The results show that the lighting performance of the two patient-room configurations varied according to their orientation, room geometry, window characteristics, surface reflectance, and luminaire properties. The north-facing room was mainly affected by limited daylight availability, whereas the south-facing room was characterised by higher daylight levels but greater spatial variation. The following sections discuss the existing condition, the effect of increased wall reflectance, and the performance of the Philips and Zumtobel LED lighting systems.
The findings are interpreted in terms of illuminance quantity, spatial uniformity, and daylight availability, as glare and field-of-view luminance contrasts were not quantified.
3.2. Baseline Performance of the Existing Lighting Condition
The existing condition revealed two different lighting behaviours in the north- and south-facing patient rooms. In the north-facing room, the main limitation was insufficient daylight contribution, while in the south-facing room the main issue was the uneven distribution of daylight under high-illuminance conditions. This confirms that orientation affects not only the amount of daylight entering the room, but also its spatial distribution within the interior. This interpretation is consistent with daylighting literature, which explains that daylight availability and distribution are influenced by orientation, sky condition, time of day, season, room geometry, and window characteristics [
15,
16].
Table 10 shows that daylight alone was generally insufficient to satisfy the recommended lighting requirements in the north-facing room, particularly during winter and overcast conditions. Only a limited number of summer cases achieved the recommended task illuminance, while work-plane uniformity remained consistently below the recommended threshold. These findings indicate that the principal limitation of the north-facing room was insufficient daylight penetration rather than inadequate room geometry. This behaviour agrees with previous investigations reporting that north-oriented patient rooms generally require greater dependence on artificial lighting because they receive predominantly diffuse daylight.
Table 11 demonstrates that the existing lighting system compensated for the limited daylight contribution by increasing both work-plane and task-area illuminance. However, the recommended bedside lighting level was achieved only when ceiling and bedhead luminaires operated simultaneously, indicating that acceptable visual conditions depended on the operation of the complete lighting installation rather than on an efficient luminaire distribution.
The combined daylight and artificial-lighting results presented in
Table 12 further improved the lighting conditions by enabling the task area to satisfy the recommended illuminance under all investigated conditions. Nevertheless, work-plane uniformity remained below the recommended value, indicating that increasing illuminance alone could not eliminate the uneven spatial distribution of light.
This behaviour is supported visually by
Figure 6. Under a summer overcast sky at 12:00, the false-colour map shows adequate illumination around the patient-bed zone and luminaire locations, while the deeper areas of the room remain less evenly illuminated. This explains why work-plane illuminance reached 574 lx while uniformity remained only 0.21. The baseline problem in the north-facing room was therefore not only the limited daylight contribution, but also the inability of the existing lighting arrangement to distribute light evenly across the occupied space.
A different lighting pattern was observed in the south-facing room.
Table 13 demonstrates that daylight availability was substantially higher than in the north-facing room and frequently exceeded the recommended illuminance level. However, this improvement was accompanied by a pronounced reduction in work-plane uniformity, indicating that excessive daylight penetration produced strong luminance contrasts rather than a balanced luminous environment. Consequently, greater daylight availability did not necessarily correspond to more balanced lighting conditions and may have increased the risk of excessive brightness near the façade.
The winter clear-sky result for the south-facing room warrants careful interpretation. At 12:00, the average work-plane illuminance reached 6283 lx. A review of the simulation inputs and outputs confirmed that this result occurred under clear-sky conditions with direct solar penetration through the south-facing window. The relatively low winter solar altitude allowed sunlight to penetrate more deeply into the room, producing very high local illuminance values and increasing the work-plane average. At the same time, the very low uniformity value (Uo = 0.054) indicates that the high average illuminance did not represent a uniformly illuminated space but rather a highly uneven daylight distribution dominated by the directly sunlit zone. Therefore, the reported value should be interpreted as a specific point-in-time clear-sky result rather than as a typical daily or seasonal illuminance level.
Table 14 shows that the existing artificial-lighting system exhibited limitations similar to those observed in the north-facing room during night-time operation. Although combined ceiling and bedhead lighting improved bedside illumination, the existing system remained dependent on operating multiple luminaires to satisfy patient-care requirements.
As shown in
Table 15, integrating daylight with artificial lighting considerably improved lighting performance during periods of limited daylight availability. However, under clear-sky conditions daylight became the dominant source of illumination.
This wide range reflects the strong influence of sky condition and time of day on the south-facing room.
Figure 7 illustrates this behaviour under summer overcast sky at 12:00. The map shows higher illumination near the window and patient-bed zone, while the deeper part of the room remains less illuminated. The corresponding work-plane illuminance was 596 lx, but uniformity remained 0.27.
The baseline analysis shows that the two rooms required different improvement priorities. The north-facing room required stronger and more balanced artificial lighting support, while the south-facing room required better management of spatial daylight variation. This is particularly relevant for patient rooms, where lighting must support general visibility, patient care, reading, examination, and circulation. The importance of appropriate lighting conditions for patient-room activities and healthcare environments has been emphasised in healthcare lighting literature [
1,
19].
3.3. Effect of Increasing Wall Surface Reflectance
Increasing wall reflectance from 0.70 to 0.80 improved the lighting performance in both rooms, although the improvement remained moderate because the existing luminaire layout and photometric distribution were unchanged. The main effect of this strategy was the enhancement of secondary reflections from wall surfaces, which helped redistribute both daylight and artificial light within the rooms. This interpretation is consistent with daylighting principles indicating that indoor light distribution is influenced by interior surface properties and inter-reflections [
14,
15].
Table 16 shows that increasing wall reflectance improved lighting performance in the north-facing room under combined daylight and artificial-lighting conditions across all simulated conditions. The most consistent improvement occurred in work-plane uniformity, while task-area illuminance continued to satisfy the recommended lighting requirements. These findings indicate that the additional reflected light primarily benefited the deeper parts of the room, reducing the contrast between areas close to the window and those located farther from the façade.
The artificial-lighting results presented in
Table 17 demonstrate a similar trend. Increasing wall reflectance slightly enhanced both work-plane and task-area illuminance while improving the spatial distribution of artificial lighting. However, the existing lighting layout remained dependent on the simultaneous operation of ceiling and bedhead luminaires to achieve the required lighting conditions, indicating that wall reflectance alone could not compensate for the limitations of the original luminaire arrangement.
The visual effect of increased wall reflectance is shown in
Figure 8. Compared with the existing condition in
Figure 6, the false-colour distribution appears more continuous across the central area of the north-facing room. The darker areas are reduced, and the transition between the patient-bed zone and deeper parts of the room becomes smoother. However, local differences in illuminance remain visible, confirming that wall reflectance alone cannot fully solve the problem of spatial imbalance.
A comparable response was observed in the south-facing room.
Table 18 shows that increasing wall reflectance improved lighting performance in the south-facing room under combined daylight and artificial-lighting conditions for both clear and overcast skies. The improvement was more pronounced in lighting uniformity than in average illuminance, suggesting that the higher-reflectance wall surfaces mainly enhanced light redistribution rather than substantially increasing the total amount of light available in the room.
The artificial-lighting results presented in
Table 19 further confirm this behaviour. General room lighting and bedside lighting both improved slightly; however, wall reflectance alone was insufficient to satisfy all lighting requirements without the support of multiple luminaires. Consequently, the intervention acted as a complementary improvement rather than a complete lighting solution.
Figure 9 supports this interpretation. Compared with
Figure 8, the false-colour map shows a wider area of adequate illumination in the south-facing room. Nevertheless, the zone close to the window and patient bed remains brighter than the deeper part of the room. This indicates that increased wall reflectance improved redistribution but did not fully control the orientation-related daylight gradient.
Overall, increasing wall reflectance acted as a useful passive retrofit measure. It improved light redistribution and slightly increased daylight utilisation without changing the room geometry or replacing the lighting system. However, its effect remained supportive rather than transformative. The results show that wall reflectance can enhance the existing lighting environment, but it cannot compensate for an inadequate luminaire distribution by itself.
3.4. Effect of Philips and Zumtobel LED Lighting Systems
Replacing the existing luminaires with Philips and Zumtobel LED systems produced the strongest improvement in overall lighting performance. Unlike the wall-reflectance strategy, these scenarios changed the artificial lighting system itself, including luminaire output, distribution, and dimming capability. Their effect was therefore more pronounced, particularly in the north-facing room and during conditions where artificial lighting played a major role. This interpretation is consistent with studies showing that optimised electric and LED lighting can improve visual performance and lighting conditions in clinical environments [
20,
21].
Table 20 shows that the Philips system improved lighting performance in the north-facing room under combined daylight and artificial-lighting conditions. The system achieved the recommended illuminance levels for both the work plane and the patient-bed task area, while work-plane uniformity improved compared with the existing combined lighting condition. This indicates that the Philips luminaires not only increased the amount of light but also distributed it more effectively across the occupied area. The predefined output reductions further indicate that the required illuminance levels could be achieved without operating the luminaires continuously at full nominal output.
Table 21 further demonstrates the improved photometric performance of the Philips system under artificial-lighting-only conditions. Compared with the existing installation, the Philips system provided better task-lighting performance using fewer active luminaires in the combined ceiling-and-bedhead lighting scenario, together with a predefined reduction in nominal luminous output. This is an important result because the existing system required the simultaneous operation of the ceiling and bedhead luminaires to support patient-bed activities, whereas the Philips scenario provided improved task lighting with greater output-control flexibility.
Table 22 shows that the Zumtobel system produced a similar improvement in the north-facing room under combined daylight and artificial-lighting conditions. The recommended illuminance levels were achieved on both the work plane and the patient-bed task area, while work-plane uniformity generally remained within or close to the required range. The predefined output reductions indicate that the artificial-light contribution could be reduced under conditions with greater daylight availability while maintaining the assessed illuminance levels.
Table 23 demonstrates that the Zumtobel system also performed effectively under artificial-lighting-only conditions. The system achieved the required lighting levels using fewer operating luminaires than the existing installation, together with a predefined reduction in nominal luminous output. This indicates that the improvement resulted from better photometric performance and light distribution rather than from increasing the number of luminaires or operating them continuously at full output. The false-colour maps in
Figure 10 and
Figure 11 visually confirm the improvement achieved by the Philips and Zumtobel systems in the north-facing room. Compared with the existing and wall-reflectance scenarios, both LED systems produced a more continuous distribution across the work plane. The deeper zones were better illuminated, and the transition between the window side, patient-bed area, and central zone became smoother. This confirms that replacing the luminaires had a stronger effect on spatial balance than increasing wall reflectance alone.
In the south-facing room, the effect of LED replacement was more strongly influenced by daylight availability.
Table 24 shows that the Philips system improved lighting performance under combined daylight and artificial-lighting conditions, particularly during overcast and low-daylight periods. The predefined output reductions decreased the artificial-light contribution when daylight availability was higher while maintaining the assessed illuminance levels on the work plane and patient-bed task area. These findings indicate the potential value of dimmable LED systems in rooms where daylight availability varies substantially throughout the day.
Table 25 shows that the Zumtobel system achieved comparable lighting performance in the south-facing room under combined daylight and artificial-lighting conditions. Under overcast and evening conditions, the system provided sufficient illuminance and improved work-plane uniformity compared with the existing lighting condition. However, under clear-sky conditions with high daylight availability, daylight remained the dominant source of illumination, and the LED system had limited ability to reduce the uneven light distribution near the façade. These findings indicate that luminaire replacement can improve artificial-lighting performance but cannot fully address daylight-related non-uniformity in room configurations with high daylight exposure.
The artificial-lighting-only results presented in
Table 26 further confirm the operational benefit of the Philips system in the south-facing room. Compared with the existing installation, the Philips system provided substantially higher task-area illuminance and better task-area uniformity under the general ceiling-lighting condition. For examination and reading activities, the required task illuminance level was achieved using fewer active luminaires in the combined ceiling-and-bedhead lighting scenario, together with a predefined reduction in nominal luminous output. These results indicate that the Philips system provided improved functional lighting and greater output-control flexibility than the existing lighting arrangement.
Table 27 demonstrates that the Zumtobel system also performed effectively under artificial-lighting-only conditions in the south-facing room. Compared with the existing installation, the system provided substantially higher task-area illuminance and better task-area uniformity under the general ceiling-lighting condition. For examination and reading activities, the required task illuminance level was achieved using fewer active luminaires in the combined ceiling-and-bedhead lighting scenario, together with a predefined reduction in nominal luminous output. These findings indicate that the Zumtobel system provided improved task lighting and greater output-control flexibility than the existing lighting arrangement.
The visual maps in
Figure 12 and
Figure 13 support these results. Both Philips and Zumtobel created a more coherent illumination pattern under summer overcast sky at 12:00. The green distribution extended across a larger portion of the room, indicating improved spatial coverage. However, the brighter zone near the window and patient-bed area remained visible, confirming that daylight contribution still shaped the overall distribution.
Overall, the Philips and Zumtobel LED replacement systems generally provided greater improvements in lighting performance than the existing installation and the wall-reflectance scenario under the assessed conditions. Their main advantage was not only achieving the recommended illuminance levels but also improving lighting uniformity in many of the investigated scenarios. The use of fewer active luminaires in some cases and predefined output reductions also indicate the potential for greater operational flexibility. These findings suggest that dimmable LED systems may provide a more effective lighting solution for hospital patient rooms when daylight and artificial-lighting contributions are considered together.
3.5. Indicative Energy and Operating Cost Comparison
Table 28 presents the rated full-output energy demand and normalised operating-cost comparison of the Philips and Zumtobel ceiling-lighting systems. Both systems used three ceiling luminaires rated at 40 W each. The total rated full-output power of the operating ceiling luminaires was therefore 120 W for each system.
Accordingly, both systems had a rated energy demand of 0.120 kWh per hour and 120 kWh per 1000 h of operation at full output. Their normalised electricity cost was therefore identical and can be expressed as 120 T, where T represents the applicable electricity tariff per kWh.
Although the two systems had the same rated full-output energy demand, their manufacturer-reported photometric characteristics differed. The Philips system provided a total nominal luminous flux of 10,500 lm, whereas the Zumtobel system provided 13,680 lm. Thus, the Zumtobel system provided approximately 30.3% greater nominal luminous flux under the same rated full-output power condition. This difference reflects its higher manufacturer-reported source-level luminous efficacy.
However, the higher nominal luminous flux of the Zumtobel system does not by itself demonstrate superior room-level lighting performance or lower operational electricity consumption. Room-level performance depends on the photometric distribution of the luminaires, their arrangement, mounting configuration, room geometry, and surface characteristics. The effectiveness of the two systems was therefore evaluated separately using the simulated illuminance, uniformity, and compliance results.
3.6. Comparative Discussion and Design Implications
The findings of this study indicate that lighting performance in hospital patient rooms cannot be adequately improved by modifying a single lighting parameter alone. Instead, quantitative lighting performance depends on the interaction between façade orientation, window configuration, daylight availability, lighting uniformity, interior surface reflectance, luminaire performance, and assigned output settings. This is particularly important in healthcare spaces, where lighting must support general visibility, reading, examination, night-time orientation, and staff-related visual tasks. Therefore, evaluating patient-room lighting only through average illuminance may provide an incomplete understanding of the luminous environment.
Façade orientation and window configuration jointly influenced daylight behaviour throughout the investigated scenarios. The south-facing room consistently received higher daylight levels than the north-facing room; however, the additional daylight did not always improve lighting performance because it was accompanied by greater spatial variation across the work plane. In contrast, the north-facing room provided lower but more stable daylight conditions and therefore responded more effectively to supplementary artificial lighting. These observations suggest that the combined effects of façade orientation and window configuration influenced both the quantity and spatial distribution of daylight. Similar conclusions have been reported in previous healthcare daylighting studies, where façade orientation significantly affected daylight penetration and visual conditions, while overall lighting performance depended on the balance between daylight availability and electric-lighting support.
Another important outcome of the study is that achieving the recommended illuminance level alone was insufficient to ensure satisfactory lighting performance. Several scenarios fulfilled the illuminance criteria but continued to exhibit relatively poor lighting uniformity, particularly under high-daylight conditions in the south-facing room. This indicates that increasing daylight availability without improving its spatial distribution may create spatially unbalanced lighting conditions despite adequate average illuminance. Consequently, lighting performance should be evaluated using illuminance and uniformity simultaneously rather than considering each parameter independently. This interpretation is consistent with recent daylighting research, which emphasises that satisfactory visual conditions depend on the spatial distribution of light as well as its intensity.
Increasing wall surface reflectance improved lighting performance by enhancing the redistribution of available light within the room. The brighter wall finish promoted additional secondary reflections, reducing spatial illuminance differences and producing a more uniform illuminance distribution. Nevertheless, the overall improvement remained moderate because the amount of daylight entering the room was unchanged. This finding suggests that interior surface reflectance primarily improves the use and redistribution of available light rather than increasing daylight availability itself. Therefore, wall reflectance should be considered a supporting design parameter that enhances lighting performance but cannot independently compensate for limitations associated with façade orientation, window configuration, or daylight access.
The LED luminaire replacement systems produced the greatest improvement among the investigated interventions. Compared with the existing installation, both Philips and Zumtobel systems consistently improved lighting uniformity while satisfying the recommended illuminance criteria under most operating conditions. More importantly, these improvements were frequently achieved with fewer operating luminaires and predefined output reductions, indicating that lighting performance depends on effective photometric distribution and appropriate output settings rather than simply on higher luminous output. While previous healthcare-lighting studies have demonstrated the benefits of controllable LED systems, the present study provides a comparative assessment of their performance alongside daylight availability and interior surface properties in existing hospital patient rooms.
To quantify the magnitude of improvement achieved by each retrofit strategy, the patient-bed visual task area under the artificial-lighting-only ceiling-lighting condition was used as the common comparison basis. This zone was selected because all investigated ceiling-lighting scenarios already provided the adopted general work-plane illuminance and uniformity levels, whereas the visual task area represents the more demanding bedside activities of reading, examination, and patient care. Percentage changes were calculated separately for each room relative to the corresponding existing ceiling-lighting condition using three ceiling luminaires. The relative change in average illuminance was calculated using Equation (5):
where
is the average illuminance obtained with the investigated intervention and
is the average illuminance under the existing ceiling-lighting condition. The absolute and relative changes in lighting uniformity were calculated using Equations (6) and (7), respectively:
where
and
represent the lighting-uniformity values under the intervention and existing conditions, respectively.
Both absolute and relative changes in uniformity were reported because percentage changes alone may appear disproportionately large when the baseline uniformity value is low.
Table 29 provides a direct side-by-side comparison of the baseline and retrofit scenarios in terms of both average illuminance and work-plane uniformity.
As shown in
Table 29, increasing wall reflectance produced a consistent supportive improvement in bedside lighting, raising visual-task-area illuminance by 4.2% in the north-facing room and 4.9% in the south-facing room. It also increased task-area uniformity from 0.65 to 0.66 in the north-facing room, reinforcing the already favourable spatial distribution, and from 0.49 to 0.51 in the south-facing room, moving the lighting distribution closer to the adopted bedside reference.
The LED replacement systems produced substantially stronger gains. The Philips system increased visual-task-area illuminance by 53.7% in the north-facing room and 101.2% in the south-facing room, reaching 332 lx and 326 lx, respectively. The Zumtobel system increased task-area illuminance by 48.6% and 93.8%, reaching 321 lx and 314 lx, respectively. Both systems therefore raised bedside illuminance above the adopted 300 lx reference in both rooms.
Task-area uniformity also improved. The Philips system increased from 0.65 to 0.72 in the north-facing room and from 0.49 to 0.58 in the south-facing room, while the Zumtobel system increased it to 0.69 and 0.56, respectively. In the south-facing room, the difference from the 0.60 reference was reduced from 0.11 under the existing condition to only 0.02 with Philips and 0.04 with Zumtobel. This corresponds to reductions of approximately 81.8% and 63.6%, respectively, in the remaining uniformity gap. These results demonstrate that LED replacement produced the strongest improvement in the lighting service delivered to the patient-bed task area, whereas increasing wall reflectance acted as a useful complementary retrofit measure.
In relation to the research questions, the two case-study rooms exhibited distinct seasonal, temporal, and sky-dependent lighting patterns. The south-facing room generally provided greater daylight availability but experienced greater spatial non-uniformity, whereas the north-facing room had lower daylight levels and greater dependence on artificial lighting. Increasing wall reflectance provided a moderate improvement in illuminance and light distribution while retaining the existing luminaire arrangement. The Philips and Zumtobel LED systems produced greater improvements in illuminance and work-plane uniformity than the wall-reflectance intervention. Their greatest benefits occurred under low-daylight and artificial-lighting-only conditions, whereas high clear-sky daylight conditions in the south-facing room continued to require additional daylight-management strategies.
From a practical perspective, the results indicate that different retrofit priorities may be appropriate for the two investigated room configurations. In the north-facing room, where daylight availability was limited, improving artificial-lighting performance provided the greatest benefit. Conversely, the south-facing room required lighting strategies that complemented its higher daylight availability by improving spatial distribution and maintaining lighting uniformity throughout the occupied space. This configuration-specific approach may provide a useful basis for hospital renovation projects in which major architectural modifications are impractical.
Overall, this study demonstrates that improving quantitative lighting conditions in hospital patient rooms requires the combined consideration of daylight availability, lighting uniformity, interior surface reflectance, and artificial-lighting performance. Rather than identifying a single universally effective intervention, the findings show that the relative effectiveness of each retrofit strategy depends on the daylight conditions and spatial characteristics of the room. The proposed comparative approach therefore provides preliminary and context-specific guidance for the renovation of patient rooms with architectural and climatic conditions comparable to those investigated in this case study.