Next Article in Journal
Culinary Knowledge and Sustainability: Chef-Led Food Waste Management in Serbia’s Hospitality Sector
Previous Article in Journal
Assessment of Corporate Governance as a Key Component of Corporate Social Responsibility: A Case Study of a Water and Wastewater Utility
Previous Article in Special Issue
Impact of Resident Density and Behaviour on the Indoor Air Concentration of Polychlorinated Biphenyls in Apartments
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Operational Performance of an MVHR System in a Retrofitted Heritage Dwelling: Indoor Air Quality, Efficiency and Duct Constraints

by
Catalina Giraldo-Soto
1,
Zaloa Azkorra-Larrinaga
1,*,
Amaia Uriarte
2,
Naiara Romero-Antón
1 and
Moisés Odriozola-Maritorena
1
1
ENEDI Research Group, Department of Energy Engineering, University of the Basque Country (UPV/EHU), Torres Quevedo 1, 48013 Bilbao, Spain
2
TECNALIA, Basque Research and Technology Alliance (BRTA), Parque Tecnológico de Bizkaia, Edificio 700, 48160 Derio, Spain
*
Author to whom correspondence should be addressed.
Sustainability 2025, 17(18), 8493; https://doi.org/10.3390/su17188493
Submission received: 31 July 2025 / Revised: 8 September 2025 / Accepted: 16 September 2025 / Published: 22 September 2025

Abstract

The integration of Mechanical Ventilation with Heat Recovery (MVHR) systems into heritage buildings poses a series of challenges, largely attributable to architectural constraints and conservation requirements. The present study offers an operational campaign of an MVHR system installed during the energy retrofit of a protected residential heritage dwelling in Vitoria-Gasteiz, Spain. Although environmental monitoring was carried out throughout the year, representative spring, autumn and winter days of continuous operation were analysed, as the occupants frequently avoided using the system due to noise perception. This limitation highlights the importance of considering acoustic comfort and user acceptance as critical factors in the long-term viability of MVHR in heritage contexts. The system was assessed under real-life conditions using continuous environmental monitoring, with a focus on indoor air quality (IAQ), thermal efficiency, airflow balance, and pressure losses. Despite the acceptable mean apparent thermal effectiveness (0.74) and total useful efficiency (0.96), the system’s performance was found to be constrained by significant flow imbalance (up to 106%) and elevated pressure drops, which were attributed to the legacy of the duct geometry. The results obtained demonstrate IAQ improved overall, with mean CO2 concentrations below ~650 ppm across the analysed dataset; however, daily means occasionally exceeded 900–1000 ppm during high-occupancy periods and in the absence of spatially distributed demand control. These exceedances are consistent with the measured outdoor baseline (~400–450 ppm) and reflect the need for post-commissioning balancing and room-level sensing to sustain Category II performance in heritage dwellings. This study provides empirical evidence on the limitations and opportunities of MVHR deployment in historic retrofits, thus informing future guidelines for sustainable interventions in heritage contexts.

1. Introduction

The building sector accounts for approximately 40% of total energy consumption and nearly 36% of CO2 emissions in the European Union [1]. A considerable proportion of this stock comprises residential buildings constructed prior to 1945, a significant number of which are designated as heritage buildings. These buildings are subject to increasing pressure to enhance their energy performance without compromising their cultural significance. In this context, Mechanical Ventilation with Heat Recovery (MVHR) systems are increasingly recognised as effective strategies to improve indoor air quality (IAQ) and reduce heating demand in energy-retrofitted buildings. Moreover, the study emphasises the vital importance of effective ventilation in limiting airborne disease transmission, an issue that was brought to the forefront during the SARS-CoV-2 pandemic and is now central to strategies for resilient and healthy buildings [2]. This underscores the necessity for the implementation of robust ventilation strategies within residential properties.
Advanced MVHR systems often include Demand-Controlled Ventilation (DCV), which adjusts airflow in real time based on indoor CO2 levels, temperature, and humidity through Building Management Systems (BMS). Recent contributions, such as the experimental assessment by Mejri et al. [3] and Duffield & Bunn [4] have demonstrated the energy-saving potential and IAQ benefits of DCV strategies under various control schemes and occupancy conditions, highlighting the growing relevance of this approach in the context of sustainable building retrofits. However, following commissioning, system performance is seldom monitored or evaluated in real-life conditions, particularly in heritage dwellings, thereby limiting opportunities for operational optimisation, early fault detection, and user feedback [5]. This absence of post-occupancy evidence is of particular significance in the context of heritage retrofits, where system integration constraints can impede the efficacy of the retrofitted systems.
Despite growing interest in MVHR systems for energy retrofits, most existing studies rely on simulation-based assessments or short-term field trials, often excluding heritage contexts. Recent works by Alhindawi et al. [6] and Bartolucci et al. [7] underscore the challenges of maintaining IAQ and energy performance in airtight dwellings and historic buildings, respectively, yet lack operational data collected under real-use conditions. This study addresses that gap by providing an empirical evaluation of MVHR performance in a protected residential dwelling, offering insights into airflow imbalance, thermal recovery, and pressure losses under heritage-constrained conditions. The findings contribute to the refinement of commissioning protocols and support evidence-based retrofit strategies for culturally significant buildings.
The process of retrofitting heritage-protected buildings is a complex undertaking, characterised by a multitude of challenges. Interventions must be minimally invasive and reversible in order to preserve architectural integrity, whilst simultaneously ensuring compliance with energy and indoor environmental quality (IEQ) targets. Although MVHR systems are often considered unsuitable for heritage buildings due to the difficulty of achieving airtightness and the potential loss of heat recovery benefits, retrofitting practices are increasingly incorporating measures to improve the performance of the building envelope. In this study, the dwelling underwent a comprehensive energy retrofit that enhanced airtightness while preserving historical features, creating a relevant context to assess the operational viability of MVHR in heritage settings. In this context, ensuring adequate IAQ through effective ventilation is critical yet challenging. MVHR systems present a compelling solution by ensuring the continuous supply of fresh air while minimising thermal losses. However, empirical evidence of their operational performance in heritage settings remains scarce. The majority of studies either concentrate on design-stage assessments or neglect to consider post-retrofit usage patterns. It is imperative that the system demonstrates efficacy in maintaining carbon dioxide levels below recommended thresholds across variable occupancy and climate conditions, whilst concomitantly reducing heating demand [8].
The pressing necessity for a swift transition towards sustainable and climate-resilient urban centres necessitates the incorporation of existing buildings, particularly those of architectural and cultural significance, into the overarching solution. As emphasised by the European Green Deal [9] and the United Nations Sustainable Development Goals (SDGs) [10], enhancing energy efficiency, advocating for healthy indoor environments, and prolonging the lifespan of buildings are foundational elements for a more sustainable urban future. In this context, the retrofitting of energy-efficient measures in combination with advanced ventilation systems is of critical importance in enabling heritage dwellings to meet 21st-century sustainability standards without compromising their historical significance. This research is consistent with broader policy and scientific objectives, providing insights that are applicable to the ongoing renovation initiatives throughout Europe.
A critical gap exists not only in design-stage and simulation-based assessments but also in post-occupancy evaluations. Very few studies report long-term, real-use monitoring of MVHR systems in heritage dwellings, limiting opportunities for operational optimisation and lessons for future retrofits. This paper addresses this gap by presenting the results of an operational campaign covering 22 days across three seasons, with continuous MVHR operation, in a social heritage dwelling within a heritage-listed building in Vitoria-Gasteiz, northern Spain. The heritage dwelling was subject to a comprehensive energy retrofit, which was designed to preserve the building’s historical features while enhancing its thermal performance. Environmental monitoring data were collected and analysed to evaluate the system’s performance under real-use conditions, considering parameters such as carbon dioxide concentration, temperature, and relative humidity.
This study aims to provide a comprehensive operational assessment of an MVHR system installed in a heritage-listed dwelling that underwent an energy retrofit. By analysing real-time environmental data (CO2, temperature, and relative humidity) under actual occupancy conditions, the study demonstrates the applicability of MVHR systems to ensure indoor air quality while minimising heating energy demand in heritage contexts. This operational approach provides evidence to support sustainable retrofit strategies, helping building operators and designers optimise ventilation performance, maintain occupant comfort, and preserve the historical value of the heritage dwelling. The study addresses two critical dimensions of sustainable retrofit performance: indoor air quality, represented by CO2 concentration, and energy performance, represented by heat recovery efficiency. Both indicators are essential for assessing sustainability in heritage dwellings. By considering thermal recovery efficiency alongside indoor air quality, the analysis acknowledges that sustainable retrofit strategies must integrate energy and health-related aspects.
The academic contributions of this research are as follows:
(a)
Empirical evaluation of MVHR performance in a heritage residential context under real-use conditions, addressing a gap in post-occupancy studies.
(b)
Analysis of the interaction between occupancy patterns and indoor CO2 dynamics, providing insights for demand-oriented ventilation strategies.
(c)
Evidence-based guidance for heritage building retrofits, supporting interventions that balance energy efficiency, indoor environmental quality, and conservation requirements.
(d)
Provision of long-term evidence of the MVHR system’s effectiveness in heritage dwelling, demonstrating its capacity to meet current energy and health standards without compromising cultural value.
The structure of this paper is as follows: Section 2 provides a detailed description of the case study, encompassing the architectural characteristics of the heritage dwelling, the energy retrofit strategy, and the MVHR system configuration. Section 3 provides a comprehensive overview of the monitoring setup and methodology. Section 4 reports and discusses the operational performance of the MVHR system under real-world conditions, focusing on indoor air quality, temperature, and humidity trends in relation to occupancy. Section 5 offers a concise overview of the key findings, emphasising their implications for sustainable heritage retrofits.

Related Work

MVHR systems have emerged as essential technologies for enhancing IAQ and improving energy efficiency in residential buildings, especially within the context of energy retrofits. Early investigations predominantly relied on theoretical assessments and simulation-based evaluations. For example, Garman et al. [11] analysed the potential of MVHR systems in cold climates through dynamic simulations, emphasising reductions in heating energy demand exploring real operational performance.
Later studies shifted toward empirical evidence, capturing the behaviour of MVHR systems under actual operating conditions. Stamp et al. [12] performed an experimental study on retrofitted housing in London, documenting seasonal variations in MVHR efficiency, although detailed analyses of user interactions and building-specific constraints were limited. Similarly, Hesaraki and Holmberg [13] combined field measurements and simulations in Nordic climates, focusing on overall energy performance but overlooking the impacts of occupancy patterns and partial-load operations.
Recent studies, such as the one by Alhindawi et al. [6] have conducted a seasonal evaluation of indoor air quality and thermal performance in naturally ventilated, airtight, energy-efficient dwellings. Their findings highlight that, even in the absence of mechanical ventilation systems, challenges related to maintaining adequate indoor air quality persist, especially during colder months when occupants tend to reduce natural ventilation to preserve thermal comfort. These results emphasise the importance of carefully balancing airtightness and ventilation strategies to ensure both energy efficiency and healthy indoor environments, a balance that becomes even more complex when dealing with retrofitting constraints in heritage buildings.
In the context of historic buildings, few works address the integration of MVHR systems from an operational perspective. Bartolucci et al. [7] emphasised, through a review of energy efficiency strategies in historic buildings, the importance of implementing ventilation systems that maintain both high IAQ and the architectural integrity of heritage assets. Similarly, Robaerti et al. [14] developed theoretical frameworks combining multi-objective optimisation and analytic hierarchy processes to guide MVHR integration into historic Italian buildings; however, their approach did not include post-occupancy monitoring to validate system performance under real operating conditions. Compared with these prior works—largely based on theoretical frameworks, catalogue values or design-stage assumptions—our study contributes post-occupancy operational evidence under heritage constraints. Specifically, we document (i) persistent supply–exhaust imbalance beyond the ±10% post-commissioning target, (ii) heritage-driven hydraulic penalties in the external duct runs (≈24–36 Pa in the exhaust path versus ≈2–5 Pa in supply), and (iii) IAQ outcomes that improve the mean yet still present daily CO2 means >900–1000 ppm under high occupancy. This operational picture complements the strategic recommendations in Bartolucci et al. by showing that balancing, duct routing and spatially distributed demand control are first-order drivers of delivered performance in retrofitted heritage dwellings.
In contrast to previous research, which has focused on theoretical optimisation or high-level reviews, this study provides detailed operational evidence of MVHR in a retrofitted heritage dwelling. This is of particular importance as it addresses the lack of empirical data in this domain. By quantifying efficiency, pressure losses, and IAQ under actual conditions, the evidence base for sustainable heritage retrofits is strengthened.
In addition to technical standards such as ASHRAE 62.1, EN 16798-1 and CIBSE Guide C, heritage retrofits are guided by conservation frameworks including the ICOMOS Principles for the Conservation of Heritage Sites and Historic England’s guidance on energy efficiency in traditional dwellings. These documents highlight the need for reversible and minimally invasive interventions, reinforcing that the operational constraints observed in this study are not only technical but also regulatory. Our findings provide empirical evidence that complements such guidance by quantifying the performance penalties associated with heritage-constrained duct geometries and imbalanced airflow conditions.
The effectiveness of MVHR also depends on proper installation and operational tuning. White et al. [15] showed that design–execution mismatches, such as misplacement of supply/exhaust terminals or incorrect airflow rates, can severely degrade performance, a problem particularly relevant in architecturally constrained environments. Hamid et al. [16] further demonstrated that occupancy-driven ventilation modes, like boost functions, have a significant impact on both energy use and CO2 concentrations.
Further research has examined the socio-technical and comfort-related aspects of the operation of MVHR, which are of particular significance in the context of heritage retrofits. In such cases, architectural and spatial constraints have been shown to exacerbate the challenges associated with the implementation of MVHR. Berneiser et al. [17] emphasised that the long-term acceptance of mechanical ventilation systems is influenced not only by technical performance but also by user attitudes, perceived comfort, and trust in the technology. Concurrently, Ouis et al. [18] conducted a review of noise emissions from ventilation systems, asserting that acoustic disturbances persist as a primary source of dissatisfaction and have the potential to compromise the efficacy of ventilation, particularly in residential settings where retrofitting constraints limit the options for effective sound insulation.
Occupancy sensing via environmental monitoring has attracted increasing interest, driven by the potential for optimising building energy management and ensuring occupant comfort. Passive, indirect methods, particularly those based on CO2 concentration monitoring, have been extensively studied as proxies for human presence, alongside auxiliary indicators such as temperature and humidity.
Initial research on occupancy estimation predominantly utilized physics-based models grounded in mass balance equations. Wei et al. [19] evaluated both steady-state and dynamic modelling approaches based on CO2 concentrations, applying them to simulations of spaces such as small offices and large conference rooms. Their study compared physical and statistical methods, highlighting trade-offs between simplicity, responsiveness, and estimation accuracy. Rather than focusing solely on energy-saving potentials, they assessed the feasibility of CO2-based methods for real-time occupancy prediction.
Experimental studies under real-world conditions have also explored the relationship between indoor CO2 concentrations and building ventilation performance. Grygierek and Ferdyn-Grygierek [20] conducted a summer-long experimental campaign in a single-family test house, using in situ measurements of metabolic CO2. Although occupancy was controlled and monitored, the primary aim was to develop a method to create specific occupancy prediction models. Their results nonetheless reinforced the close link between indoor CO2 dynamics, occupant presence, and ventilation effectiveness.
Sensor placement plays a critical role in enhancing the accuracy of CO2-based environmental monitoring for occupancy-related applications. Pei et al. [21] investigated the impact of sensor placement in mechanically ventilated spaces, finding that in mixing ventilation systems, sensors installed at exhaust vents provide more accurate predictions of breathing-zone CO2 concentrations. Conversely, in displacement ventilation systems, wall-mounted sensors at occupant breathing height yield better results. Our study (see Section 3) corroborates these findings, emphasising that strategic sensor placement is essential for improving the reliability of occupancy estimation in mechanically ventilated environments.
Comprehensive reviews by Rueda et al. [22], Chen et al. [23] and Song & Calautit et al. [24] detailed syntheses of the evolution of environmental-based occupancy detection technologies. These works systematically highlight the trade-offs among modelling complexity, data collection and processing demand, and the feasibility of deploying such systems in real-world building environments.
The technical benefits of MVHR systems are well established, nevertheless there is still a shortage of long-term empirical studies examining their operational behaviour in dwellings of heritage buildings. Furthermore, a few studies have addressed occupancy estimation, indoor air quality (IAQ) and ventilation system performance simultaneously under real-world, post-retrofit conditions. This research addresses this issue by integrating environmental monitoring, occupancy inference and system analysis in a heritage dwelling that has been retrofitted for energy efficiency.

2. Case Study

This section outlines the methodology used to evaluate the real-world operational performance of the MVHR system installed during the energy retrofit of a heritage-protected dwelling in Vitoria-Gasteiz (see Figure 1). It also describes the integrated monitoring and control setup implemented during this process.

2.1. Monitoring Setup

The study was carried out in a ground-floor (F0) dwelling of a retrofitted heritage building located in Vitoria-Gasteiz (Figure 1) [25]. The intervention encompassed the implementation of a high-efficiency dual-flow MVHR unit (SIBER DF SKY 2 2/2L model, manufactured by SIBER Spain) [26]. This intervention was undertaken with the objective of ensuring that IAQ is maintained in accordance with ASHRAE 62 standards [27].
In order to facilitate non-intrusive integration with the existing building envelope, the exterior supply and exhaust ducts were routed vertically to the rooftop. The total horizontal run (XY plane) spans 8.50 m, while the vertical rise (Z axis) measures 9.60 m. The duct geometry and characteristics, including diameters and bends, are summarised in Table 1. The configuration is designed to adhere to the manufacturer’s guidelines while addressing the spatial limitations imposed by the building’s designated heritage status.
The duct system was rigid, circular galvanised steel (Class D airtightness), with a horizontal run of 8.5 m and vertical riser of 9.6 m, incorporating two 90° swept elbows. The system included F7 supply filters and G4 extract filters, an EC fan with electronic flow regulation, and demand-control readiness through CO2 sensing. No humidity recovery or silencers were installed, consistent with the spatial constraints of the dwelling.
An intensive monitoring and control system was implemented to assess post-retrofit energy behaviour, as detailed in the DiB-EPB open-access dataset [28]. Figure 2 and Figure 3 illustrate the physical layout of the instrumentation, while Figure 4 shows the MVHR installation in the F0 dwelling.
The monitored variables include the following:
  • MVHR system energy consumption: electrical power and cumulative use.
  • Airflow parameters at supply and exhaust points: air velocity, temperature, relative humidity, and CO2 concentration.
  • Indoor environmental quality (IEQ): room temperature, relative humidity, and CO2 levels measured at breathing height in the main living area.
  • Outdoor environmental conditions: ambient temperature and humidity, obtained from a weather station located on the second floor (and Figure 3).
  • Mechanical ventilation system layout: Figure 4 shows the MVHR installation in the F0 dwelling, featuring a high-performance dual-flow unit (Siber DF SKY 2 AL) with electronic flow regulation via low-consumption EC motors.
This monitoring strategy facilitates a robust assessment of system performance under real occupancy and environmental conditions, thus enabling the evaluation of both energy efficiency and IAQ maintenance.

2.2. Data Acquisition

The data acquisition process was designed to enable a detailed and reliable evaluation of the MVHR system’s operation and its contribution to indoor air quality and energy performance. A network of sensors was installed with the objective of monitoring the key physical variables involved in the ventilation process. A series of measurements were collected on a continuous basis at 10-s intervals. The measurements comprised indoor air quality (temperature, relative humidity, and CO2), duct airflow characteristics (velocity, temperature, humidity, and CO2), outdoor ambient conditions, and electrical power consumption of the ventilation unit.
The analysis focused on 22 days across spring, autumn, and winter 2021, during which the MVHR system operated continuously at its nominal setting. These days were selected to ensure measurement stability and seasonal coverage. To further justify the selection of the 22 monitoring days, climatic distribution data were analysed for the entire year 2021. Figure 5 presents the annual variation in outdoor air temperature in Vitoria-Gasteiz, where the selected monitoring days are highlighted and cover the most representative seasonal conditions of a heating-dominated Basque climate, including early spring, late autumn, and winter. This confirms that the analysed dataset captures the dominant operational scenarios relevant for MVHR performance assessment, despite the restricted number of continuous days available due to occupant-related noise concerns. These climatic distributions therefore reinforce the validity of the operational campaign as representative of typical environmental conditions in the study context.
The selection of these days was made according to the following criteria: The study will cover the most typical seasonal conditions in a heating-dominated Basque climate, including early spring, late autumn and winter. It will also ensure data stability and completeness, avoiding sensor interruptions or anomalous records.
Indoor sensors were deployed in representative zones of occupancy, living room and bedroom, while duct-mounted probes were installed at the supply and exhaust branches to capture airflow conditions before and after the heat exchanger. The external ambient variables were recorded using a weather station installed on the building’s second floor. The electrical power consumption of the ventilation system was monitored using a precision wattmeter.
To elucidate the configuration of the monitoring system and its correlation with the performance indicators, Figure 6 presents a schematic representation of the integrated sensor layout and data-processing pipeline utilised in the study. The diagram illustrates the physical location of sensors (indoor, outdoor, duct-mounted) and their respective variables, as well as the way the collected data contributes to the calculation of Key Performance Indicators (KPIs) such as thermal efficiency, airflow balance, and pressure losses. The employment of a flowchart-style representation has been demonstrated to facilitate understanding of the direct links between raw measurements and performance evaluation metrics. This approach supports transparency and reproducibility of the methodology.
As illustrated in Figure 6, the data acquisition structure integrates multi-point measurements that are processed directly to compute thermal and airflow KPIs for system performance analysis. The diagram is structured in three layers: the top layer presents the various types of sensors installed to monitor indoor climate, MVHR system parameters, and outdoor environmental conditions. The middle layer is responsible for the grouping of the measured variables according to their spatial or functional origin, which can be categorised as follows: indoor conditions, airflow parameters, and outdoor conditions. Finally, the final layer displays the KPIs derived from the collected data, including thermal efficiency, useful efficiency, airflow imbalance, and pressure losses. Arrows are employed to illustrate the directional flow of information, thereby demonstrating the way raw measurements are integrated into the process of KPI computation. The flowchart provides a framework for understanding the translation of sensor data into performance metrics for evaluating the operation of MVHR in a heritage retrofit context, thereby promoting transparency and reproducibility.
Occupancy inferences were derived primarily from CO2 concentration dynamics. To enhance reliability, cross-checks were performed with ventilation unit operating profiles and temporal plausibility tests. However, no direct occupant logs or motion sensors were used, which introduces uncertainty in demand-controlled ventilation applicability.

2.3. Reproducibility and Data Sharing

All monitoring protocols, sensor specifications, data processing techniques, and calibration procedures are thoroughly documented in a previously published open-access doctoral dissertation by the lead author [25]. This reference provides comprehensive information regarding the measurement instrumentation employed for the assessment of carbon dioxide, temperature, humidity, air velocity, and electrical power. Additionally, it encompasses the configuration of the sensor network and the applied calibration methodologies. The document also includes sensor model numbers and manufacturer specifications, such as for duct probes and air velocity sensors. The complete dataset, incorporating both raw and processed measurements, is available via Mendeley Data [28].

3. Materials and Methods

The subsequent section delineates the set of KPIs utilised to evaluate the operational behaviour of the MVHR system installed in the retrofitted heritage dwelling. The analysis is based on real-time monitored data and focuses on thermal recovery performance, energy efficiency, air balance, and pressure losses. The performance assessment was conducted in accordance with internationally recognized standards and guidelines. Ventilation rates and indoor air quality criteria were referenced to ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality [27] and EN 16798-1: Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings [29]. Indoor air-quality thresholds were operationalised following EN 16798-1. In line with this standard, CO2 classes are defined by the differential with respect to outdoor air. Given the measured outdoor baseline of ~400–450 ppm in this study (Section 3), the operational threshold of 900 ppm corresponds approximately to the upper bound of Category II (≈+500 ppm above outdoors), while values approaching 1200 ppm denote a shift towards Category III (≈+800 ppm). Throughout the analysis we therefore report absolute CO2 values together with their implicit differential to the measured outdoor baseline. We interpret exceedances >900–1000 ppm as loss of Category II performance requiring either increased flow, improved balancing (±10% per ASHRAE 62.1), or spatially distributed demand control. Thermal efficiency and ductwork pressure loss calculations followed CIBSE Guide C: Reference Data [30] and the ASHRAE Handbook—Fundamentals [31]. These standards provided the basis for evaluating airflow balance, CO2 concentration, and thermal recovery efficiency under real-use conditions. The methodology encompasses nine calculated metrics, which are grouped into the following categories: The methodology encompasses nine calculated metrics, grouped into the following categories:
  • Thermal efficiency indicators (Equations (1)–(4));
  • The quantification of airflow and thermal power (see Equations (5)–(7));
  • Airflow imbalance (Equation (8));
  • Ductwork pressure losses (see Equations (9)–(11)).

3.1. Thermal Efficiency Indicators

Thermal performance was assessed using two complementary indicators: apparent thermal effectiveness and useful efficiency. The apparent thermal effectiveness ( ε t h e r m a l ,   a p p ) quantifies the system’s capacity to elevate the temperature of the incoming outdoor air toward indoor conditions, accounting for real-world losses across the exchanger, ductwork, and control logic (Equation (1)):
ε t h e r m a l ,   a p p = T a _ S u p _ I n t     T a _ o u t T a _ I n T a _ O u t ,
where
  • T a _ s u p i n t : temperature of supply air at the indoor grille;
  • T a _ o u t : outdoor air temperature;
  • T a _ i n : indoor air temperature.
Useful efficiency ( η u s e f u l ) expresses the ratio of sensible thermal power recovered to the electrical power consumed by the MVHR fans. It is calculated separately for the exhaust and supply branches (Equations (2)–(4)):
η u s e f u l _ E x h = Q ˙ E x h P e ,
η u s e f u l _ S u p = Q ˙ S u p P e ,
η t o t = η u s e f u l _ E x h + η u s e f u l _ S u p ,
where
  • Pe: instantaneous electric power demand of the EC fans (W),
  • Q ˙ E x h : thermal power extracted from the indoor air,
  • Q ˙ S u p : thermal power delivered to the supply air.
These expressions define the useful thermal efficiency of the exhaust and supply branches, and their sum, ηtot, represents the total system efficiency. The thermal powers Q ˙ E x h and Q ˙ S u p are calculated as described in Section 3.3. These indicators provide a system-level view of thermal recovery under operational conditions, which is essential for evaluating the real-world performance of MVHR systems in sustainability-constrained heritage retrofits.

3.2. Airflow Measurement

Volumetric airflow rates ( q ˙ ) are calculated from point velocity readings at the duct sections (Equation (5)):
q ˙ = v × A ,
where
  • v is the local air velocity (m/s);
  • A is the duct cross-sectional area (m2), calculated as A = πD2/4, with D being the duct diameter.
This method enables continuous and non-intrusive assessment of airflow rates, which is essential for verifying compliance with ventilation standards such as ASHRAE 62.1 [27]. Notably, this standard recommends maintaining supply/exhaust flow imbalance within ±10% to ensure adequate pressure control and indoor air quality, particularly in airtight, energy-efficient retrofitted buildings.

3.3. Thermal Power Calculation

Thermal power flows ( Q ˙ ) are determined based on airflow rates, air density, specific heat capacity, and temperature differences across the heat exchanger (Equations (6) and (7)):
Q ˙ E x h = q ˙ E x h   ·   ρ a · C a · ( T E x h I n t T E x h E x t )
Q ˙ S u p = q ˙ S u p ·   ρ a · C a · ( T S u p I n t T S u p E x t )
where
  •   ρ a = 1.20   k g / m 3 (air density);
  • C a = 1005 J k g · K (specific heat of air);
  • T_ExhExt and T_SupExt are temperatures of exhaust and supply air at the exchanger.
These equations provide daily quantification of thermal gains and losses, providing a basis for evaluating the useful heat recovery delivered by the system. In the context of sustainable retrofits, such calculations are essential for assessing energy efficiency and guiding improvements in system design and commissioning.

3.4. Airflow Imbalance Ratio

The airflow imbalance ratio quantifies the deviation between supply and exhaust volumetric flow rates and is defined as (Equation (8)):
I m b a l a n c e [ % ] = | Q ˙ S u p Q ˙ E x h | Q ˙ E x h × 100
This metric is critical for ensuring proper pressure management and maintaining AQ, particularly in airtight, retrofitted dwellings where even moderate imbalances can compromise system performance. Persistent imbalance reduces heat recovery efficiency and undermines the effectiveness of demand-controlled ventilation strategies, highlighting the need for precise flow measurement and post-installation balancing.

3.5. Ductwork Pressure Losses

Pressure losses in the external ductwork (Equation (11)), especially significant due to the length and geometry imposed by heritage constraints, are estimated as the sum of frictional (ΔPf) (Equation (9)) and local (ΔPI) (Equation (10)) losses:
Δ P f = f · L D ·   ρ a · v 2 2
Δ P I = k · ρ a · v 2 2
Δ P t o t = Δ P f + Δ P I
where
  • f = 0.021 Darcy friction factor;
  • k = 0.5 Local loss coefficient per 90° elbow;
  • L: duct length (m);
  • D: duct diameter (m);
  • v: air velocity (m/s);
  • ρ a : air density (kg/m3).
These pressure losses, when combined with airflow measurements, provide insight into variations in fan power demand and their impact on overall system efficiency. In heritage retrofits, where duct routing is often constrained by architectural limitations, such losses become a critical factor in overall performance degradation.
Equivalent lengths for each bend and fitting were determined using CIBSE tables [30] and added to the straight duct runs to account for additional frictional resistance. Local resistance values (k) were incorporated to reflect pressure losses from the two elbows and terminations. This approach ensures that both frictional losses along the duct length and local losses due to fittings are included in the total pressure drop estimation.
Ductwork pressure losses were estimated following standard engineering practice, as outlined in CIBSE Guide C: Reference Data [30] and the ASHRAE Handbook—Fundamentals [31]. Calculations were based on typical assumptions for duct flow, applying a friction factor of f = 0.021 and local resistance coefficients (k) of 0.5 for circular ducts and elbow fittings. Equivalent lengths for each bend and fitting were determined using CIBSE tables [30] and added to the straight duct runs to account for additional frictional resistance. Due to the constraints imposed by the building’s heritage status, it was not feasible to install instrumentation for direct static pressure measurements. Although this introduces some uncertainty, the adopted approach aligns with established methods for situations where in situ measurements are impractical.

4. Results and Discussion

This section presents the results of the performance evaluation of the MVHR system installed in the ground-floor (F0) dwelling. The analysis focuses on twenty-two days of monitored operation during 2021. The selection of these days was made on the basis that both the supply and exhaust fans were operating continuously at their standard settings. This ensured the stability of system performance. This selection enables a representative evaluation of the system’s performance under typical real-use conditions.
The results are structured around the KPIs defined in Section 3 and supported by monitored environmental data, system characteristics, and calculated parameters. Table 2, Table 3, Table 4, Table 5, Table 6, Table 7, Table 8 and Table 9 provide detailed quantitative results, which are discussed below.
  • Table 2 summarizes the operating periods of the ventilation system during selected 22 days in 2021, identified through cross-referencing the fan power profiles and airflow measurements in the F0 dwelling.
  • Table 3 compiles the physical and geometrical constants used in KPI estimation, including air density, specific heat capacity, and duct dimensions. These values form the basis for consistent thermodynamic calculations across the dataset.
  • Table 4 shows the mean values of indoor and outdoor environmental conditions, including air temperature, relative humidity, and CO2 concentrations. These averages provide insight into the prevailing conditions during the analysis window and establish context for assessing system effectiveness [28].
  • Table 5 details the monitored performance of the ventilation unit itself, including temperature and velocity measurements at various duct points, as well as fan power consumption. This data serves as the raw input for KPI estimation [28].
  • Table 6 summarizes the key performance metrics derived from the monitoring campaign. These include thermal recovery efficiency, useful energy efficiency, airflow imbalance ratio, and thermal power recovery, offering a comprehensive assessment of system performance under real operating conditions.
  • Table 7 presents the calculated airflow velocities and volumetric flows in the external ducts, both for the supply and exhaust paths. This information enables verification of compliance with ASHRAE 62.1 [27] requirements regarding flow balance and proper ventilation rates.
  • Table 8 shows the estimated pressure losses in the external duct network due to both friction and local resistances. These losses are relevant for understanding the increased electrical demand observed in the fans, particularly in retrofit contexts involving long or complex duct routing.
  • Table 9 provides statistical descriptors (mean, standard deviation, min, max) for all physical variables and calculated KPIs over the operational period. This allows for evaluation of variability and consistency in system behaviour.
The integrated analysis demonstrates that, while the MVHR system exhibited acceptable performance regarding thermal efficiency and flow balance, the pressure losses induced by the extended external ductwork contributed significantly to increased fan energy use. These findings underscore the significance of meticulous duct routing in heritage retrofits and substantiate the pertinence of the multi-sensor monitoring approach utilised in this study.
Table 2. Studied periods where ventilation system was turned on in F0 dwelling.
Table 2. Studied periods where ventilation system was turned on in F0 dwelling.
DateStart HourEnd HourOperating Time [min]
31 March 20219:5216:46415
3 April 20219:5521:11677
6 April 202115:1620:40325
8 April 20219:3121:19709
9 April 202118:0020:41162
10 April 20219:3615:06331
11 April 202115:3416:0431
14 April 20219:4016:29140
14 April 202119:5022:09410
25 April 202118:4420:39116
27 April 20219:2321:38736
5 November 202111:3911:5113
7 November 202111:2917:30362
12 November 202116:4519:59195
14 November 20219:5720:01605
20 November 202114:0514:5450
22 November 20219:0610:0055
30 November 202111:1411:2916
12 December 202110:5220:09558
16 December 202114:1718:37261
17 December 20219:0412:06183
25 December 202110:4212:0079
The operational behaviour of the MVHR system was evaluated over a set of selected days in 2021, during which the system remained continuously active. The analysis is structured around three key performance indicators (KPIs): thermal efficiency, electrical consumption and energy recovery performance. These indicators are defined in Section 3. To ensure consistent interpretation of the monitored values, the physical and geometrical constants utilised in the calculations are outlined in Table 3. These constants include air density, specific heat capacity, and duct dimensions.
Table 3. Physical and geometrical constants.
Table 3. Physical and geometrical constants.
ρa [kg/m3]Ca [kJ/kgK]Dduct_xy [m]Dduct_z [m]Aduct_xy [m]Aduct_z
[m]
Lduct_xy [m]Ldcut_z
[m]
1.221.010.130.250.010.058.509.60
As illustrated in Table 4, the mean environmental conditions during each operating period are presented, both in indoor and outdoor settings. The findings indicate that the indoor air temperature maintained a relatively stable range of 22–23 °C, while outdoor temperatures exhibited significant fluctuations. The concentrations of indoor carbon dioxide (CO2) ranged from 480 to 1000 parts per million (ppm), with several instances of exceedances of the commonly recommended thresholds for indoor air quality (IAQ) (e.g., 900 ppm). This confirms that IAQ performance was not uniform across the campaign, with distinct differences between seasons (Figure 7 and Figure 8). Importantly, although the global dataset mean remained below 650 ppm, two days (14 April 2021 and 5 November 2021) daily averages surpassed 900 ppm during autumn and winter. As Figure 7 shows, both days had an increase in dwelling occupancy of more than 1000 ppm, being unable to improve the indoor air quality despite the MVHR being in operation. This reflects reduced window airing and higher occupancy intensity in colder periods, underlining the relevance of demand-controlled ventilation strategies.
Table 4. Physical variables’ average of indoor and outdoor air of F0 dwelling.
Table 4. Physical variables’ average of indoor and outdoor air of F0 dwelling.
DateTa-Out
Average
[C]
RHOut
Average
[%]
CO2-Out
Average [ppm]
Vwind-Out
Average [m/s]
Ta-In
Average
[C]
CO2-In
Average [ppm]
RHIn
Average
[%]
31 March 202110.7077.00410.690.0022.91535.1340.58
3 April 202110.7077.00401.350.0022.66485.4243.55
6 April 20210.0070.64414.120.0022.45683.7240.07
8 April 20216.0052.30404.451.1022.58507.6135.52
9 April 20216.0052.30403.911.1022.75740.7741.85
10 April 20216.0052.30405.621.1022.58488.8443.64
11 April 20216.0052.30410.151.1022.53671.8043.12
14 April 20216.0052.30432.001.1023.67960.5039.61
14 April 20216.0052.30410.371.1022.63496.8837.37
25 April 20216.0052.30411.151.1021.90812.3057.13
27 April 20216.0052.30413.501.1022.64554.4449.27
5 November 20216.9188.09453.921.2123.221004.9647.57
7 November 20218.8187.36418.382.0922.48478.6042.57
12 November 202111.3591.27443.522.0522.36682.1846.64
14 November 20219.9790.26417.952.5622.43507.3548.73
20 November 202110.1578.17446.491.9222.38523.6440.51
22 November 20215.3287.73413.451.5822.36605.7542.52
30 November 202110.4477.63415.910.4822.31629.5743.97
12 December 202111.8280.09419.140.9122.36467.1143.66
16 December 20214.9990.87480.091.0522.16590.4238.20
17 December 20216.3099.71469.790.8522.09626.5537.21
25 December 202110.8082.74402.811.4622.39696.2745.37
The raw measurements of the ventilation system’s physical variables, air temperatures, velocities, humidity levels, CO2 concentrations, and accumulated fan energy consumption, are displayed in Table 5. These values constitute the direct input for the KPI calculations. It is noteworthy that the velocity measurements in the exhaust ducts were systematically higher than those in the supply ducts, indicating a persistent flow imbalance that affects overall system performance.
Table 5. Average and accumulated values of ventilation system’s physical variables of F0 dwelling.
Table 5. Average and accumulated values of ventilation system’s physical variables of F0 dwelling.
DateTa-SupExt Average
[C]
Ta-ExhExt Average [C]Ta-SupInt
Average [C]
Ta-ExhInt Average [C]Va-SupExt_xy Average
[m/s]
Va-ExhExt_xy Average
[m/s]
CO2-SupIn Average [ppm]CO2-ExhInt Average [ppm]RHSupExt Average [%]RHExhExt Average [%]RHSupInt Average [%]RHExhInt Average [%]Pe-Ventilation
Accumulated [kWh]
31 March 202119.7220.9220.5621.121.393.47462.12455.7141.5341.5542.2237.950.50
3 April 202119.4320.9621.0921.511.073.47413.12421.9247.0645.2044.5841.280.72
6 April 202117.8219.4319.8120.241.453.44511.76491.8145.9143.8642.5339.500.39
8 April 202117.7719.1418.9619.511.413.46436.15451.3341.9539.5539.7137.530.86
9 April 202118.2119.4919.1319.721.443.45494.83492.2946.5544.8245.4142.170.20
10 April 202118.2519.5919.2819.861.423.42425.06441.1949.7047.2047.6444.710.41
11 April 202118.3419.8019.8720.311.043.34500.97474.2149.7848.7648.2243.930.03
14 April 202117.9619.6619.9320.361.073.48632.19532.3443.4043.8743.1337.610.16
14 April 202117.4718.8918.8919.401.423.43427.37437.4143.4441.9041.8538.580.50
25 April 202119.7721.1020.8521.401.423.35607.27645.5350.9749.1249.2945.910.15
27 April 202119.3220.8120.8721.341.323.37449.71455.8952.4250.0049.4646.180.88
5 November 202116.4617.8918.4218.791.333.80556.19490.5651.1752.2750.3944.520.01
7 November 202116.8618.1318.1418.661.363.88429.49439.8050.3348.8548.5045.000.37
12 November 202117.6718.8218.6319.171.363.85515.77491.8353.2352.0152.2248.480.20
14 November 202117.5918.8818.8619.381.373.88436.14448.0255.5954.0753.7749.840.66
20 November 202116.3917.7418.1018.541.353.81445.66447.2649.0647.6046.4443.180.05
22 November 202115.9117.3317.5818.071.413.89440.32435.5350.0248.9547.8143.960.06
30 November 202115.2316.4916.6017.051.343.86483.74482.0154.0852.2151.3948.460.02
12 December 202116.4317.7717.9718.451.373.86418.02443.9555.9252.6251.8349.440.57
16 December 202114.1715.7316.1116.591.413.86490.52499.1549.1247.2246.0842.620.25
17 December 202113.4615.1015.6016.071.393.84486.23494.3847.7046.0444.5740.970.18
25 December 202116.1717.5117.5818.101.564.02489.26503.3054.1752.7052.0648.130.08
The calculated performance indicators are summarised in Table 6, including apparent thermal efficiency (ξthermal,app), total useful efficiency (ηtot), and supply/exhaust energy recovery. The results obtained demonstrate a mean thermal efficiency of 0.74 (10th–90th percentile: 0.59–0.88), and a total useful efficiency (ηtot), close to unity. These values are below the catalogue specifications but consistent with expectations under real operating conditions with heritage-imposed constraints.
The investigation revealed that flow imbalance emerged as a predominant factor affecting both thermal efficiency and energy use in the installation that was the subject of the study. As demonstrated in Table 6, the imbalance ratio ranged from 3.66% to 67.33%, with a mean of 23.41%. These values exceed the post-commissioning limits recommended by ASHRAE 62.1 [27], which advises supply and exhaust flow rates to remain within 10% of each other.
Table 6. Studied KPI of the F0 dwelling’s ventilation systems: accumulated energies, efficiency and imbalance values.
Table 6. Studied KPI of the F0 dwelling’s ventilation systems: accumulated energies, efficiency and imbalance values.
DatePe-Ventilation
Accumulated [kWh]
QExh
Accumulated [kWh]
(Equation (6))
QSup
Accumulated [kWh]
(Equation (7))
ηuseful_Exh
(Equation (2))
ηuseful_Sup
(Equation (3))
ηtot
(Equation (4))
ξthermal,app (Equation (1))Imbalance
[%]
(Equation (8))
31 March 20210.500.070.120.240.150.390.8166.69
3 April 20210.720.320.300.410.450.860.877.17
6 April 20210.390.220.230.600.581.190.883.66
8 April 20210.860.230.300.340.270.610.7829.06
9 April 20210.200.030.050.270.160.430.7867.33
10 April 20210.410.080.120.290.180.470.8058.27
11 April 20210.030.010.010.390.420.810.846.85
14 April 20210.160.080.070.460.530.990.7912.11
14 April 20210.500.180.210.420.360.780.7814.56
25 April 20210.150.030.040.300.190.490.9356.48
27 April 20210.880.330.380.430.380.810.8914.84
5 November 20210.010.010.010.710.941.650.7124.19
7 November 20210.370.190.160.430.510.940.6816.18
12 November 20210.200.070.060.320.340.660.663.85
14 November 20210.660.290.260.400.450.850.7110.80
20 November 20210.050.040.030.600.791.390.6524.43
22 November 20210.060.040.030.550.671.230.7217.73
30 November 20210.020.010.010.480.571.060.5215.44
12 December 20210.570.370.290.520.641.160.5819.99
16 December 20210.250.220.180.710.861.570.6518.10
17 December 20210.180.170.140.760.951.700.5919.87
25 December 20210.080.050.040.520.561.080.597.46
To provide a more comprehensive characterisation of the airflow performance, Table 7 presents the air velocities and volumetric flows in the external ducts. The data confirm the presence of a significant supply–exhaust imbalance. The exhaust velocities and flow rates were consistently higher than those of the supply branch. This imbalance consequently engenders disparate heat capacity rates within the exchanger, thereby inducing a direct distortion in thermal recovery indicators.
The present findings demonstrate that system-level metrics, such as ξthermal,app and ηtot, are structurally depressed under unbalanced conditions. The data indicates that the proper testing, adjusting, and balancing (TAB) procedures were either not sufficient or were circumvented during commissioning, which is a significant oversight with substantial consequences for energy and IAQ performance.
Table 7. Velocity and flow of air in exterior conducts of the F0 dwelling’s ventilation system.
Table 7. Velocity and flow of air in exterior conducts of the F0 dwelling’s ventilation system.
DateVa-SupExt_xy [m/s]Va-ExhExt_xy [m/s]QSupExt_xy [m3/s]
(Equation (5))
QExh_Ext_xy [m3/s] (Equation (5))Va-SupExt_z [m/s]
(Equation (5))
Va-ExhExt_z [m/s] (Equation (5))
31 March 20211.393.470.020.040.350.87
3 April 20211.073.470.010.040.270.87
6 April 20211.453.440.020.040.360.86
8 April 20211.413.460.020.040.350.86
9 April 20211.443.450.020.040.360.86
10 April 20211.423.420.020.040.350.86
11 April 20211.043.340.010.040.260.83
14 April 20211.073.480.010.040.270.87
14 April 20211.423.430.020.040.350.86
25 April 20211.423.350.020.040.350.84
27 April 20211.323.370.020.040.330.84
5 November 20211.333.800.020.050.330.95
7 November 20211.363.880.020.050.340.97
12 November 20211.363.850.020.050.340.96
14 November 20211.373.880.020.050.340.97
20 November 20211.353.810.020.050.340.95
22 November 20211.413.890.020.050.350.97
30 November 20211.343.860.020.050.340.97
12 December 20211.373.860.020.050.340.96
16 December 20211.413.860.020.050.350.97
17 December 20211.393.840.020.050.350.96
25 December 20211.564.020.020.050.391.01
Values estimated used the constants shown in Table 3.
As demonstrated in Table 8, quantitative analysis is employed to measure the pressure losses that occur in both the exhaust and supply ducts. This analysis reveals a clear asymmetry between the two branches. The exhaust path demonstrated a consistent loss of pressure, ranging from 26 to 35 Pa, while the supply path remained below 6 Pa.
This asymmetry, attributable to the elongated duct runs and the multiple bends in the exhaust path, resulted in the fans operating under augmented resistance, consequently escalating electrical consumption (see Table 5). The resulting energy overhead led to a reduction in net efficiency of the system, even when thermal recovery performance was satisfactory.
These findings elucidate the “hydraulic penalty” imposed by duct geometry and routing, which were shaped by the need to comply with heritage preservation constraints. This “hydraulic tax” exemplifies a broader challenge in sustainable heritage retrofits: striking a balance between respecting architectural integrity and achieving seamless integration of energy-efficient systems.
Although this work did not monitor the heating system directly, the reduction in infiltration and the recovery of sensible heat documented here are expected to reduce overall heating energy demand in the dwelling. Extrapolation of the measured ηtot values indicates that fan energy use was generally offset by recovered heat, thereby contributing to a net reduction in space-heating loads.
Table 8. Pressure losses in exterior conducts of the F0 dwelling’s ventilation system.
Table 8. Pressure losses in exterior conducts of the F0 dwelling’s ventilation system.
DateΔPf-ExhExt_xyz [Pa]
(Equation (9))
ΔPl-ExhExt_xyz
[Pa]
(Equation (10))
Δptot_ExhExt_xyz
[Pa]
(Equation (11))
ΔPf-SupExt_xyz
[Pa]
(Equation (9))
ΔPlSupExt_xyz
[Pa]
(Equation (10))
ΔPtot-SupExt_xyz
[Pa]
(Equation (11))
31 March 202110.8715.6226.491.752.524.28
3 April 202110.8615.6126.471.041.492.53
6 April 202110.6915.3726.061.892.724.60
8 April 202110.7715.4926.261.792.584.37
9 April 202110.7115.3926.101.882.704.58
10 April 202110.5615.1725.731.812.614.42
11 April 202110.0514.4424.490.981.412.40
14 April 202110.9215.6926.611.041.492.53
14 April 202110.6115.2525.851.812.604.41
25 April 202110.1014.5224.621.822.614.43
27 April 202110.2614.7525.011.572.253.82
5 November 202113.0218.7231.741.592.283.87
7 November 202113.5619.5033.061.672.404.08
12 November 202113.3619.2132.571.672.404.07
14 November 202113.5819.5133.091.692.434.13
20 November 202113.1218.8531.971.642.364.01
22 November 202113.6419.6133.261.792.584.37
30 November 202113.4719.3632.821.632.343.97
12 December 202113.4319.3032.731.702.444.13
16 December 202113.4419.3132.751.802.594.39
17 December 202113.2719.0732.341.752.514.26
25 December 202114.5920.9835.572.193.155.34
Values estimated used the constants shown in Table 3 and the estimated physical variables shown in Table 7.
Collectively, these tables furnish a thoroughgoing overview of the MVHR system’s operational performance under real-world conditions, thereby enabling a nuanced interpretation of its energy efficiency, airflow balance, and capacity to deliver acceptable indoor air quality in a protected building context.
As illustrated in Table 9, the mean value of the thermal expansion coefficient, designated as ξthermal,app, was found to be 0.74, with no observed values exceeding 0.93. The energy recovery (ηtot) metric oscillated around unity, with sporadic periods exceeding 1.0, suggesting that energy recovery was, at times, adequate to counterbalance fan consumption. However, these conditions were not sustained, largely due to flow imbalance and pressure loss penalties.
The analysis demonstrates that catalogue values are performance ceilings rather than guarantees, a fact that is especially evident in the context of heritage retrofits characterised by complex geometries. The empirical evidence collected thus far appears to provide a robust basis for the introduction of updated commissioning standards. These new standards should include mandatory TAB verification, performance-based acceptance criteria (e.g., ηtot > 1.5), and careful airflow tuning to approach the declared efficiencies in real-world applications.
Table 9. Statistical parameters of physical variables and studied KPI of the F0 dwelling’s ventilation system.
Table 9. Statistical parameters of physical variables and studied KPI of the F0 dwelling’s ventilation system.
MeanStandard
Deviation
MinMaxIQ1IQ2IQ3Interquartile Range
Pe-Ventilation Accumulated [kWh]0.330.280.010.880.080.230.520.44
Qexh Accumulated [kWh]0.140.120.010.370.040.080.230.19
Qsup [kWh]0.140.110.010.380.040.120.240.20
ηuseful_Sup0.500.240.150.950.320.480.650.33
ηuseful_Exh0.460.150.240.760.340.430.570.23
ηtot0.960.390.391.700.650.901.200.55
ξthermal,app0.740.110.520.930.650.750.820.17
Imbalance [%]23.4119.943.6667.339.9716.9625.5915.62
Δptot-ExhExt_xyz [Pa]29.353.7424.4935.5726.0129.1732.776.76
Δptot-SupExt_xyz [Pa]4.040.712.405.343.944.204.410.47
To complement the tabulated results, Figure 9, Figure 10, Figure 11, Figure 12 and Figure 13 provide synthesized visualizations that enhance the understanding of seasonal performance trends and system behaviour under real-use conditions.
Figure 9 highlights the seasonal distribution of indoor CO2 levels recorded during selected days in spring, autumn, and winter 2021. Although mean concentrations remained below 650 ppm, several exceedances above 900 ppm occurred in autumn and winter. These peaks reveal insufficient spatial ventilation control, underscoring the need for spatially distributed demand-controlled ventilation strategies in heritage retrofits, where architectural constraints often hinder airflow optimisation.
As shown in Figure 10, total useful efficiency (ηtot) exhibited noticeable seasonal variability. While median values clustered near unity, the data displayed significant dispersion across seasons. This variability stems from persistent supply–exhaust imbalances and hydraulic penalties imposed by heritage-driven duct geometry. Notably, the system occasionally achieved ηtot values above 1.0, indicating periods when recovered sensible heat exceeded fan energy consumption. However, this performance was not consistently maintained over extended periods.
Figure 11 illustrates the distribution of apparent thermal effectiveness (ξthermal,app), with values approaching 0.9 under optimal conditions but ranging overall from 0.59 to 0.93—below manufacturer specifications. This deviation reflects the combined effects of airflow imbalance, duct losses, and non-ideal operating conditions, confirming that catalogue values represent theoretical ceilings rather than guaranteed performance.
As depicted in Figure 12, a positive correlation exists between total exhaust duct pressure losses and fan energy demand. The observed linear trend confirms the existence of a “hydraulic tax”, whereby an increase in resistance due to heritage-driven duct geometry directly corresponds to higher electrical consumption by the MVHR fans. This finding serves to reinforce the importance of optimising duct routing and implementing rigorous post-installation balancing procedures with a view to minimising energy penalties.
Collectively, these visualisations validate the quantitative findings and provide actionable insights for improving the performance of MVHR systems in heritage contexts. The necessity for system-level KPIs, spatially distributed sensing, and commissioning protocols tailored to the constraints of protected buildings is emphasised.

4.1. System Performance in Real Operating Conditions

The monitored heat recovery ventilation installation exhibited a mean apparent thermal effectiveness (ξthermal,app) of 0.74 (10th–90th percentile: 0.59–0.88). Although values approaching 0.9 were observed, the central tendency lies well below the nominal performance commonly claimed for counter-flow residential exchangers. This discrepancy is explained by two structural features of the installation: (i) a very large flow imbalance between supply and exhaust streams (mean 92%, range 81–106%), and (ii) substantial hydraulic penalties arising from the heritage-constrained ductwork (a short-radius ninety-degree elbow, a horizontal branch of 8.6 m, a vertical riser of 9.6 m, and a distant outdoor terminal).
Under these conditions, ξthermal,app must be read as a system-level effectiveness: it aggregates exchanger behaviour, network losses, control interventions (for example, bypass or anti-frost), and measurement noise; it cannot be interpreted as an intrinsic exchanger effectiveness.
The total useful efficiency (ηtot)—defined as total sensible heat recovered divided by total electrical energy consumed—clustered around unity, with a mean of 0.96 and values spanning 0.39 to 1.70 (interquartile range 0.69–1.18). This indicates that, on average, the aerodynamic and control penalties offset much of the heat recovered; yet non-negligible periods exceeded unity, demonstrating that the system is intermittently capable of returning more sensible heat than the electrical energy it expends. The fact that this capability does not consolidate in the central tendency is fully consistent with the measured imbalance and pressure-loss burden.
Branch-wise useful efficiencies were lower and asymmetric:
  • ηuseful_Sup averaged 0.50 (max 0.95);
  • ηuseful_Exh averaged 0.46 (max 0.76).
These values quantify the differential aerodynamic and thermal penalties borne by each path under imbalance. They are diagnostically informative, but they should not be used as the headline energy metric, because they relate each branch’s useful heat to a shared electrical denominator while operating under very different hydraulic penalties and capacities. For energy decision-making, ηtot is the only coherent, system-integrating indicator.

4.2. Flow Imbalance as the First-Order Driver

The magnitude of the flow imbalance measured in this instance (Table 6) significantly exceeds the recommended post-commissioning thresholds, indicating that the proper testing, adjusting, and balancing (TAB) procedures were either insufficient or not fully implemented. Three empirical facts follow directly: (1) the apparent thermal effectiveness departs from nominal exchanger values because the temperature-based numerator and denominator are referenced to streams with markedly unequal heat-capacity rates; (2) the total useful efficiency remains compressed around unity because the fans are forced to operate off-design to partially compensate for the network, increasing electrical work without a proportional gain in useful heat; and (3) the supply and exhaust branch efficiencies diverge, so they cannot be expected to reconcile with ηtot under the present definitions and operating conditions. In short, the imbalance is the structural cause that invalidates any attempt to back-calculate intrinsic exchanger performance from these operational data.

4.3. Indoor Air Quality: Measurable Gains, Limited Robustness

A key goal of MVHR systems in retrofitted dwellings is to ensure consistent IAQ. As demonstrated in Table 4, the system successfully achieved a substantial reduction in indoor CO2 concentrations, with a mean level of approximately 625 ppm. However, occasional peaks above 900–1000 ppm were observed, primarily during periods of extended occupancy or when DCV was either inactive or not spatially optimised. These fluctuations were attributed to the absence of zonal CO2 sensors, which constrained the system’s capacity to adapt to varying occupancy patterns, particularly in rooms distant from the primary sensor.
To further elucidate the drivers of IAQ variability, a one-way ANOVA was performed on daily mean CO2 concentrations across the monitored seasons (spring, autumn, winter) (Figure 13). The analysis revealed no statistically significant differences between seasons (F(2,19) = 0.84; p = 0.447), indicating that seasonal effects alone do not explain the observed variability. In contrast, an ANCOVA incorporating system operating time as a covariate demonstrated a strong negative association between ventilation duration and indoor CO2 (F(1,18) = 12.07; p = 0.0027), with an estimated slope of −0.416 ppm·min−1 (≈−25 ppm·h−1). See Figure 10 for the relationship between CO2 and operating time. This finding emphasises that operational behaviour, as opposed to seasonality, is the predominant factor influencing IAQ performance in the examined heritage dwelling. The absence of interaction between season and operating time (p = 0.912) suggests that the effect of extended operation is consistent across climatic conditions.
Beyond statistical associations, Table 5 confirms continuous airflow delivery during the specified periods, evidencing that both supply and exhaust fans operated consistently throughout the monitored intervals. However, the absence of adaptive control mechanisms and system imbalance resulted in constraints on the robustness of IAQ improvements. While the intervention evidently improved air quality in comparison with the baseline conditions, it did not consistently maintain recommended thresholds across all zones and timeframes. These findings emphasise the significance of incorporating spatially distributed, demand-controlled ventilation to enhance responsiveness and ensure more stable IAQ performance in subsequent retrofitting initiatives.

4.4. Pressure Losses and the “Hydraulic Tax” of Heritage Constraints

The duct layout, shaped by the need to comply with heritage preservation guidelines, introduced non-negligible aerodynamic penalties. As presented in Table 8, the pressure losses resulting from friction and local resistances attained 24.5–35.6 Pa in the exhaust branch, in comparison to 2.4–5.3 Pa in the supply branch. This discrepancy arises due to the elongated duct runs and the multiple bends in the exhaust path, which necessitate the fans to overcome higher resistance. Consequently, this results in an increase in electrical consumption (see Table 5) and a reduction in the system’s net efficiency, despite the satisfactory thermal recovery performance.
The findings of this study elucidate the “hydraulic tax” imposed by heritage constraints: a measurable energy overhead that reflects the broader challenge of integrating energy-efficient systems within protected architectural contexts. The measurement of pressure losses revealed an approximate value of 29 Pa (mean) in the exhaust–exterior path and 4 Pa in the supply–exterior path. This is accompanied by a mean electrical power of around 66 W, which collectively substantiates the observation that the system incurs a non-trivial penalty for compliance.
This imposes a direct burden on total efficiency (ηtot) necessitating additional electrical input to maintain target flow rates in a loss-heavy network. Absent mandatory testing, adjusting, and balancing procedures, such systems may achieve regulatory compliance in theory but demonstrate suboptimal performance in practice, both in terms of energy efficiency and hygiene. The findings emphasise the necessity of minimising pressure losses through the optimisation of duct routing and the implementation of rigorous post-installation verification procedures. Such measures are imperative to ensure the full realisation of sustainability objectives in the context of heritage retrofits. Beyond efficiency losses, reducing pressure drops also contributes to lower operational energy demand, thereby supporting climate mitigation goals and reducing the environmental footprint of ventilation systems in heritage buildings. Although the heating system was not directly monitored in this study, the reduction in infiltration and the recovery of sensible heat documented here are expected to decrease the overall space-heating demand of the dwelling. Extrapolation of the measured ηtot values, which clustered around unity, indicates that the sensible heat recovered by the MVHR system broadly offset the fan energy consumption. This suggests a net reduction in heating loads during operation. Nevertheless, no comprehensive integration with the total energy demand of the dwelling or an economic/payback analysis was performed. These aspects are beyond the scope of the present work and remain essential for future investigations on the cost-effectiveness of heritage retrofits.

4.5. Methodological Implication: No Algebraic Closure Should Be Enforced

A key methodological implication of this study is that no algebraic closure should be enforced between system-level and branch-level performance indicators. As outlined in Section 3, the total system efficiency ηtot, defined as the ratio of total sensible heat recovered to electrical energy consumed, differs fundamentally from the branch-specific metrics (ηuseful_Sup and ηuseful_Exh) which are influenced by localized hydraulic penalties and airflow paths. The absence of mathematical closure between these indicators does not constitute a flaw in the data; rather, it is indicative of real-world system imbalances and dispersion losses that are inherent in heritage-constrained retrofits.
The approach of treating the installed, unbalanced ventilation system as if it were a laboratory-grade heat exchanger is methodologically unsound. The discrepancies observed in this study underscore the necessity for the refinement of commissioning protocols and data interpretation practices, with the objective of accounting for the intricacies inherent in in situ performance. In this context, it is imperative to prioritise system-level Key Performance Indicators (KPIs) such as ηtot and ξt,apparent for the evaluation of installed performance. These metrics are particularly salient as they more accurately reflect the operational realities of constrained retrofit environments. It is recommended that future research and commissioning standards incorporate this distinction to avoid misinterpretation and to support more robust, context-sensitive performance assessments.

4.6. Comparison with the Manufacturer’s Operating Ranges

The Siber DF SKY 2 MVHR unit has been specified to achieve thermal effectiveness levels of up to 95% under ideal conditions. These conditions include balanced flows, electronically commutated constant-flow fans, airtight Class D ductwork (Safe Click), and minimal hydraulic resistance. However, the monitored installation, constrained by heritage preservation requirements, deviated from these assumptions.
As demonstrated in Table 6 and Table 9, the system demonstrated a mean apparent thermal effectiveness (ξthermal,app) of 0.74 (P10–P90: 0.59–0.88), with maximum values not exceeding 0.93. The range of flow imbalance was from 81% to 106%, and pressure losses, particularly in the exhaust branch, were significant. These conditions resulted in CO2 excursions beyond the 900–1000 ppm range, leading to a decline in overall system efficiency. The total efficiency (ηtot) exhibited a tendency to approximate unity, with sporadic periods exceeding 1.0, suggesting that energy recovery could, on occasion, counterbalance fan consumption, albeit not with any degree of consistency.
These findings confirm that catalogue specifications represent performance ceilings rather than guarantees, especially in heritage retrofits where duct geometry and routing are constrained. The observed deviations justify:
(i)
the use of ηtot as a comprehensive performance metric;
(ii)
interpreting ξthermal,app as a system-level indicator rather than an intrinsic exchanger property; and
(iii)
the need for updated commissioning protocols, including mandatory testing, adjusting, and balancing, performance-based acceptance criteria (e.g., ηtot > 1.5), and airtight ductwork (Class D or equivalent).
Due to the absence of baseline monitoring, a direct comparison with pre-retrofit conditions or alternative ventilation strategies, such as natural ventilation or conventional MVHR systems, was not feasible. Nonetheless, existing literature consistently indicates that heritage dwellings lacking MVHR systems are prone to frequent CO2 exceedances and elevated infiltration-related heat losses Trofimova et al. [32] and Hesaraki & Holmberg [33]. Post-occupancy evaluations further validate the reliability of campaign-based monitoring in assessing ventilation performance, even in the absence of pre-intervention data. In addition, the demonstrated effectiveness of demand-controlled ventilation in optimising both energy consumption and indoor air quality supports the observed improvements in this case.
Ultimately, attaining catalogue-level performance in real-world heritage contexts necessitates the utilisation of high-performance equipment and the implementation of rigorous design, installation, and verification practices, which are to be adapted in accordance with the constraints inherent to protected buildings.

4.7. Comparison with Previous Work

In relation to recent heritage-focused literature, our findings operationalise the design-stage insights reported by Bartolucci et al. by quantifying the mechanisms that depress realised performance: marked flow imbalance, equivalent-length penalties and the absence of room-level demand control. While catalogue exchanger effectiveness would suggest higher system-level ξ values, the measured imbalance and hydraulic burden explain the observed ξthermal,app distribution (median ≈ 0.74) and the compression of ηtot around unity. These empirical results therefore refine existing guidance by indicating that commissioning specifications in heritage retrofits should elevate post-installation TAB, pressure-drop limits and zonal sensing to mandatory acceptance criteria.

4.8. Limitations of the Study

A further limitation of this study is that, despite the availability of year-round monitoring, the system was not continuously operated by the occupants. The main reason reported was perceived noise, which discouraged prolonged use. Consequently, the analysis was restricted to 22 days in which the MVHR system remained fully active. This highlights a recurrent barrier in the adoption of MVHR systems in retrofitted heritage dwellings: beyond technical performance, acoustic comfort and user acceptance must be addressed to ensure sustained operation.
In addition, no baseline monitoring was available prior to the retrofit, nor were parallel measurements taken under natural ventilation or conventional MVHR strategies. As a result, this study cannot quantify the net benefits relative to pre-retrofit conditions or alternative ventilation approaches. Future studies should include baseline or counterfactual scenarios to strengthen comparative evaluation.
No integration with the total dwelling energy demand or retrofit payback analysis was performed. These aspects are left for future work.

5. Conclusions

This study demonstrates that MVHR integration in heritage dwellings can improve indoor air quality and recover sensible heat, but real-world performance is constrained by flow imbalance and ductwork penalties imposed by architectural conservation requirements. The measured mean apparent thermal effectiveness (0.74) and total useful efficiency (0.96) fall below catalogue values, confirming that such figures represent idealised ceilings rather than expected outcomes in constrained retrofits.
The key findings indicate the following:
Significant flow imbalance (>80%) systematically depressed thermal efficiency, IAQ, and fan performance, underlining the need for post-commissioning balancing.
Indoor CO2 was generally reduced to a mean of ~625 ppm, though occasional exceedances above 900–1000 ppm occurred during periods of high occupancy. These findings highlight the necessity of demand-controlled operation with distributed sensing, as well as the importance of post-commissioning balancing and adaptive ventilation strategies in heritage retrofits.
Pressure losses of 25–35 Pa in the exhaust path imposed a measurable “hydraulic tax”, reinforcing the need for careful duct routing in heritage contexts.
To ensure sustainable outcomes, heritage retrofits should adopt mandatory success criteria, including flow imbalance ≤ 10%, ηtot ≥ 1.5, and CO2 < 900 ppm for ≥95% of occupied hours, supported by pressure verification and certified Testing, Adjusting and Balancing. Catalogue performance can only be approached through rigorous commissioning, geometry-aware design, and demand-responsive operation.
Importantly, the results demonstrate that integrating MVHR in heritage dwellings is feasible and can contribute to sustainability goals when technical, architectural and comfort-related factors are considered together. This aligns with the objectives of the European Green Deal and the UN Sustainable Development Goals, highlighting the compatibility of cultural preservation and energy efficiency in heritage contexts.
In conclusion, this work provides operational evidence that bridges the critical gap between the expected theoretical performance of heritage buildings and their real-world outcomes. The insights gained reinforce the idea that sustainable retrofits must integrate energy efficiency, indoor environmental quality, and conservation requirements. Future research should focus on expanding long-term monitoring and user-centred approaches to ensure that MVHR systems in heritage contexts support occupant well-being and the broader transition towards climate-resilient, sustainable built environments.

Author Contributions

Conceptualization, C.G.-S., Z.A.-L. and A.U.; methodology, C.G.-S.; software, C.G.-S.; validation, C.G.-S., Z.A.-L. and A.U.; formal analysis, C.G.-S., Z.A.-L., N.R.-A. and M.O.-M.; investigation, C.G.-S. and A.U.; resources, C.G.-S. and A.U.; data curation, C.G.-S.; writing—original draft preparation, C.G.-S. and Z.A.-L.; writing—review and editing, Z.A.-L., A.U., N.R.-A. and M.O.-M.; visualization, C.G.-S.; supervision, C.G.-S.; project administration, C.G.-S. and A.U.; funding acquisition, Z.A.-L., C.G.-S. and A.U. All authors have read and agreed to the published version of the manuscript.

Funding

This work was financially supported by the European project ENERPAT, funded under the Interreg SUDOE programme (Ref.: SOE1/P3/F0362), and by the Ensanche 21 Zabalgunea Urban Development Company of the Vitoria-Gasteiz City Council. Additional support was provided by the European Regional Development Fund (ERDF) under the slogan “A way of making Europe”, and by the Spanish Ministry of Science, Innovation and Universities (MICIU) and the State Research Agency (AEI) (Ref.: PID2021-126739OB-C22 and PID2024-156054OB-C22). The primary author acknowledges the scholarships granted by the University of the Basque Country (UPV/EHU) and the University of Bordeaux through the Euskampus—IdEx Bordeaux collaboration project (Ref.: PIFBUR 16/26), as well as postdoctoral fellowships from the Basque Government (Refs.: POS 2021 1 0019, POS 2022 2 0043, and POS 2023 2 0025).

Institutional Review Board Statement

The study involved only non-invasive environmental monitoring of indoor air parameters (temperature, humidity, CO2) without collecting personal or sensitive data. The retrofit and monitoring were authorised and supervised by the Ensanche 21 Zabalgunea Urban Development Company of the Vitoria-Gasteiz City Council within the framework of subsidized energy rehabilitation in the European project ENERPAT SUDOE.

Informed Consent Statement

Not applicable.

Data Availability Statement

Data Availability Statements are available at Mendeley Data [23].

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
MVHRMechanical Ventilation with Heat Recovery
IAQIndoor Air Quality
SDGsSustainable Development Goals
DCVDemand-Controlled Ventilation
MLMachine Learning
BMSBuilding Management Systems
SFPSpecific Fan Power
TABTesting, Adjusting and Balancing
IEQIndoor Environmental Quality
KPIKey Performance Indicators
Ta-OutOutdoor air temperature
RH-OutOutdoor relative humidity
CO2-OutOutdoor carbon dioxide
V wind-OutOutdoor Window velocity
Ta-InIndoor air temperature
RH-InIndoor relative humidity
CO2-InIndoor carbon dioxide
Ta-Sup-ExtSupply air temperature in exterior duct
Ta-Exh-ExtExhaust air temperature in exterior duct
Ta-Sup-IntSupply air temperature in interior duct
Ta-Exh-IntExhaust air temperature in interior duct
Va-Sup-Ext_xySupply air velocity of the exterior duct in XY plane
Va-Exh-Ext_xyExhaust air velocity of the exterior duct in XY plane
Va-Sup-Ext_zSupply air velocity of the exterior duct in Z axis
Va-Exh-Ext_zExhaust air velocity of the exterior duct in Z axis
CO2-Sup-IntSupply dioxide carbon in interior duct
CO2-Exh-IntExhaust dioxide carbon in interior duct
RH_Sup-ExtSupply relative humidity in exterior duct
RH_Exh ExtExhaust relative humidity in exterior duct
RH_Sup IntSupply relative humidity in interior duct
RH_Exh IntExhaust relative humidity in interior duct
Pe VentilationAccumulated Electrical energy consumption of ventilation system
Q ExhAccumulated exhaust energy
Q SupAccumulated supply energy
η t_apparentApparent thermal efficiency
η useful_SupSupply useful efficiency
η useful_ExhExhaust useful efficiency
η totTotal useful efficiency
ΔP f-ExhExt_xyzExhaust friction pressure loss in XY plane and Z axis
ΔP l-ExhExt_xyzExhaust local pressure loss in XY plane and Z axis
ΔP tot_ExhExt_xyzTotal exhaust pressure loss in XY plane and Z axis
ΔP f-SupExt_xyzSupply friction pressure loss in XY plane and Z axis
ΔP lSupExt_xyzSupply local pressure loss in XY plane and Z axis
ΔP tot-SupExt_xyzTotal supply pressure loss in XY plane and Z axis

References

  1. Directive-2018/844-EN-EUR-Lex. Available online: https://eur-lex.europa.eu/eli/dir/2018/844/oj/eng (accessed on 29 July 2025).
  2. Morawska, L.; Tang, J.W.; Bahnfleth, W.; Bluyssen, P.M.; Boerstra, A.; Buonanno, G.; Cao, J.; Dancer, S.; Floto, A.; Franchimon, F.; et al. How can airborne transmission of COVID-19 indoors be minimised? Environ. Int. 2020, 142, 105832. [Google Scholar] [CrossRef] [PubMed]
  3. Mejri, O.; Palomo Del Barrio, E.; Ghrab-Morcos, N. Experimental Assessment of Demand-Controlled Ventilation Strategies for Energy Efficiency and Indoor Air Quality in Office Spaces. Buildings 2023, 3, 17. [Google Scholar] [CrossRef]
  4. Duffield, G.; Bunn, S. Indoor Air Quality; Parliamentary Office of Science and Technology, UK Parliament: London, UK, 2023. [Google Scholar] [CrossRef]
  5. Mejri, O.; Del Barrio, E.P.; Ghrab-Morcos, N. Energy performance assessment of occupied buildings using model identification techniques. Energy Build. 2011, 43, 285–299. [Google Scholar] [CrossRef]
  6. Alhindawi, I.; McGrath, J.A.; Sood, D.; O’Donnell, J.; Byrne, M.A. A seasonal assessment of indoor air quality and thermal performance in naturally ventilated airtight energy-efficient dwellings. Build. Environ. 2025, 276, 112862, ISSN 0360-1323. [Google Scholar] [CrossRef]
  7. Bartolucci, B.; Frasca, F.; Flores-Colen, I.; Bertolin, C.; Siani, A.M. Key Performance Indicators: Their use in the energy efficiency retrofit for historic buildings. Procedia Struct. Integr. 2024, 55, 110–118, ISSN 2452-3216. [Google Scholar] [CrossRef]
  8. Zuraimi, M.S.; Pantazaras, A.; Chaturvedi, K.A.; Yang, J.J.; Tham, K.W.; Lee, S.E. Predicting occupancy counts using physical and statistical Co2-based modeling methodologies. Build. Environ. 2017, 123, 517–528. [Google Scholar] [CrossRef]
  9. European Commission. The European Green Deal. COM(2019) 640 Final. Available online: https://www.eea.europa.eu/policy-documents/com-2019-640-final (accessed on 10 May 2025).
  10. United Nations. Transforming Our World: The 2030 Agenda for Sustainable Development. A/RES/70/1. Available online: https://www.un.org/en/development/desa/population/migration/generalassembly/docs/globalcompact/A_RES_70_1_E.pdf (accessed on 10 May 2025).
  11. Garman, I.; Myhren, J.A.; Mattsson, M. Energy use of advanced ventilation systems in a cold climate single-family house. Energy Build. 2025, 330, 115329. [Google Scholar] [CrossRef]
  12. Stamp, S.; Burman, E.; Shrubsole, C.; Chatzidiakou, L.; Mumovic, D.; Davies, M. Seasonal Variations and the Influence of Ventilation Rates on IAQ: A Case Study of Five Low-Energy London Apartments. Available online: https://journals.sagepub.com/doi/10.1177/1420326X211017175 (accessed on 29 July 2025).
  13. Hesaraki, A.; Holmberg, S. Energy performance of low temperature heating systems in five new-built Swedish dwellings: A case study using simulations and on-site measurements. Build. Environ. 2013, 64, 85–93. [Google Scholar] [CrossRef]
  14. Roberti, F.; Oberegger, U.F.; Lucchi, E.; Troi, A. Energy retrofit and conservation of a historic building using multi-objective optimization and an analytic hierarchy process. Energy Build. 2017, 138, 1–10. [Google Scholar] [CrossRef]
  15. White, J.; Gillott, M.C.; Wood, C.J.; Loveday, D.L.; Vadodaria, K. Performance evaluation of a mechanically ventilated heat recovery (MVHR) system as part of a series of UK residential energy retrofit measures. Energy Build. 2016, 110, 220–228. [Google Scholar] [CrossRef]
  16. Hamid, A.A.; Johansson, D.; Bagge, H. Ventilation measures for heritage office buildings in temperate climate for improvement of energy performance and IEQ. Energy Build. 2020, 211, 109822. [Google Scholar] [CrossRef]
  17. Berneiser, J.; Maier, D.; Gölz, S.; Auerswald, S.; Carbonare, N.; Pflug, T. Socio-technical perspectives for mechanical ventilation systems in buildings: Predictors of attitude and user satisfaction. Energy Effic. 2025, 18, 14. [Google Scholar] [CrossRef]
  18. Ouis, D.; Hassanain, M.A.; Alshibani, A.; Ghaithan, A.M. Noise from Heating, Ventilation, and Air Conditioning, HVAC, Systems: A Review of its Characteristics, Effects and Control. J. Build. Eng. 2025, 112, 113770. [Google Scholar] [CrossRef]
  19. Wei, S.; Tien, P.W.; Chow, T.W.; Wu, Y.; Calautit, J.K. Deep learning and computer vision based occupancy CO2 level prediction for demand-controlled ventilation (DCV). J. Build. Eng. 2022, 56, 104715. [Google Scholar] [CrossRef]
  20. Grygierek, K.; Ferdyn-Grygierek, J. Design of ventilation systems in a single-family house in terms of heating demand and indoor environment quality. Energies 2022, 15, 8456. [Google Scholar] [CrossRef]
  21. Pei, G.; Rim, D.; Schiavon, S.; Vannucci, M. Effect of sensor position on the performance of CO2-based demand controlled ventilation. Energy Build. 2019, 199, 109358. [Google Scholar] [CrossRef]
  22. Rueda, L.; Agbossou, K.; Cardenas, A.; Henao, N.; Kelouwani, S. A comprehensive review of approaches to building occupancy detection. Build. Environ. 2020, 180, 106966. [Google Scholar] [CrossRef]
  23. Chen, Z.; Jiang, C.; Xie, L.; Wang, Y.; Li, N. Building occupancy estimation and detection: A review. Energy Build. 2018, 174, 276–292. [Google Scholar] [CrossRef]
  24. Song, W.; Calautit, J. Impact of occupancy behaviour on building energy efficiency: What’s next in detection and monitoring technologies? Next Energy 2025, 8, 100350. [Google Scholar] [CrossRef]
  25. Giraldo-Soto, C. Optimised Monitoring Techniques and Data Analysis Development for in-Situ Characterization of the Building Envelope’s Real Energetic Behaviour. Doctoral Thesis, University of Bordeaux, Bordeaux Cedex, France, University of Basque Country, Santsoena, Spain, 2021. Available online: http://www.theses.fr/2021BORD0041 (accessed on 26 July 2021).
  26. Admin, ‘SIBER Brand, MOD. SIBER DF SKY 2 2/2L-Ventilation System. Siber. Available online: https://www.siberzone.es/descarga/ (accessed on 29 July 2025).
  27. ASHRAE Standards 62.1 & 62.2. Available online: https://www.ashrae.org/technical-resources/bookstore/standards-62-1-62-2 (accessed on 29 July 2025).
  28. Giraldo-Soto, C.; Erkoreka, A.; Uriarte, A.; Flores-Abascal, I. Dataset of an energy monitoring system implemented in an eco-renovated heritage building located in Vitoria-Gasteiz and composed by three in-use dwellings with gas boiler, heat pump and ventilation systems. Mendeley Data 2025, 2. [Google Scholar] [CrossRef]
  29. EN 16798-1:2019; Energy Performance of Buildings—Ventilation for Buildings—Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Air Quality, Thermal Environment, Lighting and Acoustics. CEN: Brussels, Belgium, 2019.
  30. CIBSE (Chartered Institution of Building Services Engineers). Guide C: Reference Data; CIBSE: London, UK, 2007; ISBN 978-1-903287-80-4. 228p, Available online: https://www.cibse.org/knowledge-research/knowledge-portal/guide-c-reference-data-2007?id=a0q20000008I7oQAAS (accessed on 18 May 2025).
  31. ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers). ASHRAE Handbook—Fundamentals; ASHRAE: Atlanta, GA, USA, 2017; ISBN 978-1-939200-36-6. Available online: https://www.ashrae.org/technical-resources/ashrae-handbook/ashrae-handbook-online (accessed on 18 May 2025).
  32. Trofimova, P.; Cheshmehzangi, A.; Deng, W.; Hancock, C. Post-Occupancy Evaluation of Indoor Air Quality and Thermal Performance in a Zero Carbon Building. Sustainability 2021, 13, 667. [Google Scholar] [CrossRef]
  33. Hesaraki, A.; Holmberg, S. Demand-controlled ventilation in new residential buildings: Consequences on indoor air quality and energy savings. Indoor Built Environ. 2013, 24, 162–173. [Google Scholar] [CrossRef]
Figure 1. Exterior view of the retrofitted heritage building located in Vitoria-Gasteiz, Spain. The intervention preserved the original architectural character—stone façade, traditional fenestration, and tiled roofing, while integrating high-efficiency MVHR. The image illustrates the discreet integration of rooftop ductwork and ventilation terminals, highlighting the balance between energy performance and conservation requirements. Adapted from [25].
Figure 1. Exterior view of the retrofitted heritage building located in Vitoria-Gasteiz, Spain. The intervention preserved the original architectural character—stone façade, traditional fenestration, and tiled roofing, while integrating high-efficiency MVHR. The image illustrates the discreet integration of rooftop ductwork and ventilation terminals, highlighting the balance between energy performance and conservation requirements. Adapted from [25].
Sustainability 17 08493 g001
Figure 2. Sensor layout of the ground-floor (F0) dwelling in the retrofitted heritage building. The diagram illustrates the spatial distribution of indoor environmental sensors (temperature, relative humidity, CO2) and duct-mounted probes (air velocity, temperature, humidity, CO2) installed at supply and exhaust branches. Adapted from [25].
Figure 2. Sensor layout of the ground-floor (F0) dwelling in the retrofitted heritage building. The diagram illustrates the spatial distribution of indoor environmental sensors (temperature, relative humidity, CO2) and duct-mounted probes (air velocity, temperature, humidity, CO2) installed at supply and exhaust branches. Adapted from [25].
Sustainability 17 08493 g002
Figure 3. Exterior sensor array installed on the rooftop of the retrofitted heritage building in Vitoria-Gasteiz. The array includes meteorological sensors for ambient temperature, relative humidity, and wind speed, enabling continuous monitoring of outdoor environmental conditions. Adapted from [25].
Figure 3. Exterior sensor array installed on the rooftop of the retrofitted heritage building in Vitoria-Gasteiz. The array includes meteorological sensors for ambient temperature, relative humidity, and wind speed, enabling continuous monitoring of outdoor environmental conditions. Adapted from [25].
Sustainability 17 08493 g003
Figure 4. Layout of the mechanical ventilation system installed in the F0 dwelling. The system features a high-performance dual-flow unit (Siber DF SKY 2 AL) with electronic flow regulation via low-consumption EC motors. The diagram illustrates the supply (blue) and exhaust (red) duct networks, distributed through a false ceiling at a height of 2.30 m. Exterior ducts are also represented in both the XY-plane and Z-axis. Based on [25].
Figure 4. Layout of the mechanical ventilation system installed in the F0 dwelling. The system features a high-performance dual-flow unit (Siber DF SKY 2 AL) with electronic flow regulation via low-consumption EC motors. The diagram illustrates the supply (blue) and exhaust (red) duct networks, distributed through a false ceiling at a height of 2.30 m. Exterior ducts are also represented in both the XY-plane and Z-axis. Based on [25].
Sustainability 17 08493 g004
Figure 5. Monitored period of outdoor air temperature in Vitoria-Gasteiz during 2021. The highlighted markers indicate the zones to identify the selected monitoring days (22 days) used in the operational campaign.
Figure 5. Monitored period of outdoor air temperature in Vitoria-Gasteiz during 2021. The highlighted markers indicate the zones to identify the selected monitoring days (22 days) used in the operational campaign.
Sustainability 17 08493 g005
Figure 6. Schematic diagram of sensor network and performance evaluation flow for the MVHR system.
Figure 6. Schematic diagram of sensor network and performance evaluation flow for the MVHR system.
Sustainability 17 08493 g006
Figure 7. Indoor carbon dioxide evolution of the studied periods from 31 March 2025 to 5 November 2021.
Figure 7. Indoor carbon dioxide evolution of the studied periods from 31 March 2025 to 5 November 2021.
Sustainability 17 08493 g007
Figure 8. Indoor carbon dioxide evolution of the studied periods from 7 November 2025 to 25 December 2021.
Figure 8. Indoor carbon dioxide evolution of the studied periods from 7 November 2025 to 25 December 2021.
Sustainability 17 08493 g008
Figure 9. Seasonal distribution of indoor CO2 concentrations.
Figure 9. Seasonal distribution of indoor CO2 concentrations.
Sustainability 17 08493 g009
Figure 10. Seasonal Variability of Total Useful Efficiency (ηtot).
Figure 10. Seasonal Variability of Total Useful Efficiency (ηtot).
Sustainability 17 08493 g010
Figure 11. Seasonal distribution of apparent thermal effectiveness (ξthermal,app).
Figure 11. Seasonal distribution of apparent thermal effectiveness (ξthermal,app).
Sustainability 17 08493 g011
Figure 12. Correlation between exhaust-duct pressure losses and fan energy demand.
Figure 12. Correlation between exhaust-duct pressure losses and fan energy demand.
Sustainability 17 08493 g012
Figure 13. Daily mean indoor CO2 versus MVHR operating time (minutes per day), coloured by season. Lines show least-squares fits with 95% confidence bands. The overall ANCOVA slope is −0.416 ppm/min (95% CI −0.667 to −0.164), i.e., ≈−25.0 ppm/h; p = 0.0027.
Figure 13. Daily mean indoor CO2 versus MVHR operating time (minutes per day), coloured by season. Lines show least-squares fits with 95% confidence bands. The overall ANCOVA slope is −0.416 ppm/min (95% CI −0.667 to −0.164), i.e., ≈−25.0 ppm/h; p = 0.0027.
Sustainability 17 08493 g013
Table 1. Geometry and flow direction of exterior ventilation ducts for the ground-floor dwelling.
Table 1. Geometry and flow direction of exterior ventilation ducts for the ground-floor dwelling.
SectionLength
L [m]
Diameter
D [m]
Flow
Direction
Notes
Lx5.100.125HorizontalIncludes one 90° bend into Ly
Ly3.400.125Horizont2alIncludes a 90° bend into vertical riser
Lz9.600.250Vertical to roofIncludes two 90° swept elbows (entry + roof termination)
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Giraldo-Soto, C.; Azkorra-Larrinaga, Z.; Uriarte, A.; Romero-Antón, N.; Odriozola-Maritorena, M. Operational Performance of an MVHR System in a Retrofitted Heritage Dwelling: Indoor Air Quality, Efficiency and Duct Constraints. Sustainability 2025, 17, 8493. https://doi.org/10.3390/su17188493

AMA Style

Giraldo-Soto C, Azkorra-Larrinaga Z, Uriarte A, Romero-Antón N, Odriozola-Maritorena M. Operational Performance of an MVHR System in a Retrofitted Heritage Dwelling: Indoor Air Quality, Efficiency and Duct Constraints. Sustainability. 2025; 17(18):8493. https://doi.org/10.3390/su17188493

Chicago/Turabian Style

Giraldo-Soto, Catalina, Zaloa Azkorra-Larrinaga, Amaia Uriarte, Naiara Romero-Antón, and Moisés Odriozola-Maritorena. 2025. "Operational Performance of an MVHR System in a Retrofitted Heritage Dwelling: Indoor Air Quality, Efficiency and Duct Constraints" Sustainability 17, no. 18: 8493. https://doi.org/10.3390/su17188493

APA Style

Giraldo-Soto, C., Azkorra-Larrinaga, Z., Uriarte, A., Romero-Antón, N., & Odriozola-Maritorena, M. (2025). Operational Performance of an MVHR System in a Retrofitted Heritage Dwelling: Indoor Air Quality, Efficiency and Duct Constraints. Sustainability, 17(18), 8493. https://doi.org/10.3390/su17188493

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop