Study on Reheater Tube Wall Temperature in a 1000 MW Ultra-Supercritical Unit Under Flexible Peak-Shaving Conditions
Abstract
1. Introduction
- Existing units shall achieve a minimum power generation output of 25–40% of the rate d load;
- Newly built bituminous coal-fired pulverized coal furnace units shall strive to reach 25% or lower of the rated load under pure condensing conditions;
- Pilot demonstration units of the new generation of coal-fired power shall reach below 20% of the rated load.
2. Reheater Introduction
3. Experimental Conditions and Measurement Points Arrangement
- The boiler’s operating conditions are detailed in Table 2.
- The sensor employed is a K-type thermocouple, with an allowable tolerance of ±1.5 °C. Its calibration date is 1 March 2023.
- Temperature data collection was performed from 1 May 2023 to 31 July 2024.
4. Result Analysis
4.1. LRH
4.2. HRH
4.3. Comparison of Maximum Temperature Difference Between LRH and HRH
- (1)
- Under flexible load-following operation, load changes affect the entire boiler system. On the combustion side, load adjustments lead to corresponding changes in coal feeding rates, which in turn impact the output and operational parameters of coal mills. An imbalance in coal supply between the front and rear walls of the mills may trigger issues such as premature or delayed ignition of pulverized coal and deviation of the flame center. These problems ultimately cause fluctuations in flue gas temperature, which can further result in uneven of the reheater tube walls [21].
- (2)
- To maintain stable furnace combustion, the air supply to the furnace must increase or decrease in tandem with load adjustments. However, there is a lack of synchronization between the response time of coal feeding and that of airflow. This asynchrony is another key factor contributing to uneven wall temperatures in both LRH and HRH.
- (3)
- Changes in coal quality can also induce uneven heating. Coal with higher volatile content has a lower ignition temperature, enabling faster combustion and a shorter burnout time. To sustain stable combustion under such conditions, more coal must be fed into the furnace per unit time. This increases both the flue gas temperature and heat transfer in the reheaters, thereby raising the tube wall temperature.
- (4)
- Load variations also induce changes in the exhaust temperature of the turbine’s high-pressure cylinder (HPC). Specifically, if the HPC exhaust temperature rises—particularly during the boiler’s high-load operation—two key effects on the reheater occur. First, the flue gas flow rate and flue gas temperature at the reheater both increase. Second, the higher exhaust temperature raises the steam temperature at the reheater inlet, which reduces the temperature difference between the two heat transfer fluids (flue gas and steam) and weakens the overall heat transfer efficiency.
5. Conclusions
- (1)
- The wall temperature distribution of the LRH exhibits two parabolic patterns from the left to the right wall, with measurement points 4 and 7 corresponding to the peaks of these parabolas. The LRH experiences uneven heating, with the wall temperature difference ranging from a minimum of 63.8 °C to a maximum of 88.3 °C. Under the experimental conditions, none of the LRH tubes exceeded the maximum allowable wall temperature limit.
- (2)
- For the HRH, the maximum temperature difference value is 82.8 °C, and the minimum is 32.7 °C. At electrical loads of 217.7 MW, the maximum temperature difference of the HRH is higher than that of the LRH. However, under flexible load-following operation, the LRH faces a higher risk of tube rupture due to uneven heating compared to the HRH.
Author Contributions
Funding
Data Availability Statement
Conflicts of Interest
References
- National Development and Reform Commission, National Energy Administration. Action Plan for the Construction of Low-Carbon Transformation of Coal-Fired Power (2024–2027). Available online: https://www.ndrc.gov.cn/xxgk/zcfb/tz/202407/t20240715_1391663.html (accessed on 5 March 2025).
- The Central People’s Government of the People’s Republic of China. Energy Law of the People’s Republic of China. 8 November 2024. Available online: https://www.gov.cn/yaowen/liebiao/202411/content_6985761.htm (accessed on 5 March 2025).
- National Development and Reform Commission, National Energy Administration. 14th Five-Year Plan for Modern Energy System. 15 April 2022. Available online: https://www.ndrc.gov.cn/xwdt/tzgg/202203/P020220322583239614565.pdf (accessed on 5 March 2025).
- National Development and Reform Commission, National Energy Administration. The Special Action Implementation Plan for the Upgrading of a New Generation of Coal-Fired Power (2025–2027). Available online: https://www.ndrc.gov.cn/xxgk/zcfb/tz/202504/t20250414_1397185.html (accessed on 5 March 2025).
- Modliński, N.; Szczepanek, K.; Nabagło, D.; Madejski, P.; Modliński, Z. Mathematical procedure for predicting tube metal temperature in the second stage reheater of the operating flexibly steam boiler. Appl. Therm. Eng. 2019, 146, 854–865. [Google Scholar] [CrossRef]
- González, M.M.P.; García, F.J.F.; Ramón, I.S.; Roces, H.S. Experimental thermal behavior of a power plant reheater. Energy 2006, 31, 665–676. [Google Scholar] [CrossRef]
- Prieto, M.M.; Suárez, I.; Fernández, F.; Sánchez, H.; Viescas, C. Application of a thermal model to a power plant reheater with irregular tube temperatures. Appl. Therm. Eng. 2007, 27, 185–193. [Google Scholar] [CrossRef]
- Purbolaksono, J.; Khinani, A.; Rashid, A.; Ali, A.; Ahmad, J.; Nordin, N. A new method for estimating heat flux in superheater and reheater tubes. Nucl. Eng. Des. 2009, 239, 1879–1884. [Google Scholar] [CrossRef]
- Jiang, L.; Li, Y.; Yao, Y.; Zhang, M.; Lu, J.; Huang, Z.; Zhou, T.; Yue, G. Heat transfer and protection of HRH of a 660 MW circulating fluidized bed boiler after black out. Appl. Therm. Eng. 2022, 213, 118654. [Google Scholar] [CrossRef]
- Xie, J.; Wen, W.; Yang, B.; Yang, F.; Ping, L.; Zhang, F.; Zhang, J. Thermal deviation analysis of HRH for single-tangential π type boiler. Appl. Therm. Eng. 2021, 192, 116846. [Google Scholar] [CrossRef]
- Wang, H.; Lu, X.; Zhang, W.; Wang, Q.; Chen, J.; Kang, Y.; Kuang, W.; Xin, S.; Liu, C.; Xie, X. Study on heat transfer characteristics of the high temperature reheater tube panel in a 300 MW CFB boiler with fluidized bed heat exchanger. Appl. Therm. Eng. 2015, 81, 262–270. [Google Scholar] [CrossRef]
- Yin, L.; Xie, J. Multi-feature-scale fusion temporal convolution networks for metal temperature forecasting of ultra-supercritical coal-fired power plant reheater tubes. Energy 2022, 238, 121657. [Google Scholar] [CrossRef]
- Yin, L.; Zhou, H. Modal decomposition integrated model for ultra-supercritical coal-fired power plant reheater tube temperature multi-step prediction. Energy 2024, 292, 130521. [Google Scholar] [CrossRef]
- Wang, X.; Du, C.; Zhang, K.; Zhang, Y.; Huang, Q. Steam oxidation behavior of T92 steel tube for high temperature reheater after long-term service in ultra-supercritical boilers. Corros. Sci. 2023, 221, 111352. [Google Scholar] [CrossRef]
- Ahmad, J.; Purbolaksono, J. An incident investigation on stub tube at high temperature reheater outlet header region of a power plant. Eng. Fail. Anal. 2010, 17, 1254–1259. [Google Scholar] [CrossRef]
- Xu, M.; Xue, S.; Hu, F.; Jiang, Z.; Zheng, L.; Ren, Y.; Li, Z.; He, S.; Deng, R. Failure case study on reheater pipes in a subcritical unit served for a thermal power plant. Case Stud. Therm. Eng. 2024, 59, 104550. [Google Scholar] [CrossRef]
- Yin, L.; Zhou, H. Multiscale convolutional attention Transformer based on transfer learning for temperature forecasting of ultra-supercritical coal-fired power plant reheater. Appl. Soft Comput. 2026, 186, 114068. [Google Scholar] [CrossRef]
- Gao, L. Analysis of reasons for undertemperature of superheater an reheater at a 660 MW ultra-supercritical boiler power plant. Boil. Manuf. 2024, 4, 9–10, 15. Available online: https://kns.cnki.net/kcms2/article/abstract?v=X-VFCYicIZtEnAOO_YSOVoHfX6eoSpPaax1S1NLW5pBUq6tyPzOporNBJbuxiCD3ZcRMOzbKsdpJWl6ANVH8RMBBKQWo0ej2Ym8Vux8S0ddXN4Td-vknib8IAoipMqHkwk9juOM670j8DThtKgE0jHtvxVD7o_acZSpve0MAfURQ4dMu3LSDFoh56i_KBUHz&uniplatform=NZKPT&language=CHS (accessed on 20 April 2025).
- Yan, L.; Yan, J.; Pu, J.; Song, Y.; Wu, X.; Lu, X. Study on superheater wall temperature in a 1000 MW ultra-supercritical power plant under flexible load operation. Case Stud. Therm. Eng. 2025, 74, 106994. [Google Scholar] [CrossRef]
- Du, S. The Numerical Simulation Calculation for Tube Wall Temperature of Pedant Superheater of Power Station Boiler. Master’s Thesis, North China Electric Power University, Beijing, China, 2008. Available online: https://kns.cnki.net/kcms2/article/abstract?v=kg-5wHjgO94cLELlyTxjoHPbYSdgXmJrYMOTBVYu4yRrz_GuPYStyT8uuZiXYDa6yji-zdzD5H8sCvTu3DtZkQJ5kS8OFtwOXE8Epa4obEjQioA8hZfjB90_hwEqk7sgZW1jOvOvvLntz0m6N-eBm6hDOWNhZDGI-BjETnlT0qvEXyOOB5nk3TOSJT1uSmwy&uniplatform=NZKPT&language=CHS (accessed on 10 December 2024).
- Lei, S.; Sun, F.; Shi, Y.; Lei, W.; Jiao, P.; Wang, N.; Huang, X. Studies of the start-up parameters on wall temperature of reheater. Power Syst. Eng. 2005, 21, 29–31. Available online: https://kns.cnki.net/kcms2/article/abstract?v=kg-5wHjgO97RODdsCmBtVOGung47Ffa_yHPS-0OSHSHxhnGqtBPsJ5UtHYbKdoseHZSKpx-Ff6gSL_EuqWsj-CJas8kme3GDrDCQLt0gCOM95eHa8M_w1zVKC_8Eg6P6-V9-cpRp-T_fTJoLiu6C0vO4lhUPyw91qItAbFxKDnDdOkxpkrFUKaS-SKZ_TQhD&uniplatform=NZKPT&language=CHS (accessed on 10 December 2024).











| Physical Model | Research Method | Load Variation | Reference |
|---|---|---|---|
| The second stage reheater of the operating flexible steam boiler is represented by 52 micro-exchangers and heated pipe flow model | CFD (Computational Fluid Dynamics), NTU (number of transfer units) and log-mean temperature difference method | 60%, 100% | [5] |
| The reheater of a 370 MW controlled steam circulation coal-fired boiler | Experiment | Full load and Low load | [6] |
| The reheater of a 350 MW power plant | Model and experiment | Nominal | [7] |
| A model pipe of 100 mm in length | Ansys | Not mentioned | [8] |
| HRH of a 660 MW circulating fluidized bed boiler | Fluent | Not mentioned | [9] |
| HRH of a 660 MW ultra-supercritical boiler | Thermal deviation experiment | 600 MW | [10] |
| HRH in a 300 MW CFB boiler | Experiment and cell model | 67%, 80%, 97% | [11] |
| Ultra-supercritical coal-fired power plant reheater | A multi-feature-scale fusion temporal convolution network and modal decomposition integrated model | Not mentioned | [12,13] |
| Reheater of a power plant | X-ray diffraction, et al. | Not mentioned | [14,15,16] |
| Ultra-supercritical coal-fired power plant reheater | Multi-scale convolutional attention transformation model | Not mentioned | [17] |
| Reheater at a 660 MW ultra-supercritical boiler power plant | Operating data | From 644 MW to 660 MW | [18] |
| Load (MW) | Main Steam Pressure (MPa) | Main Steam Temperature (°C) | Oxygen Content (%) | Water-Fuel Ratio |
|---|---|---|---|---|
| 217.7 | 9.40 | 563.4 | 6.82 | 6.8 |
| 267.9 | 11.45 | 570.0 | 8.10 | 5.2 |
| 348.7 | 12.05 | 599.1 | 6.16 | 4.8 |
| 448.1 | 12.85 | 601.0 | 4.13 | 4.8 |
| 508.4 | 12.42 | 582.4 | 5.79 | 5.5 |
| 605.0 | 14.80 | 600.0 | 4.32 | 5.1 |
| 643.9 | 23.17 | 598.5 | 3.51 | 4.4 |
| 758.8 | 18.58 | 599.4 | 3.22 | 4.6 |
| 804.6 | 19.09 | 588.4 | 2.91 | 4.9 |
| 898.7 | 22.15 | 598.6 | 2.98 | 5.1 |
| 990.1 | 25.03 | 598.1 | 1.94 | 6.0 |
| Monitoring Point Name | Monitoring Points | Elevation (mm) | Limit Value of Wall Temperature |
|---|---|---|---|
| Outlet wall temperature of the low reheater 1–10 | Installed on the 1st, 31st, 61st, 91st, 121st, 151st, 181st, 211th, 241st and 271st tube panels, counting from the left side of the boiler. On the 1st tubes of each tube panel, counted from the furnace front to the rear | 72,100 | 597 °C |
| Outlet wall temperature of the high reheater 1–37 | Installed on the 1st, 3rd, 5th, 7th, 9th, 11th, 13th, 15th, 17th, 19th, 21st, 23rd, 25th, 27th, 29th, 31st, 33rd, 35th, 37th, 39th, 41st, 43rd, 45th, 47th, 49th, 51st, 53rd, 55th, 57th, 59th, 61st, 63rd, 65th, 67th, 69th, 71st, 73rd tube panels, counting from the left side of the boiler. On the 1st tubes of each tube panel, counted from the furnace front to the rear | 73,510 | 645 °C |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Yan, L.; Pu, J.; Yan, J.; Lv, C. Study on Reheater Tube Wall Temperature in a 1000 MW Ultra-Supercritical Unit Under Flexible Peak-Shaving Conditions. Processes 2025, 13, 3440. https://doi.org/10.3390/pr13113440
Yan L, Pu J, Yan J, Lv C. Study on Reheater Tube Wall Temperature in a 1000 MW Ultra-Supercritical Unit Under Flexible Peak-Shaving Conditions. Processes. 2025; 13(11):3440. https://doi.org/10.3390/pr13113440
Chicago/Turabian StyleYan, Liyun, Jiang Pu, Jin Yan, and Cai Lv. 2025. "Study on Reheater Tube Wall Temperature in a 1000 MW Ultra-Supercritical Unit Under Flexible Peak-Shaving Conditions" Processes 13, no. 11: 3440. https://doi.org/10.3390/pr13113440
APA StyleYan, L., Pu, J., Yan, J., & Lv, C. (2025). Study on Reheater Tube Wall Temperature in a 1000 MW Ultra-Supercritical Unit Under Flexible Peak-Shaving Conditions. Processes, 13(11), 3440. https://doi.org/10.3390/pr13113440

