3.1. Influence of Rotor Geometry on Internal Flow Structures
Numerical modeling of gas-dynamic processes was performed using the SolidWorks Flow Simulation module. The computational domain included the inlet manifold; compressor working chamber; outlet channel; and internal casing volume. Air, considered a compressible Newtonian gas, was adopted as the working fluid. The calculations in this section were performed using a quasi-steady frozen-rotor formulation at a fixed mid-compression angular position, taking turbulence into account. This approach captures the instantaneous pressure and velocity fields at a single compression phase and supports qualitative comparative geometry assessment; it does not provide cycle-averaged thermodynamic performance and should not be interpreted as equivalent to a full transient simulation. Conclusions drawn from this section are therefore directional in nature. Full time-accurate transient simulations using the Cartesian immersed-boundary formulation are applied in
Section 3.2 and
Section 3.3, though these were conducted for a single rotor configuration focused on pulsation response rather than on a symmetric comparative assessment of both profiles. The numerical modeling enabled a detailed investigation of the working fluid flow characteristics within a three-screw compressor for two rotor geometry variants. The analysis covered the spatial structure of gas movement, the nature of velocity changes, the intensity of vortex formations, and the distribution of static pressure both within the working chamber volume and on the rotor surfaces. A consistent transition from evaluating kinematic parameters to considering force factors allowed for a comprehensive understanding of the influence of the screw profile on hydrodynamic processes.
Figure 4 shows the quasi-steady static pressure distribution combined with a visualization of the flow streamlines within the working chamber of a three-screw compressor for two rotor profile configurations (type A and type B). The color scale represents the static pressure (Pa), and the streamlines illustrate the instantaneous flow organization, including interblade recirculation, leakage-induced jets, and vortex structures at the outlet. A comparative analysis reveals that rotor profile geometry significantly influences pressure changes, leakage intensity, and dynamic pulsation behavior.
The overall pressure increases in the compression chamber, defined as
, was slightly higher for configuration B; however, this increase was accompanied by more pronounced spatial pressure non-uniformity concentrated at the discharge port, where intermittent high-velocity leakage jets—driven by the elevated overall pressure differential—generate intensified vortex structures upon port opening (consistent with Ma
max = 0.26 and K
p = 0.081 in
Table 3). Similar behavior was observed in previous studies of screw compressors, where rotor geometry directly influenced pressure gradients and local turbulence formation [
48,
49]. Increased local pressure gradients enhance shear layer development and can increase aerodynamic losses due to increased mixing and dissipation.
Although configuration B produces a slightly higher pressure rise, the increase is accompanied by stronger spatial non-uniformity in the outlet zone and elevated pressure pulsations, as discussed in the subsequent section. Increased pulsation levels are typically associated with enhanced outlet vortex shear layers and leakage-induced shear layers, as reported in detailed CFD studies of screw compressors and rotary machines.
Velocity field analysis confirms that peak velocity values are observed in the constricted inter-rotor regions, where gas movement is determined by the gradual reduction in chamber volume during rotor rotation. These zones act as dynamic throttling regions, where flow acceleration is caused by geometric constraints and imposed kinematic compression. As the rotors advance axially, the local kinetic energy of the gas is gradually converted into pressure potential due to the compression work, leading to a monotonic increase in pressure along the compression path.
Velocity distribution is highly dependent on the rotor surface geometry. Changes in profile curvature alter local acceleration gradients and shear layer development in the inter-blade region. Increased curvature and segmented surface transitions contribute to increased jet deflection and enhanced vortex formation, leading to non-uniform velocity fields across the chamber cross-section. Conversely, smoother and more continuous surface geometry reduces local acceleration peaks, reduces shear layer enhancement, and promotes more uniform gas transport. This behavior is consistent with the results of computational fluid dynamics (CFD) studies of screw compressors, which show that rotor profile design directly influences vortex intensity, secondary flow structures, and aerodynamic losses.
Analysis of the static pressure field further reveals significant differences in the compression dynamics between the two configurations. The first configuration exhibits distinct pressure discontinuities between adjacent working chambers, manifested as localized pressure peaks and steep contour gradients. These abrupt pressure changes indicate uneven volumetric compression and increased interaction between chambers during rotor rotation. This behavior can lead to increased mechanical stress on the rotor surfaces and sealing faces, as well as increased pressure pulsation amplitude.
In contrast, Type B exhibits a more uniform pressure distribution during the mid-compression phase: the pressure increase along the axial direction is gradual, with reduced contour discontinuities and smoother transitions between adjacent working chambers. This uniformity is a characteristic of the mid-compression zone and should be distinguished from the discharge-region behaviour described above, where the higher overall pressure ratio generates intermittent high-momentum leakage jets.
This spatial uniformity arises from the gradual curvature of the asymmetric profile, which distributes compression work more evenly across the rotor revolution cycle. The reduced local pressure gradient (∇pmax reduced by ~10% relative to Type A) lowers the instantaneous driving force for inter-chamber leakage, thereby suppressing shear layer amplification in the clearance gap and reducing dynamic loading on the rotor surfaces. However, the higher overall pressure ratio maintained by Type B means that when leakage does occur—particularly during the late compression phase—the pressure differential across the clearance is disproportionately large, generating high-velocity leakage jets (as reflected in the elevated Mamax = 0.26) that contribute to downstream turbulence and mixing losses. Consequently, the reduction in localized pressure gradient intensity does not fully translate into lower aerodynamic dissipation, as the energy penalty is redistributed toward intermittent high-momentum leakage events rather than continuous shear-layer losses.
To provide a structured comparison of the two rotor profiles, key thermodynamic and flow parameters were quantified and are summarized in
Table 3.
Comparative analysis shows that rotor surface geometry plays a critical role in ensuring speed uniformity, shear layer development, vortex formation, and pressure changes within the working chamber.
The observed performance differences between Type A and Type B can be attributed to specific geometric mechanisms. In Type A, the steeper curvature transitions at the interlobe sealing region generate sharper adverse pressure gradients, which promote earlier boundary layer separation and intensify shear layer instability. The resulting vortex shedding at the rotor tip contributes to elevated turbulent kinetic energy and enhances mixing losses in the discharge region, consistent with the higher pulsation coefficient Kp = 0.064 observed for this configuration. In Type B, the reduced interlobe clearance (δr ≈ 0.06–0.10 mm) combined with the asymmetric profile geometry produces a more continuous contact line progression during rotor rotation, suppressing the formation of discrete leakage jets. The lower leakage Reynolds number range (Releak = 4.0–8.0 × 103 for Type B vs. 3.5–6.8 × 103 for Type A under comparable pressure differentials) indicates that while the absolute leakage channel geometry is tighter in Type B, the higher pressure rise (ΔPB ≈ 1.05 × 104 Pa) drives stronger pressure-driven leakage events when the sealing line transiently opens during discharge. This trade-off—between improved sealing geometry and elevated driving pressure differential—explains the counterintuitive combination of higher pressure rise yet lower volumetric efficiency (ηv = 0.88 vs. 0.91) observed in Type B. Quantitatively, the maximum spatial pressure gradient ∇pmax in Type B was reduced by ≈10% compared to Type A, particularly near the interlobe sealing region.
While the differences between Type A and Type B observed in the quasi-steady snapshot—3 percentage points in the instantaneous η
v estimate and a K
p difference of 0.017—may appear modest in absolute terms, they are directionally consistent with the geometric differences in clearance and curvature progression. It should be noted that these values reflect a single angular position and may not be representative of cycle-averaged performance; cycle-averaged transient simulations of both profiles under identical conditions would be required to confirm the quantitative ranking. Subject to this caveat, if the directional differences are sustained over the full compression cycle, their practical significance could scale considerably at the system level—though the magnitude of such scaling cannot be reliably estimated without cycle-averaged transient data for both profiles. These considerations establish that the geometry-driven differences warrant further investigation, and that their potential fleet-level consequences may be of engineering significance pending confirmation. As will be shown in
Section 3.3, when rotor geometry effects are compounded by climate-induced performance degradation and viscosity-driven mechanical losses, the cumulative annual energy and maintenance penalties per unit reach levels of clear engineering and economic significance. These considerations establish that the reported geometry-driven differences, though numerically moderate at the unit level, carry substantial consequences at the operational and fleet level.
3.2. Dynamic Response Under Harmonic and Stochastic Inlet Pulsations
The fluid model in
Section 3.1 and
Section 3.2 is identical to that described in
Section 2.1.4 (i): compressed air with density computed from the truncated virial equation of state (ρ = p/(ZRT), Z = 0.91–0.84 across the compression path); the transition to multicomponent natural gas properties occurs exclusively in the offline digital twin seasonal module described in
Section 3.3.
Two distinct pressure amplification indicators are used in this paper and should be distinguished:
Kp = Δ
Pch/Pmean is the geometry-based pulsation coefficient reported in
Table 3 for
Section 3.1—it characterises the inherent pressure non-uniformity of each rotor profile under steady-state conditions relative to the mean chamber pressure, independently of any external excitation; Π
p = ΔP
ch/ΔP
in (Equation (15)) is the transient amplification factor used throughout
Section 3.2—it quantifies how much the chamber pressure pulsation amplitude exceeds the inlet excitation amplitude, and therefore depends on both rotor geometry and the frequency content of the inlet disturbance.
Numerical simulations revealed quantitative trends in the thermo-gas-dynamic characteristics of gas compression in a screw compressor subject to transient inlet pressure fluctuations. The baseline steady-state regime was compared against non-steady-state cases, including harmonic and quasi-random inlet disturbances, enabling the evaluation of both integral performance indicators and local flow dynamics.
Under steady-state conditions (mean inlet pressure 0.32 MPa, inlet temperature 285 K), the compression process exhibited a stable monotonic pressure increase within the closed working chambers up to 1.12 MPa at the discharge opening. The maximum local gas temperature reached 412 K, while the volume-averaged discharge temperature was 398 K, confirming thermodynamically consistent compression behavior.
When harmonic inlet oscillations were imposed according to
a distinct amplification of internal pressure pulsations was observed. The pressure fluctuation amplitude inside the chambers increased to 0.074 MPa, exceeding the external excitation amplitude (0.038 MPa). The pressure amplification factor can be defined as
where
is the internal chamber pulsation amplitude and
is the inlet excitation amplitude. For the present case,
indicating nearly twofold amplification of pressure oscillations due to dynamic interaction between inlet forcing and intrinsic chamber compression.
Table 4 presents a comparative analysis of the compression process parameters under steady-state and non-steady suction conditions, highlighting the influence of inlet pressure oscillations on thermodynamic performance.
Phase analysis revealed a distinct lag between inlet excitation and internal chamber response. The peak internal pressure was shifted relative to the inlet signal by 38–52° of rotor rotation, corresponding to a temporal delay of τlag ≈ 3.6 × 10−3 s.
This phase shift arises from the interaction of two concurrent physical processes intrinsic to the screw compressor working cycle. First, the chamber closure process is geometrically governed: as the male and female rotors advance axially, the interlobe volume transitions from an open (suction-connected) state to a fully closed (isolated) state over a finite angular interval—approximately 40–60° of rotor rotation for the present geometry. During this closure interval, the chamber remains partially exposed to the suction port, allowing the inlet pressure disturbance to directly influence the trapped gas quantity. However, the pressure signal cannot instantaneously propagate through the full chamber volume due to the finite speed of sound in the compressed gas mixture. At the mean chamber conditions (T ≈ 340 K, p ≈ 0.5 MPa), the acoustic propagation time across the chamber length (~0.2 m) is on the order of 0.5 × 10−3 s, which is non-negligible relative to the rotor period (~20 × 10−3 s at 3000 rpm). Second, the compressibility of the gas mixture introduces an additional dynamic delay: as the chamber closes, the trapped gas must first be compressed from suction pressure to match the rising chamber pressure before the inlet disturbance can fully manifest as an internal pressure fluctuation. The combined effect—geometric closure lag plus acoustic propagation delay plus compressibility-induced pressure equilibration—produces the observed phase shift of 38–52°, with the specific value depending on the instantaneous phase of the inlet oscillation relative to the chamber closure event.
Beyond the phase response, unsteady suction conditions also intensified inter-chamber leakage: local pressure gradients in the rotor meshing region increased from 1.8 × 106 to 2.6 × 106 Pa/m under harmonic excitation, reflecting the amplified instantaneous pressure differentials driving backflow through the interlobe clearances.
The gas density was computed from the virial-Z equation of state (consistent with the CFD fluid model described in
Section 2.1.4 (i))
with the compressibility factor decreasing from 0.91 at suction to 0.84 at the end of compression. In the transient regime, instantaneous density fluctuated between 5.4–6.8 kg/m
3 at the inlet and 18.6–22.1 kg/m
3 prior to discharge, with oscillation amplitudes reaching 14%, directly affecting mass throughput.
The mass flow rate was calculated as
yielding 2.40 kg/s in steady operation. Under harmonic inlet oscillations, the mean flow rate decreased to 2.21 kg/s (−7.9%), while stochastic excitation broadened the instantaneous range to 1.94–2.36 kg/s with an average value of 2.17 kg/s. Consequently, the volumetric efficiency
declined from 0.91 to 0.83. The maximum reduction occurred when the minimum inlet pressure coincided with chamber closure, highlighting the phase sensitivity of volumetric performance.
Indicator diagram analysis showed significant deformation of the compression cycle under transient suction. The indicated work per cycle,
decreased from 5.42 kJ (steady) to 4.97 kJ under unsteady conditions. Accordingly, the indicated power
dropped from 326 kW to 301 kW. In contrast, the electric drive power decreased only to 312 kW—a smaller reduction than that of N
i—because the rise in irreversible internal losses (+23 kW) partially offsets the drop in compression work. The apparent paradox of simultaneously lower total power and higher losses is resolved by the energy balance: the 8–10% reduction in mass flow under unsteady suction reduces the required indicated power N
i by ≈25 kW, which outweighs the loss increase; however, the loss fraction of total shaft power grows from 11% (38/338 kW) in steady operation to 20% (61/312 kW) under harmonic excitation, confirming substantial thermodynamic efficiency degradation.
A summary of the comparative performance parameters under steady and unsteady suction conditions is presented in
Table 5.
Thermal analysis revealed a pronounced increase in temperature non-uniformity under unsteady suction conditions. The maximum local gas temperature reached 428 K, while the minimum temperature in adjacent chambers did not exceed 371 K, resulting in a peak temperature gradient of 57 K. This represents a 22% increase compared with steady-state operation. The enhanced temperature stratification is attributed to intensified viscous dissipation and local shear-layer development induced by pressure pulsations. The viscous dissipation term in the energy equation increased by ≈10%, indicating additional internal entropy generation. Consequently, the mean discharge temperature rose from 398 K (steady regime) to 406 K under transient excitation.
The instantaneous compression ratio, defined as
varied between 2.9 and 4.1, with an average value of 3.46 compared to 3.50 in steady operation. Although the mean compression ratio remained nearly unchanged, the pulsation component introduced substantial cyclic fluctuations, leading to increased mechanical loading of the rotors.
The polytropic efficiency, evaluated as
decreased from 0.78 under steady conditions to 0.71 with harmonic excitation and to 0.69 under stochastic inlet oscillations. This reduction reflects increased irreversible losses due to enhanced viscous dissipation, pressure-gradient intensification, and leakage-driven mixing processes. While the average compression ratio remained comparable to the steady-state case, transient inlet disturbances significantly amplified thermal gradients, mechanical stresses, and thermodynamic irreversibility, leading to measurable degradation of compressor efficiency.
The corresponding increase in specific compression work reached ≈6%. The specific work was evaluated as
and increased from 135 kJ/kg in steady operation to 144 kJ/kg under transient suction conditions. This growth reflects reduced thermodynamic efficiency and enhanced irreversible losses associated with pressure pulsations and leakage intensification.
Velocity field analysis revealed the formation of additional vortex structures in the suction port region during unsteady operation. At phases of reduced inlet pressure, the maximum local flow velocity increased from 48 to 63 m/s, indicating stronger acceleration through constricted sections. This intensified shear-layer development and resulted in a significant rise in turbulent kinetic energy , which increased from 32 to 51 m2/s2. Consequently, the turbulent eddy viscosity rose to Pa·s, confirming enhanced turbulent mixing and dissipation.
Leakage through radial clearances was estimated using the slot-flow relation
where
Cd = 0.6 is the discharge coefficient for a sharp-edged interlobe clearance gap (consistent with standard orifice-flow practice for screw compressor clearances [
50,
51]),
A is the effective clearance area evaluated from the CAD geometry at each time step as the product of the instantaneous sealing line length and the radial clearance
δr(
θ), and Δp is the instantaneous pressure difference between adjacent chambers extracted from the CFD solution. Equation (24) is applied as a post-processing relation to CFD-extracted values of ρ and Δp; the result was cross-validated against the directly integrated CFD mass flux across the clearance plane, with agreement within 3%.
Peak rotor contact pressures were estimated from Hertzian line-contact theory applied to the interlobe meshing region. The peak contact pressure was computed as pH = (E∗/π)·√(Δpgap·Lc/Req), where E∗ = E/[2(1 − ν2)] = 115.4 GPa is the reduced modulus for the steel rotor pair (E = 210 GPa, ν = 0.30), Δpgap is the CFD-extracted instantaneous pressure differential driving contact at the interlobe line, Lc is the instantaneous sealing line length from the CAD model, and Req is the equivalent radius of curvature at the meshing point. This estimate idealises the rotor contact as a Hertzian cylinder and neglects oil-film load sharing; the resulting values carry an estimated uncertainty of ±15% and should be interpreted as order-of-magnitude indicators of mechanical loading intensity rather than design-level stress predictions.
When the transient pressure differential increased to 0.21 MPa, leakage mass flow rose by approximately 18%, reaching 0.19 kg/s. This additional bypass flow directly reduced effective delivery while contributing to increased gas heating due to enhanced viscous dissipation and mixing, as reflected in
Table 6.
To verify the resonance mechanism, a DFT was applied to both the inlet signal pin(t) and the chamber pressure pch(t) from the stochastic simulation (Hann window, 25 revolutions, Ttotal = 500 ms, frequency resolution Δf = 2.0 Hz). The inlet PSD Sin(f) was uniform within ±3% across 1–3000 Hz, confirming a flat excitation spectrum. The transfer function magnitude |H(f)| = |Pch(f)/Pin(f)| reveals a pronounced peak at f = 2050 ± 30 Hz, which falls within 0.3% of the analytically predicted acoustic eigenfrequency of the sealed interlobe chamber, fch = c/(2Lch) = 370/(2 × 0.09) ≈ 2056 Hz. The peak gain is 8.4× above the broadband mean, with a −3 dB bandwidth of ≈140 Hz (Q ≈ 15), consistent with moderate viscous damping in an oil-flooded cavity. This spectral peak is the direct cause of the elevated Πp = 2.3 under quasi-random excitation relative to Πp = 1.95 under single-frequency harmonic forcing at 12 Hz: despite only ≈4.6% of the input energy residing near fch, selective amplification at resonance drives a disproportionate increase in the chamber pressure response. The frequency-selective nature of this amplification confirms that the working chambers act as a dynamic filter whose response cannot be predicted by single-frequency or quasi-steady models.
Collectively, the simulations demonstrate that even moderate inlet pressure oscillations induce complex and coupled modifications of the compression process, simultaneously degrading volumetric efficiency (−8 to −10%), increasing leakage mass flow (up to +27%), elevating peak contact pressures to 167–171 MPa, and raising specific compression work by ~9%. These quantitative results establish the sensitivity of screw compressor performance to unsteady suction regimes and provide a direct basis for evaluating the energetic and mechanical consequences of pulsation disturbances in real oil and gas field installations—particularly in systems where pipeline acoustics or variable well flow rates generate broadband inlet pressure spectra capable of exciting chamber resonance.
3.3. Climate Effects on Thermodynamic Performance
As a result of the conducted research, a physics-based offline digital shadow of the screw compressor—with one-way data flow from archival SCADA records—was developed, calibrated, and offline-validated for reproducing its operational performance under seasonal variations of ambient temperature typical for oil and gas fields in the Republic of Kazakhstan. The computational–experimental framework, formed using archival operational data and field measurements, enabled the establishment of quantitative relationships between climatic parameters and key compressor performance indicators, including mass flow rate, specific energy consumption, thermal regimes, and overall energy efficiency.
Processing of technological data over a full annual cycle demonstrated that ambient temperature directly influences suction gas density, which is determined by the real-gas equation of state:
where
is suction pressure,
is the compressibility factor,
is the specific gas constant, and
is the absolute gas temperature.
A decrease in ambient temperature from +30 °C to −30 °C resulted in an increase in suction gas density from 0.92 to 1.27 kg/m3, corresponding to a 38% rise. Since the geometric displacement of the compressor remains constant, this increase in inlet density led to a proportional growth in mass throughput. Offline digital twin simulations predicted an increase in mass flow rate from 47.6 to 64.8 kg/min under cold conditions.
However, the higher mass throughput was accompanied by increased mechanical and energy demand. The model indicated elevated compression work, higher shaft torque, and intensified thermal loading of the compressor components. These results confirm that seasonal climatic variations significantly affect both performance and energy consumption of screw compressors operating with multicomponent natural gas mixtures.
The integrated analysis demonstrates that ambient temperature acts as a critical external parameter governing suction density, compression load, and overall energy balance, emphasizing the importance of incorporating climatic variability into digital performance prediction models (see
Table 7).
The electrical power consumption of the compressor was evaluated using the thermodynamic relation
where
is the mass flow rate,
is the adiabatic exponent,
is the discharge pressure, and
is the overall efficiency accounting for mechanical, volumetric, and electrical losses.
Offline digital twin simulations demonstrated that under winter operating conditions (−25 … −30 °C), the actual drive power increased to 298–305 kW compared with 272–278 kW at +20 °C. The average increase amounted to ≈9%. Although the rise in suction density enhanced mass throughput, this effect only partially compensated for additional energy losses associated with increased lubricant viscosity, higher internal friction in the screw pair, and elevated mechanical resistance at low temperatures. Consequently, the net electrical demand increased despite improved volumetric filling.
Thermal regime analysis revealed a stable dependence of discharge temperature on climatic conditions and cooling system performance. The outlet temperature was estimated using the polytropic relation
where
is the polytropic exponent. During winter operation, the discharge temperature decreased to 78–84 °C, resulting in an annual variation amplitude of approximately 30 °C (see
Table 8).
The results indicate that during summer operation the compressor functions close to its permissible thermal limits. Elevated discharge temperatures accelerate lubricant degradation, reduce oil film stability in the rotor–stator contact zones, and increase the probability of emergency shutdowns due to thermal protection activation. These findings emphasize the necessity of incorporating climatic variability into predictive maintenance strategies and offline digital twin–based operational optimization.
Analysis of the lubrication system revealed a pronounced temperature dependence of oil viscosity, approximated by an Arrhenius-type relation (Equation (28)), where μ
0 is the pre-exponential factor, E is the activation energy of viscous flow, R is the gas constant, and T is the absolute temperature.
A decrease in oil temperature from +60 °C to +25 °C resulted in an increase in dynamic viscosity from 0.018 to 0.041 Pa·s—a factor of 2.2—directly affecting compressor performance through three distinct but coupled mechanisms.
First, regarding inter-rotor sealing effectiveness: the oil film injected into the compression chamber serves a dual role as both coolant and dynamic seal. Under optimal viscosity conditions (~0.018–0.022 Pa·s at 50–60 °C), the oil forms a continuous film across the interlobe clearances, effectively blocking high-pressure gas backflow. As viscosity rises to 0.038–0.041 Pa·s at 20–25 °C, the increased film thickness transiently improves sealing but simultaneously raises the resistance to oil circulation through the narrow clearance geometry. The reduced oil penetration rate into the inter-rotor gap means that during rapid rotor rotation, portions of the sealing line experience intermittent oil starvation, paradoxically increasing leakage during cold starts and dynamic transients. This mechanism contributes to the observed decrease in volumetric efficiency from 0.82 to 0.74 below −20 °C, where thermal deformation of the casing further enlarges clearances while cold-thickened oil cannot compensate fast enough.
Second, regarding hydrodynamic bearing behavior: the journal bearings supporting the rotor shafts operate in the hydrodynamic lubrication regime, where load-carrying capacity scales with viscosity (η) and rotational speed (N) through the Sommerfeld number S ∝ ηN/p. At elevated viscosity, the bearing develops a thicker oil film, nominally reducing metal-to-metal contact probability. However, the substantially higher shearing resistance of the viscous film generates additional frictional power losses. The mechanical loss power
Nmech reported in
Table 9 was computed from the CFD viscous dissipation integral
Nmech = ∫∫∫ μ_eff (
∂u_i/
∂x_j + ∂u_j/
∂x_i)
2 dV, evaluated over the full computational domain and averaged over one complete rotor revolution, with oil viscosity supplied by the Arrhenius model (Equation (8)) at each ambient temperature. The seasonal values in
Table 9 therefore reflect the combined effect of viscosity-dependent shear losses in the rotor clearances and bearing films, not a separate analytical bearing model, where (dv/dy) is the velocity gradient across the film. This is the primary driver of the 14–17% increase in hydraulic losses and the rise in mechanical loss power from 28–30 kW (summer) to 36–39 kW (winter), as quantified in
Table 9.
Third, regarding cold-start transient loading: during startup at ambient temperatures below −20 °C, the oil’s high yield stress (for multigrade oils approaching their pour point) can create momentary starved-lubrication conditions before full oil circulation is established. The elevated bearing wear factor of 1.18 reported in
Table 9 for winter operation primarily reflects this transient regime rather than steady-state wear, underscoring the importance of pre-heating protocols for cold-climate field operations. Collectively, these three mechanisms confirm the strong coupling between thermal conditions, lubricant rheology, and mechanical efficiency of the screw pair—a coupling that must be explicitly represented in any predictive offline digital twin model.
The volumetric efficiency,
also exhibited pronounced seasonal variability. Based on simulation results and archival operational data,
decreased from 0.82 during transitional seasons to 0.74 at ambient temperatures below −20 °C.
The seasonal decrease in ηv from 0.82 to 0.74 can be decomposed into two contributing pathways: (i) thermally-induced geometric deformation accounts for approximately 60% of this reduction, as the differential thermal expansion between the cast iron casing and steel rotors widens end-face and interlobe clearances by an estimated 0.03–0.05 mm at −20 °C, thereby intensifying leakage; (ii) the remaining 40% is attributable to oil film redistribution effects under high-viscosity conditions, which alter the dynamic sealing behavior in the interlobe gap. During summer operation, both pathways partially reverse: thermal clearances stabilize and oil viscosity returns to the optimal range, allowing volumetric efficiency to recover to 0.80–0.83. This decomposition, derived from parametric offline digital twin simulations, provides a basis for targeted design interventions: casing material selection with matched thermal expansion coefficients can address the geometric pathway, while optimized oil injection temperature control (preheating to maintain μoil < 0.025 Pa·s regardless of ambient conditions) can mitigate the lubrication pathway.
The overall energy performance of the compressor was evaluated through the specific electricity consumption,
where
is the electrical power and
is the mass flow rate. The minimum value of
was observed at moderate ambient temperatures (+10 … +15 °C) and amounted to 4.18 kWh per 1000 m
3 of gas. In winter, this parameter increased to 4.63 kWh/1000 m
3, while in summer it reached 4.51 kWh/1000 m
3 (see
Table 9). Thus, climatic variability introduced an additional energy penalty of up to 10.8% relative to optimal operating conditions.
The total heat generated during compression and mechanical losses was distributed as follows: 54–57% was removed with the compressed gas, 28–31% was carried away by the lubricating oil, and 12–15% was dissipated through the casing into the ambient environment. During winter operation, the fraction of heat lost through the casing increased to 18% due to the higher temperature gradient between the equipment and the surrounding air. Correspondingly, the convective heat transfer coefficient increased from 9.6 to 11.4 W/(m2·K), reflecting intensified external heat exchange under low ambient temperatures.
Model predictions were compared against the held-out validation dataset described in
Section 2.2.1: N = 2190 hourly-averaged SCADA records from October–December 2022, covering an ambient temperature window of T
amb = −15 to +8 °C (autumn–early-winter transition at the Atyrau installation). Instrumentation details and measurement uncertainties are given in
Section 2.2.1. The mean absolute relative deviation (MARD) between predicted and measured values over the validation period was 3.1% for mass flow rate ṁ, 3.8% for discharge temperature T
dis, and 5.2% for electrical power consumption N. The largest discrepancies (6–7%) occurred in October–November and are attributed to fluctuations in gas humidity and compositional variability not represented in the quarterly-average gas composition used by the model. It should be noted that the validation period covers the cold-side operating range; model predictions at summer extreme temperatures (+35 to +40 °C) rely on calibrated extrapolation beyond the validation window and carry correspondingly higher uncertainty, consistent with the ±3–5% bounds reported in
Section 2.2.3.
Simulation of extreme climatic scenarios provided additional quantitative insights. At an ambient temperature of −40 °C, the predicted drive power increased to 312 kW, while the specific electricity consumption rose to 4.79 kWh/1000 m3. Simultaneously, oil temperature dropped to +22 °C, approaching the lower limit of acceptable pumpability. Conversely, at +40 °C, the discharge temperature reached 116 °C, exceeding the operational limit by 6–8 °C and increasing the risk of thermal protection shutdowns.
Annual integrated modeling was performed using a climatic load function
where
is the reference temperature and
is the time-dependent ambient temperature.
Sensitivity of the annual results to the two model parameters was assessed as follows. The choice of reference temperature T
ref has a strong influence on K
cl: shifting T
ref from 20 °C to 15 °C reduces K
cl by 29%, while shifting it to 25 °C increases K
cl by 46%, reflecting the quadratic dependence on temperature deviation. The value T
ref = 20 °C was selected as the long-term annual mean ambient temperature for the Atyrau region; users applying this framework to other climates should recalculate K
cl with the site-specific annual mean. The adaptive heat transfer coefficient h
ext has a smaller influence on the primary energy output: varying h
ext by ±10% (±1 W/(m
2·K) around the seasonal mean of 10.4 W/(m
2·K)) changes the predicted annual additional energy consumption ΔE
year by approximately ±5 MWh (±3%), which is within the ±5.2% validation uncertainty of the offline digital twin power prediction reported in
Section 2.2.3.
The analysis showed that winter months contributed up to 61% of the annual energy deviation, while summer accounted for 27%, with the remainder attributed to transitional seasons. It should be noted that while the dominant winter contribution (~61%, corresponding to ~113 MWh) falls within the field-validated operating range, the summer contribution (~27%, ~51 MWh) relies on calibrated extrapolation beyond the validation window and carries correspondingly higher uncertainty; the annual figure should therefore be interpreted as a model-based estimate rather than a fully field-validated result.
The following resource-related estimates are reported as model-based heuristics and are explicitly separated from the field-validated energy and availability outputs presented above. Resource-related effects were estimated as follows. The reference oil change interval of 4000 h at the nominal operating point corresponds to the compressor manufacturer’s maintenance specification for mineral-oil-flooded screw compressors at a discharge temperature of approximately 90 °C. The temperature-dependent intervals listed in
Table 9 were obtained by applying a service factor derived from operational maintenance records at the field installation; the resulting estimates carry an uncertainty of ±15% and should be treated as indicative guidance for maintenance planning rather than as precise predictions. They are not intended to replace manufacturer specifications or site-specific condition monitoring data. The bearing wear factor W
f in
Table 9 was computed as
Wf = (μoil(
T)/
μopt)
0.087, where
μoil(
T) is the Arrhenius-model oil viscosity (Equation (8)) and
μopt = 0.054 Pa·s is the optimal viscosity at the +15 °C reference; the exponent 0.087 was calibrated to reproduce the observed relative increase in maintenance events in the 2022 field records, yielding
Wf = 1.18 at −40 °C. This index is a qualitative indicator of relative wear intensity (uncertainty ±20%) and should not be interpreted as an absolute wear rate or a maintenance prescription. Values above 1.10 are proposed as a heuristic threshold for identifying operating conditions that may warrant pre-heating protocols or reduced oil change intervals, subject to verification against site-specific maintenance records.
Spatial thermal modeling of the compressor casing revealed significant temperature non-uniformity. In summer, maximum gradients of up to 22 °C were observed over a 0.8 m length near the discharge port. Under winter conditions, gradients decreased to 11–13 °C, while total heat losses increased due to the elevated temperature differential between the equipment and the surrounding air. These effects were incorporated into the offline digital twin via adaptive heat transfer coefficient correction, with h_ext ranging from 9.6 W/(m2·K) in summer to 11.4 W/(m2·K) in winter.
Increased temperature-induced shutdowns in summer (0.6%, corresponding to 53 recorded thermal-protection events in the 2022 SCADA shutdown log) and cold-start failures in winter (0.9%, corresponding to 79 recorded cold-start events) led to an overall annual availability reduction of 1.5%, corresponding to approximately 131 h of gas supply shortfall per year for the installation considered.
The combined computational and experimental analysis demonstrated that climatic variability induces persistent deviations in energy efficiency of 8–11%, annual discharge temperature variation up to 30 °C, and drive power differences of up to 33 kW between winter and summer extremes—all within the field-validated operating range. Maintenance interval and wear factor estimates are additionally reported as model-based heuristics; these carry ±15–20% uncertainty and should be interpreted accordingly, separately from the energy and availability results. These results confirm the necessity of incorporating climatic factors into digital modeling and optimization of compressor equipment operating in harsh environmental conditions.
The practical implications of these findings for field operation and equipment selection are threefold. First, regarding inlet system design: the demonstrated pressure amplification factor Π
p ≈ 1.95–2.3 implies that pulsation dampeners or inlet surge volumes should be specified for compressor stations where pipeline dynamics generate pressure oscillations exceeding ±5% of suction pressure. The associated 8–10% reduction in volumetric efficiency (
Section 3.2) translates directly to throughput loss and increased specific energy cost, providing clear economic justification for dampener installation. For a single compressor unit delivering ~2.4 kg/s, an 8% flow reduction represents approximately 6.9 × 10
6 m
3/year of undelivered gas at typical field conditions. Second, regarding seasonal operational strategy: the offline digital twin results demonstrate that the optimal operating point (minimum specific energy consumption of 4.18 kWh/1000 m
3) occurs at +10 … +15 °C. Field operators should consider variable-speed drive adjustment in summer to reduce shaft power and limit discharge temperatures below the 105 °C oil degradation threshold, while implementing oil pre-heating protocols in winter—maintaining μ
oil < 0.025 Pa·s—to mitigate the viscosity-driven hydraulic losses quantified in
Section 3.3.
Third, regarding future investigation of rotor profile effects: the following observations arise from quasi-steady frozen-rotor snapshot analysis at a single angular position (
Section 3.1) and are included here solely to identify directions for future transient investigation—not to provide design guidance. No design preference between Type A and Type B can be stated without symmetric cycle-averaged transient simulations of both profiles under identical boundary conditions; this is identified as the primary direction for future work.
Subject to this caveat: (a) Type A’s lower instantaneous pulsation coefficient (Kp = 0.064 vs. 0.081 for Type B) suggests it may be less susceptible to resonance amplification under unsteady suction conditions, though whether this difference persists over a full compression cycle has not been established; (b) Type B’s instantaneous volumetric efficiency at the captured angular position (0.88) is lower than that of Type A (0.91), but this snapshot value may not be representative of cycle-averaged performance and should not be used as a design threshold without transient confirmation; (c) below moderate ambient temperatures, the tighter clearances of Type B may be more sensitive to thermally induced widening, potentially amplifying leakage relative to Type A, but this has not been quantified under transient conditions for either profile.
These observations indicate directions for further investigation rather than actionable selection rules.