Next Article in Journal
Dynamic Identification of Tensile Force in Tie-Rods by Interferometric Radar Measurements
Previous Article in Journal
Attainable Moment Set Optimization to Support Configuration Design: A Required Moment Set Based Approach
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Zero-Energy Building Integrated Planning Methodology for Office Building Considering Passive and Active Environmental Control Method

1
Division of Smart Grid, Graduate School of SangMyung University, Seoul 03016, Korea
2
Division of Architecture, College of Engineering, Sun Moon University, Chungnam 31460, Korea
*
Author to whom correspondence should be addressed.
Appl. Sci. 2021, 11(8), 3686; https://doi.org/10.3390/app11083686
Submission received: 6 March 2021 / Revised: 31 March 2021 / Accepted: 6 April 2021 / Published: 19 April 2021
(This article belongs to the Section Energy Science and Technology)

Abstract

:
The objective of this study is to derive a design methodology for a zero-energy building considering the energy production and consumption of the building. In order to establish the design methodology, various factors affecting the energy production and consumption of the building are derived, and the effect of the heat transmission rate, the surface to volume ratio (S/V ratio), the location and the orientation of the building are analyzed by simulation method. As a result, the S/V ratio and the heat transmission rate are the most important factors in the central region of Korea where consumes large amounts of heating and cooling energy. This is because the final energy consumption varies depending on the heat loss through the envelope. It was confirmed that solar power generation is the most important factor in the southern regions of Korea where the energy consumption is relatively small. The final energy consumption varies depending on the solar power generation in these areas. Therefore, when designing a zero-energy building, the zero-energy of the building can be achieved by using the design methodology established in this study.

1. Introduction

Zero-energy buildings minimize the energy consumed through the building envelope by installing high-performance insulation and a double skin facade. Zero energy is also achieved by generating energy using renewable energy such as solar or geothermal heat sources. Korea has decided to mandate zero-energy buildings in stages from 2020 to 2030, and the government is currently proposing support measures such as easing building standards, subsidies, and tax support, along with pilot projects. In this study, in order to optimize the upcoming general introduction of zero-energy buildings, the study aims to establish an integrated planning methodology for zero-energy buildings by proposing an approach for integrated planning methodology from the point of view of zero-energy buildings that is expanded from the existing design methodology (interpretation of space, logical arrangement, aesthetic form, maximum floor area ratio, etc.). This planning methodology is verified in terms of energy loss and energy production.
This study proposes an integrated design process that considers a building’s orientation, heat transmission rate of the building envelope, surface to volume ratio (S/V ratio) of the building in terms of heat gain and heat loss, and also examine the potential for solar power generation. In this study, an optimal design plan for a zero-energy building was derived by comparing the building envelope element that can reduce the energy consumption of the building and the solar energy production. The solar panel is considered in combination with the building envelope because the electric energy production is determined according to the roof area and the direction of the building. The design concept of a zero-energy building was derived by reviewing previous studies on the building design method. The passive and active elements were extracted by analyzing the case of zero-energy buildings and design criteria. A differential design concept for zero-energy buildings was established and a zero-energy building planning methodology was established. Finally, the process was verified by simulating energy consumption and production (Figure 1).

2. Preliminary Review

2.1. Review of the Building Design Processes

As shown in Figure 2, the existing architectural design process consists of Pre-Design, Schematic Design, Detailed Design, Construction Document, Construction Stage, and Post Occupancy (Maintenance) processes. In the general architectural design process, the design focuses on the form and function of the building in the basic design stage, and then the structural design for the stability of the building is performed in the detailed design stage. In this process, consideration of high-efficiency facilities and eco-friendly elements which is necessary to enhance the possibilities of achieving a zero energy building are of low importance [1].
Currently, a new methodology is being used to design green buildings. The American Institute of Architects has also continued its efforts to develop new design methodologies and design standards for sustainable architecture [1]. The International Energy Agency (IEA) shows the commonly used integrated design process (Figure 3). This is a design process in which experts in the energy field cooperate from the initial design stage to develop alternatives, compare them with the set goals, and develop them again [2,3]. Only after this stage did the possibility of implementing a zero-energy building begin to gradually increase [4]. Previous research has been conducted to refine the integrated building design process. Each step in the building planning process in the University of British Columbia’s Green Building Design Program can be associated with each step of the architectural design process shown in Figure 3. This process consists of seven steps, from the first step of the program planning and site selection to the seventh step of creating specifications and construction drawings [5].
In Korea, the ecological architectural design process considers an integrated building design process [6]. The content of this process focuses on the design stage that has a great influence on the environmental and energy performance of a building, and deals with design, initial work, conceptual design, basic design, and integrated design [7].
In this study, in order to derive the necessary process of zero-energy building planning, the related items were extracted by separating the contents related to the energy production and consumption of the building from the previously considered building design process (Table 1).
From the comparison of common elements of the design processes, the process of implementing a zero-energy building should first optimize the application of passive methods to minimize the use of cooling and heating energy. Next, the energy used by the building should be minimized by supplying the energy required for the functioning of the building through the production of renewable energy.

2.2. Review of the Building Codes

In order to derive the necessary elements of zero-energy building planning, previous studies and the standards related to energy-saving building design in Korea and Germany was analyzed. Additionally, case studies of zero-energy buildings were conducted. According to research by Chang [8] and Lee [9], in the case of buildings with the same volume and thermal performance, energy consumption is inversely correlated with envelope area. In addition to deriving correlations with building energy according to various building shapes with the same volume according to the combination of unit modules, changes according to the window area ratio were also examined. In this study, a building with a small envelope area exposed to the outside air increases energy savings. Even for buildings of the same volume, the window area ratio is changed according to the layout and shape of the building, so the window–wall ratio should be considered in the design process.
In order to derive the passive elements, the difference between the energy saving elements of the building was derived, as shown in Table 2, by comparing the energy saving design standards of Korea and the passive house standards of Germany. The design of a zero-energy building needs to consider the orientation of the building and the proportion of windows on the south side at the building planning stage, as in the German passive house standard. In addition, the results of Lee’s research [9] related to active elements are summarized, as shown in Table 3, and applied to this study to select solar power generation, solar heat collection, and geothermal energy as renewable energy sources that can be applied to zero-energy buildings [10].

2.3. Review of the Projects

The elements necessary for zero-energy building planning were derived from building case studies. Examples for analysis are representative eco-friendly and zero-energy buildings in Europe, Japan, and the United States, with 19 in Europe, 5 in Japan, and 11 in the US; Table 4). In total, for 35 cases of eco-friendly and zero energy buildings, the frequently applied technologies are summarized in high-performance windows (34 times), high-performance insulation (33 times), solar control device, BIPV (Building Integrated PhotoVoltaics), solar heat collection (20 times), and heat recovery ventilation system (19 times).

3. Zero-Energy Building Planning Method

Based on the preliminary review, the necessary elements of the zero-energy building design are the orientation, layout and shape of the building, the area and insulation of the envelope, the window insulation performance, natural ventilation, heat recovery ventilation, solar radiation control device, high efficiency air conditioner, high efficiency boiler, high efficiency lighting, solar power generation, solar heat collection, and geothermal heat (Table 5).
The concept of the zero-energy building planning process was established based on the necessary elements of zero-energy building planning reviewed in the previous section. The first necessary element of zero-energy building planning is determining a shape of building that can fundamentally reduce the building load by decreasing the seasonal heating/cooling demand according to S/V of the building [11]. This has become much more important compared to the past, when solar power generation panel or BIPV was not installed because the installation capacity of solar energy is determined among the renewable energy that can be installed according to the shape of the building. The second factor is to orient the building so that it uses as much solar energy as possible. The third factor is the design of a renewable energy system [12]. As the biggest difference between the previous green architecture, green building, eco-friendly architecture, ecological architecture and zero energy architecture, the building does not consume energy but actively produces energy to reduce the negative total energy use of the building to zero or negative. The fourth factor is the design of insulation and windows as a shell that can reduce energy requirements [13,14].
As the energy requirement decreases, zero energy can be achieved with less energy production, so improving the insulation performance and air-tight envelope are essential factors. The fifth factor is the design of a building system of heating, cooling, hot water, ventilation, and lighting that allows the energy demand to be met with the minimum input energy [15]. Manufacturers must continuously develop new products to increase efficiency. Apart from the control of individual products, linkage control between products from the energy point of view and integrated control from the point of energy optimization should be implemented. Figure 4 shows the above contents as a sequential process. The heating, cooling, hot water, ventilation, and lighting design is the last component of the design process because it is an area that must be in charge of the manufacturer or product level.
In particular, the difference between the concept of the zero-energy building planning process proposed herein and the planning process performed in the existing architectural design is that the shape of the building is first confirmed before the orientation of the building. Whereas the existing building shape design was to reduce the required energy in terms of heat gain and heat loss by the envelope, from a zero-energy building perspective, the shape of building is interpreted as a variable that can determine the installation capacity of solar panels for renewable energy production. This variable eventually determines the energy production of a zero-energy building. Therefore, after determining the shape of the building, the most advantageous direction can be found in terms of energy. In addition, in considering the renewable energy system, in the case of zero-energy buildings, an optimal solution between increasing energy production using renewable energy and reducing energy demand through high-performance insulation and windows is needed to achieve the goal of the integrated concept of energy independence.
Figure 5 is a schematic diagram of the process of integrated zero-energy building planning methodology. First, the type of site where the project is being executed, the applicable building-to-land ratio and floor area ratio, and weather data of the area are collected as basic data, and then the building-to-land ratio and maximum floor area ratio or target floor area ratio are set with the client.
As the basic data of energy simulation, the heat transmission rate of the building energy saving design standard of the site is applied, and the maximum solar installation capacity that can be installed in the roof area is calculated. The calculated data are used to determine the shape of the building, the S/V ratio, and the direction of the building in which the sum of energy consumption and energy production is minimized by performing energy simulation while repeatedly changing the shape and S/V ratio of the building. Next, the range or the cost of the project that can be invested in energy consumption and production are estimated.
Exterior wall insulation and window insulation increase the build cost but decrease the ongoing energy consumption, and the cost increase and energy production increase when investing in a solar system are compared. Finally, an optimal financial solution is found by optimizing the design of the cooling, heating, hot water, ventilation, and lighting system.

4. Verification of Zero-Energy Building Integrated Planning Methodology

In this section, to verify the zero-energy building planning process, the calculation of solar power generation according to the shape, S/V ratio, and direction of the building was verified as energy consumption and production. The small office model, which is the simplest form of 16 reference building models provided by the Department of Energy (DOE), was selected. In this model, the floor area and the number of floors were adjusted so that the volume and total floor area were the same and the S/V ratio was different. According to the characteristics of the S/V ratio, the energy consumption and production changes were compared and analyzed, and the results were analyzed.

4.1. Verification According to S/V Ratio and Solar Panel Installation

In order to compare and analyze the energy consumption and energy production according to the S/V ratio of the building, a standard building to compare the difference in energy production and demand according to the S/V ratio change was modeled, as shown in Figure 6, using TRNSYS [16]. The small office of DOE was modeled by modifying it to have the same volume and different S/V ratios, as shown in Table 6. In order to realistically consider the energy consumption and energy production calculation of the simulation model, the heat transmission rate of the building energy conservation design standard was applied, as shown in Table 7. Table 8 shows the indoor cooling and heating setting conditions for the simulation.
The simulation revealed that the annual energy consumption is affected by the S/V ratio, as shown in Figure 7. For buildings of the same volume, the smaller the outer envelope area, the smaller the energy requirement. Therefore, in zero-energy building planning, it is necessary to reduce the envelope area as much as possible. The design of the building is decided under comprehensive considerations such as the client’s demand, aesthetic point of view, and site constraints, but in order to achieve a zero-energy building, a design with the lowest S/V ratio should be selected from among various design candidates.
Energy production was calculated assuming that solar panels are installed on 50% of the roof area. As the floor area gradually increases from case 1 to case 6 as the S/V ratio changes, the solar panel installation area of the roof is also increased. The annual energy production is affected by the S/V ratio, as shown in Figure 7. For buildings of the same volume, the energy production increases as the roof area among the envelope areas increases. In the case of a building in which solar power is applied as a renewable energy source, the change in the energy consumption and the energy production occurs at the same time according to the change in the S/V ratio. Therefore, when planning a zero-energy building, it is necessary to determine the S/V ratio from an optimal solution point of view rather than determining the shape of the building based on one of the criteria of energy consumption or energy production. As a result, as shown in Figure 7, in terms of final energy requirements based on the sum of energy consumption and energy production, the case 2 building type with S/V of 0.58 is the most reasonable alternative when planning a zero-energy building.

4.2. Verification of Building Orientation and Solar Panel Installation

While changing the orientation of the building, energy consumption and energy production were estimated. The energy saving rate according to the zero-energy building planning method can be determined by calculating the final energy consumption according to the various directions of the building. Among the DOE reference buildings, a large office building could represent a square-shaped general building, which is suitable for the installation of roof solar panel and BIPV modules. In this study, a large office of DOE was simulated using TRNSYS (Figure 8) with boundary conditions, as shown in Table 9 and Table 10.
The indoor cooling and heating conditions were set, as shown in Table 11, and the energy consumption of the building was calculated by summing the three items: heating load, cooling load, and latent heat. In particular, the energy consumption was calculated by changing the orientation of the buildings in three regions with different latitudes among a total of 36 orientations at 10-degree intervals from the south direction. The simulation shown in Figure 9 revealed that the energy consumption is the largest in the northeast direction, and regardless of the area where the building is located, the direction with the least energy consumption is south (Figure 10). Therefore, analyzing and selecting the building orientation are necessary to minimize the energy consumption in the zero-energy building planning process.
Solar panels applied for energy production can be classified into rooftop PV and BIPV modules. The rooftop PV is always installed facing south in the northern hemisphere, and it was assumed to be installed so that the sunlight and panels could be incident at 90 degrees. In addition, it is assumed that BIPV is installed on the outer wall of the building to maintain a 90-degree angle to the ground (Table 12). For solar power generation conditions, Reference Insolation 1000 W/m2 and NOCT (normal operating solar cell temperature) Insolation 800 W/m2 were used for solar energy simulation. Energy production was calculated for each of the 36 orientations by adding up the annual production of rooftop PV and BIPV modules.
The simulation revealed that the energy production decreases in the order of Daejeon, Busan, and Seoul due to the difference in insulation by region. Therefore, in the planning of a zero-energy building, the effect of solar power installation should be reflected depending on the region. In addition, to analyze the correlation between the direction of the building and the energy production, the energy production of a total of 36 orientations at 10-degree intervals from the south direction was identified. As shown in Table 13, the west has the highest energy production and the northeast has the lowest energy production. This is the effect of the BIPV installation, and the proportion of the BIPV module installed on the south side of the square building is larger than that on the east and west sides. The west side, where the south side receives sunlight until the latest, has the greatest power generation.
The final energy consumption analysis, shown in Table 14 and Figure 11, revealed that large offices in the case of applying the heat transmission rate of the central region to the Daejeon region decrease in the order of Seoul, Daejeon, and Busan. This is due to local weather conditions, and the Busan area, which shows relatively high energy production conditions and relatively low basic energy consumption, is the most advantageous area, with a final energy consumption of 80% of that of Seoul.
Finally, for large office buildings, the final energy consumption was estimated by subtracting the energy production from the energy consumption of the three areas in Seoul, Daejeon, and Busan (Table 15). Figure 11 shows the energy reduction as a result of the analysis of the final energy consumption derived by assuming that the energy produced by the rooftop PV and the BIPV module is consumed in the building. The energy consumption reduction ranges from 17% to 30%, due to differences in solar panel application boundary conditions. In addition, the energy reduction increases in the order of Seoul, Daejeon, and Busan, mostly due to the difference in energy consumption, with only minor difference in energy production in each region.

5. Conclusions

This study establishes and verifies a zero-energy building planning methodology that considers the building’s energy consumption and energy production, which are critical in the design process. Therefore, the effect of the S/V ratio of the same volume building on the energy consumption, the effect of solar panels installation on the energy production, and the final energy requirement were analyzed. The results are summarized as follows.
(1) The planning methodology focused on a zero-energy building should minimize the energy consumption by applying passive technology and reduce the final energy demand by producing renewable energy. In addition to increasing the amount of energy consumption through passive design elements, energy production elements centered on solar energy source must be considered in the planning methodology.
(2) An area that consumes a lot of heating and cooling energy has a high energy requirement, so any reduction in the energy requirement strongly affects the final energy requirement considering the energy production. In such an area, since the energy requirement is proportional to the envelope area, the energy-saving S/V ratio should be considered in the planning methodology of a zero-energy building.
(3) In order to increase the building’s solar energy production, a plan for the maximum application of new and renewable energy sources such as BIPV and rooftop solar power must be implemented. Also, the building’s S/V ratio and orientation must be considered in a design process to reduce the final energy consumption through solar energy production.
(4) Insulation is most important in the central region of Korea, and solar power installation in the southern region. Therefore, the process of planning a zero-energy building needs to integrate the energy consumption and production according to the building location.
In the future, there are plans to study the effect of achieving zero energy buildings by applying various renewable energy sources and to evaluate them in terms of LCA (life cycle assessment) in order to optimize the design methodology.

Author Contributions

Conceptualization, S.L.; methodology, S.P.; software, S.L.; validation, S.P.; investigation, S.P.; data curation, S.L.; writing—original draft preparation, S.L.; writing—review and editing, S.P.; visualization, S.L.; supervision, S.P.; project administration, S.L.; funding acquisition, S.P. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Sun Moon University Research Grant of 2019.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Acknowledgments

This work was supported by the Sun Moon University Research Grant of 2019.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Kim, M.G.; Kang, H.S. A study on design application of eco-friendly integrated design process. J. Korea Inst. Ecol. Arch. Environ. 2013, 13, 87–94. [Google Scholar] [CrossRef]
  2. International Energy Agency. Integrated Design Process: A Guideline for Sustainable and Solar-Optimized Building Design; International Energy Agency: Paris, France, 2003. [Google Scholar]
  3. Sahib, Y. Modernizing Building Energy Codes 2013; The International Energy Agency Policy Pathway Series; International Energy Agency: Paris, France, 2013; pp. 24–28. [Google Scholar]
  4. Lee, B.Y.; Kim, K.H. A study on the integrated design process for sustainable architecture. J. Arch. Inst. Korea 2009, 25, 55–62. [Google Scholar]
  5. University of British Columbia. UBC Integrated Design Process. 2020. Available online: https://planning.ubc.ca/sustainability/sustainability-action-plans/green-building-action-plan/institutional-building-requirements/ubc-integrated-design-process (accessed on 28 February 2021).
  6. Lee, H.J. A Study on the Energy Self-Sufficient House. Master’s Thesis, Graduate School of Semyung University, Chungbuk, Korea, 2016. [Google Scholar]
  7. Tae, Y.R. Architectural design process by the changes of sustainable design guidelines of public project. J. Korean Solar Energy Soc. 2010, 30, 63–70. [Google Scholar]
  8. Chang, W.S.; Shin, H.C.; Choi, W.K. Energy sensitivity analysis according to the design variables with the same volume building. J. Korean Inst. Arch. Sustain. Environ. Build. Syst. 2014, 8, 104–110. [Google Scholar]
  9. Lee, M.J.; Kim, W.S.; Lee, W.J.; Lee, W.T. A study about reduction rates of building energy demand for a detached house according to building energy efficient methods. J. Arch. Inst. Korea 2012, 28, 275–283. [Google Scholar]
  10. Kim, S.H. A Study for Building Design Process Using Ecological Approach. Master’s Thesis, Graduate School of Sungkyunkwan University, Seoul, Korea, 2002. [Google Scholar]
  11. Choi, W.K.; Kim, H.J.; Suh, S.J. A study on the analysis of energy consumption patterns according to the building shapes with the same volume. J. Korean Solar Energy Soc. 2007, 27, 103–109. [Google Scholar]
  12. Hong, W.-P. Economic analysis and energy saving evaluation for smart grid system of hospital building. J. Korean Inst. Illum. Electr. Install. Eng. 2010, 24, 129–139. [Google Scholar] [CrossRef]
  13. Jang, H.J.; Park, J.C. A study on the energy efficiency evaluation of zero energy building. J. Korean Inst. Arch. Sustain. Environ. Build. Syst. 2010, 4, 149–156. [Google Scholar]
  14. Rodriguez-Ubinas, E.; Rodriguez, S.; Voss, K.; Todorovic, M.S. Energy efficiency evaluation of zero energy houses. Energy Build. 2014, 83, 23–35. [Google Scholar] [CrossRef] [Green Version]
  15. Peippo, K.; Lund, P.; Vartiainen, E. Multivariate optimization of design trade-offs for solar low energy buildings. Energy Build. 1999, 29, 189–205. [Google Scholar] [CrossRef]
  16. Zogou, O.; Stapountzis, H. Energy analysis of an improved concept of integrated PV panels in an office building in central Greece. Appl. Energy 2011, 88, 853–866. [Google Scholar] [CrossRef]
Figure 1. Research process.
Figure 1. Research process.
Applsci 11 03686 g001
Figure 2. Conventional building design process.
Figure 2. Conventional building design process.
Applsci 11 03686 g002
Figure 3. Integrated building design diagram by IEA Task 23.
Figure 3. Integrated building design diagram by IEA Task 23.
Applsci 11 03686 g003
Figure 4. Simplified concept of zero-energy building planning process.
Figure 4. Simplified concept of zero-energy building planning process.
Applsci 11 03686 g004
Figure 5. Zero-energy building integrated planning methodology.
Figure 5. Zero-energy building integrated planning methodology.
Applsci 11 03686 g005
Figure 6. Simulation model for energy analysis by TRNSYS: (a) energy consumption model; (b) energy production model.
Figure 6. Simulation model for energy analysis by TRNSYS: (a) energy consumption model; (b) energy production model.
Applsci 11 03686 g006
Figure 7. Energy consumption, production and final energy consumption according to S/V ratio change.
Figure 7. Energy consumption, production and final energy consumption according to S/V ratio change.
Applsci 11 03686 g007
Figure 8. Large office simulation model.
Figure 8. Large office simulation model.
Applsci 11 03686 g008
Figure 9. Energy consumption according to the building orientation.
Figure 9. Energy consumption according to the building orientation.
Applsci 11 03686 g009
Figure 10. Energy consumption according to the region.
Figure 10. Energy consumption according to the region.
Applsci 11 03686 g010
Figure 11. Final energy consumption and reduction rate according to region.
Figure 11. Final energy consumption and reduction rate according to region.
Applsci 11 03686 g011
Table 1. Comparison of common elements of each design process.
Table 1. Comparison of common elements of each design process.
ContentsGreen Building Design Program by UBC [5]Biological Building Design Process by Kim [10]
Passive elements4th Stage: Building orientation and configuration
4.1 Use site resources to reduce building loads and enhance indoor environmental quality
4.2 Develop a project specific building form and massing
4.3 Configure internal layout to reduce loads and enhance IEQ
5th Stage: Building systems design
5.1 Energy design
5.3 Envelope design
3rd Stage: Concept design
① Sunlight, topography (slope), airflow analysis
⑤ Agreement on building design and system access plan according to energy source
4th Stage: Basic design
② Building design (building shape and structure, Openings, Material)
5th Stage: Integrated design
①Building orientation/shape (natural cooling technique, surface area ratio minimization, buffer space, thermal zoning, natural solar technique)
③ Building envelope design
④ Opening design
Active
elements
5th Stage: Building systems design
5.1 Energy design
5.4 Ventilation design
5.6 Lighting design
5.7 Mechanical design
5.8 Finalize building systems design
6th Stage: Interior finishes and appliances
6.1 Reduce internal loads
4th Stage: Basic design
③ System design
5th Stage: Integrated design
⑤ HVAC system
⑥ Lighting power system
⑨ Evaluation
Table 2. Comparison of Korean building energy saving design standards and German passive house standards.
Table 2. Comparison of Korean building energy saving design standards and German passive house standards.
Energy Saving ElementsEnergy Saving Design Standards of BuildingsPassive House Design Standards
Building orientation-South
Window area ratio on the south facade-40%
Insulation of the facadeClassification by building location and components0.1 W/(m2K)
GlassClassification by building location and components≤0.75 W/(m2K)
Window frame ≤0.80 W/(m2K)
Air-tightness (infiltration)<5 m2/(h·m2)≤0.6/h
Heat storage performanceDescription on night electricity heat storage systemRecommended
Heat recovery ventilation systemExplained in the mechanical equipment section of the energy performance indexEfficiency > 80%
ShadingsExplained in the architectural section of the energy performance indexRecommended
Table 3. Types of renewable energy and the applicability of produced energy to buildings.
Table 3. Types of renewable energy and the applicability of produced energy to buildings.
Energy Producing ElementsNew and Renewable Energy SourceType of Produced EnergyBuilding Applicability
New energyHydrogenElectricity, thermal energyLow
Fuel CellElectricity, thermal energyMedium
Coal gasification and liquefied electricityElectricity, thermal energy, gasLow
Renewable
energy
SunlightElectricityHigh
Solar heatThermal energyHigh
WindElectricityMedium
WaterElectricityLow
OceanElectricityLow
GeothermalThermal energyHigh
BiomassElectricity, thermal energy, gasMedium
WasteElectricity, thermal energyMedium
Table 4. Zero-energy building technology for various projects.
Table 4. Zero-energy building technology for various projects.
ProjectRegionApplied Technology
EuropeJapanU.S.AHigh-Performance InsulationHigh-Performance WindowSolar Control DeviceHRV SystemMotion SensorTABSBIPVSolar Heat CollectionGeothermalBio-MassRecycleReuseLocal MaterialsRenewable Materials
3 Liter Twin Houses
Buttisholz
Chinolo House
Goteborg
Hannover House
Hockerton Housing
Horbranz House
House W
Husby Amfi
ISIS Solar Passive Apartment
Kassel House
Konstanz
Kuchl House
Nebikon House
Passivehouse in Gaspoltshofen
Plus-energy Settlement
Riverdijk
Steinhude Sea Recreation Facility
Sunny Woods
Okamoto Solar House
Okayama House
Sunny Eco House
Sustainable Solar House
Zero Energy House in Kanagawa
Adam Joseph Lewis Center
Aldo Leopold Legacy Center
Audubon Center
Challengers Tennis Club
Demonstration House in Kansas City
Environmental Technology Center
Home Depot Smart Home
Idae Z2 Squared Design Facility
Nueva School
Science House
World Headquarter for IFAW
Total195113334201987202010411388
Table 5. Passive and active design elements of zero energy buildings.
Table 5. Passive and active design elements of zero energy buildings.
ContentsPassive ElementsActive Elements
Energy consumptionOrientation of the building
layout and shape of the building, area and insulation of the envelope, window insulation performance, natural ventilation, solar radiation control device
Heat recovery ventilation, high efficiency air conditioner, high efficiency boiler, high efficiency lighting
Energy production-Solar power generation, solar heat collection, geothermal heat
Table 6. S/V ratio modification of small office.
Table 6. S/V ratio modification of small office.
CaseWidth [m]Depth [m]Height [m]Ratio of Lateral to Longitudinal Length [-]Floor AreaSurface AreaVolumeS/V Ratio
111.611.611.61.0134.6807.31560.90.52
216.116.16.021.0259.2906.11560.40.58
340.010.03.94.0400.01190.01560.00.76
422.622.63.11.0510.81298.11562.90.83
530.020.02.61.5600.01460.01560.00.94
638.019.02.12.0722.01690.21559.51.08
Table 7. Properties of small office simulation model.
Table 7. Properties of small office simulation model.
Building TypeWall TypeTotal Thickness [m]U-Value [W/mwK]
CentralSouthernCentralSouthern
Small OfficeAdjacent ceiling0.3580.3300.2200.260
Adjacent wall0.2070.1780.3600.450
Exterior roof0.4800.4200.1500.180
Exterior wall0.2700.2130.2600.320
Ground floor0.4300.3700.2200.250
Window0.0260.0261.4901.800
Table 8. Annual boundary condition of small office simulation model.
Table 8. Annual boundary condition of small office simulation model.
PropertiesCondition
Heating setting temperature20 °C, Humidity 30%
Cooling setting temperature26 °C
Weather dataRepresentative weather data by statistical analysis of the region from 1981 to 2010 for 30 years
Number of ventilations0.5 time/h
Table 9. Modification of DOE (Department of Energy) reference building for large office simulation.
Table 9. Modification of DOE (Department of Energy) reference building for large office simulation.
Building TypeFloor Area [m2]Story
OriginalModifiedCentralOriginal
Large Office46,3203656Large Office46,320
Table 10. Properties of large office simulation model.
Table 10. Properties of large office simulation model.
Building TypeWall TypeTotal Thickness [m]U-Value [W/mwK]
CentralSouthernCentralSouthern
Large OfficeAdjacent ceiling0.3580.3300.2200.260
Adjacent wall0.2070.1780.3600.450
Exterior roof0.4800.4200.1500.180
Exterior wall0.2700.2130.2600.320
Ground floor0.4300.3700.2200.250
Window0.0260.0261.4901.800
Table 11. Annual boundary condition of large office simulation model.
Table 11. Annual boundary condition of large office simulation model.
PropertiesCondition
Heating setting temperature20 °C, Humidity 30%
Cooling setting temperature26 °C
Weather dataRepresentative weather data by statistical analysis of the region from 1981 to 2010 for 30 years
Number of ventilations0.5 time/h
Table 12. Boundary condition for photovoltaic modules.
Table 12. Boundary condition for photovoltaic modules.
ContentsAreaCapacity
Rooftop PV70% (Rooftop)256.5 kW
BIPV30% (South facade)62.7 kW
30% (West facade)41.8 kW
30% (East facade)41.8 kW
Total-402.8 kW
Table 13. Building orientation with high energy production.
Table 13. Building orientation with high energy production.
Contents1st2nd3rd
Orientation [°]Produced Energy [kJ/h]Orientation [°]Produced EnergyOrientation [°]Produced Energy
Seoul90600,004,585100599,863,95780597,264,743
Daejeon90752,933,65080752,350,262100749,617,380
Busan90747,771,04680745,898,465100745,453,000
Table 14. Building orientation with low energy production.
Table 14. Building orientation with low energy production.
Contents36th35th34th
Orientation [°]Produced Energy [kJ/h]Orientation [°]Produced EnergyOrientation [°]Produced Energy
Seoul230434,560,713250433,433,754240432,252,401
Daejeon250531,999,645240528,155,941230528,077,720
Busan250506,904,344230504,696,289240503,629,377
Table 15. Final energy consumption.
Table 15. Final energy consumption.
ContentsAverage of Energy Demand [kJ/h]Average of Energy Generation [kJ/h]Final Average of Energy Demand [kJ/h]
Seoul3,089,933,688520,313,9582,569,619,730
Daejeon (Southern U-Value)3,502,698,245644,985,6572,857,712,588
Daejeon (Central U-Value)3,198,209,7462,553,224,089
Busan2,684,092,649631,502,3702,052,590,279
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Lee, S.; Park, S. Zero-Energy Building Integrated Planning Methodology for Office Building Considering Passive and Active Environmental Control Method. Appl. Sci. 2021, 11, 3686. https://doi.org/10.3390/app11083686

AMA Style

Lee S, Park S. Zero-Energy Building Integrated Planning Methodology for Office Building Considering Passive and Active Environmental Control Method. Applied Sciences. 2021; 11(8):3686. https://doi.org/10.3390/app11083686

Chicago/Turabian Style

Lee, Soonmyung, and Sanghoon Park. 2021. "Zero-Energy Building Integrated Planning Methodology for Office Building Considering Passive and Active Environmental Control Method" Applied Sciences 11, no. 8: 3686. https://doi.org/10.3390/app11083686

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop