Next Article in Journal
Ground Improvement Using Recycled Concrete Columns: A Case Study of Wind Turbine Foundation
Previous Article in Journal
Online Robust Detection of Structural Anomaly Under Environmental Variability via Orthogonal Projection and Noisy Low-Rank Matrix Completion
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Measurement and Prediction of Airborne Sound Insulation Performance of Different Vertical Partition Walls in Indoor Environments: A Case Study

1
Department of Mechanical, Energy and Management Engineering, University of Calabria, 87036 Arcavacata, Italy
2
Department of Computer, Modelling, Electronics and System Engineering, University of Calabria, 87036 Arcavacata, Italy
*
Author to whom correspondence should be addressed.
Buildings 2025, 15(20), 3753; https://doi.org/10.3390/buildings15203753
Submission received: 29 April 2025 / Revised: 7 July 2025 / Accepted: 13 October 2025 / Published: 17 October 2025
(This article belongs to the Section Building Energy, Physics, Environment, and Systems)

Abstract

This paper presents a case study in which the airborne sound insulation performance of vertical partitions is experimentally assessed and model-predicted by incorporating the indoor environment’s geometric configuration and material characteristics into the analysis. An experimental campaign was carried out to verify whether the partition actually installed in situ complies with the minimum acoustic requirements and to validate the results obtained from the predictive model, subsequently used to evaluate the acoustic performance of alternative configurations. Specifically, a case study was conducted on an existing wall separating two indoor environments at the University of Calabria (Italy), where experimental measurements revealed that the current structure fails to meet the minimum acoustic insulation requirement set by Italian regulation. To evaluate the potential improvement in acoustic performance resulting from the use of alternative structures, predictive modeling based on UNI EN ISO 12354-1 was carried out. In the simulations, the rooms were modeled according to their actual geometry, and different types of vertical partitions between the two spaces were assessed, including heavyweight masonry walls, lightweight gypsum-based systems, and drywall linings, all built using commercially available acoustic insulation materials. In addition, four other cost-effective insulated walls were evaluated, which were insulated, at most, using standard thermal insulation. In addition to acoustic performance, implementation costs were also considered. Among the acoustically insulated partitions, the highest-performing construction achieved a R w of 58.0 dB for €168.9/m2, while a cost-effective construction based on double gypsum boards reached a R w equal to 51.4 dB with a cost of €65.9/m2.

1. Introduction

The control of noise in indoor environments is a critical challenge in modern architecture [1], engineering [2], and urban planning [3,4]. The presence of unwanted sound, or noise pollution, can significantly affect comfort [5], productivity [6], and health [7] in various settings, including residential, office, and industrial spaces [8]. With the increasing densification of urban areas and the widespread adoption of open-plan spaces, the need for effective acoustic management has become more pressing than ever [9,10]. Consequently, the study and development of acoustic enhancement strategies are crucial for mitigating the adverse effects of noise and ensuring acceptable indoor sound quality [11].
Acoustic enhancement strategies generally fall into two categories: sound absorption and sound insulation [12]. Sound absorption involves reducing the reflection of sound waves within a space, thereby improving the overall acoustic environment [13]. This is particularly relevant for reducing reverberation times and enhancing speech intelligibility. On the other hand, sound insulation focuses on preventing the transmission of sound from one space to another, which is essential for ensuring privacy and reducing disturbances [14,15]. While significant research has been conducted on developing materials for sound absorption and insulation, challenges persist, especially in designing effective solutions that balance economic and functional constraints.
One of the most significant challenges in indoor acoustic management is the presence of partition walls that inadequately isolate noise between adjacent spaces [16]. Such partitions, commonly found in office buildings, educational institutions, and healthcare facilities, often fail to provide sufficient sound attenuation, leading to disruptive noise transfer between rooms [17]. The impact of poor acoustic insulation is well-documented, with studies indicating that excessive noise exposure in workplaces can lead to reduced cognitive performance, increased stress levels, and lower job satisfaction [18,19,20].
Numerous methods have been developed to enhance the acoustic performance of partitions, including the use of composite materials [21], decoupling techniques, and resonant absorbers. Traditional solutions, such as increasing the mass of walls or incorporating air gaps [22], remain effective but may not always be feasible due to space or weight constraints. More recently, researchers have explored the use of advanced materials, such as metamaterials and porous absorbers, which offer promising results in terms of both sound absorption and insulation [12]. Qu et al. [23] explore the design and application of lightweight partitions made of composite materials with high sound insulation properties, specifically in hotel interior spaces.
The review by Tao et al. [24] provides an overview of recent advancements in acoustic materials and noise control strategies [25,26], including the use of polyurethane foams, sandwich panels, and textile materials for sound absorption.
Caniato et al. [27,28,29] explore the energy and acoustic performance of timber in buildings, providing an overview of the potential of this material to enhance sound insulation. Additionally, they analyze the use of numerical models to predict the noise generated by service equipment in both heavyweight and lightweight timber buildings, contributing to a better understanding of sound insulation dynamics in such structures. Secchi et al. [30] present an experimental and environmental analysis of new sound-absorbing and insulating elements made from recycled cardboard, highlighting the effectiveness of low-cost sustainable materials in acoustic insulation.
Current studies primarily focus on identifying the sound insulation properties of individual materials, often through laboratory measurements. However, these approaches do not account for the fact that the real-world performance of these materials depends on the context in which they are applied, including factors such as the reverberation time of the room in which they are placed. This limitation highlights the need for research that considers both material properties and their interaction with the surrounding acoustic environment [31]. Despite the extensive research on indoor noise control, the study of the acoustic performance of building partitions still presents certain challenges, particularly in reconciling experimental validation, modeling, and economic analysis. In this context, the aim of this work is to assess the improvement in the apparent airborne sound insulation index of a vertical partition. This is achieved by experimentally evaluating the acoustic performance of an existing wall and then validating and utilizing a predictive model to compare commercial sound-insulating solutions with cost-effective insulated wall configurations. The ultimate goal is to identify constructions that meet national regulatory limits for acoustic performance while reducing costs. The innovation of this study lies in achieving regulatory acoustic insulation requirements through cost-effective solutions, specifically by proposing and evaluating wall configurations that utilize low-cost thermal insulation materials for sound insulation, instead of acoustic materials. In particular the work provides a comparative techno-economic analysis between walls insulated with purpose-designed acoustic materials and thermal insulated walls, providing a practical guide for selecting optimal wall systems based on both acoustic performance and economic viability.
The use of Echo® software version 8.4 [32] to generate a model based on the actual spatial configuration of the rooms allows for overcoming the simplifications often adopted in theoretical studies, making the results more representative of real-world conditions. While many studies focus on innovative materials in isolation, without considering their practical application, this study evaluates the effectiveness of different constructions in a realistic scenario, including also standard sandwich-type building assemblies with air cavities and conventional porous thermal insulation (which is more cost-effective than dedicated acoustic insulation) [33]. Therefore, this work provides useful insights directly applicable to the building sector. This approach not only identifies the most effective configurations in terms of sound insulation but also assesses the economic impact of different constructions, an aspect often overlooked in scientific literature, providing a comprehensive framework for the design and optimization of building partitions. By integrating various acoustic treatment strategies, the paper seeks to provide actionable insights for architects, engineers, and policymakers aiming to design quieter and more comfortable indoor spaces.
Section 2 details the methodology, including the description of the procedures for assessing the sound insulation index using both experimental measurements and theoretical models, the case study and the presentation of improvement constructions. Section 3 presents the results obtained, including the sound pressure levels, the reverberation time, and the apparent airborne sound insulation index of the actual partition measured experimentally, as well as the theoretical acoustic outcomes of the proposed enhancements. Finally, Section 4 outlines the conclusions.

2. Materials and Method

This section describes the procedure followed to determine the improvement in the apparent airborne sound insulation index of a vertical partition, achieved through the implementation of acoustically insulated walls or cost-effective insulated partitions (insulated, at most, with typical thermal insulation materials). To this end, an experimental campaign was conducted to assess the acoustic performance of the existing partition under investigation. The results were used both to verify whether the in situ wall complies with the national regulatory limits DPCM 05/12/1997 [34], and to validate the outcomes of a predictive model. The same model was then used to evaluate the acoustic performance of the proposed alternative constructions.

2.1. Experimental Determination of the Apparent Airborne Sound Insulation Index R w

To experimentally determine the apparent airborne sound insulation index R w of the vertical partition, it was necessary to measure the reverberation time in the receiving room and the sound pressure levels in both the source and receiving rooms, in accordance with UNI EN ISO 16283-1 [35].
For the latter, a dodecahedral source was used to generate pink noise in the source room, and sound pressure levels were measured at five random positions in both rooms. These measurements were performed in third-octave bands over the frequency range from 100 Hz to 3150 Hz. The measured sound pressure levels were corrected for the background noise level recorded in the receiving room with the source turned off.
For the measurement of the reverberation time in the receiving room in third-octave bands RT60 an impulsive sound source was used. At this point, the apparent airborne sound insulation trend R′ in third-octave bands between the source and receiving rooms is given by:
R = L p 1 L p 2 + L c o r r + 10 · log S d · R T 60 0.16   · V 2
where for each frequency band, Lp1 and Lp2 represent the spatial-temporal logarithmic averages of the sound pressure levels measured at the five positions in the receiving and source rooms, respectively.
Finally, by comparing the experimental curve R′ with the reference curve provided by UNI EN ISO 717-1 [36], the apparent airborne sound insulation index R w was determined.
This procedure, along with the processing of the experimental data, was implemented using the VibRum Plus® software version 1.88 [37], as illustrated in Section 2.8.1.

2.2. Prediction of the Apparent Airborne Sound Insulation Index R w

The following paragraph describes the predictive calculation method outlined in UNI EN ISO 12354-1 [38]. In particular, the apparent airborne sound insulation index of a vertical partition R w is equal to:
R W = 10 log 10 R D d , W 10   + D f = 1 n 10 R D f , W 10   + F d = 1 n 10 R F d , W 10 + F f = 1 n 10 R F f , W 10 + A 0 S j = 1 m 10 D n , j , W 10
where A 0 is the reference equivalent absorption area, set at 10 m2; S is the area of the separating partition and D n , j , W represents the sound transmission coefficient of any elements eventually inserted within the partition. Rij,w represents the sound insulation index for the sound propagation path ij, and it is calculated as:
R i j , W = R i , W + R j , W 2 + R i j , W + k i j + 10 log S l i j
R i , W and R j , W are the sound reduction indices of the individual building components involved in the propagation path; R i j , W accounts for any increase in sound reduction due to the presence of additional layers along the propagation path; k i j is the vibration reduction index through the junction between elements, which depends on the junction type and the surface mass of the involved partitions and l i j is the length of the junction.
As detailed in Section 2.8.2, the predictive calculation was implemented using the Echo® software.

2.3. Case Study

The acoustic in situ analysis was carried out with reference to the vertical partition wall separating two adjacent indoor environments at the University of Calabria, Rende (Italy). The first room, identified as the source room, is a technical space with a volume of 172 m3, while the adjacent room, designated for office use, represents the receiving room with a volume of 183 m3. Figure 1 highlights in red the vertical partition under investigation, which consists of 2 cm thick plywood panels enclosing an unventilated air cavity of 6 cm thickness. The stratigraphy of the remaining building elements is described in detail in Section 2.8.2.
Figure 2 and Figure 3 show the plan and sectional views, along with their geometric dimensions in meters, of the receiving and source room, respectively. As shown in the figures, a suspended ceiling is present, consisting of an unventilated air gap and a layer of polystyrene.

2.4. Measurement Equipment

The measurements were carried out using a Svantek 979 (Svantek Italy, Milan, Italy) integrating sound level meter, equipped with a condenser microphone and calibrated with a certified Class 1 acoustic calibrator. The noise was generated using a “12-dodicifacce” DF02AD dodecahedral loudspeaker (Safe, Padova, Italy) (see Figure 4).
Signal sampling was carried out without any weighting (Z-weighting mode) at a sampling frequency of 48 kHz. All data acquisitions were performed in third-octave bands, as required by the regulation. The integration interval and measurement duration were set to 1 s (Slow time constant) and 15 s, respectively. Regarding the measurement of the reverberation time in the receiving room, the integration interval and duration were set to 0.125 s (Fast time constant) and 1 s, respectively.

2.5. Acoustically Insulated Wall Configurations

Several wall assemblies were evaluated and compared, each built using commercially available sound-insulating materials produced by three different companies operating in the acoustics sector (Isolmant, FIBRAN and Fermacell).
With regard to Isolmant (Tecnasfalti, Milan, Italy), the acoustic performance of the walls is improved through the use of a panel made of recycled polyester-based technical textile fiber (see Figure 5). The wall configurations analyzed are as follows:
  • Perfetto Special 1 features a total thickness of 30 cm and consists of a 15 cm thick masonry block layer, a 5 cm air cavity containing 3 cm of insulating material, and a second masonry layer of 10 cm. Additionally, an elastic joint between the wall and the floor is provided by means of a perimeter acoustic decoupling strip, in order to reduce flanking sound transmission.
  • Perfetto Special 2 has an overall thickness of 26 cm and is composed of a 12 cm thick masonry block layer, a 4 cm cavity with 3 cm of insulation, and a 10 cm thick masonry block layer.
  • Perfetto Special CG comprises a 2 cm plaster layer, 8 cm of hollow clay brick, a 2 cm base coat, and a 7.5 cm metal frame filled with 4.5 cm of insulation and covered with a double 2.5 cm gypsum board. The geometrical configuration of the metal support frame is illustrated in Figure 6.
The main characteristics used for the determination of the apparent airborne sound insulation index R w of the Isolmant analyzed wall configurations are reported in Table 1 [39].
FIBRAN (Fibran, Genova, Italy) proposes lightweight and less invasive solutions compared to those developed by Isolmant, employing gypsum plasterboard panels and rockwool as the insulating material. Specifically:
  • The FIBRAN B-040/A13—1 wall system has a total thickness of 10 cm and consists of two FIBRANgyps A13 plasterboards, each 1.3 cm thick, a 4 cm layer of FIBRANgeo B-040 rockwool, a 1 cm air cavity, and other two plasterboards, also 1.3 cm thick.
  • The FIBRAN B-050/SUPER13 configuration follows the same stratigraphy as the previous one, while featuring two FIBRANgyps SUPER13 plasterboards, a 5 cm thick layer of FIBRANgeo B-050 rockwool, and a 2.5 cm air cavity.
  • The FIBRAN B-040/A13—2 wall features the same materials as the first configuration, with a 5 cm thick air cavity, bordered this time by two layers of FIBRANgeo B-040 rockwool, each 4 cm thick.
The main characteristics used for the determination of the apparent airborne sound insulation index R w of the FIBRAN analyzed wall configurations are reported in Table 2 [40].
To avoid the demolition of the existing wall and the construction of a new partition, Fermacell (James Hardie Europe GmbH, Dusseldorf, Germany) offers the possibility of improving acoustic performance through the installation of an additional acoustic partition, consisting of a 1 cm thick gypsum-fiber board and a 5 cm rock wool panel placed in the air cavity [41], as shown in Figure 7. In the predictive calculations, it was assumed that this additional partition is applied to both sides of the existing wall.

2.6. Cost-Effective Insulated Walls

This section presents and analyses structural proposals aimed at improving the apparent airborne sound insulation index R w to meet regulatory requirements, while maintaining cost-effectiveness through the use of, at most, typical thermal insulation material. Specifically, four different types of walls were studied, as described below:
  • Type A: masonry wall consisting of a 2 cm thick plaster layer, 8 cm thick hollow brick wall, and another 2 cm thick plaster layer.
  • Type B: masonry wall of Type A with an additional partition on the side of the receiving room, consisting of 1.3 cm thick drywall layer, 5 cm thick layer of sintered expanded polystyrene, and 2 cm thick non-ventilated air cavity.
  • Type C: partition wall consisting of two plasterboard layers, each 2.6 cm thick, enclosing a 5 cm thick rock wool panel and a 5 cm thick non-ventilated air cavity, and employing double metal studs for acoustic decoupling.
  • Type D: metal stud partition wall consisting of two plywood layers, each 3 cm thick, enclosing a 5 cm thick rock wool panel and a 5 cm thick non-ventilated air cavity, and employing double metal studs for acoustic decoupling.
The main characteristics for determining the R w index of the four analyzed walls are shown in Table 3.

2.7. Cost Analysis

Based on manufacturer catalogs [42,43,44,45] and a market analysis of 10 different manufacturers in the sector, the cost per square meter was estimated for each of the proposed constructions. The values reported in Table 4 refer to the complete system, including ancillary components, plasterboard panels, masonry elements, metal framework, and labor costs.

2.8. Software

2.8.1. On-Site Measurements Processing Software

For processing the measurements, the VibRum Plus® software was used, which implements the reference standard UNI EN ISO 16283-1:2014 in order to determine the apparent airborne sound insulation index R w . To this end, the software compares the sound insulation trend R′ obtained from the processing of the experimental measurements, with the limiting curve from the UNI EN ISO 717-1 standard. The software requires both the volume of the rooms and the surfaces of the building components.

2.8.2. Predictive Calculations Software

The predictive calculations of the sound insulation indices for the proposed vertical partitions were conducted using the ECHO® software, in which the volumes and surfaces defining the emitting and receiving rooms were reconstructed. Furthermore, the physical and geometrical description of the layers constituting the wall, surface mass, and sound insulation performance Rw of each building components were specified. Figure 8 containsthe characteristics of the vertical partition (shown in red) and the building components of the two rooms (shown in yellow), as actually installed in situ.
After verifying that the apparent airborne sound insulation R w index of the partition currently installed in situ, obtained using the Echo® software, is in good agreement with the value measured experimentally (as shown in Section 3.2), the characteristics of the vertical partition were modified according to the proposed and analyzed construction typologies and, for each of them, the software computed the corresponding R w index.
Figure 9 shows the sound propagation paths between the two rooms, relative to the considered construction joint shown in red, with the relevant path i-j indicated by the blue arrow. As indicated in Equation (3), to evaluate the term Rij along this path, it is necessary to define the type and length of the joints.

3. Results

This section presents the results obtained from the experimental campaign and processed using the VibRum Plus® software, with the aim of evaluating the apparent airborne sound insulation index R w of the actual vertical partition. Subsequently, the result of the predictive calculation is shown in order to assess whether the R w value obtained with the Echo® software is consistent with the experimentally measured outcome. Finally, the apparent airborne sound insulation indices obtained either through the use of acoustically insulated walls with commercially available insulating materials, or through the cost-effective insulated walls proposed in this study, are presented along with the corresponding cost estimates.

3.1. Experimental Measurement Results

With reference to the partition currently installed in situ, Figure 10, Figure 11 and Figure 12 present the frequency-domain spectral analysis of the equivalent sound pressure levels, obtained from the spatial average of five measurements taken in the source room, the receiving room, and the background noise in the receiving room, respectively. The last bar in each graph represents the total equivalent sound pressure level. Both at the total and spectral levels (with the exception of the low frequency bands), a reduction in sound pressure levels is observed between the source and receiving rooms, as a result of the presence of the vertical partition separating the two environments.
Figure 13 shows the frequency analysis in the time domain of the sound pressure levels prior to integration, measured in one-third octave bands in the receiving room. For the experimental measurement of RT, the sound pressure level drops of 10 dB, 20 dB and 30 dB were considered and, for each of them, the time corresponding to a 60 dB decay was obtained through linear extrapolation (EDT, RT20 and RT30, respectively). The RT value corresponds to the extrapolated time associated with the highest drop achievable. Table 5 reports the reverberation time RT as a function of frequency.
Using the VibRum Plus® software, the acquisitions were processed, and the UNI EN ISO 717-1 standard was implemented to determine the value of the index R w . Figure 14 shows the trend of the apparent airborne sound insulation trend R′ in black, and the limiting curve provided by the standard in red. At high frequencies, the figure shows that the critical coincidence frequency occurs at 1600 Hz, where a reduction in sound insulation performance is observed, followed by an attenuated increase. The R w value is provided alongside the C and Ctr values, defined by the standard as the spectral adaptation terms for high and medium-low frequencies, respectively.
The value of R w obtained from the experimental measurements is 28 dB, and since the Italian regulations on passive acoustic performance for buildings [34] prescribe a value greater than 50 dB, the result shows that the actual partition does not meet the acoustic insulation requirements.

3.2. Predictive Calculation Results

Using the Echo® software, the predictive calculation was conducted considering the vertical partition currently installed between the two rooms. Figure 15 presents the results of the term Rij as a function of the sound propagation path.
The predicted value of the apparent airborne sound insulation index R w for the vertical partition currently used to separate the two rooms was found to be 32.1 dB, which shows good agreement with the experimentally determined value of 28 dB. This confirms that the software can be effectively used to evaluate the performance of the vertical partitions under investigation.

3.3. Acoustically Insulated Wall Configurations

Table 6 presents the R w index obtained from the predictive calculations along with the total cost associated with each type of analyzed vertical partition. Figure 16 shows the breakdown of the total cost into its individual contributions for each commercial construction.
As shown, the most expensive construction is the Perfetto Special 1, mainly due to the significant cost contributions of both the masonry and the insulation layer, which also provides the best acoustic performance. Conversely, the most cost-effective construction is the Fermacell partition, which, however, fails to meet the regulatory requirements and exhibits the lowest sound insulation performance. Similarly, the FIBRAN B-040/A13—1 system does not comply with the national standard and is also more expensive than the Perfetto CG, which is the most economical among the configurations that meet regulatory limits, with an index R w of 52.5 dB. In the case of FIBRAN B-040/A13—2, which includes a double insulating layer and results in a slightly higher cost, the regulatory threshold is met, and the R w value is only 0.5 dB lower than that of the FIBRAN B-050/SUPER13 configuration. However, the cost of the latter is comparable to that of the Perfetto Special 2, while its acoustic performance is 5.4 dB lower. The Perfetto Special 2 construction, which achieves an R w value only 1.2 dB lower than the Perfetto Special 1, is less expensive due to the use of 12 cm thick concrete blocks instead of 15 cm.

3.4. Cost-Effective Insulated Walls

Similarly, for the proposed cost-effective insulated walls, Table 7 reports the results of the predicted apparent sound insulation index R w and the corresponding total cost for each construction. Figure 17 illustrates the cost breakdown for each wall type.
The results indicate that, compared to the currently installed wall, which provides a predicted index R w of 32.1 dB (with an experimentally measured value of 28 dB), the use of Wall Type A, consisting of standard uninsulated masonry, yields an acoustic performance improvement. However, it still fails to meet the regulatory requirement, achieving an index of 41.2 dB. The other three wall types exceed the minimum required value. In particular, Wall Type B, a masonry wall combined with a lining, provides the highest airborne sound insulation performance, equal to 53.8 dB. Among the configurations with an index greater than 50 dB, the most cost-effective is Wall Type C, a plasterboard partition. Wall Type D, which incorporates plywood panels, delivers a slightly higher performance of 52.7 dB, only 1.3 dB more than Wall Type C, it is the most expensive construction due to the high cost of plywood. In contrast, Wall Type C allows for a 30% cost saving relative to Wall Type B, with only a 2.4 dB reduction in the performance index. Furthermore, Wall Type C is the lightest among the proposed alternatives, with a surface mass of 51.8 kg/m2, and features a compact thickness of just 15 cm.

4. Conclusions

This study investigated the improvement in the apparent sound insulation index R w for airborne noise as a function of the wall system used to separate two indoor environments at the University of Calabria. An experimental campaign was conducted to assess the acoustic performance of the existing wall and to validate the theoretical prediction model used for evaluating alternative structural solutions. The experimental study was carried out using a Svantek 979 sound level meter (Svantek Italy, Milan, Italy) equipped with a condenser microphone and a Svantek SI 312 dodecahedral sound source. Data processing was performed using VibRum Plus® software.
The results showed that the existing wall does not comply with the minimum regulatory requirement of 50 dB, exhibiting an R w value of 28 dB. This was compared with the predicted results obtained via the Echo® software, showing good agreement. This software was subsequently used to evaluate theoretical improvements in acoustic performance achievable through the use of acoustically insulated walls with commercially available insulating materials or cost-effective insulated walls proposed in this study. For each option, a cost analysis was also carried out to identify a cost-effective construction that meets the regulatory minimum of 50 dB.
Regarding commercial systems, the best acoustic performance was associated with the Perfetto Special 1 system, which also exhibits the highest cost. Conversely, although the use of a Fermacell lining is easy to install and inexpensive, its performance index of 47.3 dB does not satisfy the regulatory limit. The Perfetto CG system achieves an index of 52.5 dB with only a 3.08% cost increase compared to the Fermacell construction.
In terms of the cost-effective insulated constructions, replacing the existing wall with Wall Type A (hollow brick masonry without acoustic insulation) represents the most economical intervention and improves the sound reduction index to 41.2 dB. However, this remains below the threshold. The remaining three wall types met the regulatory limit, with a maximum difference of 2.4 dB between Wall Type B (53.8 dB) and Wall Type C (51.4 dB). Wall Type B, a masonry construction, shows a 42.9% higher cost compared to Wall Type C, which is a plasterboard partition. Moreover, Wall Type C has the lowest surface mass among the proposed constructions. Wall Type D is the least economical due to the use of plywood panels, with a cost approximately double that of Wall Type C, offering only a 1.3 dB improvement. Comparing the commercial construction Perfetto CG with the cost-effective insulated Wall Type C reveals a marginal advantage of 1.1 dB in favor of the former, which comes at a 69.4% higher cost. In terms of weight and thickness, Wall Type C exhibits a surface mass of 51.8 kg/m2 and a thickness of 15 cm, whereas the commercial masonry system has significantly higher values of 122 kg/m2 and 22 cm, respectively.
A limitation of this study lies in the uncertainty associated with the predictive calculation model, which, despite validation against the existing wall, still requires experimental verification through real-world implementation of the proposed constructions. However, such an approach is impractical in the context of retrofitting existing environments or designing new constructions. Therefore, the presented results are of significant value in the field of building acoustics, providing technical and economic guidance for the selection of effective wall systems capable of achieving regulatory sound insulation requirements at minimized cost. Future work will involve the demolition of the current wall and the construction of the Wall Type C to evaluate its in situ performance.

Author Contributions

F.N.: Methodology, Conceptualization, Writing—review and editing. A.C.: Methodology, Conceptualization, Writing—original draft. R.B.: Formal Analysis, Writing—review and editing. D.I.: Methodology, Validation, Visualization, Software, Data Curation. V.F.: Resources, Supervision. D.K.: Conceptualization, Investigation, Supervision, Project Administration. All authors have read and agreed to the published version of the manuscript.

Funding

This research did not receive any specific grant from funding agencies in the public, commercial, or not-for-profit sectors.

Data Availability Statement

Data will be made available on request.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Łapińska, A.; Grochowska, N.; Cieplak, K.; Płatek, P.; Wood, P.; Deuszkiewicz, P.; Dużyńska, A.; Sztorch, B.; Głowcka, J.; Przekop, R.; et al. Architecture influence on acoustic performance, EMI shielding, electrical and thermal, properties of 3D printed PLA/graphite/molybdenum disulfide composites. Mater. Des. 2024, 245, 113241. [Google Scholar] [CrossRef]
  2. Arias-Cárdenas, B.; Lacasta, A.M.; Haurie, L. Bibliometric analysis of research on thermal, acoustic, and/or fire behaviour characteristics in bio-based building materials. Constr. Build. Mater. 2024, 432, 136569. [Google Scholar] [CrossRef]
  3. Llorca-Bofí, J.; Heck, J.; Dreier, C.; Vorländer, M. Urban background sounds under various weather conditions categorized for virtual acoustics. J. Environ. Manag. 2024, 371, 123081. [Google Scholar] [CrossRef]
  4. Haselhoff, T.; Schuck, M.; Lawrence, B.T.; Fiebig, A.; Moebus, S. Characterizing acoustic dimensions of health-related urban greenspace. Ecol. Indic. 2024, 166, 112547. [Google Scholar] [CrossRef]
  5. Esfandiari, M.; Mohamed Zaid, S.; Ismail, M.A.; Reza Hafezi, M.; Asadi, I.; Mohammadi, S.; Vaisi, S.; Aflaki, A. Occupants’ Satisfaction toward Indoor Environment Quality of Platinum Green-Certified Office Buildings in Tropical Climate. Energies 2021, 14, 2264. [Google Scholar] [CrossRef]
  6. Wang, X.; Li, D.; Menassa, C.C.; Kamat, V.R. Investigating the effect of indoor thermal environment on occupants’ mental workload and task performance using electroencephalogram. Build. Environ. 2019, 158, 120–132. [Google Scholar] [CrossRef]
  7. Bluyssen, P.M.; Zhang, D.; Kurvers, S.; Overtoom, M.; Ortiz-Sanchez, M. Self-reported health and comfort of school children in 54 classrooms of 21 Dutch school buildings. Build. Environ. 2018, 138, 106–123. [Google Scholar] [CrossRef]
  8. Tarrazó-Serrano, D.; Castiñeira-Ibáñez, S.; Bautista, A.S.; Rubio, C.; Uris, A. Optimization of acoustic subwavelength slit barrier to control low-frequency noise in industrial buildings. J. Build. Eng. 2025, 103, 111926. [Google Scholar] [CrossRef]
  9. Zhang, X.; Ba, M.; Kang, J.; Meng, Q. Effect of soundscape dimensions on acoustic comfort in urban open public spaces. Appl. Acoust. 2018, 133, 73–81. [Google Scholar] [CrossRef]
  10. Ren, X. Combined effects of dominant sounds, conversational speech and multisensory perception on visitors’ acoustic comfort in urban open spaces. Landsc. Urban Plan. 2023, 232, 104674. [Google Scholar] [CrossRef]
  11. Chen, K.; Kang, J.; Ma, H. Evaluation of healthy indoor acoustic environments in residential buildings by the occupants: A mixed-method approach. Build. Environ. 2023, 246, 110950. [Google Scholar] [CrossRef]
  12. Arjunan, A.; Baroutaji, A.; Robinson, J.; Vance, A.; Arafat, A. Acoustic metamaterials for sound absorption and insulation in buildings. Build. Environ. 2024, 251, 111250. [Google Scholar] [CrossRef]
  13. Shtrepi, L.; Prato, A. Towards a sustainable approach for sound absorption assessment of building materials: Validation of small-scale reverberation room measurements. Appl. Acoust. 2020, 165, 107304. [Google Scholar] [CrossRef]
  14. Chen, S.; Chen, Q.; Fan, H.; Liu, L.; Yan, Z.; Chen, Y.; Luo, L.; Li, J. Lightweight, strong, and sound insulation bio-based structural material from discarded coconut wood. Constr. Build. Mater. 2025, 458, 139765. [Google Scholar] [CrossRef]
  15. Mehrzad, S.; Taban, E.; Soltani, P.; Samaei, S.E.; Khavanin, A. Sugarcane bagasse waste fibers as novel thermal insulation and sound-absorbing materials for application in sustainable buildings. Build. Environ. 2022, 211, 108753. [Google Scholar] [CrossRef]
  16. Li, K.; Dauchez, N.; Nennig, B. A metaporoelastic structure that overcomes the sound insulation weaknesses of single and double panel partitions. Appl. Acoust. 2023, 210, 109409. [Google Scholar] [CrossRef]
  17. Júnior, O.J.S.; Pinheiro, M.A.S.; Silva, J.J.R.; Pires, T.A.C.; Alencar, C.O.S. Sound insulation of gypsum block partitions: An analysis of single and double walls. J. Build. Eng. 2021, 39, 102253. [Google Scholar] [CrossRef]
  18. Araújo Alves, J.; Neto Paiva, F.; Torres Silva, L.; Remoaldo, P. Low-Frequency Noise and Its Main Effects on Human Health—A Review of the Literature between 2016 and 2019. Appl. Sci. 2020, 10, 5205. [Google Scholar] [CrossRef]
  19. Pawlaczyk-Luszczyńska, M.; Szymczak, W.; Dudarewicz, A.; Sliwińska-Kowalska, M. Proposed criteria for assessing low frequency noise annoyance in occupational settings. Int. J. Occup. Med. Environ. Health 2006, 19, 185–197. [Google Scholar] [CrossRef] [PubMed]
  20. Van Kempen, E.; Casas, M.; Pershagen, G.; Foraster, M. WHO Environmental Noise Guidelines for the European Region: A Systematic Review on Environmental Noise and Cardiovascular and Metabolic Effects: A Summary. Int. J. Environ. Res. Public Health 2018, 15, 379. [Google Scholar] [CrossRef]
  21. Martellotta, F. Innovative Composite Materials for Sound Absorption and Insulation: Where We Are and Where We Are Going. Materials 2021, 14, 1954. [Google Scholar] [CrossRef] [PubMed]
  22. Moravec, M.; Pinosova, M.; Badida, M.; Izarikova, G.; Badidova, M. Analysis of the Acoustic Parameters of Building Partition Structures of Varying Composition. Buildings 2024, 14, 2440. [Google Scholar] [CrossRef]
  23. Qu, T.; Wang, B.; Min, H. Lightweight Composite Partitions with High Sound Insulation in Hotel Interior Spaces: Design and Application. Buildings 2022, 12, 2184. [Google Scholar] [CrossRef]
  24. Tao, Y.; Ren, M.; Zhang, H.; Peijs, T. Recent progress in acoustic materials and noise control strategies—A review. Appl. Mater. Today 2021, 24, 101141. [Google Scholar] [CrossRef]
  25. Zhao, C.; Prasad, M.G. Acoustic Black Holes in Structural Design for Vibration and Noise Control. Acoustics 2019, 1, 220–251. [Google Scholar] [CrossRef]
  26. Oyelade, A.O.; Akano, T.T.; Odesanmi, G.A. Enhancing the sound transmission loss in double-leaf partitions with lateral local resonators substructure. Adv. Mech. Eng. 2022, 14, 1–10. [Google Scholar] [CrossRef]
  27. Caniato, M.; Bettarello, F.; Gasparella, A. Energy and Acoustic Performances of Timber in Buildings. Encycl. Renew. Sustain. Mater. 2018, 2, 78–91. [Google Scholar] [CrossRef]
  28. Caniato, M.; Bettarello, F.; Schmid, C.; Fausti, P. The use of numerical models on service equipment noise prediction in heavyweight and lightweight timber buildings. Build. Acoust. 2018, 26, 35–55. [Google Scholar] [CrossRef]
  29. Caniato, M.; Bettarello, F.; Ferluga, A.; Marsich, L.; Schmid, C.; Fausti, P. Acoustic of lightweight timber buildings: A review. Renew. Sustain. Energy Rev. 2017, 80, 585–596. [Google Scholar] [CrossRef]
  30. Secchi, S.; Asdrubali, F.; Cellai, G.; Nannipieri, E.; Rotili, A.; Vannucchi, I. Experimental and environmental analysis of new sound-absorbing and insulating elements in recycled cardboard. J. Build. Eng. 2016, 5, 1–12. [Google Scholar] [CrossRef]
  31. Yang, F.; Cao, Y.; Wu, M.; Albu, F.; Yang, J. Frequency-Domain Filtered-x LMS Algorithms for Active Noise Control: A Review and New Insights. Appl. Sci. 2018, 8, 2313. [Google Scholar] [CrossRef]
  32. TEP s.r.l., ECHO 8. ANIT, Via Lanzone, 31-20123 Milano. Available online: https://www.anit.it/echo (accessed on 10 February 2025).
  33. Zarastvand, M.; Ghassabi, M.; Talebitooti, R. Prediction of acoustic wave transmission features of the multilayered plate constructions: A review. J. Sandw. Struct. Mater. 2022, 24, 218–293. [Google Scholar] [CrossRef]
  34. Presidenza del Consiglio dei Ministri. DPCM 5 Dicembre 1997: Determinazione dei Requisiti Acustici Passivi Degli Edifici, Serie Generale n. 297. 22 December 1997. Available online: https://www.gazzettaufficiale.it/eli/id/1997/12/22/97A10190/sg (accessed on 1 February 2025).
  35. EN ISO 16283-1:2014; Acoustics—Field Measurement of Sound Insulation in Buildings and of Building Elements—Part 1: Airborne Sound Insulation. UNI: Milan, Italy, 2014.
  36. EN ISO 717-1:2013; Acoustics—Rating of Sound Insulation in Buildings and of Building Elements—Part 1: Airborne Sound Insulation. UNI: Milan, Italy, 2013.
  37. Svantek Italia. VibRum Plus—Software Modulare per Elaborazione dati Acustici. Available online: https://www.svantek.it/category/prodotti-rumore-vibrazioni/software/ (accessed on 1 February 2025).
  38. EN ISO 12354-1:2017; Building Acoustics—Estimation of Acoustic Performance of Buildings from the Performance of Elements—Part 1: Airborne Sound Insulation Between Rooms. UNI: Milan, Italy, 2017.
  39. Catalog Isolmant. Available online: https://www.isolmant.com/it/prodotti/rumore-aereo/isolamento-pareti-con-intercapedine/ (accessed on 10 February 2025).
  40. FIBRANgyps—500 Dry Construction Systems—Catalog. Available online: https://fibran.it/wp-content/uploads/sites/2/2020/10/FIBRANgyps-catalogo-500-sistemi-a-secco.pdf (accessed on 10 February 2025).
  41. Fermacell Catalog—Gypsum-Fibre Board. Available online: https://www.fermacell.it/it/prodotti/lastre-in-gessofibra-fermacell/lastra-gessofibra (accessed on 10 February 2025).
  42. Isolmant—Pricing Catalog. Available online: https://www.isolmant.com/it/download/listini (accessed on 1 March 2025).
  43. “FIBRAN—Pricing Catalog,” 2025. Available online: https://fibran.it/downloads/listino-prezzi (accessed on 1 March 2025).
  44. Fermacell Gypsum-Fibre Pricing. Available online: https://edilcommerce.com/67-fermacell (accessed on 1 March 2025).
  45. Rockwool—Pricing Catalog 2025. Available online: https://www.rockwool.com/it/download-strumenti/listini (accessed on 1 March 2025).
Figure 1. Case study environment.
Figure 1. Case study environment.
Buildings 15 03753 g001
Figure 2. Receiving room.
Figure 2. Receiving room.
Buildings 15 03753 g002
Figure 3. Source room.
Figure 3. Source room.
Buildings 15 03753 g003
Figure 4. Svantek dodecahedral loudspeaker and Svantek 979 integrating sound level meter.
Figure 4. Svantek dodecahedral loudspeaker and Svantek 979 integrating sound level meter.
Buildings 15 03753 g004
Figure 5. (a) Isolmant Perfetto Special (b) Isolmant Perfetto CG.
Figure 5. (a) Isolmant Perfetto Special (b) Isolmant Perfetto CG.
Buildings 15 03753 g005
Figure 6. Schematic representation of the metal support.
Figure 6. Schematic representation of the metal support.
Buildings 15 03753 g006
Figure 7. Additional partition produced by Fermacell.
Figure 7. Additional partition produced by Fermacell.
Buildings 15 03753 g007
Figure 8. Characteristics of the vertical partition and building components as installed on-site.
Figure 8. Characteristics of the vertical partition and building components as installed on-site.
Buildings 15 03753 g008
Figure 9. Joint characteristics.
Figure 9. Joint characteristics.
Buildings 15 03753 g009
Figure 10. Spectral and total equivalent sound pressure levels in the source room.
Figure 10. Spectral and total equivalent sound pressure levels in the source room.
Buildings 15 03753 g010
Figure 11. Spectral and total equivalent sound pressure levels in the receiving room.
Figure 11. Spectral and total equivalent sound pressure levels in the receiving room.
Buildings 15 03753 g011
Figure 12. Spectral and total background noise in the receiving room.
Figure 12. Spectral and total background noise in the receiving room.
Buildings 15 03753 g012
Figure 13. Time-domain frequency analysis of sound pressure measured in the receiving room.
Figure 13. Time-domain frequency analysis of sound pressure measured in the receiving room.
Buildings 15 03753 g013
Figure 14. Apparent airborne sound insulation trend R′ and determination of the R w index.
Figure 14. Apparent airborne sound insulation trend R′ and determination of the R w index.
Buildings 15 03753 g014
Figure 15. Sound insulation index as a function of the sound propagation path in the case of the partition currently installed between the two rooms.
Figure 15. Sound insulation index as a function of the sound propagation path in the case of the partition currently installed between the two rooms.
Buildings 15 03753 g015
Figure 16. Cost breakdown for each proposed commercial wall configuration.
Figure 16. Cost breakdown for each proposed commercial wall configuration.
Buildings 15 03753 g016
Figure 17. Cost breakdown for each cost-effective insulated wall.
Figure 17. Cost breakdown for each cost-effective insulated wall.
Buildings 15 03753 g017
Table 1. Main characteristics of the wall configurations using Isolmant materials.
Table 1. Main characteristics of the wall configurations using Isolmant materials.
Wall TypeThickness (m)Insulation Thickness
(m)
Superficial Mass (kg/m2)Total Area
(m2)
Rw
(dB)
Perfetto Special 10.300.03017029.567
Perfetto Special 20.260.03016029.563
Perfetto CG0.220.04512229.555
Table 2. Main characteristics of the wall configurations using FIBRAN materials.
Table 2. Main characteristics of the wall configurations using FIBRAN materials.
Wall TypeThickness (m)Insulation Thickness
(m)
Superficial Mass
(kg/m2)
Total Area
(m2)
Rw
(dB)
FIBRAN B-040/A13—10.100.0438.629.551
FIBRAN B-050/SUPER130.130.0553.329.559
FIBRAN B-040/A13—20.180.0840.329.562
Table 3. Main characteristics of the novel configurations.
Table 3. Main characteristics of the novel configurations.
Wall TypeThickness (m)Insulation Thickness
(m)
Superficial Mass
(kg/m2)
Total Area
(m2)
Rw
(dB)
A0.120.00118.029.541.4
B0.200.05130.729.541.4
C0.150.0551.829.559.3
D0.160.0567.029.561.5
Table 4. Costs per square meter for the analyzed partition walls.
Table 4. Costs per square meter for the analyzed partition walls.
Wall TypeCost (€/m2)
Perfetto Special 1168.9
Perfetto Special 2147.5
Perfetto CG111.7
FIBRAN B-040/A13—1115.6
FIBRAN B-050/SUPER13147.15
FIBRAN B-040/A13—2 122.92
Fermacell54.2
A51.81
B94.2
C65.9
D142.6
Table 5. Reverberation time measurements.
Table 5. Reverberation time measurements.
Frequency (Hz)EDT (s)RT20 (s)RT30 (s)RT (s)
1000.8010.637-0.637
1251.2180.6060.5110.511
1601.0090.7820.7970.797
2000.4580.7960.6850.685
2500.8430.7590.7130.713
3150.6200.6360.7080.708
4000.4820.5820.5920.592
5000.4850.6400.6790.679
6300.5770.4340.5260.526
8000.3940.4820.5610.561
10000.4100.4660.4920.492
12500.4590.4610.4660.466
16000.4150.4270.4160.416
20000.4140.4180.4360.436
25000.4600.4430.4930.493
31500.3910.4910.4900.490
Table 6. Predicted apparent airborne sound insulation index and total cost for each commercial wall configuration.
Table 6. Predicted apparent airborne sound insulation index and total cost for each commercial wall configuration.
Wall Type R w
(dB)
Total Cost (€)
Perfetto Special 158.05068.0
Perfetto Special 256.84424.6
Perfetto CG52.53350.8
FIBRAN B-040/A13—147.93468.3
FIBRAN B-050/SUPER1351.44414.5
FIBRAN B-040/A13—250.93687.6
Fermacell47.33250.6
Table 7. Predicted apparent airborne sound insulation index and total cost for the proposed cost-effective insulated walls.
Table 7. Predicted apparent airborne sound insulation index and total cost for the proposed cost-effective insulated walls.
Wall Type R w (dB)Total Cost (€)
A41.21554.3
B53.82826.4
C51.41977.7
D52.74276.7
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Nicoletti, F.; Cristaudo, A.; Bruno, R.; Iorio, D.; Ferraro, V.; Kaliakatsos, D. Measurement and Prediction of Airborne Sound Insulation Performance of Different Vertical Partition Walls in Indoor Environments: A Case Study. Buildings 2025, 15, 3753. https://doi.org/10.3390/buildings15203753

AMA Style

Nicoletti F, Cristaudo A, Bruno R, Iorio D, Ferraro V, Kaliakatsos D. Measurement and Prediction of Airborne Sound Insulation Performance of Different Vertical Partition Walls in Indoor Environments: A Case Study. Buildings. 2025; 15(20):3753. https://doi.org/10.3390/buildings15203753

Chicago/Turabian Style

Nicoletti, Francesco, Antonio Cristaudo, Roberto Bruno, Danilo Iorio, Vittorio Ferraro, and Dimitrios Kaliakatsos. 2025. "Measurement and Prediction of Airborne Sound Insulation Performance of Different Vertical Partition Walls in Indoor Environments: A Case Study" Buildings 15, no. 20: 3753. https://doi.org/10.3390/buildings15203753

APA Style

Nicoletti, F., Cristaudo, A., Bruno, R., Iorio, D., Ferraro, V., & Kaliakatsos, D. (2025). Measurement and Prediction of Airborne Sound Insulation Performance of Different Vertical Partition Walls in Indoor Environments: A Case Study. Buildings, 15(20), 3753. https://doi.org/10.3390/buildings15203753

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop