Next Article in Journal
Biogenic Silver Nanoparticles: Synthesis and Application as Antibacterial and Antifungal Agents
Next Article in Special Issue
Study of Microscale Meniscus Confined Electrodeposition Based on COMSOL
Previous Article in Journal
Blood Vessel Segmentation of Retinal Image Based on Dense-U-Net Network
Previous Article in Special Issue
A Spiral Distributed Monitoring Method for Steel Rebar Corrosion
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Combined Positioning Method Used for Identification of Concrete Cracks

1
Structure Health Monitoring and Control Institute, Shijiazhuang Tiedao University, Shijiazhuang 050043, China
2
School of Mechanical Engineering, Shijiazhuang Tiedao University, Shijiazhuang 050043, China
3
School of Materials, Shijiazhuang Tiedao University, Shijiazhuang 050043, China
*
Author to whom correspondence should be addressed.
Micromachines 2021, 12(12), 1479; https://doi.org/10.3390/mi12121479
Submission received: 1 November 2021 / Revised: 26 November 2021 / Accepted: 27 November 2021 / Published: 29 November 2021

Abstract

:
Fully distributed fiber optic sensors are characteristically used for the measurement of long distances and continuous distribution of space. However, due to the different fiber type, fiber length, ambient temperature and strain, fully distributed fiber optic sensors fail to locate damage accurately and cause a greater error. Therefore, this paper proposes a new positioning method of combining fully distributed fiber optic sensors with fiber Bragg gratings, which enables accurately the localization of a structural damage during the long-term monitoring of fully distributed fiber optic sensors. Moreover, the coupling mechanism of the reflected light from fiber grating and excited Brillouin scattering light is illustrated. Further, it is experimentally verified by locating the cracks of 2 m long reinforced concrete beams. The experimental results show that this proposed method is capable of monitoring the generation of the beam crack and further locating the crack on the concrete beam with an approximate error of 10 cm.

1. Introduction

Some long-distance structures such as pipelines, bridges, highways and railways play an important role in national economies and are prone to be damaged arising from the falling stone, sinkhole collapse and heavy loads. Under the action of these adverse loads, these structures are prone to long-term cumulative damage or sudden damage [1,2]. Many scholars have adopted different methods to monitor concrete cracks [3,4,5]. Deformation, strain and stress are the most important parameters for structural damage identification. In order to correctly measure and locate the structural deformation and stress, the sensors must be deformed in coordination with the structures. Fiber grating sensing technology and distributed optic fiber sensing technology [6,7,8] have been widely used in the engineering of structure monitoring [9,10,11,12,13,14,15,16] due to their high accuracy, strong resistance to electromagnetic interference, light weight, long distance and other advantages. Generally, the damage of the long-distance structure has the characteristics of wide distribution and strong randomness. Damage identification and localization are of great significance for long-term structural monitoring, providing the basis for maintaining the safety and stability of the structure. Brillouin optical time-domain analysis (BOTDA) technology is popularly and increasingly being utilized to measure strains in concrete structures. Feng [13] enhanced the measured strain by using the rubber gasket. Fan [16] developed a new method to investigate the concrete deterioration under steel corrosion with the use of a distributed fiber optic sensor. Mao [17] monitored concrete cracking under practical conditions by using BOTDA and fiber Bragg gratings (FBG). The optical time-domain reflectometer (OTDR) is a common piece of metrology equipment for evaluating optical fiber uniformity. An OTDR trace shows not only the fiber attenuation but also the magnitude and location of any losses and reflections along the fiber’s length. Crunelle [18] proposed a novel interrogating device that allows a very large number of sensing points to be detected and located. Yang [19] proposed a method to detect the damage of high-voltage transmission lines by OTDR. There are other methods to locate the cracks based on FBG. Mao [20] measured the cracks in reinforced concrete by FBG. Inners [21] monitored the cracks by acoustic emission. Among the existing damage localization methods, the widely used ones are fiber Bragg grating (FBG) localized methods [18,21,22] and fully distributed positioning methods of optical sensing fiber [13,16,17,19,20,22,23,24]. The above-mentioned methods either have a limited measurement range or many sensors to locate the damage sites and fail to achieve a precise spatial positioning for a long-distance distributed sensor.
In order to solve the pinpointing of crack monitoring for fully distributed fiber optic sensors, this paper proposes a positioning method of a combination of FBG and a fully distributed fiber optic sensor. The FBG and fully distributed fiber optic sensor are in a single sensing fiber. FBG was used as a localization indicator to eliminate the positioning error induced by the fiber length, refractive index, strain and ambient temperature. Meanwhile, a 2 m long concrete beam crack experiment was performed to validate its positioning accuracy.

2. Analysis of Brillouin-Scattering-Based Sensing Principle and Time-Domain Localization Theory

A Brillouin-scattering-based fully distributed fiber optic sensor enables the measurement of temperature and strain along the fiber based on Brillouin frequency shift:
v B ( ε , T ) = 2 v 0 c n ( ε , T ) E ( ε , T ) [ 1 k ( ε , T ) ] [ 1 + k ( ε , T ) ] [ 1 2 k ( ε , T ) ] ρ ( ε , T )
where n is the refractive index of the fiber, v B ( ε , T ) is the Brillouin frequency shift, E is the Young’s modulus of the fiber, ρ is the fiber density and k is the Poisson’s ratio of the fiber. The above-mentioned parameters are related to temperature and strain. The relationship between strain and temperature and Brillouin frequency shift can be expressed as:
v B ( ε , T ) = v B ( 0 ) + C T ( T T 0 ) + C ε ε
where v B ( 0 ) is the initial strain, C ε is a strain sensitivity factor, typically 0.048 MHz/µε, C T is a temperature sensitivity coefficient, typically 1.07 MHz/°C, and T T 0 is the temperature difference (°C). From Equation (2), the variation of temperature and strain is reflected by the magnitude of the Brillouin frequency shift [13].
Meanwhile, the distance from any point in the fiber to the detection light source can be measured by the of OTDR technology and get a spatial localization [6]:
z = c t 2 n
where c is the propagation speed of light waves in optical fiber (m/s), n is the refractive index of optical fiber and t is the time of light propagation (s). Equation (3) can be differentiated as:
d z = c t 2 n 2 d n = L n 2 d n
Equation (4) shows that the spatial position of the sensing fiber is influenced by three factors: (1) the refractive index of the fiber n ; (2) the length of the fiber L ; and (3) Δ n induced by the strain and ambient temperature. The positioning error of spatial localization for a one-kilometer-long fiber is calculated to be 1.5 m [25] using the parameters of fiber refractive index variation of 0.811 × 10−5/°C and −0.1649 × 10−6/με, which arises from a ambient temperature change of 60 °C and a 1000 με deformation of sensing fiber Accordingly, the positioning error is much more greater for up to hundreds of kilometers of fully distributed fiber sensor. In addition, factors such as the performance of the fully distributed sensing test instrument itself [17,26] generates a positioning error. Therefore, it is essential to improve the localization accuracy of fully distributed sensors. In order to decline or even eliminate the positioning error of a long-distance distributed sensor, a combined FBG and BOTDA sensing system was proposed. FBG is used as a localization indicator in fully distributed fiber sensor [27,28]. Hence, the location of FBG transforms a long-distance distributed sensor into a short-distance distributed sensor.

3. Experiment

3.1. Coupling Test of Fiber Grating and Brillouin Scattering

In the combined FBG and BOTDA sensing system, the authors used FBG as a localization indicator in fully distributed fiber sensing [27,28]. To explore the coupling mechanism of fiber grating and excited Brillouin scattering, the optical path (Figure 1) was set to detect the pump and probe end light source spectra of an NBX-6040A instrument. Meanwhile, the coupling spectra between the pump and probe light sources and three purchased FBGs were measured by AQ6317 optical spectrum analyzer (OSA). Their performance parameters are shown in Table 1. In addition, the Brillouin optical power spectrum of six FBGs was measured (Figure 2). The wavelength signal of FBG was recorded by OSA with a wavelength repeatability of 10 pm.

3.2. Concrete Crack Location Experiment

The sensing fiber used in the experiment was a single-mode silicon fiber with a white protective sleeve, 900 μm in diameter. Two FBGs were used as positioning tools, named FBG1 and FBG2. Their performance parameters are shown in Table 2.
To detect cracks of different widths, there were two pasting methods used on the surface of the concrete beam. The 1.5 m length sensing fiber was fully pasted along the concrete beam, named full adhesive type. The other method is point type, which had a 1.5 m distributed sensing fiber glued on the beam with a 10 cm interval. The fully pasted sensing fiber detects small cracks. On the contrary, the point-glued method is used for detecting a wide crack. The first three segments were fully adhesive optical fiber, and the last three segments were point-paste type optical fiber, respectively labeled as 1, 2, 3, 4, 5 and 6 (Figure 3). The location of the sensing fiber and FBG is shown in Figure 4; they were all pasted with two-component epoxy adhesive. In the experiment, the concrete beam was fixed on a steel frame, and bolts and channels were used to fix the ends of the concrete beam. Meanwhile, a QLD32 screw jack was used to load step-by-step, and the step load was recorded through the LH-S10-2T pressure transducer (Figure 5). The applied load was from 0 to 8 kN. The location and time of crack were simultaneously observed by the naked eye. The fiber strain was recorded by NEUBREX’s NBX-6040A high-precision analyzer with a spatial resolution of 10 cm. Its sampling rate and interval was 2 × 1015 and 5 cm, respectively.

4. Results and Discussion

4.1. Coupling Mechanism of FBG and Brillouin Scattering

Figure 6 and Figure 7 are pump and probe light source spectra, respectively. It is shown that the wavelength range of pump and probe light sources are from 1460 to 1600 nm. The central wavelength of pulsed pump light and continuous probe light is 1548.52 nm and 1548.61 nm, respectively.
To explore the coupling characteristics of Brillouin scattering and FBG, their coupling spectra were measured by AQ6317 spectrometer. As shown in Figure 8a, it was caused by the superposition of the reflection of the pump light through FBG and the transmission of the probe light through FBG. The transmission spectrum of FBG was formed due to higher-energy pump light, shown in Figure 8b. Subsequently, a AQ6317 spectrometer was used to test the spectrum of six FBGs in the wavelength range of 1460~1620 nm. Figure 9 is the coupling spectra between FBGs, probe and pump light. FBGs in the wavelength range of 1520~1580 nm have reflective spectra, while the other FBGs have transmission spectra (Figure 9) generated by the superposition of the two beams of light from the pump and probe end passing through FBGs. When the pump light power is higher than the probe light, FBGs have a reflection spectrum; otherwise, they have the transmission spectrum. Therefore, the light power peak of FBGs is generated by FBG reflection. When FBGs and fully distributed sensing fibers are measured in a single line, a light power peak occurs.

4.2. Concrete Crack Localization

Figure 10 shows the excited Brillouin scattering power distribution of a distributed sensing fiber sensor. The rectangular shading is the power reflection spectrum of FBG1 and FBG2. Their spatial locations along the sensing fiber were 3.131 m and 70.585 m, respectively. The actual distance from FBG1 to the beam end was 4.29 m. Therefore, the spatial locations of the three sections of the fully adhesive fiber were 7.421 m, 13.421 m and 16.421 m, respectively; the actual distance from FBG2 to the starting position of the concrete beam was 4.41 m, and the spatial positions of the three sections of point-sticky fiber were 74.995 m, 80.995 m and 83. 995 m, respectively. In addition, the graph also shows the power fluctuations along the fiber caused by fiber bends and flange connections.
Figure 11 shows the strain distribution along the sensing fiber without applied load. It is shown in Figure 11 that six fiber segments were initially prestressed. Due to the limitation of spatial resolution, the location of the beam end failed to be accurately determined. The enlarged graph (inset in Figure 11) illustrates the distributed strain of the first fully adhesive fiber segment. The red ball label is the location of the beam end (7.187 m) from the distributed strain curve, while its actual location was 7.421 m. Thus, the positioning error of the beam end was 0.234 m. However, the length between the beam end and FBG1 (3.131 m) was 4.29 m, and hence the location of beam end (7.421 m) was precisely calculated using the FBG1 spatial site (3.131 m). It is found that a positioning error is consequently eliminated using FBG1 as a localization indicator.
The cracks gradually generated with an increasing load. Eventually, there were nine transverse cracks successively observed by naked eye. An 8 kN load was ultimately applied to achieve differential concrete cracks. When the load was 4.5 kN, the ①, ②, ③, ④ and ⑤ cracks occurred and, subsequently, the 6 and ⑦ cracks at 5 kN and the ⑧ and ⑨ cracks at 8 kN, as shown in Figure 12.
Figure 13 shows the Brillouin frequency shift distribution along the sensing fiber. Figure 13b–d show an enlarged Brillouin frequency shift distribution of the three segments of the fully pasted fiber sensor, respectively. The green rectangular area is the beam length, and sharp frequency shift peaks appear at the 1, 2 and 3 fiber segments. The first frequency shift peak appeared when the beam was loaded to 4.5 kN, subsequently, the second sharp peak was generated at the 7 kN load and, ultimately, the third sharp peak at 7.5 kN load. The same experimental findings are observed in Figure 13c,d. Hence, the Brillouin frequency shift spectrum reflected the number of cracks well.
Figure 14 shows the crack location of the full-bonded sensing fiber and the actual location of the crack. In Figure 14, the black line represents the actual location of a crack, the red, blue and yellow lines represent correspondingly positioning sites of these cracks and their generated order. The crack locations are mainly concentrated in the rectangular shaded area, and the ①, ②, ③, ④ and ⑦ cracks were precisely located. At the same time, the identical cracks (Table 3) are identified by the 1, 2 and 3 segments of the sensing fiber. As a result, their positioning errors of corresponding cracks were approximately 10 cm. The error is perhaps attributable to: (i) a lower spatial resolution; (ii) a positioning error of FBG is 2–3 cm [27,28]; (iii) an error induced by the actual length measurement of used optical fiber. In addition, the ⑤, ⑧ and ⑨ cracks were not identified either due to fiber debonding or the closely positioned cracks being unidentified due to a lower spatial resolution of the BOTDA instrument.
Figure 15 shows the Brillouin frequency shift spectrum along the point-glued fiber and Figure 15b–d are the enlarged Brillouin frequency shifts of 4, 5 and 6 point-glued fiber segments, respectively. Compared with the fully bonded fiber sensor, the Brillouin frequency shift of the 4, 5 and 6 segments increased as the load increased, step-by-step, while sharp Brillouin frequency shift peaks failed to occur. The point-bonding method contributed to the experimental phenomena. The sensing fiber was uniformly stressed with the increasing load, consequently, the Brillouin frequency shift increased and uniformly distributed along the sensing fiber. Therefore, each crack cannot be identified when the generated cracks (Figure 15) are basically located in the middle part of the beam (green shading) using the point-glued method.
When the concrete beam was loaded to 4 kN, the ①, ②, ③, ④ and ⑤ cracks appeared, the Brillouin frequency shift of the 4, 5 and 6 segments of the sensing fiber increased, and the wave trough of Brillouin frequency shift spectrum simultaneously appeared. The wave trough disappeared at a 5 kN load. The location of the trough at different segment of sensing fiber was 75.821 m, 80.184 m and 84.856 m, respectively. Due to the generation of the ⑦ crack located between the ③ and ④ cracks, the location of the trough was the ⑦ crack.
In order to verify whether the location of the trough was the ⑦ crack, the hot water bag was placed at the ⑦ crack. As observed in Figure 16, Brillouin frequency shift at the location of the wave trough increased significantly with an increasing temperature. Therefore, it is inferred that the wave trough was experimentally verified to be the location of the crack. The location of the ⑦ crack was 75.821 m, 80.195 m and 84.795 m on the 4, 5 and 6 segments of the sensing fiber, respectively. The location of the beam end was correspondingly calculated as 74.995 m, 80.995 m and 83.995 m. Thus, the distance between the ⑦ crack to the beam end is calculated to 0.826 m, 0.811 m and 0.861 m. Accordingly, the identified ⑦ crack location is basically identical to its actual location (Figure 17).

5. Conclusions

In this paper, the FBG-based pinpointing method was proposed and the coupling characteristics between the reflected light from FBG and Brillouin scattering light was illustrated. It was utilized to locate cracks in a 2 m long concrete beam and then the feasibility of the locating method was verified. The following main conclusions are:
(1) FBG was used as a location indicator in a pinpointing method for a fully distributed fiber optic sensor. The experimental results indicate that the appearance of power peaks in the excited Brillouin power spectrum is caused by the reflection of FBG in the wavelength range of 1520~1580 nm. The coupling mechanism between the reflection of FBG and the Brillouin scattering light is the superposition of the pump light reflection from FBG and the probe light transmission through FBG.
(2) The positioning experiment of cracks using FBG-based pinpointing method showed that the crack generation and propagation process of a concrete beam can not only be accurately recorded but can also be pinpointed with a 10 cm error. This work provides a method for early warning and location of structural damage.

Author Contributions

Conceptualization and formal analysis, J.L.; data curation, B.S.; writing—original draft preparation, J.L. and B.S.; investigation and resources, J.W. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the National Natural Science Foundation of China (51778379) and the Natural Science Foundation of Hebei Province (E2019210201).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data presented in this study are available from the corresponding author, [J.L.], upon reasonable request.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Goszczyńska, B.; Trmpczyński, W.; Tworzewska, J. Analysis of Crack Width Development in Reinforced Concrete Beams. Materials 2021, 14, 3043. [Google Scholar] [CrossRef]
  2. Tittelboom, K.V.; Belie, N.D. Self-Healing in Cementitious Materials—A Review. Materials 2013, 6, 2182–2217. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  3. Niederleithinger, E.; Wang, X.; Herbrand, M.; Muller, M. Processing Ultrasonic Data by Coda Wave Interferometry to Monitor Load Tests of Concrete Beams. Sensors 2018, 18, 1971. [Google Scholar] [CrossRef] [Green Version]
  4. Zhang, J.; Li, Y.; Du, G.; Song, G. Damage Detection of L-Shaped Concrete Filled Steel Tube (L-CFST) Columns under Cyclic Loading Using Embedded Piezoceramic Transducers. Sensors 2018, 18, 2171. [Google Scholar] [CrossRef] [Green Version]
  5. Bremer, K.; Alwis, L.; Weigand, F.; Kuhne, M.; Zheng, Y.; Kruger, M.; Helbig, R.; Roth, B. Evaluating the Performance of Functionalized Carbon Structures with Integrated Optical Fiber Sensors under Practical Conditions. Sensors 2018, 18, 3923. [Google Scholar] [CrossRef] [Green Version]
  6. Luo, J.; Hao, Y.; Ye, Q.; Hao, Y.; Li, L. Development of optical fiber sensors based on Brillouin scattering and FBG for on-line monitoring in overhead transmission lines. J. Lightwave Technol. 2013, 31, 1559–1565. [Google Scholar] [CrossRef]
  7. Sun, A.; Semenova, Y.; Farrell, G.; Chen, B.; Li, G.; Lin, Z. BOTDR integrated with FBG sensor array for distributed strain measurement. Electron. Lett. 2010, 46, 66. [Google Scholar] [CrossRef]
  8. Lan, C.; Zhou, Z.; Ou, J. Monitoring of structural prestress loss in RC beams by inner distributed Brillouin and fiber Bragg grating sensors on a single optical fiber. Struct. Control. Health Monit. 2014, 21, 317–330. [Google Scholar] [CrossRef]
  9. Delgado, F.S.; Carvalho, J.P.; Coelho, T.V.N.; Dos Santos, A.B. An Optical Fiber Sensor and Its Application in UAVs for Current Measurements. Sensors 2016, 16, 1800. [Google Scholar] [CrossRef] [Green Version]
  10. Sun, Y.; Cao, H.; Ma, L.; Cui, H.; Huang, Y. A wavelength selective application for an optical fiber surface plasmon resonance sensor. Opt. Commun. 2016, 363, 110–116. [Google Scholar] [CrossRef]
  11. Hong, C.Y.; Zhang, Y.F.; Liu, L.Q. Application of distributed optical fiber sensor for monitoring the mechanical performance of a driven pile. Measurement 2016, 88, 186–193. [Google Scholar] [CrossRef]
  12. He, J.; Zhou, Z.; Ou, J. Optic fiber sensor-based smart bridge cable with functionality of self-sensing. Mech. Syst. Signal Process. 2013, 35, 84–94. [Google Scholar] [CrossRef]
  13. Feng, W.; Yin, J.; Borana, L.; Qin, J.; Wu, P.; Yang, J. A network theory for BOTDA measurement of deformations of geotechnical structures and error analysis. Measurement 2019, 146, 618–627. [Google Scholar] [CrossRef]
  14. Zeni, L.; Picarelli, L.; Avolio, B.; Coscetta, A.; Papa, R.; Zeni, G.; Di Maio, C.; Vassallo, R.; Minardo, A. Brillouin optical time-domain analysis for geotechnical monitoring. J. Rock Mech. Geotech. Eng. 2015, 7, 458–462. [Google Scholar] [CrossRef] [Green Version]
  15. Fan, L.; Bao, Y.; Meng, W.; Chen, G. In-situ monitoring of corrosion-induced expansion and mass loss of steel bar in steel fiber reinforced concrete using a distributed fiber optic sensor. Compos. Part B Eng. 2019, 165, 679–689. [Google Scholar] [CrossRef]
  16. Fan, L.; Tan, X.; Zhang, Q.; Meng, W.; Chen, G.; Bao, Y. Monitoring corrosion of steel bars in reinforced concrete based on helix strains measured from a distributed fiber optic sensor. Eng. Struct. 2020, 204, 110039. [Google Scholar] [CrossRef]
  17. Mao, J.; Xu, F.; Gao, Q.; Liu, S.; Jin, W.; Xu, Y. A Monitoring Method Based on FBG for Concrete Corrosion Cracking. Sensors 2016, 16, 1093. [Google Scholar] [CrossRef] [Green Version]
  18. Crunelle, C.; Caucheteur, C.; Wuilpart, M.; Mégret, P. Quasi-distributed temperature sensor combining Fibre Bragg Gratings and temporal reflectometry technique interrogation. Opt. Lasers Eng. 2009, 47, 412–418. [Google Scholar] [CrossRef]
  19. Yang, L.; Xiao, R.; Ji, X.; Ren, L.; Jia, Z.; Li, H. OTDR-based detection of broken strands and damage in high-voltage transmission conductors. J. Optoelectron. Laser 2013, 24, 961–966. [Google Scholar]
  20. Mao, J.; Chen, J.; Cui, L.; Jin, W.; Xu, C.; He, Y. Monitoring the Corrosion Process of Reinforced Concrete Using BOTDA and FBG Sensors. Sensors 2015, 15, 8866–8883. [Google Scholar] [CrossRef]
  21. Innes, M.; Davis, C.; Rosalie, C.; Norman, P.; Rajic, N. Acoustic Emission Detection and Characterisation Using Networked FBG Sensors. Procedia Eng. 2017, 188, 440–447. [Google Scholar] [CrossRef]
  22. Tian, S.; Wen, K.; Wang, D. Research on damage localization of steel beams based on long-range fiber grating sensors. Adv. Laser Optoelectron. 2013, 4, 77–82. [Google Scholar]
  23. Broth, Z.; Hoult, N.A. Dynamic distributed strain sensing to assess reinforced concrete behaviour. Eng. Struct. 2020, 204, 110036. [Google Scholar] [CrossRef]
  24. Rodriguez, G.; Casas, J.R.; Villalba, S. Shear crack width assessment in concrete structures by 2D distributed optical fiber. Eng. Struct. 2019, 195, 508–523. [Google Scholar] [CrossRef]
  25. Yuan, L. Influence of temperature and strain on refractive index of optical fiber. J. Opt. 1997, 17, 1714–1717. [Google Scholar]
  26. Li, Q.; Zhang, C.; Li, L.; Zhong, X. Localization mechanisms and location methods of the disturbance sensor based on phase-sensitive OTDR. Optik 2014, 125, 2099–2103. [Google Scholar] [CrossRef]
  27. Li, J.; Zhao, D.; Hou, Y.; Sun, B. Power coupling characteristics between FBG and back-scattering signals. Int. J. Mod. Phys. B 2017, 31, 1741014. [Google Scholar] [CrossRef] [Green Version]
  28. Li, J.; Sun, B.; Kinzo, K. The influence of FBG on Brillouin distributed sensor. J. Civ. Struct. Health Monit. 2015, 5, 629–643. [Google Scholar] [CrossRef]
Figure 1. Schematic diagram of the optical path of pump and probe light sources for spectral testing.
Figure 1. Schematic diagram of the optical path of pump and probe light sources for spectral testing.
Micromachines 12 01479 g001
Figure 2. Spectral test optical path diagram. (a) Pump; (b) probe.
Figure 2. Spectral test optical path diagram. (a) Pump; (b) probe.
Micromachines 12 01479 g002
Figure 3. Diagram of fiber optic paste method.
Figure 3. Diagram of fiber optic paste method.
Micromachines 12 01479 g003
Figure 4. Relative spatial position of sensing fiber and fiber grating.
Figure 4. Relative spatial position of sensing fiber and fiber grating.
Micromachines 12 01479 g004
Figure 5. Schematic diagram of experimental device. (a) Cross-section dimensions of the beam; (b) schematic diagram of experiment; (c) experimental diagram.
Figure 5. Schematic diagram of experimental device. (a) Cross-section dimensions of the beam; (b) schematic diagram of experiment; (c) experimental diagram.
Micromachines 12 01479 g005
Figure 6. Pump light spectrum. (a) overall spectrum; (b) central wavelength of pump light.
Figure 6. Pump light spectrum. (a) overall spectrum; (b) central wavelength of pump light.
Micromachines 12 01479 g006
Figure 7. Probe light spectrum. (a) Overall spectrum; (b) central wavelength of probe light.
Figure 7. Probe light spectrum. (a) Overall spectrum; (b) central wavelength of probe light.
Micromachines 12 01479 g007
Figure 8. Interactive spectra. (a) Probe and FBG; (b) pump and FBG.
Figure 8. Interactive spectra. (a) Probe and FBG; (b) pump and FBG.
Micromachines 12 01479 g008
Figure 9. FBGs and BOTDA double-ended spectra.
Figure 9. FBGs and BOTDA double-ended spectra.
Micromachines 12 01479 g009
Figure 10. Power spectrum of stimulated Brillouin scattering.
Figure 10. Power spectrum of stimulated Brillouin scattering.
Micromachines 12 01479 g010
Figure 11. Distributed strain along the sensing fiber without applied load.
Figure 11. Distributed strain along the sensing fiber without applied load.
Micromachines 12 01479 g011
Figure 12. Crack distribution along the concrete beam.
Figure 12. Crack distribution along the concrete beam.
Micromachines 12 01479 g012
Figure 13. Brillouin frequency shift along the fully bonded optical fiber. (a) Overall view of Brillouin frequency shift of 3 segments of fiber; (b) enlarged view of the first segment pasted optical fiber; (c) enlarged view of the second segment pasted optical fiber; (d) enlarged view of the third segment pasted optical fiber.
Figure 13. Brillouin frequency shift along the fully bonded optical fiber. (a) Overall view of Brillouin frequency shift of 3 segments of fiber; (b) enlarged view of the first segment pasted optical fiber; (c) enlarged view of the second segment pasted optical fiber; (d) enlarged view of the third segment pasted optical fiber.
Micromachines 12 01479 g013aMicromachines 12 01479 g013b
Figure 14. Position of concrete cracks using the full-pasted fiber sensor.
Figure 14. Position of concrete cracks using the full-pasted fiber sensor.
Micromachines 12 01479 g014
Figure 15. Brillouin frequency shift along the pointed-bonded optical fiber. (a) Overall view; (b) the fourth segment pasted optical fiber; (c) the fifth segment pasted optical fiber; (d) the sixth segment pasted optical fiber.
Figure 15. Brillouin frequency shift along the pointed-bonded optical fiber. (a) Overall view; (b) the fourth segment pasted optical fiber; (c) the fifth segment pasted optical fiber; (d) the sixth segment pasted optical fiber.
Micromachines 12 01479 g015
Figure 16. Frequency spectrum of point-glued sensing fiber under the varied temperature.
Figure 16. Frequency spectrum of point-glued sensing fiber under the varied temperature.
Micromachines 12 01479 g016
Figure 17. Schematic diagram of crack location of point bonded optical fiber (blue: actual location, red: FBG locating cracks).
Figure 17. Schematic diagram of crack location of point bonded optical fiber (blue: actual location, red: FBG locating cracks).
Micromachines 12 01479 g017
Table 1. Properties of FBGs along the sensing fiber.
Table 1. Properties of FBGs along the sensing fiber.
Number of FBGPerformance Parameters
Wavelength/nmBandwidth/nmReflectance %
FBG11525.030.2384.54
FBG21529.880.2182.59
FBG31535.010.2184
Table 2. Performance parameters of FBG sensor.
Table 2. Performance parameters of FBG sensor.
Number of FBGPerformance Parameters
Wavelength/nmBandwidth/nmReflectance %
FBG11544.740.2273.39
FBG21529.910.2391.54
Table 3. Performance parameters of FBG sensor.
Table 3. Performance parameters of FBG sensor.
SegmentDistance/mIdentification Length/mCrack NumberActual Length /mPositioning Error/m
17.9570.53660.40.136
8.0080.58710.50.087
8.1620.74120.610.131
8.2130.79230.70.092
8.3670.94670.820.126
212.8340.58710.50.095
12.6800.74120.630.093
12.6280.79330.70.111
12.5260.89570.830.065
317.0940.67320.610.063
17.3000.87970.830.049
17.3510.9370.830.100
17.4020.9814 or 90.92 or 1.030.061 or 0.049
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Li, J.; Shen, B.; Wang, J. A Combined Positioning Method Used for Identification of Concrete Cracks. Micromachines 2021, 12, 1479. https://doi.org/10.3390/mi12121479

AMA Style

Li J, Shen B, Wang J. A Combined Positioning Method Used for Identification of Concrete Cracks. Micromachines. 2021; 12(12):1479. https://doi.org/10.3390/mi12121479

Chicago/Turabian Style

Li, Jianzhi, Bohao Shen, and Junjie Wang. 2021. "A Combined Positioning Method Used for Identification of Concrete Cracks" Micromachines 12, no. 12: 1479. https://doi.org/10.3390/mi12121479

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop