Feasibility of Reducing Electricity Consumption of Air Conditioning Equipment by Condenser Direct Evaporative Cooling Technology. Example of Case Study in Dubai
Abstract
:1. Introduction
2. Materials and Methods
2.1. Analysis of the Evaporative Cooling System Efficiency in Real Conditions
2.1.1. System Description
- Chiller electricity consumption;
- Chiller cooling output;
- Hourly external dry-bulb air temperature hourly external relative humidity.
2.1.2. Description of System Tests
2.1.3. Testing Procedures
- Test No. 1: Chiller electricity energy test 4 Days “Off”/4 Days “On”–direct evaporative cooling system comparison
- Test No. 2: Chiller electricity energy test 7 Days “Off”/7 Days “On” and Test No. 3: Chiller electricity energy test 13 Days “Off”/13 Days “On”–direct evaporative cooling system comparison.
- Test No. 4: compressor COP test, test duration: 2 h
2.2. Analysis of the Dependence of the System Efficiency on the Inlet Water Temperature
2.2.1. Case A
2.2.2. Case B
- hair = 11.030 (kg/h) × 96 (kJ/kg) = 1058 MJ/h,
- therefore water entalpy at 20 °C
- = 83 KJ/kg and at 40 °C
- = 167.5 KJ/kg.
3. Results
4. Discussion
5. Conclusions
- The electricity consumption of the X chiller equipped with the direct evaporative cooling system consumes, on average during a 1-day test, approximately 1935 kWh, which comes out to 472 MWh per year. Without direct evaporative cooling system, the average chiller electricity consumption during a 1-day test is around 2766 kWh which results in 675 MWh per year. Therefore, the average energy savings will be 203 MWh annually, if the operation period of the tested compressor is 100% of the air-conditioning duration with direct evaporative cooling system switched on. For the examined case the operation period was 60%, which results in average energy savings of around 122 MWh annually.
- When the inlet water temperature was below the wet bulb temperature, an increase in the air to water mass ratio was observed. According to the calculations, it was concluded that the decrease of the inlet water temperature did not cause significant changes in the heat balance of the system.
- The expected ROI period of such system is 4.2 years.
Author Contributions
Funding
Institutional Review Board Statement
Data Availability Statement
Acknowledgments
Conflicts of Interest
Nomenclature
evaporation, kJ/kg | |
inlet water enthalpy, kJ/kg | |
water flow rate, kg/h | |
air mass flow rate, kg/h | |
specific enthalpy, kJ/kg | |
RH | relative humidity, % |
Tair | air temperature, °C |
TDB | dry bulb temperature, °C |
Tinwater | inlet water temperature, °C |
TWB | wet bulb temperature, °C. |
Vair | air volume, m3/h |
ρ | density of air, kg/m3 |
References
- Delmastro, C.; Abergel, T. Is Cooling the Future of Heating?—Analysis—IEA. Available online: https://www.iea.org/commentaries/is-cooling-the-future-of-heating (accessed on 11 September 2021).
- Cooling as a Service (CaaS). The Global Innovation Lab for Climate Finance. Available online: https://www.climatefinancelab.org/project/cooling-service/ (accessed on 11 September 2021).
- Martin, A. Chart: Air Conditioning Biggest Factor in Growing Electricity Demand Statista. Available online: https://www.statista.com/chart/14401/growing-demand-for-air-conditioning-and-energy/ (accessed on 11 September 2021).
- European Commission: Clean Energy for all Europeans. 2019. Available online: https://ec.europa.eu/info/news/clean-energy-all-europeans-package-completed-good-consumers-good-growth-and-jobs-and-good-planet-2019-may-22_en (accessed on 11 September 2021).
- Sousa, A.; Aguilar-Alba, M.; García-Barrón, L. Climate Change, Aquatic Ecosystems and Human Infectious Diseases in a Globalised World. Atmosphere 2021, 12, 653. [Google Scholar] [CrossRef]
- Kim, S.H.; Yoon, Y.R.; Kim, J.W.; Moon, H.J. Novel integrated and optimal control of indoor environmental devices for thermal comfort using double deep q-network. Atmosphere 2021, 12, 629. [Google Scholar] [CrossRef]
- Zajacs, A.; Borodiņecs, A.; Bogdanovičs, R. Assessment of the efficiency and reliability of the district heating systems within different development scenarios. In Smart Innovation, Systems and Technologies; Springer: Singapore, 2020. [Google Scholar] [CrossRef]
- Palomba, V.; Varvagiannis, E.; Karellas, S.; Frazzica, A. Hybrid Adsorption-Compression Systems for Air Conditioning in Efficient Buildings: Design through Validated Dynamic Models. Energies 2019, 12, 1161. [Google Scholar] [CrossRef] [Green Version]
- Hu, S.; Yan, D.; Qian, M. Using bottom-up model to analyze cooling energy consumption in China’s urban residential building. Energy Build. 2019, 202, 109352. [Google Scholar] [CrossRef]
- Ketwong, W.; Deethayat, T.; Kiatsiriroat, T. Performance enhancement of air conditioner in hot climate by condenser cooling with cool air generated by direct evaporative cooling. Case Stud. Therm. Eng. 2021, 26, 101127. [Google Scholar] [CrossRef]
- Yang, J.; Chan, K.T.; Wu, X.; Yu, F.W.; Yang, X. An analysis on the energy efficiency of air-cooled chillers with water mist system. Energy Build. 2012, 55, 273–284. [Google Scholar] [CrossRef]
- Huang, C.N.; Ye, Y.H. Development of a water-mist cooling system: A 12,500 Kcal/h air-cooled chiller. Energy Rep. 2015, 1, 123–128. [Google Scholar] [CrossRef] [Green Version]
- Yang, J.; Chan, K.T.; Wu, X.S. Experimental studies of energy performance of air-cooled chillers with water mist system. In Proceedings of the 2nd International Postgraduate Conference on Infrastructure and Environment, IPCIE 2010, Hong Kong, China, 1–2 June 2010. [Google Scholar]
- Yang, J.; Chan, K.T.; Wu, X. Application of water mist pre-cooling on the air-cooled chillers. Proceedings of IBPSA 2009-International Building Performance Simulation Association 2009, Glasgow, UK, 27–30 July 2009. [Google Scholar]
- Sarbu, I.; Adam, M. Experimental and numerical investigations of the energy efficiency of conventional air conditioning systems in cooling mode and comfort assurance in office buildings. Energy Build. 2014, 85, 45–58. [Google Scholar] [CrossRef]
- Andrade, C.; Mourato, S.; Ramos, J. Heating and Cooling Degree-Days Climate Change Projections for Portugal. Atmosphere 2021, 12, 715. [Google Scholar] [CrossRef]
- Gyilbag, A.; Amou, M.; Tulcan, R.X.S.; Zhang, L.; Demelash, T.; Xu, Y. Characteristics of Enhanced Heatwaves over Tanzania and Scenario Projection in the 21st Century. Atmosphere 2021, 12, 1026. [Google Scholar] [CrossRef]
- Yu, F.W.; Chan, K.T. Improved energy performance of air-cooled chiller system with mist pre-cooling Mist improvement on air-cooled chillers. Appl. Therm. Eng. 2011, 31, 537–544. [Google Scholar] [CrossRef]
- Abaranji, S.; Panchabikesan, K.; Ramalingam, V. Experimental study on the direct evaporative air-cooling system with vermicompost material as the water storage medium. Sustain. Cities Soc. 2021, 71, 102991. [Google Scholar] [CrossRef]
- Cui, Y.; Zhu, J.; Zoras, S.; Liu, L. Review of the recent advances in dew point evaporative cooling technology: 3E (energy, economic and environmental) assessments. Renew. Sustain. Energy Rev. 2021, 148, 111345. [Google Scholar] [CrossRef]
- Kumar, S.; Salins, S.S.; Reddy, S.V.K.; Nair, P.S. Comparative performance analysis of a static & dynamic evaporative cooling pads for varied climatic conditions. Energy 2021, 233, 121136. [Google Scholar] [CrossRef]
- Shahzad, K.; Sultan, M.; Bilal, M.; Ashraf, H.; Farooq, M.; Miyazaki, T.; Sajjad, U.; Ali, I.; Hussain, M.I. Experiments on energy-efficient evaporative cooling systems for poultry farm application in Multan (Pakistan). Sustainability 2021, 13, 2836. [Google Scholar] [CrossRef]
- Ashraf, H.; Sultan, M.; Shamshiri, R.R.; Abbas, F.; Farooq, M.; Sajjad, U.; Md-Tahir, H.; Mahmood, M.H.; Ahmad, F.; Taseer, Y.R.; et al. Dynamic evaluation of desiccant dehumidification evaporative cooling options for greenhouse air-conditioning application in multan (Pakistan). Energies 2021, 14, 1097. [Google Scholar] [CrossRef]
- Ndukaife, T.A.; Nnanna, A.G.A. Enhancement of Performance and Energy Efficiency of Air Conditioning System Using Evaporatively Cooled Condensers. Heat Transf. Eng. 2019, 40, 375–387. [Google Scholar] [CrossRef]
- ASHRAE. ANSI/ASHRAE Standard 55-2017: Thermal Environmental Conditions for Human Occupancy. 2017. Available online: https://webstore.ansi.org/Standards/ASHRAE/ANSIASHRAE552020?source=blog&_ga=2.28042556.1409240200.1631498293-1225420834.1631498293 (accessed on 11 September 2021).
- Sajjad, U.; Abbas, N.; Hamid, K.; Abbas, S.; Hussain, I.; Ammar, S.M.; Sultan, M.; Ali, H.M.; Hussain, M.; Rehman, T.; et al. A review of recent advances in indirect evaporative cooling technology. Int. Commun. Heat Mass Transf. 2021, 122, 105140. [Google Scholar] [CrossRef]
- Martínez, P.; Ruiz, J.; Martín, Í.; Lucas, M. Experimental study of an ultrasonic mist generator as an evaporative cooler. Appl. Therm. Eng. 2020, 181, 116057. [Google Scholar] [CrossRef]
- Shanks, K.; Nezamifar, E. Impacts of climate change on building cooling demands in the UAE. In Proceedings of the SB13 Dubai: Advancing the Green Agenda Technology, Practices and Policies, Dubai, United Arab Emirates, 8–10 December 2013; Volume 80. [Google Scholar]
- Mirkovic, M.; Alawadi, K. The effect of urban density on energy consumption and solar gains: The study of Abu Dhabi’s neighborhood. Energy Procedia 2017, 143, 277–282. [Google Scholar] [CrossRef]
- Shelquist, R. Shelquist Engineering. Equations—Air Density and Density Altitude. Available online: https://wahiduddin.net/calc/density_altitude.htm (accessed on 11 September 2021).
- Malli, A.; Seyf, H.R.; Layeghi, M.; Sharifian, S.; Behravesh, H. Investigating the performance of cellulosic evaporative cooling pads. Energy Convers. Manag. 2011, 52, 2598–2603. [Google Scholar] [CrossRef]
Test | The Direct Evaporative Cooling System Status | Electricity Consumption (kWh) | Water Consumption (m3) |
---|---|---|---|
No. 1:4 days | Off On | 11,057 7740 | 11.04 |
No. 2:7 days | Off On | 16,536 12,071 | 20.04 |
No. 3:13 days | Off On | 27,593 20,295 | 36.40 |
Direct Evaporative System Status | Average Consumption per Year 1 | Price, EUR | Price, EUR | Savings | |||
---|---|---|---|---|---|---|---|
Electricity, kWh | Water, m | Electricity 2 | Water 2 | Electricity, kWh | EUR | ||
OFF | 675,000 | 70,878.30 | 70,878.30 | ||||
ON | 472,000 | 673 | 49,516.68 | 1769.80 | 51,286.48 | 20,3000 | 21,209.90 |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2021 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Borodinecs, A.; Lebedeva, K.; Prozuments, A.; Brahmanis, A.; Grekis, A.; Zajecs, D.; Zekunde, A.; Vatin, N. Feasibility of Reducing Electricity Consumption of Air Conditioning Equipment by Condenser Direct Evaporative Cooling Technology. Example of Case Study in Dubai. Atmosphere 2021, 12, 1205. https://doi.org/10.3390/atmos12091205
Borodinecs A, Lebedeva K, Prozuments A, Brahmanis A, Grekis A, Zajecs D, Zekunde A, Vatin N. Feasibility of Reducing Electricity Consumption of Air Conditioning Equipment by Condenser Direct Evaporative Cooling Technology. Example of Case Study in Dubai. Atmosphere. 2021; 12(9):1205. https://doi.org/10.3390/atmos12091205
Chicago/Turabian StyleBorodinecs, Anatolijs, Kristina Lebedeva, Aleksejs Prozuments, Arturs Brahmanis, Aldis Grekis, Deniss Zajecs, Artis Zekunde, and Nikolai Vatin. 2021. "Feasibility of Reducing Electricity Consumption of Air Conditioning Equipment by Condenser Direct Evaporative Cooling Technology. Example of Case Study in Dubai" Atmosphere 12, no. 9: 1205. https://doi.org/10.3390/atmos12091205
APA StyleBorodinecs, A., Lebedeva, K., Prozuments, A., Brahmanis, A., Grekis, A., Zajecs, D., Zekunde, A., & Vatin, N. (2021). Feasibility of Reducing Electricity Consumption of Air Conditioning Equipment by Condenser Direct Evaporative Cooling Technology. Example of Case Study in Dubai. Atmosphere, 12(9), 1205. https://doi.org/10.3390/atmos12091205