1. Introduction
Stator winding single-phase ground fault is one of the most common faults of large generators [
1]. The large ground fault current produces arc and burns the stator iron core. The lamination of the iron core is sintered together, resulting in maintenance difficulties. Moreover, the ground fault current also destroys the winding insulation and expands the accident. If not effectively suppressed and protected, the single-phase ground fault may develop into a turn-to-turn or phase-to-phase short-circuit fault, which may cause serious damage to the generator [
2,
3]. In order to reduce the damage and ensure the safe operation of the generator, a reliable ground fault protection method, a suitable neutral grounding mode, effective arc suppression, and an elimination method are the key problems that have attracted a lot of attention by scholars.
At present, the fundamental zero-sequence voltage criterion [
4], third-harmonic voltage criterion [
5], and low-frequency injection protection criterion [
6] are mainly used as the generator stator ground fault protection. The above protection criterion can accurately detect ground faults and isolate the generator from the system to avoid further damage. However, under some cases of minor fault degree, tripping the generator blindly and quickly is not suitable. The sustainable power supply of the system is destroyed, and it is easy to cause large-scale power outage accidents. In addition, for serious ground faults, the residual magnetic field in the stator windings remains for a long time after the generator exciting current drops to zero. Thus, the ground fault current does not disappear and the safety of the stator iron core cannot be guaranteed. Therefore, the fault current should be suppressed to reduce the safety threat.
Generators generally adopt the neutral grounding mode of ungrounded [
7], grounding through the arc-suppression coil [
8], and grounding through high resistance [
9]. For a generator with an ungrounded neutral point, high transient overvoltage is easily caused under single-phase ground faults [
10], which destroy the insulation of the stator windings. Thus, it is rarely used in large generators. Compared with the ungrounded mode, the high-resistance grounding mode increases the resistance component in the fault current, which cannot suppress the fault current. The arc-suppression coil-grounding mode can generate inductive current after ground faults and compensate the capacitive components in the fault current [
11]. It plays a positive role in restraining the fault current and preventing the fault from spreading. However, it cannot supplement the harmonic components in the fault current, and the residual current can still maintain the arc burning after compensation [
12]. Practical operation experience shows that none of the classical grounding mode can achieve reliable arc elimination, and it is still necessary to trip the generator under severe ground faults.
To achieve effective ground fault current suppression and avoid arc ignition, an active arc suppression method is proposed in the literature [
13]. By controlling the fault point voltage lower than the arc reignition voltage with an external injected source, the arc suppression can be reliably achieved. Since the phase potential of the generator stator contains a certain amount of third-harmonic potential [
14,
15], the dual-frequency active arc-suppression algorithm is adopted. However, the method in the literature [
13] is applied to a small generator, and the generator neutral point is still grounded through the resistance in the arc-suppression process. As a result, most of the injected power from the active arc-suppression device is consumed by the grounding resistance. Large generators have a high voltage grade and the large capacitive current to ground [
16,
17]. If the active arc-suppression device is applied in practical engineering, it needs a large-capacity inverter. It is large in volume and costs a lot, which makes it difficult to widely promote.
To reduce the capacity of the inverter, a hybrid flexible neutral grounding method is proposed in this paper, which combines the dual-frequency active arc-suppression device with the arc-suppression coil-grounding mode. The arc-suppression coil can compensate for most of the fundamental components in the ground fault current, whereas the active arc-suppression device only compensates for the third-harmonic components and a small part of the fundamental components. Therefore, the capacity of the inverter can be greatly reduced, and only 20 kVA can meet the requirements of arc extinguishing. After arc suppression, to identify the transient and permanent ground faults, a fault-type identification criterion is proposed based on the phase-angle difference between the third-harmonic voltage and current variation at the generator neutral point. The third-harmonic quantities can avoid the blind area at the neutral point caused by the fundamental quantities. Simulation and dynamic experimental test results show that the proposed method is not affected by the fault scenario, generator operation mode, and generator excitation regulation, which can realize reliable arc suppression and fault-type identification.
3. Fault-Type Identification Method Based on Third-Harmonic Quantities
When the hybrid flexible neutral grounding mode is adopted, the arc can be eliminated and the fault current can be suppressed during single-phase ground faults. As for the instantaneous faults, the insulation of the stator windings can be recovered and the generator can be restored to the normal operating state. As for the permanent faults, after tripping the dual-frequency active arc-suppression device, the voltage at the fault point recovers and the winding insulation is broken down again. Then, the ground-fault current is regenerated, which may further damage the insulation of the generator. As a result, after the arc suppression is realized, it is necessary to distinguish transient and permanent grounding faults with effective fault-type identification strategies.
For ground faults near the neutral side of the stator winding, the fault current is mainly composed of the third-harmonic quantities. For a ground fault at the neutral point, the fault current contains only the third-harmonic component, not the fundamental component [
2]. In addition, for the hybrid flexible grounding mode, the arc-suppression coil compensates for most of the fundamental component of the fault current, so if the fundamental quantities are used for fault-type identification, there is a blind area near the neutral side and the sensitivity is low. Therefore, in this paper, the third-harmonic quantities are used to identify the fault type.
In the literature [
2], it is pointed out that the variation of third-harmonic voltage at any point in the generator stator windings is equal to the third-harmonic voltage variation at the neutral point. When the third-harmonic voltage applied to the neutral point is reduced, it is assumed that the voltage variation is ∆
Ui3. At this point, for instantaneous faults, the change of third-harmonic current ∆
In3s of the neutral line is:
For a permanent ground fault, due to the insulation voltage recovery at the fault point, the arc re-ignites. At this time, in addition to the capacitive current to the ground, the current through the neutral line includes the resistive current flowing through the fault resistance. The third-harmonic current variation ∆
In3y of the neutral line is:
Comparing Equations (6) and (7), the phasor diagram of the third-harmonic current variation after adjusting the third-harmonic voltage at the neutral point under different fault types is shown in
Figure 4.
After changing the injected third-harmonic voltage, the fault-type identification can be realized by identifying whether the neutral current contains the resistive component. At present, in the ground-fault protection of large generators, the setting value of the fault-resistance criterion is usually set as 4 kΩ. It can be considered that the maximum value of
Rg in Equation (7) is 4 kΩ. Based on the grounding capacitance parameters of the presented large generator in
Section 3, the maximum phase-angle difference between ∆
In3y and ∆
Ui3 is 83.73°. Considering a certain margin, based on the phase-angle difference between ∆
In3 and ∆
Ui3 under different fault types, the fault-type identification criterion is constructed as follows:
After the fault-type identification is realized, the dual-frequency active arc-suppression device can be tripped under the instantaneous fault conditions and the normal operation of the generator should be restored. For permanent fault conditions, the output voltage of the dual-frequency active arc suppression device should be restored to the initial value. Then, the loads should be smoothly transferred before the generator is tripped from the system. Thus, large-scale power failure can be avoided.
5. Dynamic Test Verification
The quasi-distributed parameter model could only reflect the structural characteristics of the generator stator windings, but could not reflect the demagnetization effect of the load to the generator potential and the excitation regulation characteristics of the generator. Therefore, it could only be verified that the proposed method was effective under the no-load operation. However, it could not be verified that the proposed method was suitable for different operating conditions. To fully verify the effectiveness of the proposed method, experimental tests were carried out on a dynamic model generator. The capacity of the generator was 15 kVA, and the rated voltage was 400 V. It adopted the arc-suppression coil neutral grounding mode, and the compensation degree was 10%. A programmable AC power source was used to simulate the dual-frequency active arc suppression device. It could output voltages of different frequencies at the same time. The voltage amplitude adjustment range was 0~300 V, the phase-adjustment range was −180°~+180°, and the frequency-adjustment range was 15~1600 Hz. The experimental system could be used to verify the hybrid flexible grounding method.
The wiring diagram of the dynamic experimental system is shown in
Figure 6, and the photo is shown in
Figure 7.
Taking the single-phase ground fault at the generator terminal of the A-phase as an example, the fault potential was equal to the A-phase potential. Under the no-load operation condition, the fundamental and third-harmonic phase potentials were measured online. Based on Fourier transform, the amplitudes and phase angles were 222.69 V∠−44.25° and 2.91 V∠123.75°, respectively. The output voltage of the programmable AC power supply were set to be equal in amplitude and opposite in phase to the fault potential. During the experimental test process, the switch KD between the generator terminal and the sliding-line resistor was used to set the ground fault, and the switch KY between the programmable AC power supply and the generator neutral point was used to input the dual-frequency active arc-suppression device. The resistance of the sliding-line resistor was regulated to 200 Ω. In this process, the waveforms of the fault-point voltage and the ground-fault current are shown in
Figure 8a.
After putting in the dual-frequency active arc-suppression device, the fault-point voltage was reduced to 0.14 V and the fault current was suppressed to 0. Due to the neutral voltage regulation, the non-fault phase voltage at the generator terminal rose to the line voltage. Since the system insulation is usually designed according to the line voltage level, it did not affect the insulation safety. The experiment was repeated under the load conditions of 50% and 100%. Under the 50% load condition, influenced by the load demagnetization and the excitation regulation, the amplitudes and phase angles of the fundamental and third-harmonic phase potentials changed to 239.05 V∠−17.12° and 4.76 V∠−163.18°, respectively. Under the 100% load condition, the amplitudes and phase angles of the fundamental and the third-harmonic phase potentials were 230.16 V∠−26.25° and 7.28 V∠101.25°, respectively. The output voltage of the programmable AC power supply was set with equal amplitude and the opposite phase of the phase potential, and the arc-suppression results are shown in
Figure 8b,c. The test results show that the proposed method was not affected by the operating conditions and the generator excitation regulation.
To verify the effectiveness of the proposed fault-type identification method under different operating conditions, after the completion of arc suppression, the injected fundamental voltage was controlled unchanged, and the injected third-harmonic voltage was changed to make its amplitude half of before. For instantaneous faults, before changing the injected voltage, the switch KD was cut off, so the faulty branch was removed. For permanent faults, the faulty branch was always reserved. Corresponding to different load conditions, Fourier transform was used to calculate the phase-angle difference between ∆
In3 and ∆
Ui3. The calculation results are shown in
Table 6.
In
Table 6, the phase-angle differences of the phasors were solved by Fourier transform. The experimental calculation results shown in
Table 6 show that the phase-angle difference between ∆
In3 and ∆
Ui3 was approximately 90° under transient fault conditions, which meets the criterion of Equation (8). However, the criterion of Equation (8) was not satisfied under the condition of permanent faults. The proposed method can effectively identify the transient and permanent ground faults without being affected by the load condition and excitation regulation.