significantly enhance convective heat transfer. As l3 increases to the intermediate range, localized secondary-flow structures develop more effectively, enhancing fluid interaction between the core flow and near-wall regions. However, excessively large l3 values generate stronger flow blockage and larger low-velocity recirculation regions, which weaken the local heat-transfer effectiveness.
Figure 11c shows that the thermal resistance decreases with increasing l3 and h3, consistent with the trend observed in Module 2. Nevertheless, the region corresponding to the minimum thermal resistance does not fully coincide with the region of maximum Nusselt number. This difference highlights the distinction between local convective heat-transfer enhancement and the overall thermal performance of the cooling system.
The hydraulic characteristics show a stronger dependence on the geometric parameters. As shown in Figure 12a, the pressure drop remains relatively low over most of the design space but increases sharply at large values of l3 and h3, particularly at l3 = 9 mm and h3 = 10 mm, where Δ P = 24,902.73 Pa. This indicates significant flow obstruction caused by the increased length and height of the baffles. The combined influence of thermal enhancement and hydraulic penalty is reflected in the thermo-hydraulic performance factor REF, as shown in Figure 12b. The maximum REF value is obtained at l3 = 2 mm and h3 = 10 mm, while a relatively high-performance region is observed in the range of small-to-moderate l3 and large h3 values. In this region, the enhancement of convective heat transfer remains effective while the pressure-drop increase is still acceptable, resulting in favorable overall thermo-hydraulic performance. In contrast, excessively large l3 values lead to a reduction in REF because the hydraulic penalty increases more rapidly than the thermal benefit, despite the relatively high heat-transfer capability.
The Reynolds-number distribution shown in Figure 12c further shows that all investigated cases remain within the laminar-flow regime. Although the Reynolds number increases with increasing l3 and h3 due to stronger local flow acceleration, all calculated values remain below the typical transition threshold for mini-channel flow. This result validates the applicability of the laminar-flow assumption adopted in the present numerical model.
Therefore, the optimal configuration of Module 3 is identified at l3 = 2 mm and h3 = 10 mm, where the maximum REF value is achieved while maintaining favorable thermal enhancement and acceptable hydraulic performance within the investigated design space. These results further suggest that the optimal cold plate design should be determined based on a balanced thermo-hydraulic criterion rather than individual thermal or hydraulic indicators alone. The corresponding quantitative thermo-hydraulic performance parameters of Module 2 (Module 2-opt) and Module 3 (Module 3-opt) are summarized in Table 7.

5. Investigation and Evaluation of the Optimized Model Performance

In this study, to evaluate the influence of cylindrical and fin-type baffles on the thermo-hydraulic performance of the cooling channel under different inlet flow rates, and to compare the Module 2-opt and Module 3-opt, a comparative analysis was conducted with the baseline configuration (Module 1) under identical conditions. The mass flow rate was varied from 0.02 to 0.1 kg/s, while the applied heat flux was fixed at q = 20,000 W / m 2 , and the inlet coolant temperature was maintained at 293 K. The range of 0.02–0.1 kg/s was selected as a practical operating window: lower flow rates would provide insufficient forced convection, whereas higher flow rates would cause a disproportionately large pressure-drop penalty.
As shown in Figure 13a, the average surface temperature decreases with increasing mass flow rate for all configurations due to the enhancement of convective heat transfer. Among the investigated cases, Module 3-opt consistently exhibits the lowest wall temperature, followed by Module 2-opt, while the baseline configuration shows the highest values. At a mass flow rate of 0.1 kg/s, the average temperature of the heat-transfer surface of Module 2-opt and Module 3-opt decreases to approximately 300 K and 299 K, respectively, compared with about 309 K for Module 1. This indicates improved cooling performance for the optimized configurations. A similar trend is observed for the Nusselt number in Figure 13b, where both optimized configurations achieve substantially higher values than the baseline model. Module 3-opt consistently exhibits the highest Nu values across the investigated operating range, indicating stronger convective heat-transfer enhancement due to the fin-type flow-guiding structure. In addition, the thermal resistance shown in Figure 13c decreases continuously with increasing mass flow rate for all configurations, with Module 3-opt maintaining the lowest values throughout the investigated range. These results demonstrate that the optimized internal structures improve the overall heat-dissipation capability of the cold plate.
Despite the improvement in thermal performance, the optimized configurations also introduce additional hydraulic losses, as shown in Figure 14a. The pressure drop increases significantly with increasing mass flow rate for all configurations due to the higher flow velocity and intensified viscous dissipation inside the channels. Compared with the baseline model, both Module 2-opt and Module 3-opt exhibit noticeably larger pressure-drop values because of the additional flow obstruction induced by the internal baffle structures. The combined effect of thermal enhancement and hydraulic penalty is reflected in the thermo-hydraulic performance factor (REF), as shown in Figure 14b. For both optimized configurations, the REF value initially increases with mass flow rate and reaches a maximum at approximately 0.04 kg/s, after which it gradually decreases as the hydraulic penalty becomes dominant. Across the investigated operating range, Module 3-opt consistently maintains higher REF values than Module 2-opt, indicating a more favorable balance between heat-transfer enhancement and pressure-drop increase.
The detailed quantitative thermal and thermo-hydraulic performance parameters for the three configurations are summarized in Table 8 to enable a clearer comparison between the baseline and optimized cold-plate designs across different mass flow rates. Particular attention is given to the maximum temperature ( T max ) and temperature difference ( Δ T ), which are important indicators for evaluating cooling effectiveness and temperature uniformity.
The results demonstrate that both optimized configurations significantly reduce T max and Δ T over the entire investigated operating range compared with the baseline model. For example, at a mass flow rate of 0.06 kg/s, the baseline configuration exhibits a T max of 325.03 K and a Δ T of 26.45 K, whereas Module 2-opt reduces these values to 307.55 K and 11.78 K, respectively. Under the same operating conditions, Module 3-opt further decreases T max to 307.28 K while maintaining a similarly low Δ T of 11.84 K. These reductions indicate a substantial enhancement in thermal management capability and a more uniform temperature distribution across the cold plate surface. A similar trend is observed throughout the investigated mass-flow-rate range. As the mass flow rate increases from 0.02 to 0.10 kg/s, both optimized configurations consistently maintain lower T max and significantly smaller Δ T values than the baseline configuration. This behavior confirms that the introduction of the optimized baffle structures effectively enhances convective heat transfer and improves thermal uniformity within the cooling channels.
In addition, although the pressure drop increases with increasing mass flow rate, the optimized configurations provide considerably higher Nusselt numbers and REF values than the baseline model. Among the investigated cases, Module 3-opt generally exhibits the best overall thermo-hydraulic performance, achieving the highest heat-transfer enhancement while maintaining favorable thermal uniformity characteristics within the studied operating range.
Figure 15 presents the surface temperature distribution of the cold plate for the three configurations under different mass flow rates, showing a clear increase in temperature from inlet to outlet due to heat accumulation and the reduced temperature difference between the coolant and the heat-transfer surface. In the baseline model (Module 1), a pronounced temperature gradient and downstream hotspot are observed, indicating continuous thermal boundary layer development and weak fluid mixing. Although both enhanced configurations (Modules 2-opt and Module 3-opt) exhibit low-temperature regions, their distributions differ: Module 2-opt shows localized and discontinuous cooling due to vortex-induced mixing behind the cylindrical baffles, whereas Module 3-opt presents more widely distributed low-temperature regions, reflecting more uniform flow mixing along the channel. Overall, Module 3-opt achieves the best thermal performance with the most uniform temperature distribution, followed by Module 2-opt and then Module 1, which is consistent with the previously reported higher Nusselt number, lower thermal resistance, and improved temperature uniformity.
Figure 16 illustrates the velocity streamline distributions of the representative cold-plate configurations under different mass flow rates. As the mass flow rate increases, the flow velocity inside the channels becomes stronger, accompanied by more pronounced secondary-flow development and flow redistribution effects. Compared with the baseline model, both optimized configurations introduce stronger local flow disturbance inside the channels. In the cylindrical-baffle configuration, localized recirculation regions are generated downstream of the baffles, which enhance fluid interaction near the heated surface. In contrast, the fin-type configuration provides a relatively more continuous and uniform flow-guiding effect along the channel direction. These flow characteristics are consistent with the enhanced heat-transfer performance and improved thermo-hydraulic behavior observed for the optimized configurations.
Across the entire investigated range, Module 3-opt consistently maintains higher REF values than Module 2-opt, indicating a more favorable balance between heat transfer enhancement and hydraulic losses. Based on these results, the optimal operating condition is identified at a mass flow rate of approximately 0.04 kg/s, and Module 3-opt provides the best overall thermo-hydraulic performance within the studied range.

6. Conclusions

This study proposes two enhanced configurations for a parallel-channel cold plate used in battery thermal management systems, namely cylindrical-type and fin-type baffles, to improve the thermo-hydraulic performance of the cooling system. A three-dimensional CFD model was developed to simulate the fluid flow and heat-transfer characteristics inside the cold plate. In addition, a Poly-Hexcore meshing strategy combined with local mesh refinement was adopted to ensure numerical accuracy while reducing computational cost and computational time. Based on the validated numerical model, a systematic parametric investigation involving 150 configurations was conducted to analyze and optimize the influence of baffle dimensions on the thermo-hydraulic performance of the system.
The main findings of this study are summarized below:
  • The introduction of cylindrical-type and fin-type baffles inside the channel improves heat transfer by promoting fluid mixing and disrupting the thermal boundary layer. As a result, the temperature of the heat-transfer surface is reduced and the temperature uniformity is improved.
  • The geometric parameters of the baffles strongly influence the overall cooling performance of the cold plate. Increasing the baffle size improves the heat-transfer capability by intensifying flow disturbance and convective heat exchange. However, larger baffles also lead to a substantial increase in pressure drop because of increased flow obstruction, frictional losses, and the formation of local recirculation regions.
  • The thermo-hydraulic performance factor (REF) was found to be effective for simultaneously evaluating heat-transfer enhancement and hydraulic penalty. Based on this criterion, the cylindrical-type baffles achieved the optimal performance at intermediate geometric parameters, whereas the fin-type baffles provided a more favorable balance between heat-transfer enhancement and pressure drop over most of the investigated design space.
  • The present results further indicate that the thermo-hydraulic optimization of cold plates should be performed through a design-space analysis rather than focusing on a single thermal parameter. The CFD framework proposed in this study enables a consistent evaluation and comparison of different enhancement configurations and may provide a useful reference for the design and optimization of battery cold plates.
Although the present CFD model shows good agreement with the reference experimental data, the optimized configurations investigated in this study have not yet been validated experimentally. In addition, the present work mainly focuses on steady-state flow conditions and a specific operating range. The thermo-hydraulic performance of the proposed configurations may vary under different operating conditions or transient thermal states. Furthermore, the present study mainly uses the thermo-hydraulic performance factor (REF) to evaluate the overall performance and identify the optimal configuration within the investigated operating range. Although REF simultaneously considers heat-transfer enhancement and pressure-drop penalty, it does not fully reflect other important thermal requirements of battery systems, such as the maximum temperature and temperature uniformity.
Therefore, future studies will focus on the experimental validation of the optimized configurations, the extension of the operating range, the investigation of transient heat-transfer characteristics, and the development of multi-objective optimization strategies considering thermo-hydraulic performance, the maximum temperature and temperature uniformity simultaneously. In addition, manufacturability, hybrid enhancement structures, and more complex baffle arrangements will be investigated to further improve the system’s cooling performance.

Author Contributions

T.D.N.: Conceptualization, Project administration, Writing—original draft, Writing—review & editing. B.V.L.: Supervision, Methodology, Software, Writing—review & editing. D.N.: Writing—review & editing, Visualization. T.D.D.: Writing—original draft, Visualization, Formal analysis. D.H.V.: Writing—original draft, Visualization, Formal analysis. Y.-H.C.: Writing—review & editing. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by Hanoi University of Science and Technology (HUST), under project code T2025-PC-037.

Data Availability Statement

The data presented in this study are available from the corresponding author upon reasonable request.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

REFThermo-hydraulic performance factor
NuAverage Nusselt number
ReReynolds number
RThermal resistance [K/W]
Δ T Surface temperature difference [K]
Δ P Pressure drop [Pa]
QHeat transfer heat
LMTDLog mean temperature difference
qHeat flux [W/m2]
TTemperature [K]
T wall Heat transfer surface temperature [K]
T L , out Outlet liquid temperature [K]
T L , in Inlet liquid temperature [K]
mMass flow rate [kg/s]
uVelocity [m/s]
PPressure [Pa]
DHydraulic diameter [m]
AEffective heat transfer area [m2]
BWetted perimeter [m]
ρ Density [kg/m3]
μ Dynamic viscosity [kg/(m·s)]
CpSpecific heat [J/(kg·K)]
kThermal conductivity [W/(m·K)]
T max Maximum surface temperature [K]
T min Minimum surface temperature [K]
P in Inlet pressure [Pa]
P out Outlet pressure [Pa]

References

  1. Hwang, F.S.; Confrey, T.; Reidy, C.; Picovici, D.; Callaghan, D.; Culliton, D.; Nolan, C. Review of Battery Thermal Management Systems in Electric Vehicles. Renew. Sustain. Energy Rev. 2024, 192, 114171. [Google Scholar] [CrossRef]
  2. Bibin, C.; Vijayaram, M.; Suriya, V.; Sai Ganesh, R.; Soundarraj, S. A Review on Thermal Issues in Li-Ion Battery and Recent Advancements in Battery Thermal Management System. Mater. Today Proc. 2020, 33, 116–128. [Google Scholar] [CrossRef]
  3. Lu, M.; Zhang, X.; Ji, J.; Xu, X.; Zhang, Y. Research Progress on Power Battery Cooling Technology for Electric Vehicles. J. Energy Storage 2020, 27, 101155. [Google Scholar] [CrossRef]
  4. Kumar, R.; Goel, V. A Study on Thermal Management System of Lithium-Ion Batteries for Electrical Vehicles: A Critical Review. J. Energy Storage 2023, 71, 108025. [Google Scholar] [CrossRef]
  5. Tosun, E.; Ilinčić, P.; Keyinci, S.; Yakaryilmaz, A.C.; Ozcanli, M. A Review on Air and Liquid Cooling Strategies for Lithium-Ion Batteries. Appl. Sci. 2025, 15, 12617. [Google Scholar] [CrossRef]
  6. Martellucci, L.; Capata, R.; Marco, M.D. Comparative Review of Cooling Systems for Lithium-Ion Battery Modules with 21700 Cylindrical Cells. Batteries 2026, 12, 107. [Google Scholar] [CrossRef]
  7. Akbarzadeh, M.; Kalogiannis, T.; Jaguemont, J.; Jin, L.; Behi, H.; Karimi, D.; Beheshti, H.; Van Mierlo, J.; Berecibar, M. A Comparative Study between Air Cooling and Liquid Cooling Thermal Management Systems for a High-Energy Lithium-Ion Battery Module. Appl. Therm. Eng. 2021, 198, 117503. [Google Scholar] [CrossRef]
  8. Arora, S.; Kapoor, A.; Shen, W. A Novel Thermal Management System for Improving Discharge/Charge Performance of Li-Ion Battery Packs under Abuse. J. Power Sources 2018, 378, 759–775. [Google Scholar] [CrossRef]
  9. Liu, H.; Shi, C.; Liu, C.; Chang, W. A Review of Lithium-Ion Battery Thermal Management Based on Liquid Cooling and Its Evaluation Method. Energies 2025, 18, 4569. [Google Scholar] [CrossRef]
  10. Kumar, D.; Gupta, R.B.; Ranjan, R.; Dutta, T. CFD Simulation Of Lithium-Ion Battery Pack Thermal Management System With Different Cooling Fluids Under High Discharge Rate Condition. J. Enhanc. Heat Transf. 2025, 32, 105–127. [Google Scholar] [CrossRef]
  11. Jin, L.W.; Lee, P.S.; Kong, X.X.; Fan, Y.; Chou, S.K. Ultra-Thin Minichannel LCP for EV Battery Thermal Management. Appl. Energy 2014, 113, 1786–1794. [Google Scholar] [CrossRef]
  12. Chung, Y.; Kim, M.S. Thermal Analysis and Pack Level Design of Battery Thermal Management System with Liquid Cooling for Electric Vehicles. Energy Convers. Manag. 2019, 196, 105–116. [Google Scholar] [CrossRef]
  13. Madani, S.S.; Schaltz, E.; Kær, S.K. Thermal Analysis of Cold Plate with Different Configurations for Thermal Management of a Lithium-Ion Battery. Batteries 2020, 6, 17. [Google Scholar] [CrossRef]
  14. Shen, J.; Chen, X.; Xu, X.; Kong, J.; Song, Z.; Wang, X.; Zhou, F. Thermal Performance of a Hybrid Cooling Plate Integrated with Microchannels and PCM. Appl. Therm. Eng. 2024, 236, 121917. [Google Scholar] [CrossRef]
  15. Cao, J.; Ling, Z.; Fang, X.; Zhang, Z. Delayed Liquid Cooling Strategy with Phase Change Material to Achieve High Temperature Uniformity of Li-Ion Battery under High-Rate Discharge. J. Power Sources 2020, 450, 227673. [Google Scholar] [CrossRef]
  16. Lu, Y.; Wang, J.; Liu, F.; Liu, Y.; Wang, F.; Yang, N.; Lu, D.; Jia, Y. Performance Optimisation of Tesla Valve-Type Channel for Cooling Lithium-Ion Batteries. Appl. Therm. Eng. 2022, 212, 118583. [Google Scholar] [CrossRef]
  17. Huang, Y.; Wang, S.; Lu, Y.; Huang, R.; Yu, X. Study on a Liquid Cooled Battery Thermal Management System Pertaining to the Transient Regime. Appl. Therm. Eng. 2020, 180, 115793. [Google Scholar] [CrossRef]
  18. Tete, P.R.; Gupta, M.M.; Joshi, S.S. Numerical Investigation on Thermal Characteristics of a Liquid-Cooled Lithium-Ion Battery Pack with Cylindrical Cell Casings and a Square Duct. J. Energy Storage 2022, 48, 104041. [Google Scholar] [CrossRef]
  19. Rao, Z.; Qian, Z.; Kuang, Y.; Li, Y. Thermal Performance of Liquid Cooling Based Thermal Management System for Cylindrical Lithium-Ion Battery Module with Variable Contact Surface. Appl. Therm. Eng. 2017, 123, 1514–1522. [Google Scholar] [CrossRef]
  20. Kumar, D.; Samanta, A.; Dutta, T. Comparison of a Novel Mini-Channel Design with Other Coolant Channel Designs for Liquid Cooling Type of Battery Thermal Management System: A Numerical Study. Results Eng. 2025, 28, 107768. [Google Scholar] [CrossRef]
  21. Carello, M.; Bovio, M.; Ricci, F.; Dall’Acqua, S.; Strano, D.I.; Rizzello, A. CFD Simulation and Modelling of a Battery Thermal Management System: Comparison between Indirect and Immersion Cooling. SAE Int. J. Adv. Curr. Pract. Mobil. 2023, 6, 545–558. [Google Scholar] [CrossRef]
  22. Aydin, N.; Gurses, D.; Beyazoglu, E. Efficient Immersion Cooling of Lithium-Ion Batteries: A CFD and MOGA-Based Optimization Study. Appl. Sci. 2025, 15, 11564. [Google Scholar] [CrossRef]
  23. Zhu, H.; Ma, Y.; E, J.; Wei, S. Channel Structure Design and Optimization for Immersion Cooling System of Lithium-Ion Batteries. J. Energy Storage 2024, 77, 109930. [Google Scholar] [CrossRef]
  24. Patil, S.R.; Lokavarapu, B.R.; Thaliyanveedu, H.K. Optimization of Battery Cooling System Used in Electric Vehicles. J. Energy Storage 2023, 58, 106299. [Google Scholar] [CrossRef]
  25. Yang, H.; Wang, Z.; Li, M.; Ren, F.; Ma, B. Numerical Study on Cross-Linked Cold Plate Design for Thermal Management of High-Power Lithium-Ion Battery. Batteries 2023, 9, 220. [Google Scholar] [CrossRef]
  26. Jayarajan, S.A.; Azimov, U. CFD Modeling and Thermal Analysis of a Cold Plate Design with a Zig-Zag Serpentine Flow Pattern for Li-Ion Batteries. Energies 2023, 16, 5243. [Google Scholar] [CrossRef]
  27. Rahmani, A.; Dibaj, M.; Akrami, M. Enhancing Battery Pack Cooling Efficiency Through Graphite-Integrated Hybrid-Battery Thermal Management Systems. Batteries 2025, 11, 113. [Google Scholar] [CrossRef]
  28. Madani, S.S.; Schaltz, E.; Knudsen Kær, S. Design and Simulation of Internal Flowing Twisted Conduits for Cooling of Lithium-Ion Batteries through Thermal Characterization. Batteries 2020, 6, 31. [Google Scholar] [CrossRef]
  29. Shahid, S.; Agelin-Chaab, M. Investigation of Heat Transfer Enhancement Techniques on a Scalable Novel Hybrid Thermal Management Strategy for Lithium-Ion Battery Packs. Batteries 2024, 10, 32. [Google Scholar] [CrossRef]
  30. You, N.; Ham, J.; Shin, D.; Cho, H. Performance Analysis of the Liquid Cooling System for Lithium-Ion Batteries According to Cooling Plate Parameters. Batteries 2023, 9, 538. [Google Scholar] [CrossRef]
  31. Kim, M.; Ham, J.; Shin, D.; Cho, H. Comparison of Cooling Performance in a Cylindrical Battery with Single-Phase Direct Contact Cooling under Various Operating Conditions. Batteries 2022, 8, 195. [Google Scholar] [CrossRef]
  32. Zhao, K.; Sun, X.; Xia, Y.; Li, Q.; Shen, L.; Lin, M. Cold Plate Performance Enhancement Based on Parametric Modeling of Multiple Structures. Front. Energy Res. 2023, 10, 1087682. [Google Scholar] [CrossRef]
  33. Monika, K.; Chakraborty, C.; Roy, S.; Sujith, R.; Datta, S.P. A Numerical Analysis on Multi-Stage Tesla Valve Based Cold Plate for Cooling of Pouch Type Li-Ion Batteries. Int. J. Heat Mass Transf. 2021, 177, 121560. [Google Scholar] [CrossRef]
  34. Sameer Mahmoud, N.; Mohammad Jaffal, H.; Abdulnabi Imran, A. Performance Evaluation of Serpentine and Multi-Channel Heat Sinks Based on Energy and Exergy Analyses. Appl. Therm. Eng. 2021, 186, 116475. [Google Scholar] [CrossRef]
  35. Yao, F.; Guan, X.; Yang, M.; Wen, C. Study on Liquid Cooling Heat Dissipation of Li-Ion Battery Pack Based on Bionic Cobweb Channel. J. Energy Storage 2023, 68, 107588. [Google Scholar] [CrossRef]
  36. Han, J.-W.; Garud, K.S.; Kang, E.-H.; Lee, M.-Y. Numerical Study on Heat Transfer Characteristics of Dielectric Fluid Immersion Cooling with Fin Structures for Lithium-Ion Batteries. Symmetry 2022, 15, 92. [Google Scholar] [CrossRef]
  37. Wu, K.; Zhao, H.; Wang, Y. Cold Storage and Release Characteristics of Phase Change Cold Storage Plate with Non-Uniform Fins. Energies 2024, 17, 3610. [Google Scholar] [CrossRef]
  38. Zhao, G.; Wang, X.; Negnevitsky, M.; Li, C.; Zhang, H.; Cheng, Y. A High-Performance Vortex Adjustment Design for an Air-Cooling Battery Thermal Management System in Electric Vehicles. Batteries 2023, 9, 208. [Google Scholar] [CrossRef]
  39. Zhang, Y.; Fu, Q.; Liu, Y.; Lai, B.; Ke, Z.; Wu, W. Investigations of Lithium-Ion Battery Thermal Management System with Hybrid PCM/Liquid Cooling Plate. Processes 2022, 11, 57. [Google Scholar] [CrossRef]
  40. Gungor, S.; Lorente, S. PCM-Based Passive Cooling Solution for Li-Ion Battery Pack, a Theoretical and Numerical Study. Appl. Therm. Eng. 2024, 257, 124262. [Google Scholar] [CrossRef]
  41. Jaffal, H.M.; Mahmoud, N.S.; Imran, A.A.; Hasan, A. Performance Enhancement of a Novel Serpentine Channel Cooled Plate Used for Cooling of Li-Ion Battery Module. Int. J. Therm. Sci. 2023, 184, 107955. [Google Scholar] [CrossRef]
  42. Abdulhaleem Abdulqader, A.; Jaffal, H.M. Comparative Investigation on Heat Transfer Augmentation in a Liquid Cooling Plate for Rectangular Li-Ion Battery Thermal Management. Results Eng. 2024, 24, 102913. [Google Scholar] [CrossRef]
Figure 1. The geometry of the parallel-channel cold plate and the investigated channel configurations.
Figure 1. The geometry of the parallel-channel cold plate and the investigated channel configurations.
Batteries 12 00183 g001
Figure 2. Enhanced models: (a) Parallel channel cold plate with cylindrical baffles. (b) Parallel channel cold plate with fin-type baffles.
Figure 2. Enhanced models: (a) Parallel channel cold plate with cylindrical baffles. (b) Parallel channel cold plate with fin-type baffles.
Batteries 12 00183 g002
Figure 3. Computational mesh and local refinement regions of the cold-plate model.
Figure 3. Computational mesh and local refinement regions of the cold-plate model.
Batteries 12 00183 g003
Figure 4. Mesh independence results for Module 1.
Figure 4. Mesh independence results for Module 1.
Batteries 12 00183 g004
Figure 5. MMCHS: (a) Original geometry reproduced from Mahmoud et al. [34]. (b) Reproduced model used in the present numerical simulation.
Figure 5. MMCHS: (a) Original geometry reproduced from Mahmoud et al. [34]. (b) Reproduced model used in the present numerical simulation.
Batteries 12 00183 g005
Figure 6. Computational mesh and local refinement regions of the MMCHS.
Figure 6. Computational mesh and local refinement regions of the MMCHS.
Batteries 12 00183 g006
Figure 7. Direct overlay comparison between the reference experimental data from Mahmoud et al. [34] and the present numerical results for the MMCHS: (a) reference experimental data [34]; (b) numerical results obtained in the present study.
Figure 7. Direct overlay comparison between the reference experimental data from Mahmoud et al. [34] and the present numerical results for the MMCHS: (a) reference experimental data [34]; (b) numerical results obtained in the present study.
Batteries 12 00183 g007
Figure 8. Geometric parameter ranges of the enhanced configurations: (a) Module 2; (b) Module 3.
Figure 8. Geometric parameter ranges of the enhanced configurations: (a) Module 2; (b) Module 3.
Batteries 12 00183 g008
Figure 9. Effects of geometric parameters on Module 2 performance: (a) Average temperature of the heat-transfer surface ( T wall ). (b) Average Nusselt number (Nu). (c) Thermal resistance (R).
Figure 9. Effects of geometric parameters on Module 2 performance: (a) Average temperature of the heat-transfer surface ( T wall ). (b) Average Nusselt number (Nu). (c) Thermal resistance (R).
Batteries 12 00183 g009
Figure 10. Effects of geometric parameters on Module 2 performance: (a) Pressure drop ( Δ P ). (b) Thermo-hydraulic performance factor (REF). (c) The Reynolds number of Module 2.
Figure 10. Effects of geometric parameters on Module 2 performance: (a) Pressure drop ( Δ P ). (b) Thermo-hydraulic performance factor (REF). (c) The Reynolds number of Module 2.
Batteries 12 00183 g010
Figure 11. Effects of geometric parameters on Module 3 performance: (a) Average temperature of the heat-transfer surface ( T wall ). (b) Average Nusselt number (Nu). (c) Thermal resistance (R).
Figure 11. Effects of geometric parameters on Module 3 performance: (a) Average temperature of the heat-transfer surface ( T wall ). (b) Average Nusselt number (Nu). (c) Thermal resistance (R).
Batteries 12 00183 g011
Figure 12. Effects of geometric parameters on Module 3 performance: (a) Pressure drop ( Δ P ). (b) Thermo-hydraulic performance factor (REF). (c) The Reynolds number of Module 3.
Figure 12. Effects of geometric parameters on Module 3 performance: (a) Pressure drop ( Δ P ). (b) Thermo-hydraulic performance factor (REF). (c) The Reynolds number of Module 3.
Batteries 12 00183 g012
Figure 13. Performance comparison of Modules 1–3: (a) Average temperature of the heat-transfer surface ( T wall ). (b) Average Nusselt number (Nu). (c) Thermal resistance (R).
Figure 13. Performance comparison of Modules 1–3: (a) Average temperature of the heat-transfer surface ( T wall ). (b) Average Nusselt number (Nu). (c) Thermal resistance (R).
Batteries 12 00183 g013
Figure 14. Performance comparison of Modules 1–3: (a) Pressure drop ( Δ P ). (b) Thermo-hydraulic performance factor (REF).
Figure 14. Performance comparison of Modules 1–3: (a) Pressure drop ( Δ P ). (b) Thermo-hydraulic performance factor (REF).
Batteries 12 00183 g014
Figure 15. Surface temperature distribution of the cold plate.
Figure 15. Surface temperature distribution of the cold plate.
Batteries 12 00183 g015
Figure 16. Velocity streamline distributions of the baseline and optimized cold-plate configurations under different mass flow rates.
Figure 16. Velocity streamline distributions of the baseline and optimized cold-plate configurations under different mass flow rates.
Batteries 12 00183 g016
Table 1. Dimensional parameters of the model.
Table 1. Dimensional parameters of the model.
SymbolDescriptionDimension (mm)
LLength of the cold plate205
WWidth of the cold plate110
HHeight of the cold plate12
Hi/HoInlet/Outlet height10
Wi/WoInlet/Outlet width10
lfFlow distributor length145
wfFlow distributor width5
wWidth of each mini channel10
hfFlow distributor height10
d2Diameter of module 2 baffle1–6
h2Height of module 2 baffle1–10
s2Baffle spacing (module 2)12
l3Length of module 3 baffle1–9
h3Height of module 3 baffle1–10
t3Wall thickness (module 3)1.5
s3Baffle spacing (module 3)9
Table 2. Material properties of the model.
Table 2. Material properties of the model.
MaterialAluminumCopperWater–Liquid
Density [ kg / m 3 ]27198978998.2
Specific Heat [J/(kg·K)]8713814182
Thermal Conductivity [W/(m·K)]202.4387.60.6
Dynamic viscosity [kg/(m·s)] 0.001003
Table 3. Thermal and hydraulic boundary conditions.
Table 3. Thermal and hydraulic boundary conditions.
Boundary TypeThermal Boundary ConditionHydraulic Boundary
Condition
Inlet T L = T in v x = v y = v z
Outlet T L x = 0 P = 1 atm
Fluid–solid interface k L T L = k s T s v x = v y = v z
Heat-flux wall k s T s x = q v x = v y = v z
Other wall k L T L = 0 , k s T s = 0 v x = v y = v z
Table 4. Geometric parameters of the MMCHS model.
Table 4. Geometric parameters of the MMCHS model.
SymbolDescriptionDimension (mm)
WWidth of the cold plate50
LLength of the cold plate75
HHeight of the cold plate5
hfInlet/Outlet height2
wfInlet/Outlet width4
Table 5. Validation results for the MMCHS model.
Table 5. Validation results for the MMCHS model.
Mass Flow (kg/s)Experimental Data [34]Present Numerical
Results
Error (%)
Average Nusselt (Nu)0.00214.234.547.39
0.00274.624.814.04
0.00334.905.022.43
0.00395.085.508.29
0.00455.235.647.86
Pressure drop Δ P (Pa)0.002110091.488.52
0.0027136125.157.98
0.0033184171.946.55
0.0039229224.571.94
0.0045291282.522.91
Table 6. Parametric design space and simulation cases.
Table 6. Parametric design space and simulation cases.
ModuleParameterRange (mm)Step (mm)Total Case
Module 2d21–6160
h21–101
Module 3l31–9190
h31–101
Table 7. Best-performing configuration under the present conditions and corresponding performance of Module 2 and Module 3.
Table 7. Best-performing configuration under the present conditions and corresponding performance of Module 2 and Module 3.
Moduled2 (l3)
(mm)
h2 (h3)
(mm)
T wall (K)Nu Δ P (Pa)RREF
Module 2-opt43301.8813.19239.800.0173.25
Module 3-opt210301.3116.18233.070.0154.10
Table 8. Thermo-hydraulic performance comparison of the baseline and optimized cold plate configurations under different mass flow rates.
Table 8. Thermo-hydraulic performance comparison of the baseline and optimized cold plate configurations under different mass flow rates.
ModuleMass Flow (kg/s) T wall (K) T max (K) Δ T (K)Nu Δ P (Pa)RREF
Module 10.02323.01339.7537.595.5322.860.0601
0.04320.77336.5836.425.6571.380.0591
0.06314.43325.0326.457.08139.590.0471
0.08310.52320.0322.628.77228.280.0381
0.1309.05318.6921.699.82331.500.0341
Module 2-opt0.02308.92317.2418.667.7929.880.0293.23
0.04304.11310.3713.9710.82112.050.0213.66
0.06301.88307.5511.7813.19239.800.0173.25
0.08300.86306.1010.7214.98424.850.0152.76
0.1300.07304.909.7916.61665.460.0142.53
Module 3-opt0.02308.59316.6718.339.1431.170.0283.64
0.04303.67310.4714.2512.62108.680.0204.40
0.06301.31307.2811.8416.18233.070.0164.10
0.08300.06305.4710.4319.18405.420.0133.70
0.1299.21304.109.3121.92625.240.0123.55
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Nguyen, T.D.; Nguyen, D.; Do, T.D.; Vu, D.H.; Chang, Y.-H.; Le, B.V. Thermo-Hydraulic Optimization of Parallel-Channel Cold Plates Using CFD: A Comparative Study of Cylindrical and Fin-Type Baffles for Battery Thermal Management. Batteries 2026, 12, 183. https://doi.org/10.3390/batteries12050183

AMA Style

Nguyen TD, Nguyen D, Do TD, Vu DH, Chang Y-H, Le BV. Thermo-Hydraulic Optimization of Parallel-Channel Cold Plates Using CFD: A Comparative Study of Cylindrical and Fin-Type Baffles for Battery Thermal Management. Batteries. 2026; 12(5):183. https://doi.org/10.3390/batteries12050183

Chicago/Turabian Style

Nguyen, Tien Dung, Dong Nguyen, Trong Duong Do, Dinh Hoan Vu, Yeong-Hwa Chang, and Bao Viet Le. 2026. "Thermo-Hydraulic Optimization of Parallel-Channel Cold Plates Using CFD: A Comparative Study of Cylindrical and Fin-Type Baffles for Battery Thermal Management" Batteries 12, no. 5: 183. https://doi.org/10.3390/batteries12050183

APA Style

Nguyen, T. D., Nguyen, D., Do, T. D., Vu, D. H., Chang, Y.-H., & Le, B. V. (2026). Thermo-Hydraulic Optimization of Parallel-Channel Cold Plates Using CFD: A Comparative Study of Cylindrical and Fin-Type Baffles for Battery Thermal Management. Batteries, 12(5), 183. https://doi.org/10.3390/batteries12050183

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop