1. Introduction
Over the past decade, Northern Thailand has been persistently affected by smog and fine particulate matter (PM). This has posed significant risks to human respiratory health and has led to Chiang Mai being ranked as one of the world’s most polluted cities [
1]. According to the data from the Ministry of Public Health, from 1 January to 30 April 2016 alone, there were 1,117,683 cases of health issues attributed to smog and airborne dust [
2]. While the primary sources include wildfires and agricultural burning, the persistent nature of this pollution in urban areas has made Chiang Mai one of the world’s most polluted cities.
Currently, air filtration and circulation systems are predominantly applied in small rooms. The U.S. Environmental Protection Agency (USEPA) recommends using air filters achieving a clean air delivery rate (CADR) equivalent to four times the room volume per hour [
3]. This recommended rate is higher than that of ASHRAE standards, primarily because such systems lack directional airflow control. Consequently, air must be circulated and purified multiple times to effectively remove dust particles infiltrating through various openings, leaks, or other uncontrolled pathways. In contrast, centralized air filtration systems for large buildings such as hotel lobbies, school auditoriums and department stores operate differently. These systems typically integrate primary filtration within the central air handling unit before delivering air through ductwork and are often supplemented by secondary local filtration in individual rooms. This approach ensures clean air delivery and energy efficiency. However, using conventional HEPA filter systems in this large space is often impractical due to high maintenance costs, declining clean air delivery rates over the filter’s service life, and undesirable air temperature increases caused by pressure drops across the dense filter media. These limitations highlight the need for improved dust elimination technologies. The implementation of active particle growth stages has been shown to effectively balance high PM
2.5 removal efficiency with fan power demands, offering a more sustainable alternative to traditional HEPA-only systems in large-scale infrastructures [
4]. Wet scrubbers and cyclone technologies are widely used in industry due to their relatively low energy consumption [
5]. However, they achieve high efficiency (80%) only for particles larger than 5 µm, while their efficiency drops sharply for finer particles, reaching as low as 10% for those smaller than 2.5 µm [
6]. This efficiency gap highlights a critical need for innovative “pre-conditioning” technologies that can enlarge sub-micron particles to a more filterable size before they reach mechanical collection stages. Recent global assessments highlight that the active pre-conditioning of sub-micron particles through growth mechanisms can reduce the overall energy consumption of HVAC systems by up to 25% compared to high-resistance HEPA-only configurations [
7]. Furthermore, integrating these units into hybrid filtration architectures is essential for maintaining high air exchange rates in large-scale environments [
8].
Therefore, the objective of this research is to develop the Evaporator Condensation Growth Particle Scrubber (ECGP) to address this efficiency gap. Unlike traditional scrubbers that rely primarily on water sprays, the ECGP system promotes particle growth by inducing heterogeneous condensation through controlled adiabatic pressure modulation cycles. This design aims to simplify the system by generating a supersaturated environment internally, effectively transitioning PM2.5 into the PM10 range. This paper evaluates the physical feasibility and performance of the ECGP as a scalable, cost-effective solution for improving indoor air quality in large-scale public buildings.
2. Materials and Methods
The development of the Evaporator Condensation Growth Particle Scrubber (ECGP) utilizes a synergistic approach to increase particle size by promoting droplet growth through controlled thermodynamic cycles. A schematic diagram of the experimental system is shown in
Figure 1. The apparatus comprises three main sections: (1) an aerosol generation system, (2) a particle growth chamber, and (3) a particle measurement system.
The aerosol generation system comprised a sealed cubic chamber (39 cm × 39 cm × 39 cm) in which incense smoke was produced. A deionized (DI) water spray was concurrently introduced into this chamber to humidify the aerosol stream and act as a vapor source for subsequent condensation. The temperature, relative humidity and initial particle size distribution within the chamber were monitored using integrated sensors. To transfer the aerosol into the growth section. A vacuum was first created in the particle growth chamber and the valve connecting the two chambers was then opened, allowing the humidified incense smoke to be drawn into the growth chamber by the pressure differential.
Experimental Materials and Characteristics: To ensure data reliability and eliminate interference, the following materials were utilized.
Deionized (DI) Water: High-purity deionized water (resistivity > 18 MΩ·cm at 25 °C) served as the primary vapor source for humidification. The use of DI water was critical to eliminate potential interference from dissolved ions or mineral impurities, ensuring that the resulting droplets were chemically inert and did not compromise the sensitivity of the PM sensors.
Particulate Matter (Incense Smoke): Commercial incense smoke was employed as a representative surrogate for complex particulate matter (PM). The combustion of incense generates a polydisperse aerosol comprising organic fractions (e.g., polycyclic aromatic hydrocarbons), volatile organic compounds (VOCs) and trace inorganic residues such as potassium carbonate (K2CO3) and silica (SiO2). Due to their varied surface-active properties, these chemical constituents function as effective condensation nuclei, facilitating the heterogeneous condensation process observed in this study.
The particle growth chamber consisted of a cylindrical tube with an inner diameter of 4.25 cm and a length of 90 cm in
Figure 1. The humidified aerosol from the generation unit was introduced into this chamber. To trigger particle growth, the chamber was first evacuated. When the aerosol entered this low-pressure environment, it underwent adiabatic expansion, cooling the mixture below its dew point and creating a supersaturated state. Following this expansion, the pressure was allowed to recover. In the supersaturated environment, water vapor heterogeneously condensed onto the incense particles, forming larger, particle-laden droplets. The chamber was equipped with sensors to monitor the evolution of particle size, humidity, and temperature throughout this process as shown in
Figure 1.
Particle measurement was performed using a Sensirion SPS30 particulate matter sensor (Sensirion AG, Stäfa, Switzerland). This sensor was selected for its ability to provide size-binned particle concentration data across the relevant range of 0.3 to 10 µm, which is critical for quantifying the ECGP system’s performance in shifting the particle size distribution. All experiments were conducted within the sensor’s specified optimal operating range of 20 to 40 °C and below 80% relative humidity to ensure data reliability. The sensor’s built-in fan and advanced algorithm help mitigate contamination, supporting consistent measurement throughout the testing period. To mitigate potential measurement bias at RH > 80%, the SPS30 sensor utilized its internal heater and high-speed fan to prevent condensation on the optical components. Furthermore, the comparison was made based on the PM2.5/PM10 ratio rather than absolute mass concentration to normalize potential humidity-induced drift. To ensure data reliability and consistency, all experiments for each condition were conducted in 10 trials, and the results presented represent the synchronized trends observed across these multiple trials.
The experimental system for studying particle growth is illustrated in
Figure 2. The apparatus consists of two primary components: the aerosol generation chamber and the cylindrical test chamber.
The aerosol generation chamber is designed to generate a controlled environment containing incense smoke, which serves as the surrogate for particulate matter (PM), and high humidity generated by an ultrasonic atomizer. The chamber is equipped with integrated sensors to monitor real-time temperature (T1), relative humidity (RH1), and mass concentrations of PM2.5 and PM10 (1PM).
The cylindrical test chamber is linked to the generation chamber by a control valve, which regulates aerosol transfer between two compartments. To facilitate aerosol transfer, a vacuum pump is utilized to depressurize the cylindrical chamber. The vacuum pump depressurized the chamber −0.8 bars relative to atmospheric pressure. This pressure differential allows the prepared aerosol to be drawn into the test chamber when the interconnecting valve is opened.
For active pressure modulation, the pressure modulation system is integrated into the cylindrical chamber. It consists of an internal balloon connected to an external air pump. Inflating the balloon compresses the air within the chamber, thereby increasing the internal pressure to induce the evaporative condensation process. The air was pumped into the balloon until the internal chamber pressure reached a peak of 1 bar (gauge) to ensure sufficient vapor–nucleus interaction. The test chamber also contains a second set of sensors (T2, RH2, and 2PM) for monitoring the internal conditions during experiments.
This study involved five distinct experimental conditions designed to evaluate PM2.5 and PM10 behavior and investigate particle growth potential:
Baseline (Ambient Air): An analysis of standard atmospheric conditions within the system.
Particulate Matter Only (Incense Smoke): The introduction of incense smoke without added humidity or pressure modulation.
Water Vapor Only (Ultrasonic Atomizer): The introduction of high-humidity mist into the air stream.
Particulate Matter with Pressure (Incense Smoke + Pressure): An evaluation of smoke particles under mechanical compression.
Integrated Condition (Incense Smoke + Ultrasonic Atomizer + Pressure): Combined high humidity and increased pressure to maximize evaporative condensation and particle growth.
In each condition, particle growth effectiveness was quantified by comparing PM mass concentrations between the aerosol generation chamber (inlet) and the test chamber (outlet) and by analyzing changes in the PM2.5/PM10 ratio.
Theoretical Condensation and Evaporation Models
The use of condensation to promote particle growth for enhanced removal has been extensively studied. Liu [
9] demonstrated a “Condensation Growth Particle Scrubber” where sub-micron particles in exhaust streams were enlarged by creating a saturated, low-temperature gas environment, facilitating coagulation and subsequent removal. Similarly, Yoshida [
10] applied condensation-based particle enlargement to industrial dust collection, showing its effectiveness for sub-micron particles in flue gas using methods such as mixing hot saturated air with cold air or steam injection. Recent advancements by Liu et al. [
11] have further optimized these processes by tuning the vapor saturation ratio within growth tubes to maximize heterogeneous condensation efficiency.
Fundamental studies on the growth of mechanics have been conducted in controlled settings. Tammaro [
12] investigated heterogeneous condensation in a growth tube (40 cm × 1.5 cm), finding that particle size expansion could be achieved by optimizing vapor temperature and residence time. Xu [
13] later refined this tube design by implementing a recirculation mechanism to re-condense particles, further enhancing size growth. Fan [
14] complemented these experimental studies with a numerical investigation, identifying key factors influencing PM
2.5 enlargement, including contact angle, vapor saturation ratio, and initial particle size. Additionally, Wang et al. [
15] provided a deeper molecular-scale understanding of water vapor condensation on sub-micron particles, confirming that surface chemistry significantly dictates the activation energy required for stable droplet formation.
Parallel research on spray-based dust suppression provides context for water droplet interactions. Klenk [
16] and Swanson [
17] studied water spray systems, concluding that finer sprays and optimized droplet particle size matching significantly improve fine dust collection efficiency. Beard and Pruppacher [
18] provided foundational evaporation kinetics data for falling water droplets, which is relevant for understanding droplet stability in aerosol systems. The reliability of measurement systems in these high-humidity environments has also been validated by Roberts et al. [
19], who demonstrated that laser scattering sensors, such as the SPS30, maintain high accuracy for size-binned PM monitoring even under saturation levels.
While previous studies confirm the principle of condensational growth and spray effectiveness, most systems rely on external vapor injections or complex flow designs. Furthermore, recent discourse in indoor air quality emphasizes the need for hybrid filtration systems that integrate pre-conditioning units to manage large-scale environments efficiently. This study proposes a novel, integrated approach: the Evaporator Condensation Growth Particle Scrubber (ECGP). Unlike prior systems, the ECGP generates the supersaturated environment internally via a controlled pressure modulation cycle (adiabatic expansion and compression) within a single chamber, using an intrinsic water source. This design aims to simplify the system while effectively transitioning sub-micron PM2.5 into the more filterable PM10 range, addressing a key efficiency gap in existing scrubber and cyclone technologies.
5. Conclusions
The persistent crisis of fine particulate matter (PM2.5) in Northern Thailand, particularly in urban centers like Chiang Mai, underscores the urgent need for cost-effective and high-efficiency filtration technologies. This study successfully demonstrated the physical feasibility of the Evaporator Condensation Growth Particle Scrubber (ECGP) in enhancing the size of sub-micron particles through a synergistic, pressure-driven condensational growth mechanism. While this study confirms the physical feasibility of using incense smoke as a surrogate, future research will evaluate the ECGP system with actual ambient smog to account for variations in hygroscopicity and surface chemistry.
Our experimental findings confirmed that neither mechanical pressure nor high humidity alone is sufficient to achieve stable particle growth. However, the integration of solid nuclei, high relative humidity (approximately 95%) and adiabatic cycles resulted in a significant shift in particle size distribution. The vacuum-induced suction phase combined with balloon-mediated compression acted as a primary driving mechanism for heterogeneous condensation onto incense smoke nuclei. This integrated process achieved a measurable decrease in the PM2.5/PM10 mass ratio from approximately 100% to 83%, effectively transitioning approximately 17.5% (with a standard deviation < 1% across 10 trials, p < 0.05) of the fine mass into the larger, more filterable PM10 fraction. While the PM2.5/PM10 mass ratio provided a practical indicator of particle growth in this study, the authors acknowledge the limitation of not utilizing a Scanning Mobility Particle Sizer for detailed number-based distribution analysis. Consequently, future research will prioritize the integration of high-resolution aerosol spectrometers and microscopy validation to provide a more granular characterization of the condensational growth kinetics.
The resulting particles exhibited high physical stability and resistance to re-evaporation, which is critical for their eventual removal. By growing particles beyond the 2.5 µm threshold, the ECGP technology offers a promising pathway to address the low-efficiency limitations (typically <10%) of standard cyclone and scrubber systems for sub-micron dust.
In conclusion, the ECGP represents a promising innovation for large-scale indoor air purification in public infrastructures, such as schools and hospitals, where traditional HEPA filtration may be cost-prohibitive. Future work will focus on integrating the ECGP with downstream collection units to evaluate total system removal efficiency, alongside optimizing pressure modulation cycles and evaluating energy consumption for real-world application under diverse environmental conditions.