Flow-Induced Strength Analysis of Large Francis Turbine Under Extended Load Range

1
Power Station Management Bureau, Y.R. Wanjiazhai Water Multi-Purpose Dam Project Co., Ltd., Linyi 036412, China
2
Department of Energy and Power Engineering, Tsinghua University, Beijing 100084, China
3
Future Energy Research Institute, S.C.I. Energy (Swiss), 8706 Zurich, Switzerland
*
Author to whom correspondence should be addressed.
Appl. Sci. 2025, 15(5), 2422; https://doi.org/10.3390/app15052422
Submission received: 9 December 2024 / Revised: 11 February 2025 / Accepted: 20 February 2025 / Published: 24 February 2025

Abstract

:
To meet the load requirements of the power grid, the hydroelectric power plants need to extend the operational load range of the turbine units, which are often operated under off-design operating conditions. This new challenge significantly changes the flow characteristics of the hydro turbine units. Strong vibrations and high stresses caused by pressure pulsations at various loads directly lead to severe damage to the runner blades, threatening the safe operation of the hydropower unit. In this study, the detailed flow dynamics analysis under three loading conditions of a large-scale Francis turbine, i.e., 33.3%, 66.6%, and 100% of the Francis turbine’s rated power, is investigated with computational fluid dynamics (CFD) calculations. The pressure files at different operating conditions are adopted to carry out the corresponding flow-induced strength analysis of the Francis runner prototype. The pressure distributions and flow velocity distributions at these three typical operating conditions are studied, and the maximum stress of the runner gradually increases with the power output of the turbine, but it is only around one-third of the yield stress of the runner material. It reveals that the runner is safe to operate in the extended operation range from a 33.3% to 100% of the rated power load. The analysis approach in this work can be applied to other hydraulic machinery including Francis turbines, pumps and pump–turbines.

1. Introduction

The global energy crisis, characterized by rising energy demand, resource depletion, and environmental concerns, necessitates a transition towards more sustainable energy sources. Hydropower, as one of the most important and technically mature renewable energy sources that can be developed on a large scale, plays a pivotal role in this transformation and increases sustainable energy generation [1,2,3]. Francis turbines can operate efficiently in a wide range of current and head conditions and are widely used in hydropower power plants as one of the most important baseload generating units for power systems.
Francis turbine units remain the mainstay of hydropower generation worldwide due to their ability to adapt to a wide range of heads and their high efficiency. Their adaptability and reliability have contributed significantly to the global push towards renewable energy. Photovoltaic and wind turbines as the mainstay of new energy have the disadvantage of intermittency and volatility, with power generation output fluctuating according to changes in weather and time. The instability of photovoltaic and wind power requires large hydropower units as a regulating power source to balance the grid and ensure the stability and reliability of the power supply. In order to cope with load fluctuations after a huge amount of photovoltaic and wind power is connected to the grid, hydropower units, especially large Francis turbines, are required to operate in the load range to balance the grid and ensure the stability and reliability of the power supply.
Changes in electricity consumption lead to continuous fluctuations in the load demand on the grid for hydroelectric power plants throughout the day. The hydropower units in the power plants must operate frequently under a broad range of loads under off-design operating conditions in order to meet the power grid’s requirements for absorbing new energy sources, such as photovoltaic and wind power. This has resulted in severe issues with the turbine runners and has drastically altered the operating characteristics of the units [4,5]. Francis turbine runners are susceptible to unstable flow when they operate under off-design conditions for an extended period. This can result in intense vibrations in the runner blades and a reduction in power generation efficiency [6,7]. Francis turbines can experience flow-induced cracks and damage in severe instances [8,9,10]. Figure 1 shows damage to the runner blade of a large prototype Francis turbine.
Scholars worldwide have conducted a large number of in-depth studies on the unsteady flow characteristics of Francis turbines when they are operated outside of their rated operating conditions. The flow distribution in the Francis runner flow channel under partial loads is irregular, causing cavitation on the runner blades. Cavitation erosion decreases turbine performance, increases hydraulic losses, and causes material loss on the runner blades [12,13]. The runner blades of Francis turbines may develop pits and cracks as a result of prolonged cavitation erosion [14,15]. The time- and frequency-domain properties in the vaneless region of Francis units under various load conditions were monitored and simulated [16].
At part-load conditions, the Francis turbine unit can experience draft tube pressure pulsations, leading to severe hydraulic vibrations in the Francis turbine unit and threatening its stability [17,18]. Experimental and numerical studies of swirling flow and flow instability in Francis turbines under different loads have been carried out to capture the transient rotating flow characteristics in the draft tube [19]. Through the Francis turbine model test, it is possible to directly observe the complex flow characteristics of the draft tube vortex ropes under different operating conditions [20].
The physical mechanisms of unsteady flow and flow-induced structural vibration and stress in Francis turbine units under different operating conditions can be further elucidated by performing field measurements of pressure pulsation and stress on a prototype Francis runner [19,21,22]. To gain a deeper understanding of the prototype unit’s vibration mechanism underwater, the vibration measurements of a simplified hydraulic turbine model have been carried out using novel distributed fiber optic sensing technology to monitor vibrations and stresses [23]. The underwater structural vibrations of Francis turbine runners were measured and simulated to evaluate the model behavior of the runners considering the added-mass effects of the surrounding water [24]. Studies involving field measurements and numerical simulations have shown that unsteady flow-induced stresses in Francis runners are closely related to pressure pulsation levels, rotational speed, and the geometric configuration of the turbine [25].
According to the results of a study into the runner blade breakdown of a 200 MW Francis turbine, cavitation damage from operations at low part loads combined with severe high-cycle fatigue caused the blade to crack [26]. Another investigation discovered that cracks on the runner blades of a prototype Francis turbine were produced by operating load conditions deviating from the rated condition [10]. Some Francis units may also be damaged as a result of excessive dynamic stresses within the runner and flow-induced structural resonance under off-design conditions [8]. According to some experts, the Francis runner’s blades cracked because of the uneven weld surface, which was exacerbated by the weld filler material’s hydrogen embrittlement [9]. The development of cracks in Francis turbine runners is a complicated issue that is impacted by several variables. One of the most frequent conclusions is that turbulence, particularly in off-design operating conditions, is a major factor in causing these cracks, even though the precise causes may differ.
Many researchers have studied the flow dynamics and structural vibration of Francis turbine runners by computational fluid dynamics (CFD), finite element method (FEM) and field measurements, respectively. However, the research for the comprehensive analysis of large prototype Francis turbines with full three-dimensional fluid–structure interaction (FSI) methods is still relatively limited [27]. In order to capture the flow-induced dynamic behavior more accurately and to avoid serious flow-induced damage in Francis turbines, the flow-induced strength analysis of a 183 MW prototype Francis turbine is carried out in this study following the workflow shown in Figure 2.
First, a geometrical model of the Francis turbine unit’s fluid and structural domains is created. Second, three operating loads are chosen to perform the CFD analysis of the Francis turbine unit’s entire flow passage in order to thoroughly examine the pressure distribution and the flow distribution characteristics: 33.3%, 66.6%, and 100% of the rated power. Ultimately, the finite element model of the Francis runner is mapped with the pressure data calculated from the CFD analysis, and an in-depth investigation of the runner’s stress distribution is conducted.

2. Methodology and Mathematical Physics Equations

2.1. Fluid Dynamics Governing Equations

The governing equations for turbulent fluid flow in the hydraulic Francis turbine units are based on the fundamental laws of mass, momentum, and energy conservation. Since the water in hydraulic turbines is thought to be incompressible and at a constant temperature, the Reynolds-averaged Navier–Stokes (RANS) equations can be used to explain the fundamental laws of mass and momentum conservation:
u i ¯ t + ( u i ¯ u j ¯ ) x j = 1 ρ p ¯ x i + x j [ ν ( u i ¯ x j + u j ¯ x i ) ] u i u j ¯ x i + f i ¯
u i ¯ x i = 0
where i and j are indicators which fall in 1 , 2 , 3 , x i and x j are the Cartesian coordinate directions, u ¯ i and u ¯ j are the time-averaged terms of the fluid velocity, and u ¯ i and u ¯ j are time-fluctuating terms of the fluid velocity. Time is represented by t, fluid density by ρ , time-averaged pressure by p ¯ , kinematic viscosity by ν , Reynolds stress tensor by u i u j ¯ , and time-averaged external forces by f i ¯ .
The RANS equations introduce an additional unknown quantity, the Reynolds stress tensor u i u j ¯ , which accounts for the effects of turbulent fluctuations on the mean flow field [28]. To close the RANS equations, various turbulence models are introduced, which parameterize the Reynolds stress tensor in terms of the mean flow properties and turbulence quantities. The k- ε model is based on transport equations for the turbulent kinetic energy k and its dissipation rate ε , and assumes an isotropic eddy viscosity to relate Reynolds stresses to mean flow gradients [29]. Utilizing transport equations for k and the turbulent kinetic energy dissipation rate ω , the k- ω model improves predictions in near-wall regions and for flows with adverse pressure gradients [30]:
k = 1 2 u i u j ¯
ε = ν ( u i x k u i x k ) ¯
ω = ε k
These turbulent models utilize the Boussinesq hypothesis, introducing the turbulent viscosity ν T to express the Reynolds stress tensor as
u i u j ¯ = ν T ( u i ¯ x j + u j ¯ x i ) + 2 3 k δ i j
The Shear Stress Transport (SST) model is a hybrid approach that combines the advantages of the k- ω model in near-wall regions with the k- ε model in the free-flow regions, providing enhanced accuracy in separating flows [31]. The SST model is widely used for the turbulent flow simulations for hydraulic turbines and therefore also adopted in this investigation:
ω t + x j ( u ¯ j ω ) = x j ( ν + ν T σ ω 2 ) ω x j + 2 ( 1 F 1 ) 1 σ ω 2 ω k x j ω x j β 2 ω 2 + α ω k P k
k t + ( u ¯ j k ) x j = x j ( ν + ν T σ k 2 ) k x j β k ω + P k
The mixing function F 1 in Equation (7) is expressed as
F 1 = tanh ( arg 1 4 )
arg 1 = min max k β ω y , 500 ν y 2 ω , 4 k σ ω 2 C D k ω y 2
C D k ω = max 2 ρ 1 σ ω 2 ω k x i ω x i , 10 10
where y is the distance to the nearest wall.
The turbulent kinetic energy generation term P k in Equation (8) can be written with the strain rate S i j as
P k = 2 ν T S i j u ¯ i x j
where S i j is the strain rate.
S i j = 1 2 ( u i ¯ x j + u j ¯ x i )
The turbulent viscosity ν T used in the above equations is defined as
ν T = α 1 k max ( α 1 ω , S F 2 )
F 2 = tanh ( arg 2 2 )
arg 2 = max 2 k β ω y , 500 ν y 2 ω
The other parameters are α 1 = 0.31 , α 2 = 0.44 , β = 0.09 , β 2 = 0.0828 , σ k 2 = 1 , and σ ω 2 = 1 / 0.856 .

2.2. Fluid-Induced Structural Dynamics Governing Equations

With the calculated results by the fluid dynamics analysis, the fluid-induced force F f acting on the structure surfaces S of the pumped-storage unit can be obtained by
F f = S p d S
Taking the flow-induced force F f applied on the pumped-storage unit into account, the fluid-induced structural dynamics equation can be expressed as
M s a + D s v + S s d = F s + F f
where M s , D s , and S s denote the mass, damping, and stiffness matrices of the structures for the pumped-storage unit, respectively. a , v , and d represent the acceleration, velocity, and displacement vectors of the unit structures, respectively. F s is the external force acting on the unit structures but excludes the flow-induced force F f .
The structural displacement d of the unit structures can be obtained by solving Equation (18), and the flow-induced stress σ of the structures for the pumped-storage unit can be obtained by the following equation:
σ = E s B d d
where [ E s ] and [ B d ] are the elasticity matrix and the strain–displacement matrix of the structures for the pumped-storage unit.
With the maximum, middle, and minimum principal stresses ( σ 1 , σ 2 and σ 3 ), the equivalent stress σ e q . can be calculated by Equation (20) to investigate the flow-induced stress behavior of the structures for the pumped-storage unit, including the head-cover bolts and bottom-ring bolts:
σ e q . = ( σ 1 σ 2 ) 2 + ( σ 2 σ 3 ) 2 + ( σ 3 σ 1 ) 2 2

3. Specifications of the Francis Turbine Unit and Investigated Operating Conditions

The hydropower plant of this study has six large-scale Francis turbine generation units, each rated at 183 MW. The turbine units’ rated head and maximum head are 68 m and 80 m. The rated discharge and the rotating speed of the turbine are 294 m 3 s 1 and 100 rpm, respectively. The Francis turbine unit has 20 stay vanes and 20 guide vanes, and the turbine runner has 13 blades. The rotating direction of the turbine runner is clockwise in the top view. The parameter specifications of the Francis turbine unit are listed in Table 1.
The three-dimensional geometrical model of the water passage of the Francis turbine prototype is shown in Figure 3. The inlet and outlet of the turbine flow passages are also illustrated in the figure. The spiral case is the Francis turbine unit’s flow intake structure, and its spiral design helps to maintain an even distribution of flow velocity and pressure, thereby minimizing energy loss as the water enters the stay vane flow passage. Stay vanes within the stay ring, positioned radially between the spiral case and the guide vanes, provide structural support to the spiral case and other structures of the turbine unit. The guide vanes can be adjusted in their opening angle to regulate water flow and finely control the power output on the turbine. The Francis runner is the core component of the turbine. When the water flows through the Francis runner, its potential and kinetic energy are converted into the mechanical energy of the rotor system. The draft tube, located at the outlet of the runner, discharges water from the runner to the downstream and converts the remaining kinetic energy of water exiting the runner into pressure energy. This increases the overall efficiency of the turbine by reducing energy losses. The water in the crown chamber and band chamber between the runner and the surrounding stationary structures balances the pressure and thrust of the runner. Labyrinth seals in the crown and belt chambers help to reduce water leakage of the runner passage.
The power plant operation statistics show that the Francis turbine units often operate at 74 m, close to the maximum head. To meet the requirements of the grid load regulation, the turbine units of the power plant have to operate under off-design operating conditions for a long period and even extend their operation to the low load zone. In this study, three operating conditions of 33.3%, 66.6%, and 100% of the rated power are adopted for the CFD simulation and subsequent flow-induced strength analysis. The operating parameters of the selected operating conditions are analyzed based on site measurements (Table 2).
To perform the CFD simulation of the turbine unit, the fluid domain computational model of the Francis turbine is generated with high-quality tetrahedral and hexahedral meshes. The meshes near the structure wall surfaces of key flow domains such as runner blades and guide vanes are refined. There are five mesh layers near the wall surfaces, with the first mesh height of 0.1 mm and an expansion ratio of 1.2. Three groups of meshes are generated for the fluid domain of the Francis turbine unit, with 7.3 million, 14.2 million, and 25.8 million elements, respectively, and the mesh sensitivity assessment is performed to ensure the reliability and convergence of the calculation results. The deviation of the power output of the Francis turbine at 100% of load calculated by the first mesh group from the target 183 M W is around 10%, which cannot be used. The power output of the second and third mesh groups is close to the measured power onsite. However, the simulation time with the third mesh group is much longer than that with the second mesh group. According to the computing resources and requirements, the second mesh group with 14.2 million elements is selected to ensure a reasonable balance between calculation accuracy and efficiency (Table 3).
The meshes of different fluid domains including the spiral case, stay vanes, guide vanes, Francis runner, crow and band chambers, and draft tube of the turbine unit, and the entire fluid domain of the turbine unit are presented in Figure 4 and Figure 5.
The flow domains of the spiral case, stay vane, guide vane, draft tube, and crown and band chambers are set up in the stationary frame, and the runner flow domain is located in the rotating frame with the rated rotating speed of 100 rpm, which allows to simulate the centrifugal and Coriolis forces and other rotational effects on the fluid flow. Interface surfaces are specified between the runner fluid domain and adjacent fluid domains to transfer data between the rotating frame and the stationary frame.
The spiral case inlet and the draft tub outlet are defined with the field-measured flow discharge and static pressure values from site campaigns in the power plant. All surfaces of the fluid domain connected to the turbine unit structures are designated as no-slip walls. Automatic wall treatment is selected for the wall surfaces. The total physical time in the simulation is set to 3.6 s, corresponding to 10 rotation revolutions for the Francis runner, and the residual threshold of the CFD simulations is specified as 10 6 . It can ensure the convergence of the CFD simulation and avoid unnecessary calculation overhead caused by an excessively long calculation time. Finally, 720 steps per revolution is set up to fully capture the complex turbulent flow in the turbine flow domains.

4. Results and Discussions of Flow-Induced Strength Analysis

4.1. Flow Pressure Distributions and Velocity Distributions of the Francis Turbine Unit

Under three different operating loads of 33.3%, 66.6%, and 100% of the rated power, the simulation results of the power output of the Francis turbine approach the measured ones, which verifies the reliability of the CFD calculation results. In order to better compare the calculation results of the Francis turbine under different operating conditions, the pressure and velocity of the turbine in this study are normalized according to the flowing formulae:
p = p ρ f g H
u = u u m a x .
where g is the acceleration of gravity, H is the operating head of the Francis turbine unit, and u m a x . is the maximum velocity value of the three load cases.
The normalized pressure distribution in the flow domain of the Francis turbine unit at three different operating conditions, 33.3%, 66.6%, and 100% of the rated power, are demonstrated in Figure 6, Figure 7 and Figure 8, respectively.
The results reveal that at 33.3%, 66.6%, and 100% loads of the rated power, the pressure of the Francis turbine flow domains decreases from the spiral case to the draft tube in general. The pressure in the spiral case is the highest in the flow domain, where the hydraulic energy is dominated by pressure energy. In the runner flow domain, the pressure drops significantly across the runner due to the pressure energy being transferred from the fluid to the rotating blades as kinetic energy. After the runner runner outlet, the fluid flows into the draft tube, which acts as a diffuser to recover part of the kinetic energy into pressure energy. The pressure in the draft tube is the lowest in the entire flow passages of the Francis turbine unit.
Under various loads, the flow rate and flow direction of the water entering the runner can be controlled by adjusting the guide vane openings. Since the guide vane opening angles are significantly different at the three loads, the local pressure distributions in the guide vane domains also vary with each other. At a 33.3% rated power load, the guide vane opening is relatively small, and the water flow is ejected to the runner blade fluid channels from the narrow gaps between adjacent guide vanes. There is a significant difference in pressure between the upstream and downstream of the guide vanes. The pressure upstream of the guide vane is higher, and the pressure downstream of the guide vane is lower. With the guide vane opening increases at a 66.6% rated power load, the discharge increases accordingly to generate more power. And the pressure level of the flow between the guide vanes increases. At a 100% rated power load, the guide vanes are fully opened, and the pressure gradually decreases from the spiral case toward the guide vane outlet. The pressure gradient in the guide vane region is less than that at 33.3% and 66.6% loads of rated power. The normalized flow velocity distributions of the Francis turbine flow domain at 33.3%, 66.6%, and 100% loads of rated power are shown in Figure 9, Figure 10 and Figure 11, respectively.
The flow streamlines of the Francis turbine under different operating conditions from 33.3% to 100% of the rated power load have obvious differences. At the 33.3% rated power load, the flow in the spiral case is relatively stable, but the flow between guide vanes and in the vaneless region is obviously irregular. Due to the small opening of the guide vanes and the narrow water flow passages in between, the fluid velocity increases when passing through the gap between adjacent guide vanes, forming a high shear zone with high speed locally. The fluid streamline distribution in the draft tube is disordered and asymmetric with obvious vortex and backflow. The loss of fluid kinetic energy increases, resulting in a reduction in turbine efficiency. At the 66.6% rated power load, the flow in the spiral case remains stable. With a large guide vane opening, the flow in the guide vane flow domain and the runner flow domain is improved. The streamlines gradually become regular and the flow velocity of the high speed ring in the vaneless region is decreased. In the runner blade flow channel, the streamlines are relatively smooth, and the energy transfer is more efficient. The streamline distribution is more regular than that at the 33.3% rated power load, and the vortex and backflow are weakened but not completely eliminated.
When the power output reaches 100% of the rated power load, the flow streamlines of the turbine flow passage are distributed more regularly, and the energy transfer is the highest. The flow velocity distribution in the spiral case is very uniform and provides stable inflow conditions to the guide vane region. The flow lines are distributed regularly among the guide vanes, and the water gradually accelerates as it passes through the guide vanes, forming a uniform flow field into the runner flow domain. The high-speed ring in the vaneless region disappears. The streamlines flow smoothly along the blade surface inside the Francis runner without obvious separation or turbulence, and the kinetic energy is gradually converted into mechanical energy. The streamlines in the draft tube are of high regularity. The flow velocity decreases evenly, and backflow and vortex phenomena are almost disappeared. At the 100% rated power load, the flow distributions in all flow domains are optimized to the best state, and the turbine efficiency and stability reach the highest level.

4.2. Flow-Induced Strength Analysis of the Francis Runner

In order to evaluate the strength of the Francis runner under three different operating conditions, the flow-induced strength analysis of the runner needs to be performed by combining the above CFD simulations with finite element analysis (FEA). The data of the pressure distributions on the runner at 33.3%, 66.6%, and 100% loads of rated power can be exported from the CFD analysis performed in the previous section and mapped on the finite element of the Francis runner as surface loads.
High-quality tetrahedral elements are used to create the Francis runner’s finite element model (Figure 12). The Francis turbine runner blades’ geometrical curvature varies significantly, particularly at the fillets, which are likely to become locations of concentrated stress. To accurately record the stress values, the mesh at the runner blades’ fillets is improved and refined. The Francis runner is subjected to the boundary conditions, which include the fixed restrictions, rotating speed, and gravity acceleration.
The Francis runner in this study is made of stainless steel, and the material parameters of the runner are summarized in Table 4 and include a density of 7700 kg m 3 , a Young’s modulus of 2.1 × 10 5 MPa , a Poisson’s ratio of 0.3, and a yield stress of 550 MPa. This value of yield stress ensures that the Francis runner can withstand operational loads under normal and transient conditions without permanent deformation.
The pressure files across the entire flow passage of the Francis turbine unit at three different loads can be exported from the CFD analysis discussed in the previous section. This CFD-derived pressure data can then be accurately mapped onto the nodes of the finite element model to facilitate the subsequent flow-induced structural stress analysis (Figure 13).
As shown in Figure 14, the maximum stresses of the runner at 33.3%, 66.6%, and 100% loads of rated power are located in the fillets between the blade trailing edge and the crown.
When the Francis runner is running stably at a rated speed, its load is determined by the hydraulic torque acting on the runner. As the load of the Francis unit increases, the opening of the unit’s guide vanes increases accordingly; therefore, the water flow entering the runner flow passage and the runner hydraulic torque increases. Eventually, the value of the runner hydraulic torque is equal to the value of the counter load torque on the turbine shaft so that a new torque equilibrium is formed in the Francis turbine unit. As shown in Figure 15, the maximum stress of the runner gradually increases with the power from 33.3% to 100% of the rated power load.
As the hydraulic torque on each runner blade increases with the load, the flow-induced stress of the runner blades also increases accordingly. The maximum stress values of the runner at the 33.3% rated power load and the 66.6% rated power load are 0.45 and 0.74 times the stress at the 100% rated power load, which is around 1/3 of the yield stress of runner material. Therefore, the runner is safe during the extended operation range from 33.3% to 100% of the rated power load. As the service life of the Francis turbine increases, the performance of the materials used in the turbine runner may degrade, especially for materials that are susceptible to cavitation erosion or corrosion. To ensure the safe and efficient operation of the units, it is still recommended to strengthen the inspection of the runners to prevent problems before they occur.
The Francis runner’s fatigue and cavitation resistance deteriorate with deteriorating material, making the runner blades more vulnerable to stress concentration at off-design conditions. This can hasten damage and impact the turbine’s stability and service life. To address these issues, the next plan is to measure the flow characteristics and strength behavior of the Francis turbine under about 60 different operating conditions, ranging from 0 to 100% loads of rated power. Then, with the help of the corresponding flow-induced strength simulations, the flow pattern and flow-induced stress characteristics under these operating conditions will be thoroughly analyzed, and effective vibration monitoring and control measures will be implemented to guarantee the turbine’s dependability and efficiency after long operating times.

5. Conclusions

In the study, the geometrical model CFD calculation models of the entire fluid domain including the spiral case, stay vanes, guide vanes, turbine runner, crow and band chambers, and draft tube of the turbine unit were constructed. CFD simulations and the flow-induced strength analysis under three operating conditions in the extended load range from the 33.3% rated power load to the full load have been performed.
The Francis turbine flow domain pressure drops from the spiral case to the draft tube under 33.3%, 66.6%, and 100% loads of rated power, according to the CFD calculation results. Nevertheless, the guide vane region’s local pressure distributions change with various loads. The pressure differential between the guide vanes’ upstream and downstream is evident for the 33.3% and 66.6% loads of rated power, with the upstream pressure being higher than the downstream pressure. The pressure gradient in the guide vane region is lower at the 100% rated power load when the guide vanes are fully opened than when it is at 33.3% and 66.6% loads of rated power.
The flow velocity distributions of the turbine under three operating conditions vary from one another. The flow in the spiral case is relatively stable for all loads. However, the flows in the guide vane region and the vaneless zone are strongly related to the guide vane openings. The flow forms a high-speed ring in the vaneless region at the 33.3% rated power load due to the small guide vane opening. The fluid velocity in the draft tube at the 33.3% and 66.6% rated power loads is asymmetric and disordered with the vortex and backflow. At the 100% rated power load, the flow of the whole turbine flow domain is more regular and stable. The high-speed ring in the vaneless region and the backflow and vortex in the draft tube disappear.
According to the Francis runner’s flow-induced strength analysis, the runner’s maximum stress progressively rises as the power increases from 33.3% to 100% of the rated power load. Therefore, the maximum stress on the runner blades increases with the Francis runner’s load. Under 100% of the rated power load, the analyzed runner’s maximum stress is 2.2 and 1.4 times that under 33.3% and 66.6% of the rated power load, respectively, but it is only about one-third of the runner material’s yield stress. This runner is safe to operate throughout the extended range of 33.3% to 100% of the rated power load. Because of the Francis runner’s distinctive design, the flow-induced structural stress on the runner blades varies nonlinearly with the runner load.
The study provides an in-depth analysis of flow-induced stresses of a large Francis turbine over an extended load range. By integrating CFD and FEA approaches, this study fills a critical gap in understanding the operating limits of large Francis turbines to ensure their safe operation under varying load conditions. The analysis approach proposed in this study can be applied to other hydraulic machinery including Francis turbines, pumps, and pump–turbines.

Author Contributions

Conceptualization, X.H.; methodology, X.H.; investigation, X.L. and X.H.; validation, W.C.; writing—original draft preparation, X.H. and X.L.; writing—review and editing, X.H. and W.C.; supervision, Z.W. All authors have read and agreed to the published version of the manuscript.

Funding

This research and the APC were funded by the project “Study on Stable Operation of Units in Wanjiazhai Hydropower Station” of Wanjiazhai Water Multi-Purpose Dam Project Co., Ltd. Grant number: WJZ-ZB-2022-027.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

The authors Xingping Liu and Weijiang Chen are employed by the company Power Station Management Bureau, Y.R. Wanjiazhai Water Multi-Purpose Dam Project Co., Ltd. The authors declare that this study received funding from Wanjiazhai Water Multi-Purpose Dam Project Co., Ltd. The funder was not involved in the study design, collection, analysis, interpretation of data, the writing of this article or the decision to submit it for publication. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as potential conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
CFDComputational fluid dynamics
FEFinite element
FEAFinite element analysis
FSIFluid–structure interaction
OPOperating condition
SSTShear stress transport

References

  1. Bayazıt, Y. The effect of hydroelectric power plants on the carbon emission: An example of Gokcekaya dam, Turkey. Renew. Energy 2021, 170, 181–187. [Google Scholar] [CrossRef]
  2. Paraschiv, L.S.; Paraschiv, S. Contribution of renewable energy (hydro, wind, solar and biomass) to decarbonization and transformation of the electricity generation sector for sustainable development. Energy Rep. 2023, 9, 535–544. [Google Scholar] [CrossRef]
  3. Rodríguez-Pérez, A.M.; Rodríguez-Gonzalez, C.A.; López, R.; Hernández-Torres, J.A.; Caparrós-Mancera, J.J. Water Microturbines for Sustainable Applications: Optimization Analysis and Experimental Validation. Water Resour. Manag. Int. J. Publ. Eur. Water Resour. Assoc. (EWRA) 2024, 38, 1011–1025. [Google Scholar] [CrossRef]
  4. Ambec, S.; Crampes, C. Electricity provision with intermittent sources of energy. Resour. Energy Econ. 2012, 34, 319–336. [Google Scholar] [CrossRef]
  5. Rehman, S.; Al-Hadhrami, L.M.; Alam, M.M. Pumped hydro energy storage system: A technological review. Renew. Sustain. Energy Rev. 2015, 44, 586–598. [Google Scholar] [CrossRef]
  6. Aakti, B.; Amstutz, O.; Casartelli, E.; Romanelli, G.; Mangani, L. On the performance of a high head Francis turbine at design and off-design conditions. J. Physics Conf. Ser. 2015, 579, 012010. [Google Scholar] [CrossRef]
  7. Seidel, U.; Mende, C.; Hübner, B.; Weber, W.; Otto, A. Dynamic loads in Francis runners and their impact on fatigue life. In Proceedings of the IOP Conference Series: Earth and Environmental Science; IOP Publishing: Bristol, UK, 2014; Volume 22, p. 032054. [Google Scholar]
  8. Flores, M.P.; Urquiza, G.; Rodriguez, J.A. A Fatigue Analysis of a Hydraulic Francis Turbine Runner. World J. Mech. 2012, 2, 28–34. [Google Scholar] [CrossRef]
  9. Frunzǎverde, D.; Muntean, S.; Mǎrginean, G.; Câmpian, V.; Marşavina, L.; Terzi, R.; Şerban, V. Failure analysis of a Francis turbine runner. IOP Conf. Ser. Earth Environ. Sci. 2010, 12, 012115. [Google Scholar] [CrossRef]
  10. Adhikari, M.P.; Poudel, L. Fatigue Analysis of Francis Turbine Runner as a Result of Flow-induced Stresses. In Proceedings of IOE Graduate Conference, 2019-Winter; Institute of Engineering, Tribhuvan University: Kirtipur, Nepal, 2019; Volume 7, pp. 7–13. [Google Scholar]
  11. Liu, P.; Huang, X.; Yang, T.; Wang, Z. Flow-Induced Fatigue Damage of Large Francis Turbines Under Multiple Operating Loads. Appl. Sci. 2024, 14, 12003. [Google Scholar] [CrossRef]
  12. Gordon, J.L. Determining turbine runner metal loss caused by cavitation erosion. Int. Water Power Dam Constr. 1991, 43, 21–24. [Google Scholar]
  13. Escaler, X.; Egusquiza, E.; Farhat, M.; Avellan, F.; Coussirat, M. Detection of cavitation in hydraulic turbines. Mech. Syst. Signal Process. 2006, 20, 983–1007. [Google Scholar] [CrossRef]
  14. Celebioglu, K.; Altintas, B.; Aradag, S.; Tascioglu, Y. Numerical research of cavitation on Francis turbine runners. Int. J. Hydrogen Energy 2017, 42, 17771–17781. [Google Scholar] [CrossRef]
  15. Tiwari, G.; Shukla, S.; Prasad, V.; Patel, V.k. Numerical Investigation of Hydrodynamics of the Cavitating Turbulent Flow in a Low Head Prototype Francis Turbine. AIP Conf. Proc. 2020, 2273, 50006. [Google Scholar] [CrossRef]
  16. Kobro, E. Measurement of Pressure Pulsations in Francis Turbines; Norwegian University of Science and Technology: Trondheim, Norway, 2010. [Google Scholar]
  17. Pasche, S.; Gallaire, F.; Avellan, F. Origin of the synchronous pressure fluctuations in the draft tube of Francis turbines operating at part load conditions. J. Fluids Struct. 2019, 86, 13–33. [Google Scholar] [CrossRef]
  18. Nicolet, C.; Zobeiri, A.; Maruzewski, P.; Avellan, F. Experimental investigations on upper part load vortex rope pressure fluctuations in francis turbine draft tube. Int. J. Fluid Mach. Syst. 2011, 4, 179–190. [Google Scholar] [CrossRef]
  19. Sotoudeh, N.; Maddahian, R.; Cervantes, M.J. Investigation of Rotating Vortex Rope formation during load variation in a Francis turbine draft tube. Renew. Energy 2020, 151, 238–254. [Google Scholar] [CrossRef]
  20. Ciocan, G.D.; Iliescu, M.S.; Vu, T.C.; Nennemann, B.; Avellan, F. Experimental study and numerical simulation of the FLINDT draft tube rotating vortex. J. Fluids Eng. 2007, 129, 146–158. [Google Scholar] [CrossRef]
  21. Huang, X.; Ou, H.; Huang, H.; Wang, Z.; Wang, G. Flow-Induced Stress Analysis of a Large Francis Turbine Under Different Loads in a Wide Operation Range. Appl. Sci. 2024, 14, 11782. [Google Scholar] [CrossRef]
  22. Cao, D.; Dodge, M.; Zhou, Y.; Liu, J. Stress measurement of runner blade for a Francis prototype turbine. J. Physics Conf. Ser. 2024, 2752, 012215. [Google Scholar] [CrossRef]
  23. Yao, C.; Huang, X.; Zhu, P.; Brès, C.S.; Thévenaz, L. Preliminary Study of Distributed Fiber Optic Sensing Technologies in Hydraulic Machinery. In Proceedings of the Light, Energy and the Environment 2018 (E2, FTS, HISE, SOLAR, SSL), Singapore, 5–8 November 2018; Optica Publishing Group: Washington, DC, USA, 2018; p. EM2A.3. [Google Scholar] [CrossRef]
  24. Lais, S.; Liang, Q.; Henggeler, U.; Weiss, T.; Escaler, X.; Egusquiza, E. Dynamic Analysis of Francis Runners—Experiment and Numerical Simulation. Int. J. Fluid Mach. Syst. 2009, 2, 303–314. [Google Scholar] [CrossRef]
  25. Zhang, D.; Quan, Q.; Huang, X.; Wang, Z.; Wang, B.; Xiao, Y. Transient Flow-Induced Stress Investigation on a Prototype Reversible Pump–Turbine Runner. Energies 2024, 17, 3026. [Google Scholar] [CrossRef]
  26. Luna-Ramírez, A.; Campos-Amezcua, A.; Dorantes-Gómez, O.; Mazur-Czerwiec, Z.; Muñoz-Quezada, R. Failure analysis of runner blades in a Francis hydraulic turbine—Case study. Eng. Fail. Anal. 2016, 59, 314–325. [Google Scholar] [CrossRef]
  27. Huang, X.; Chen, L.; Wang, Z.; Li, H.; Chen, S.; Hu, K.; Li, C.; Qiu, L. Stress Characteristic Analysis of Pump-Turbine Head Cover Bolts during Load Rejection Based on Measurement and Simulation. Energies 2022, 15, 9496. [Google Scholar] [CrossRef]
  28. Chou, P.Y. On velocity correlations and the solutions of the equations of turbulent fluctuation. Q. Appl. Math. 1945, 3, 38–54. [Google Scholar] [CrossRef]
  29. Jones, W.P.; Launder, B.E. The prediction of laminarization with a two-equation model of turbulence. Int. J. Heat Mass Transf. 1972, 15, 301–314. [Google Scholar] [CrossRef]
  30. Menter, F. Zonal Two Equation k-ω Turbulence Models For Aerodynamic Flows. AIAA Paper 1993, 1993, 2906. [Google Scholar] [CrossRef]
  31. Menter, F.R. Two-equation eddy-viscosity turbulence models for engineering applications. AIAA J. 1994, 32, 1598–1605. [Google Scholar] [CrossRef]
Figure 1. Flow-induced damage of the runner blade of a large Francis turbine [11].
Figure 1. Flow-induced damage of the runner blade of a large Francis turbine [11].
Applsci 15 02422 g001
Figure 2. The workflow of flow-induced strength analysis of the Francis turbine in this study.
Figure 2. The workflow of flow-induced strength analysis of the Francis turbine in this study.
Applsci 15 02422 g002
Figure 3. The geometrical model of the water passage of the Francis runner unit.
Figure 3. The geometrical model of the water passage of the Francis runner unit.
Applsci 15 02422 g003
Figure 4. Meshes of different fluid domains of the Francis turbine unit.
Figure 4. Meshes of different fluid domains of the Francis turbine unit.
Applsci 15 02422 g004
Figure 5. The fluid domain mesh of the Francis turbine.
Figure 5. The fluid domain mesh of the Francis turbine.
Applsci 15 02422 g005
Figure 6. Normalized pressure distribution of the Francis turbine unit (OP1, 33.3% rated power load).
Figure 6. Normalized pressure distribution of the Francis turbine unit (OP1, 33.3% rated power load).
Applsci 15 02422 g006
Figure 7. Normalized pressure distribution of the Francis turbine unit (OP2, 66.6% rated power load).
Figure 7. Normalized pressure distribution of the Francis turbine unit (OP2, 66.6% rated power load).
Applsci 15 02422 g007
Figure 8. Normalized pressure distribution of the Francis turbine unit (OP3, 100% rated power load).
Figure 8. Normalized pressure distribution of the Francis turbine unit (OP3, 100% rated power load).
Applsci 15 02422 g008
Figure 9. Normalized flow velocity distribution of the Francis turbine unit (OP1, 33.3% load of rated power).
Figure 9. Normalized flow velocity distribution of the Francis turbine unit (OP1, 33.3% load of rated power).
Applsci 15 02422 g009
Figure 10. Normalized flow velocity distribution of the Francis turbine unit (OP2, 66.6% load of rated power).
Figure 10. Normalized flow velocity distribution of the Francis turbine unit (OP2, 66.6% load of rated power).
Applsci 15 02422 g010
Figure 11. Normalized flow velocity distribution of the Francis turbine unit (OP3, 100% load of rated power).
Figure 11. Normalized flow velocity distribution of the Francis turbine unit (OP3, 100% load of rated power).
Applsci 15 02422 g011
Figure 12. Finite element model of the Francis turbine for the flow-induced stress analysis.
Figure 12. Finite element model of the Francis turbine for the flow-induced stress analysis.
Applsci 15 02422 g012
Figure 13. Mapping the CFD-derived pressure profile to the finite element model of the Francis turbine.
Figure 13. Mapping the CFD-derived pressure profile to the finite element model of the Francis turbine.
Applsci 15 02422 g013
Figure 14. Comparison of the normalized maximum stress of the Francis runner under three different loads.
Figure 14. Comparison of the normalized maximum stress of the Francis runner under three different loads.
Applsci 15 02422 g014
Figure 15. Normalized stress of the Francis runner under three different loads.
Figure 15. Normalized stress of the Francis runner under three different loads.
Applsci 15 02422 g015
Table 1. The specifications of the Francis turbine unit.
Table 1. The specifications of the Francis turbine unit.
SpecificationValueUnit
Rated power183MW
Rated head68m
Maximum head80m
Rated discharge294 m 3 s 1
Rotating speed100rpm
Stay vane number20-
Guide vane number20-
Runner blade number13-
Table 2. Operating conditions of the Francis turbine unit.
Table 2. Operating conditions of the Francis turbine unit.
Operating Condition (OP)Guide Vane Opening (%)Flow Discharge (%)Power Output (%)
OP1464233.3
OP2676866.6
OP3100100100
Table 3. Meshes of different fluid domains of the Francis turbine unit.
Table 3. Meshes of different fluid domains of the Francis turbine unit.
Fluid DomainElement Amount (× 10 6 )Element Type
Spiral case and stay vane10.0Hexahedral and Tetrahedral
Guide vane1.60Hexahedral
Crown chamber and band chamber0.35Hexahedral
Francis runner1.62Hexahedral and Tetrahedral
Draft tube0.63Hexahedral and Tetrahedral
Total14.2Hexahedral and Tetrahedral
Table 4. Parameters of the hydro-generator unit.
Table 4. Parameters of the hydro-generator unit.
ParameterValueUnit
Density7700 kg m 3
Young’s modulus2.1 × 10 5 MPa
Poisson’s ratio0.3-
Yield stress550MPa
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Liu, X.; Huang, X.; Chen, W.; Wang, Z. Flow-Induced Strength Analysis of Large Francis Turbine Under Extended Load Range. Appl. Sci. 2025, 15, 2422. https://doi.org/10.3390/app15052422

AMA Style

Liu X, Huang X, Chen W, Wang Z. Flow-Induced Strength Analysis of Large Francis Turbine Under Extended Load Range. Applied Sciences. 2025; 15(5):2422. https://doi.org/10.3390/app15052422

Chicago/Turabian Style

Liu, Xingping, Xingxing Huang, Weijiang Chen, and Zhengwei Wang. 2025. "Flow-Induced Strength Analysis of Large Francis Turbine Under Extended Load Range" Applied Sciences 15, no. 5: 2422. https://doi.org/10.3390/app15052422

APA Style

Liu, X., Huang, X., Chen, W., & Wang, Z. (2025). Flow-Induced Strength Analysis of Large Francis Turbine Under Extended Load Range. Applied Sciences, 15(5), 2422. https://doi.org/10.3390/app15052422

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop