Next Article in Journal
Spatial Analysis of Accidental Oil Spills Using Heterogeneous Data: A Case Study from the North-Eastern Ecuadorian Amazon
Next Article in Special Issue
Heating and Cooling Performance of Office Buildings with a-Si BIPV Windows Considering Operating Conditions in Temperate Climates: The Case of Korea
Previous Article in Journal
Measuring the Benefits of the “One Belt, One Road” Initiative for Manufacturing Industries in China
Previous Article in Special Issue
Building Integrated Shading and Building Applied Photovoltaic System Assessment in the Energy Performance and Thermal Comfort of Office Buildings
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Development of a Metamodel to Predict Cooling Energy Consumption of HVAC Systems in Office Buildings in Different Climates

by
Mauricio Nath Lopes
1,* and
Roberto Lamberts
2
1
Department of Refrigeration and Air Conditioning, Federal Institute of Santa Catarina (IFSC), São José CEP 88103-310, Brazil
2
Department of Civil Engineering, Federal University of Santa Catarina (UFSC), Florianópolis CEP 88040-900, Brazil
*
Author to whom correspondence should be addressed.
Sustainability 2018, 10(12), 4718; https://doi.org/10.3390/su10124718
Submission received: 15 November 2018 / Revised: 30 November 2018 / Accepted: 6 December 2018 / Published: 11 December 2018

Abstract

:
The use of energy for space cooling is growing faster than any other end use in buildings, justifying the search for improvements in the energy efficiency of these systems. A simplified model to predict cooling energy consumption in Brazilian office buildings was developed. Artificial neural networks (ANNs) were trained from consumption data obtained by building simulation. As it is intended to be applicable to different climates, a new climate indicator also appropriate for hot and humid climates was proposed and validated. The Sobol sensibility analysis was performed to reduce the number of input factors and thus the number of cases to be simulated. The data was built with the simulation of 250,000 cases in Energyplus. Studies were conducted to define the sample size to be used for the ANN training, as well as to define the best ANN architecture. The developed metamodel was used to predict the consumption of Heating, Ventilating and Air Conditioning (HVAC) system of 66,300 new unseen cases. The results showed that the new proposed climate indicator was more accurate than the usual climate correlations, such as cooling degree hours. The developed metamodel presented good performance when predicting annual HVAC consumption of the cases used to obtain the model (R2 = 0.9858 and NRMSE = 0.068) and also of the unseen cases (R2 = 0.9789 and NRMSE = 0.064).

1. Introduction

Building energy consumption is growing, and has reached significant values in developed countries. Several factors contribute to the growing energy demand, including population growth, an increased demand for building services, the need for better comfort levels, and greater time spent by occupants inside buildings [1]. The use of energy for space cooling is growing faster than any other end use in buildings; it more than tripled between 1990 and 2016, and could triple again by 2050 [2]. For this reason, an improvement in the energy efficiency of buildings is currently one of the main objectives of energy policies in developed and emerging countries [3].
Elaborated and simplified methods have been proposed to predict building energy consumption. These methods have been applied in the design, operation, and retrofit of buildings in recent years [4,5,6,7]. The variety of methods can be divided into three primary categories: Engineering methods, statistical methods and hybrid methods. The engineering methods (also known as white box methods) use physical principles to calculate thermal dynamics and energy behavior of the building. Several dynamic building simulation softwares have been developed in order to use elaborated engineering methods such as DOE-2, EnergyPlus, BLAST, ESP-r and TRNSYS. Although these simulation tools are effective and accurate, they require many details of the building, its systems, and climate parameters, and these details are generally not available or are difficult to obtain. Another disadvantage is the time required by expert professionals, making evaluations difficult and expensive [5]. The statistical methods (also known as black box methods) are based on the deduction of a function that describes the behavior of a specific system from a relevant database. Additionally, these methods have been regarded as an alternative to the engineering methods, especially for the modeling of existing buildings [8], or during the early stage of architectural design [9], or in the control and operation of the buildings systems [10]. The main techniques used to create statistical models for estimate building energy consumption are multiple linear regression, artificial neural networks (ANN) and support vector machines (SVM). Statistical methods are limited by the fact that they require data, especially in large amounts [4]. In order to overcome the limitations of each previous method, the coupling between them generates hybrid methods or gray box methods.
In building modeling, there are three main strategies of coupling between the engineering and statistical methods. The first strategy uses statistical methods (machine learning) as physical parameters estimator. The second strategy uses statistics (multiple linear regression, ANN or SVM) in order to implement a learning model from data built with an engineering method. The third strategy uses statistical methods in fields where physical models are not effective and accurate enough [4].
In Brazil, the voluntary building energy labelling system for commercial buildings permits the evaluation of a building’s energy efficiency by a simplified or simulation method. The simplified method was developed using the second strategy mentioned above, since multiple linear regression was used with data obtained by simulations of different building sizes and constructive characteristics. Due to its limitations, this method is used to evaluate the envelope’s efficiency, not to predict the energy consumption of the building [11]. Recently, Melo et al. [12] developed a more accurate model to predict the annual cooling energy demand of commercial buildings and, thus, to replace the current method. Again, the model does not predict the energy that the Heating, Ventilating and Air Conditioning (HVAC) system will consume to supply the cooling demand. Reviews regarding prediction of building energy consumption [4,5,6] show that most studies develop models to estimate building energy performance and to predict heating/cooling demand rather than identifying actual consumption. Predicting building energy consumption is not an easy task since it is a function of the building characteristics, the energy systems characteristics, weather parameters, and occupants’ behavior [4]. Methods to include the impacts of occupant behavior have only been recently developed and there are many gaps in knowledge and limitations to current methodologies [13,14,15].
The objective of this research is to develop a hybrid model to predict the cooling energy consumption of HVAC systems in Brazilian office buildings. This study utilizes chilled water HVAC systems. The model consists of training an artificial neural network from consumption data obtained by building simulations of a large number of office buildings. Thus, the research was divided into three phases. In the first phase, a new climate indicator was developed for hot and humid climates. In the second phase, a sensitivity analysis was performed in order to identify the key variables. Simulations of office buildings using the EnergyPlus software were performed to obtain the data. In the third phase, the data were pre-processed to improve the stability of the neural networks training process, and a study was conducted to define the sample size to be used in these training. Then, the artificial neural networks were obtained and a refinement of the metamodel architecture was analyzed. Finally, the model was used to predict HVAC consumption of unseen cases to evaluate its performance.

2. Climate Indicator

The climate is a determining factor in the cooling demand of buildings, as well as in the efficiency of air conditioning equipment. For example, air cooled chillers operate more efficiently at times when the outdoor air temperature is lower. The weather files were used in building simulation while climate correlations were used in simplified methods of building energy prediction. This climate correlations generally used in the literature are heating degree days (HDD) and cooling degree days (CDD). These correlations are calculated from the mean daily dry bulb temperature and are useful where sensible heat is predominant: Cold or dry climates. In hot and humid climates, there is an increase in energy consumption associated with the dehumidification process. Therefore, it is necessary to look for new indicators which also consider the latent heat present in the cooling demand of the building. Huang et al. [16], Sailor et al. [17], Sailor [18], and Krese et al. [19] use the enthalpy latent days (ELD) to incorporate the influence of the latent load. Recent studies have sought to incorporate the influence of both loads (sensitive and latent) on a single climate indicator, either by the use of enthalpy [20] or the use of wet bulb temperature [21,22]. As high humidity is a characteristic of many Brazilian regions, it was necessary to analyze which climate indicator was appropriate to be used in this study, as described below.

2.1. Building Model

The annual cooling demand for a building model was obtained for 20 Brazilian cities using Energyplus software and their respective weather data files in EPW (Energyplus Weather Data) format. Two cities with extreme climates (cold and hot) were initially selected (Curitiba and Manaus), and then 18 other cities were included to represent intermediate climates. The concept of shell and core building was considered for the modeled office buildings, as presented in Figure 1a. A 15-story office building was used as a building model. Each floor was modeled with four perimeter thermal zones and an internal thermal zone, as show in Figure 1b. The perimeter zones were considered as the regions that extend from each facade up to 4.5 m towards the interior of the building (Figure 1b). Table 1 presents the characteristics of the model building and the HVAC system.
The annual cooling demand for the building was obtained through the sum of the hourly cooling demands on the chiller evaporator (output variable called Chiller Evaporator Cooling Energy in Energyplus). Heating demand was not the focus of this research because it is insignificant in Brazilian office buildings, but cannot be neglected in cold climates

2.2. CDH Calculation

According to McQuiston et al. [23], the degree-day method was the first method developed to estimate heating energy in single-family residential houses, and the procedure was based on the assumption that, on a long-term basis, solar and internal gains for a residential structure will offset heat loss when the mean daily outdoor temperature is 18 °C (base temperature). Therefore, this method considers that the building only needs heating when the outdoor temperature is lower than the base temperature. The calculated fuel consumption is proportional to the difference between the mean daily temperature and the base temperature. Based on this method, which considers that heating energy consumption is directly proportional to the degree-days value, the HDD (heating degree days) climate indicator is internationally used as a climate correction factor in the models for building energy consumption prediction [24]. Analogously, there is the definition of the cooling degree days (CDD) indicator, which allows evaluating the influence of the climate on the building cooling energy consumption, and it is calculated as follows.
CDD = n = 1 N ( t ¯ o t b ) +
where CDD is the cooling degree days, N is the number of days for the period analyzed, t ¯ o is the average daily outdoor temperature, and tb is the base temperature.
The cumulative energy consumption of a building has a linear relationship with the cumulative degree days (adding all the degree days from the first day to the last day for calculation of the energy consumption), as showed by Lin et al. [25] and Lukomshi et al. [26].
The base temperature is set individually for each building, but it is common to use certain values. The ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers) [27], for example, publishes CDD values for temperatures of 10.0, 18.3, 23.3 and 26.7 °C.
Adopting the same concept of degree days, the climate indicator can also be calculated considering the average temperature of each hour, instead of the average daily temperature. Thus, the cooling degree hours (CDH) is calculated according to the equation below.
CDH = n = 1 N ( t o t b ) +
where CDH is the cooling degree hours, N is the number of hours for the period analyzed, to is the average hourly outdoor temperature, and tb is the base temperature.
The CDH was the first climate indicator analyzed in this research because it better represents the period when the HVAC (Heating Ventilating and Air Conditioning) system is operating than cooling degree days (CDD) [28]; further, the estimation of cooling energy consumption is more accurate. The cooling degree hours (CDH) value for twenty Brazilian cities was calculated. The influence of the choice of the base temperature was evaluated through the use of values between 15 and 22 °C. A linear regression was used to represent the relationship between the annual cooling demand and the corresponding CDH value. The statistical index R2 (coefficient of determination) and the standard error were used to evaluate the goodness-of-fit between the predicted value of demand and the value obtained by simulation.
The results of the annual cooling demand for a building model and the CDH indicator (base temperature = 18 °C) are presented in Table 2 for each of the twenty Brazilian cities analyzed. Figure 2 shows the result of the linear regression used to relate CDH and annual cooling demand. The value obtained for R2 was 0.9428, and for the standard error was 12.11 kWh/m2·year.
The CDH was recalculated for different base temperatures to evaluate its influence on the results. Table 3 presents the value of the coefficient of determination (R2) obtained in each case. The analysis of the results shows that the value of R2 did not present significant variation, and the best result was obtained using the base temperature of 18 °C.

2.3. CEH Calculation

Buildings located in regions with hot and humid weather present a large amount of latent load on their cooling demand. Shin and Do [20] used the degrees days method to develop models for energy consumption predictions for two buildings in Texas. Two models were created, one using CDD calculated with dry bulb temperature (CDDT) according to Equation (1), and the other calculated with enthalpy (CDDH) according to Equation (3). As a result, the comparison utilizing the enthalpy-based CDD method resulted in a percent error of approximately 2% less than that of the temperature-based CDD method.
CDD H = n = 1 N ( h ¯ o h b ) +
where CDDH is the enthalpy-based cooling degree days, N is the number of days for the period analyzed, h ¯ o is the average daily outdoor enthalpy, and hb is the base enthalpy.
Considering most Brazilian cities present high values of temperature and humidity, enthalpy was also used in order to create a new climate indicator—called the CEH (Cooling Enthalpy Hours)—Equation (4).
CEH   = n = 1 N · ( h o h b ) +
where CEH is the cooling enthalpy hours, N is the number of hours for the period analyzed, ho is the average hourly outdoor enthalpy, hb is the base enthalpy, α = 0 if t < tb or α = 1 if t ≥ tb; t is the average hourly outdoor temperature and tb is the base temperature.
The CEH differs from the CDDH because it considers the positive differences of enthalpy only when the outdoor temperature is higher than the base temperature. The CEH indicator was calculated for different base enthalpies (values between 34 and 52 kJ/kg), always considering the base temperature of 18 °C. Table 4 presents the value of the coefficient of determination (R2) obtained in each case. For the base enthalpy of 35 kJ/kg, which presented the highest value of R2, the standard error of the linear regression was 9.50 kWh/m2·year. Figure 3 shows the linear regression used to relate CEH and annual cooling demand. This result shows that the use of CEH as a climate indicator is more accurate than the use of the traditional CDH indicator.

2.4. CEH Calculation for 407 Brazilian Cities

The new climate indicator CEH and the building model annual cooling demand were calculated for 407 Brazilian cities for which weather files were available. The value of 18 °C was considered for the base temperature and 35 kJ/kg for the base enthalpy. The same procedure was performed considering the definition of Shin and Do [20], but for an hourly basis according to the equation below.
CDH H   = n = 1 N ( h o h b ) +
where CDHH is the enthalpy-based cooling degree hours, N is the number of hours for the period analyzed, ho is the average hourly outdoor enthalpy, hb is the base enthalpy. A comparison between these two indicators allowed us to evaluate the improvement obtained with the new climate indicator.
Figure 4 shows the graph that illustrates the correlation between CDHH and annual cooling demand, where the value obtained for R2 was 0.9418, and the standard error was 12.27 kWh/m2·year. Figure 5 shows the correlation between CEH and annual cooling demand, where R2 was 0.9533, and the standard error was 11.00 kWh/m2·year.
The lowest CEH value calculated for these 407 cities was 2261 and the highest 350,672. Considering groups formed in each interval of 20,000, we obtained 18 climate zones that can be used to characterize the Brazilian climate. A frequency distribution was conducted to verify how each zone was represented from the 407 cities. Figure 6 shows this frequency distribution and Appendix A lists the cities chosen to characterize each of these 18 zones.

2.5. CEH Validation with Other Buildings

The CDH, CDHH and CEH indicators were also evaluated for buildings other than the building model. The results of 28 new cases were obtained in this research. All buildings are 40-story offices with rectangular geometry and height between floors is equal to 3 m. The external walls have thermal transmittance equal to 2.6 W/m2·K, thermal capacitance of 145 kJ/m2·K, and solar absorptance of 0.4. The internal walls have a thermal capacitance of 145 kJ/m2·K. The roof presents thermal transmittance equal to 1.93 W/m2·K, thermal capacitance of 106 kJ/m2·K, and solar absorptance of 0.5. The setpoint used was 23 °C.
Case 1 is a building with dimensions of 20 × 35 m with the WWR (Windows Wall Ratio) of 25% in the four facades. In Case 1, the vector orthogonal to the length makes an angle of 22.5° with the north, the glass has a solar factor of 0.27 and thermal transmittance of 4.3 W/m2·K, the lighting power density (LPD) is 8.75 W/m2, the occupancy rate is 5.0 m2/person, the daily time of operation is 9 h only on weekdays, and the air infiltration rate is 0.37 ACH (air changes per hour). Cases 2–7 are variations of Case 1, where all characteristics are identical except for one. In Case 2 the WWR was changed to 0.65; in Case 3 the solar factor of glass was changed to 0.57; in Case 4 the LPD was changed to 13.75 W/m2; in Case 5 the occupancy rate was changed to 13 m2/person; in Case 6 the daily time of operation was changed to 13 h and, in Case 7 the solar orientation of the building was changed to 112.5°. Cases 8–14 are identical in respective to Cases 1–7 except for their dimensions, 20 × 95 m. Similarly, Cases 15–21 are identical in respective to Cases 1–7 but with dimensions of 40 × 70 m. Finally, Cases 22–28 follow the same logic, where the building has dimensions of 40 × 190 m.
Table 5 presents the values of R2 obtained when a linear correlation between annual cooling demand and each climate indicator is used. These results show that the CEH indicator performs better than the CDH and CDHH, since the R2 value increases 7.8% on average when CDHH is used in place of CDH and increases 1.1% when CEH is used in the place of CDHH.
Considering these results, the CEH indicator was chosen to be the climate indicator, and it will be one of the input factors of the artificial neural network to predict energy consumption of HVAC system in office buildings.

3. Data Construction

3.1. Sensitivity Analysis

The objective of this step was to determine the characteristics of the office buildings that, once changed, provide significant changes in their cooling demand, as well as to determine which parameters of the HVAC system have the greatest influence on energy consumption. Thus, only these characteristics and parameters had their values changed to obtain the cases which were simulated to obtain the data. Sensitivity analysis techniques allow evaluating the relative importance of the input factors of a model. These techniques indicate which input factors are most important in determining the uncertainty in the output and if it is possible to keep fixed the values of some input factors of the model.

3.1.1. Input Factors

The building was modeled considering rectangular geometry. The distance between floors was set at three meters. Each floor was modeled with four perimeter thermal zones and an internal thermal zone. The variables used to characterize the geometry were width of building base, ratio between length and width, number of floors, solar orientation and window wall ratio (WWR). The solar factor and thermal transmittance of glasses, the solar absorptance, thermal transmittance and thermal capacity of external walls and roofs, and the thermal capacity of internal walls were the factors used to represent the properties of building materials.
The variables used for heat gains were air infiltration, lighting power density, occupation rate, and daily working hours of weekdays. It was considered that each person dissipates 120 W, where 40% is latent heat and 60% is sensible heat. Dunn and Knight [29] conducted a study in UK offices and demonstrated that there is a strong correlation between the power density of equipment and the occupancy rate. The average value of equipment load obtained by them was 158 W per person. However, due to the continuous growth in the efficiency of office equipment, this value has reduced in recent years. We fit an equation relating occupancy rate and equipment power density from the data presented in Dunn and Knight’s paper [29]. Then, we applied a correction factor of 0.886 in this equation, corresponding to the reduction of the average value of equipment load from 158 to 140 W/m2 as verified by Korolija [30], resulting in the following equation.
EPD = 116.45 · ( Occ ) 0.923
where EPD is equipment power density in W/m2 and Occ is the occupancy rate in m2/person.
The weather was modeled through the use of 18 weather files which characterize the climate zones defined in the previous step. The HVAC system was modeled with fancoil units in each thermal zone and one chiller. The variables used to characterize the HVAC system were thermostat setpoint temperature, use of economizer, use of heat recovery, use of night cycle, use of chilled water temperature reset, ventilation type, chilled water pump rated head, condenser water pump rated head, outdoor air flow rate, and chiller.
Table 6 presents the range of values used for each variable in sensitivity analysis. Some used uniform distribution while others employed discrete. The level 1 for outdoor air flow rate considers 2.5 L/s·person and 0.3 L/s·m2; level 2 considers 3.1 L/s·person and 0.4 L/s·m2; and level 3 considers 3.5 L/s·person and 0.5 L/s·m2. The chilled water pump rated head corresponds to the sum of primary and secondary pump rated head. When the system has primary and secondary circuits, the primary pump rated head was considered equal to 150,000 Pa. The characteristics adopted for the chiller were the type of condensation (air or water), the coefficient of performance at full load (COP), and IPLV (Integrated Part Load Value) defined by AHRI (Air Conditioning, Heating and Refrigeration Institute) according to AHRI Standard 550/590. The influence of the chiller on the energy consumption was evaluated with the use of 10 different chillers, whose performance curves were obtained in the Energyplus datasets.

3.1.2. Sensibility Analysis Method

The objective of the sensitivity analysis was to identify which input factors could be maintained with fixed values in the data construction procedure without causing a significant impact on the results. Thus, both the number of cases to be simulated and the computational time were reduced. The most appropriate sensitivity analysis methods for this purpose are variance-based methods [31]. The two commonly used variance-based method are FAST (Fourier Amplitude Sensitivity Test) and Sobol. In this research we opted for the Sobol method because it is more precise, despite being more computationally expensive. Tian [31] reviewed the use of sensitivity analysis methods in building energy analysis and recommended two softwares: R [32] and SIMLAB [33], the second being used in the present work.

3.1.3. Simulation of a Sample and Sensitivity Analysis

The size of the sample for the sensitivity analysis by the Sobol method is defined by the following equation [34],
Sample   size = ( 2 · k + 2 ) · N
where k is the number of input factors and N is the number representative of the sample size required to compute a single estimate.
We chose the higher value for N available in SIMLAB (N = 2048) resulting in a sample of 126,976 cases, since we had 30 input factors (Table 6). These cases were simulated using the Energyplus software to obtain the annual cooling demand of the building per square meter of floor (kWh/m2) and annual energy consumption of HVAC system per square meter of floor (kWh/m2).
The results of the simulations of the 126,976 cases were uploaded to SIMLAB, which generated the first and total effects sensitivity indices. The output variables evaluated were annual cooling demand and annual HVAC consumption. The weather, occupancy rate, and daily working hours were the variables that had the greatest influence on the annual demand, since they were the highest values of the first order indices. The input variables with the greatest influence on the HVAC consumption were the occupation rate, the weather, and the supply fan delta pressure. Nine of the 30 input variables had less influence on both output variables because their total order indices were close to zero, namely: Solar absorptance of external walls, thermal transmittance of external walls, thermal capacity of external walls, solar absorptance of roof, thermal transmittance of roof, thermal capacity of roof, thermal capacity of internal walls, night cycle, and chilled water temperature reset.

3.2. Building Simulation

As a result of the previous step, the number of input variables was reduced from 30 to 21 variables. Therefore, nine variables had their values fixed. A new input variable called “number of chillers in parallel” was included to evaluate the performance of the use of chillers operating in parallel. Table 7 presents the values that were used for these 22 variables and for the nine variables whose values remained fixed.
The number of cases determined by the possible combinations of these values amounted to 526,727,577,600,000 cases. The simulation of all cases is impracticable, and therefore it was necessary to perform a sampling. The sample size was determined for estimating a population mean [35] (considering large population) with the confidence level of 99% and desired margin of error equal to 0.5% of the standard deviation of the variable of interest (annual HVAC consumption). The value of this standard deviation obtained in the 126,976 previous simulated cases was 29.64 kWh/m2. Thus, the sample size obtained by the calculations was 265,225 cases, and 250,000 cases was the sample size adopted. The method of sampling was the Latin hypercube [36] because this method of sampling was more accurate and with less variance than those obtained with the Monte Carlo method [37].
The set of 250,000 cases was simulated using 30 computational nodes, operating with parallel processing, running the EnergyPlus software (version 8.5). The SDumont supercomputer (processing capacity in the order of 1.1 Petaflop/s) located in the National Laboratory of Scientific Computation (LNCC) in the city of Petropolis-RJ was used. A script was developed in Python language to manipulate the objects of the IDF file (Input Data File) allowing us to automate the effort of creating these 250,000 input files, as well as the EPW files (EnergyPlus Weather Data). Another script was developed to collect the results in the output files at the end of each simulation. In this way, the data was obtained.

4. Development of the Metamodel

4.1. Data Pre-Processing

The results of the simulations were analyzed in order to evaluate if the sizing of the HVAC system was effective. The percentage of unmet hours was analyzed. Only 5405 cases (2.2% of the simulated cases) presented a percentage higher than 10%, and were excluded from the data. Another 632 cases presented severe errors in the simulation process and were also excluded from the data, resulting in 243,963 cases remaining.
Some input variables used in the simulation were categorical, such as “chilled water pump configuration.” It is recommended that the categorical predictors be decomposed into more specific variables for better model performance (ANN training, in this case) [38]. To use these data in models, the categories were re-encoded into smaller bits of information called “dummy variables.” Usually, each category gets its own dummy variable that is a zero/one indicator. Thus, the variable called “economizer/heat recovery cycle,” which had three categories, was replaced by two variables (economizer cycle and heat recovery), both binary (0-without, 1-with). Similarly, the variable “chilled water pump configuration” was replaced by two variables (presence of secondary circuit and use of variable chilled water flow), both binary (0-without, 1-with). The three levels used in “outdoor air flow rate” were replaced by the values 2.5, 3.1, and 3.8, which correspond to the flow values (l/s) per person of each of the respective levels. The variable “chiller” with 25 categories was replaced by two variables (COP at 100% capacity and IPLV). After these data transformations, the initial architecture of the neural network model considered 18 predictor variables (input nodes) and 1 response variable (output node), as listed in Table 8.
Creating a good model may be difficult due to specific characteristics of the data; therefore, some transformations can improve the numerical stability of some calculations present in the process. The centering, scaling and skewness transformations were employed here. The variables used as input data in the simulations already had a homogeneous distribution due to the Latin Hypercube sampling. However, the same did not happen with the simulation results (annual cooling demand and annual HVAC energy consumption). Thus, these variables were transformed using the Box-Cox method [39] to reduce data asymmetries.

4.2. Sample Size

After pre-processing, the next step was to train and evaluate artificial neural networks. The use of the whole data set (243,963 cases) in the training process was impractical due to the large processing time required. It was necessary to define a sample size that would guarantee a satisfactory confidence.
Different sample sizes were determined for estimating a population mean [35] (considering finite population) with the different confidence levels (90%, 95%, 99.0%, 99.5% and 99.9%). The population size was the total number of cases (243,963), the standard deviation of the annual HVAC energy consumption was 48.47 kWh/m2, and desired margin of error was considered equal to 1% of this standard deviation (0.48 kWh/m2). Thus, the sample sizes obtained for each of the five confidence levels were: 24,359, 33,190, 52,136, 68,624, and 75,008 cases, corresponding to 10%, 14%, 21%, 28%, and 31% of the cases, respectively. Therefore, we chose to test the use of samples with sizes of 5%, 10%, 15%, 20%, 25%, and 30% of the cases. Note that an additional size (5%) has been included.
An approach for quantifying how well the model operates is to use resampling, where different subversions of the training data set are used to fit the model [38]. We used a form of resampling called repeated 10-fold cross-validation where the number of repetitions used was six times. A neural network with a single hidden layer was trained using each of the different sample sizes previously defined. We used the rule of thumb to define the number of neurons in the hidden layer, which says the number of hidden neurons should be 2/3 the size of the input layer, plus the size of the output layer [40]. Our model had 18 inputs and one output, so we used 13 neurons in the hidden layer. Each neural network was used to predict the annual HVAC cooling energy consumption of each case of the data (243,963 cases) and the performance indicators (R2, RMSE, and NRMSE) were calculated. Table 9 shows these values and the processing time for each of the sample sizes. The neural networks were obtained using the nnet package of the R language in a computational cluster composed of 16 Intel Xeon E7-4830 processors of 2.2 GHz. This package used sigmoidal function as activation function and BFGS method as optimizer.
The processing time has a linear behavior with the sample size, i.e., the larger the sample size, the longer the processing time. The values of the performance indicators improved as sample size increased; this improvement is greater in the first increments (10% and 15%) and lower in the subsequent (20%, 25% and 30%). For example, RMSE decreased by 1.2% when the sample size changed from 5% to 10%, 1.5% when it changed from 10% to 15%, 0.1% when it changed from 15% to 20%, 0.5% when it changed from 20% to 25%, and 0.9% when it changed from 25% to 30%. Therefore, we chose to use the sample size of 15% in the following steps because the ANN obtained from this sample size had intermediate performance with shorter processing time.

4.3. Refining Architecture of Neural Network

In this step we aimed to improve the metamodel by varying some parameters of the ANN architecture. First the size of the hidden layer (number of neurons) was changed. New ANNs were created with neurons in the hidden layer in the proportions of 0.35, 0.50, 0.80, 0.95, 1.10, 1.25, 1.40, 1.55, 1.70, 1.85, and 2.00 times the value of the sum of the number input and outputs neurons. Since the model has 18 predictors and 1 response, the new ANNs were created with 7, 10, 15, 18, 21, 24, 27, 29, 32, 35, and 38 neurons in the hidden layer. Each ANN was used to predict the annual HVAC cooling energy consumption of each case of the data and the performance indicators (R2, RMSE, NRMSE) were calculated. Moreover, to obtain a comprehensive performance measure, these indicators and processing times were combined into a synthesis index (SI) in the same way as [41]. Table 10 shows the performance indicators and processing time for each of this ANN, as well as the synthesis index (SI).
The neural network with 32 neurons in the hidden layer presented better performance (higher SI value) and, therefore, it was used as the baseline in the following studies. This network was called ANN32. Figure 7 shows the results obtained when this ANN was used to predict the annual HVAC energy consumption of all cases.
After establishing the number of neurons in the hidden layer, the influence of the inclusion, exclusion, or alteration of predictor variables was evaluated. The first change analyzed was the inclusion of a new predictor variable, the number of daily hours of operation of the HVAC system. A new ANN was trained (using cross-validation with 10 k-fold repeated six times) including this predictor variable and keeping 32 neurons in the hidden layer, resulting in values of R2 = 0.9885, RMSE = 5.20669, and NRMSE = 0.061313. Therefore, the improvement in the performance measures was small when compared to the baseline (reduction of 1.7% in the RMSE), and it did not justify the increase in the complexity of the metamodel.
Another change analyzed was the substitution of the IPLV value as predictor variable by the values of COP at 25%, 50%, and 75% chiller capacity, which composes the IPLV calculation. As there was an increase in the number of input neurons (20 instead of 18 in the baseline), new ANNs were created with 32, 35, and 38 neurons in the hidden layer. The best performance was obtained with the network with 35 neurons, where R2 = 0.9887, RMSE = 5.158972, and NRMSE = 0.060751. This network was called ANN35_COP. The improvement in the performance measures was slightly better than the previous analysis (reduction of 2.6% in the RMSE when compared to the baseline).
The last modification carried out had the objective of evaluating the influence of the use of the frequency histogram of the cooling demand as predictor variables. The baseline ANN used four values (bins) representing the demand histogram as predictor variables. A new ANN was trained without the use of these values. As there was a decrease in the number of input neurons (14 instead of 18 in the baseline), new ANNs were created with 27, 29, and 32 neurons in the hidden layer. The best performance was obtained with the network with 29 neurons, where R2 = 0.9858, RMSE = 5.771209, and NRMSE = 0.067961. This network was called ANN29_wDEM. There was an expected reduction in the performance, but it was not significant enough to discourage the adoption of this architecture for the metamodel.
The performance of the ANN baseline and the new ANNs obtained in the last two studies was also evaluated for new cases. These cases were created using values different from those used when the data was obtained. This procedure is described below.

4.4. Evaluation of Models with Unseen Cases

New cases were modeled and preprocessed in the same way described in Section 3.2 and Section 4.1. Table 11 presents the values used to obtain the so-called unseen cases. The number of cases determined by the possible combinations of the values presented in Table 6 amounts to 6,193,152 cases. The sample size of 66,300 cases was determined for estimating a population mean [35] (considering large population) with the confidence level of 99% and desired margin of error equal to 1.0% of the standard deviation of the annual HVAC consumption (standard deviation obtained in the 243,963 simulated cases for the data was 48.47 kWh/m2). The method of sampling was the Latin hypercube.
The ANN32, ANN35_COP, and ANN29_wDEM obtained in the previous step were used to predict the annual HVAC consumption of these unseen cases. Table 12 shows the performance measures obtained with each ANN when used in this prediction.
The simpler network (ANN29_wDEM) presented the best performance in the prediction of unseen cases. For this reason, it was considered the final metamodel of this research, which allows us to predict the consumption of Brazilian office buildings from the knowledge of 14 variables (ventilation type, supply fan delta pressure, use of economizer, use of heat recovery, level of outdoor air flow rate, chilled water pump rated head, condenser water pump rated head, use of secondary circuit in chilled water, use of variable chilled water flow, chiller COP at 100% capacity, chiller IPLV, number of chillers in parallel, annual cooling demand per square meter of floor area, and CEH climate indicator). Figure 8 shows the results obtained when the ANN29_wDEM was used to predict the annual HVAC energy consumption of the unseen cases.

5. Discussion

The high values obtained for the coefficient of determination (R2 above 0.9) show that there is a strong correlation between the annual building cooling demand and the temperature-based climate indicator (CDH), as well as for the new indicator proposed in this paper (CEH). The CEH presented a better adjustment quality when a linear regression was used to relate annual cooling demand with climate indicator. The standard error reduced about 20% (from 12.11 to 9.50 kWh/m2·year) when CEH was used in place of the usual CDH. The variation in the base enthalpy and base temperature values allows us to conclude that these values do not significantly influence if the values used are close to 37 kJ/kg and 18 °C respectively.
The building cooling demand cannot be predicted simply from the calculation of the climate indicator (CEH) of the city where it is built. This demand will be the result of several factors that characterize the building, such as construction materials, usage patterns, equipment density, lighting power density, and occupation, among others. The climate indicator is often used as the dependent variable in prediction energy models to determine reference values (benchmark), and its main function is to adjust the consumption value for the climate under analysis.
Regression analysis is one of the most popular techniques for the development of models for building energy consumption prediction [42]. When the regression equations are obtained from a complete and accurate set of experimental data, they can provide precise results in an easier and faster way than using building simulation tools [43]. Artificial intelligence methods, especially artificial neural networks, have recently been used in models for building energy consumption predictions. In both methods, it is necessary to characterize the climate with the smallest possible number of variables in order to simplify the model. Therefore, the results obtained in this research demonstrate that the CEH indicator can be used for this purpose.
The results obtained for the 407 Brazilian cities confirmed the good performance of the CEH with climate indicator, since the R2 value remained high (0.9533) and the standard error low (11.00 kWh/m2·year). They also showed the CEH performed better than the CDHH indicator based on the proposal of Shin and Do [20] whose results were R2 = 0.9418 and standard error = 12.27 kWh/m2·year. The representation of the Brazilian climate in the 18 suggested climate zones was adequate due to the observed frequency distribution (Figure 6).
The CDH, CDHH, and CEH indicators were also evaluated for buildings other than the building model, and again the results showed that the CEH had the best performance. Therefore, the energy consumption prediction model proposed here could be developed for Brazilian office buildings considering the CEH indicator and these eighteen climate zones.
The sensitivity analysis indicated that the annual cooling demand and annual HVAC energy consumption were less sensitive to the changes in the thermal characteristics of the walls and roof (solar absorptance, thermal transmittance, and thermal capacity), in agreement with the results obtained by Lam et al. [44,45]. The annual HVAC energy consumption also was less sensitive to the use of night cycle and chilled water temperature reset.
The use of all simulated cases (243,963) in the ANN training process is impracticable and so it was necessary to define the ideal size for training. ANNs obtained with larger samples present better performance, but they require longer processing time in their training process. The results showed that for this population the use of samples with 36,594 cases generated ANNs with compatible performance to those generated with larger samples. This sample size corresponds to the value determined for estimating a population mean with the confidence levels equal to 95% and desired margin of error equal to 1% of the standard deviation of the variable of interest. In this case, the size calculated as described above represented 15% of the population, but this percentage may not be generalized to other cases. In each new situation the sample size must be calculated using the estimation of population mean technique.
The increase in the size of the hidden layer of the neural network had a greater influence on its performance than the increase in the sample size, in the same way that was observed by Versage [46]. The use of the synthesis index allowed us to define the ideal number of neurons as 32 in the hidden layer of the ANN with 18 neurons in the input layer and 1 neuron in the output layer (initially idealized architecture).
Neural network improvement studies showed that the inclusion of a new variable (daily hours of HVAC system operation) generated a small increase in the network performance (reduction of 1.7% in the RMSE) and did not justify the adoption of this change. These studies indicated that two other alterations could be justifiable: Replacing the IPLV input variable by COP at 25%, at 50%, and at 75% chiller capacity; and excluding the four input variables that characterize the frequency histogram of the cooling demand. Then, these two new ANNs and the baseline ANN were used to predict the annual HVAC system consumption of 66,300 new cases, which were generated with values not used when creating the data; the results demonstrated that the performance of these three ANNs are similar. Thus, the ANN with less complex architecture was adopted as the final metamodel of this research.

6. Conclusions

Climate indicators that only use the dry bulb temperature in their calculations (CDD and CDH) do not consider the presence of the latent heat fraction present in the building cooling demand. This limitation has an influence on the models of building energy prediction that use these indicators in hot and humid climates, because the energy spent in these climates is significant for the air dehumidification process.
The CEH indicator proposed in this paper was more accurate and it could be used as a climate indicator in models of cooling demand prediction for the Brazilian climate. After performing an analysis to determine which values of base temperature and base enthalpy should be employed, we conclude that the most appropriate values are 18 °C and 35 kJ/kg, respectively. A small variation around these values did not present a significant change in the results.
As the CEH calculation is a summation of enthalpy differences of a weather file, similar values of CEH can be obtained from climates with different enthalpy frequency distributions. Even so, the results showed that the CEH indicator is effective in relating the climate to the annual cooling demand. Future work may investigate ways to characterize the difference between these climates that have similar CEH values.
The sensitivity analysis by the Sobol method allowed the reduction of 30% in the number of input variables previously idealized in the process of creating the cases that composed the data of this research. The changes in the thermal characteristics of the walls and roof (solar absorptance, thermal transmittance and thermal capacity) have less influence on cooling demand and HVAC consumption than changes in the other characteristics of the building.
Artificial neural networks of good performance can be trained with a sample whose size is calculated estimating a population mean with the confidence levels equal to 95% and desired margin of error equal to 1% of the standard deviation of the variable of interest.
The metamodel with 14 neurons in the input layer (variables 1 to 14 in Table 8), 29 neurons in the hidden layer, and 1 neuron in the outer layer presented good performance to predict the annual HVAC consumption for the cases used to obtain the model (R2 = 0.9858 and NRMSE = 0.067961), and also for the unseen cases (R2 = 0.9789 and NRMSE = 0.063788). This metamodel presented similar performance to the other metamodels analyzed, but it features a less complex architecture.
This research has limitations related to the standard configurations of the statistical package used (nnet package in R), such as the activation function and the optimizer. An advanced configuration could improve on the training time and accuracy of ANNs. The trained neural networks have only one hidden layer, the variation of this hyperparameter could also impact the performance of the model. The metamodel was developed for chilled water HVAC systems; hence it does not apply to other types of HVAC systems (direct expansion, variable refrigerant flow). The occupancy variation and the supposed influence of occupant behavior were not considered, thus characterizing another limitation. Future research can be developed to cover other types of HVAC systems. The results obtained using the metamodel developed here can be compared with results of other simplified HVAC consumption prediction models.

Author Contributions

M.N.L. performed the simulation, the ANNs training, the analysis, the validation and wrote the paper; R.L. supervised the research and reviewed the paper. And both developed the methodology.

Funding

This research received no external funding.

Acknowledgments

The authors would like to thank CNPq (The Brazilian National Council for Scientific and Technological Development) for financial support of this research, LNCC (National Laboratory of Scientific Computation) and IFSC (Federal Institute of Santa Catarina).

Conflicts of Interest

The authors declare no conflicts of interest.

Appendix A

Table A1. Cities chosen to characterize the 18 climate zones and their respective CEH values.
Table A1. Cities chosen to characterize the 18 climate zones and their respective CEH values.
Climate ZoneRepresentative CityCEH
1Petropolis—RJ12.217
2Campos do Jordao—SP34.190
3Lagoa Vermelha—RS50.577
4Bage—RS69.614
5Sao Paulo—SP93.780
6Porto Alegre—RS112.434
7Sorocaba—SP130.992
8Belo Horizonte—MG147.155
9Goiania—GO170.751
10Rio de Janeiro—RJ194.336
11Governador Valadares—MG211.805
12Vitoria—ES229.685
13Palmas—TO255.547
14Recife—PE266.710
15Natal—RN291.197
16Boa Vista—RR310.958
17Sao Luis—MA332.020
18Manaus—AM342.270

Appendix B

Table A2. Characteristics of the chillers used in sensibility analysis (Data obtained from the equations available in the Energyplus dataset).
Table A2. Characteristics of the chillers used in sensibility analysis (Data obtained from the equations available in the Energyplus dataset).
Manufacturer/Model Condenser TypeCOP at 100%COP at 75%COP at 50%COP at 25%IPLV
McQuay AGZ070DAir2.8433.5704.2074.4183.951
Carrier 30XA220Air3.0673.7964.7885.6224.454
Trane RTWA 383 kWWater4.1744.8595.5265.2545.199
Carrier 23XL 724 kWWater4.7195.9407.1365.6036.426
Trane RTHB 1051 kWWater5.0566.3807.3175.2726.656
Carrier 19XR 1403 kWWater5.3696.9028.6258.4637.849
Carrier 19EX 5148 kWWater5.8676.8207.4545.7796.971
York YT 2110 kWWater6.3157.4408.2676.0537.635
York YK 5465 kWWater6.6227.6808.4535.9717.812
York YK 5170 kWWater6.8707.9988.9076.5308.220

Appendix C

Table A3. Characteristics of the chillers used to create the data (Data obtained from the equations available in the Energyplus dataset).
Table A3. Characteristics of the chillers used to create the data (Data obtained from the equations available in the Energyplus dataset).
Manufacturer/ModelCondenser TypeCOP at 100%COP at 75%COP at 50%COP at 25%IPLV
McQuay AGZ025BSAir2.6723.2073.7414.0273.541
York YLAA0150SEAir2.7903.5584.7565.9534.377
York YLAA0170SEAir2.8863.6474.3004.4944.035
York YLAA0120SEAir2.8913.7375.5078.2235.064
Carrier 30XA240Air2.9553.7105.0026.4824.617
Trane CGAM130Air3.0544.1405.4566.0474.950
Carrier 30XA325Air3.0783.7994.7525.5244.428
Trane CGWD 207 kWWater4.0044.8705.7685.7245.368
Trane RTWA 383 kWWater4.1744.8595.5265.2545.199
McQuay PFH 932 kWWater4.9085.5726.3275.8865.943
Trane RTHB 1051 kWWater5.0566.3807.3175.2726.656
York YK 2412 kWWater5.2515.2835.1643.6995.039
York YS 781 kWWater5.4136.8207.9295.7477.176
Carrier 19FA 5651 kWWater5.5096.1246.4295.1356.136
York YT 1495 kWWater5.5127.68111.52910.6709.749
York YS 879 kWWater5.6816.6867.1204.8816.655
Carrier 19XL 1797 kWWater5.7145.7524.8682.6904.987
York YT 1023 kWWater5.7836.9077.7115.6787.110
Trane CVHF 4610 kWWater5.8367.1948.4306.5157.655
York YS 1758 kWWater5.8576.8927.1274.8346.740
Carrier 19XR 1407 kWWater5.9686.9447.4726.3137.096
Trane CVHE 1758 kWWater6.0576.5636.3274.8856.250
York YT 1758 kWWater6.3287.3378.0436.2327.512
Trane CVHF 2317 kWWater6.6208.65511.25710.1009.979
Trane CVHF 2043 kWWater7.0058.2849.0076.7538.413

Appendix D

Table A4. Characteristics of the chillers used to create the unseen cases (Data obtained from the equations available in the Energyplus dataset).
Table A4. Characteristics of the chillers used to create the unseen cases (Data obtained from the equations available in the Energyplus dataset).
Manufacturer/ModelCondenser TypeCOP at 100%COP at 75%COP at 50%COP at 25%IPLV
Carrier 30RB330Air2.8073.4833.9764.0503.766
York YLAA0175HEAir2.9643.7514.4284.6314.153
Trane CVHE 1329 kWWater5.1995.2735.1694.6175.147
Carrier 23XL 1062 kWWater5.5156.7677.8905.6667.128
York YK 4966 kWWater5.6836.4646.4374.2606.179
Carrier 19XL 1674 kWWater5.8096.4636.5034.3156.217
York YT 1055 kWWater5.9157.0927.9195.6807.283

References

  1. Chua, K.J.; Chou, S.K.; Yang, W.M.; Yan, J. Achieving better energy-efficient air conditioning—A review of technologies and strategies. Appl. Energy 2013, 104, 87–104. [Google Scholar] [CrossRef]
  2. International Energy Agency (IEA). The Future of Cooling—Opportunities for Energy-Efficient Air Conditioning; OECD/IEA: Paris, France, 2018. [Google Scholar]
  3. Pérez-Lombard, L.; Ortiz, J.; Coronel, J.F.; Maestre, I.R. A review of HVA systems requirements in building energy regulations. Energy Build. 2011, 43, 255–268. [Google Scholar] [CrossRef]
  4. Fumo, N. A review on the basics of building energy estimation. Renew. Sustain. Energy Rev. 2014, 31, 53–60. [Google Scholar] [CrossRef]
  5. Foucquier, A.; Robert, S.; Suard, F.; Stéphan, L.; Jay, A. State of the art in building modelling and energy performances prediction: A review. Renew. Sustain. Energy Rev. 2013, 23, 272–288. [Google Scholar] [CrossRef]
  6. Zhao, H.; Magoules, F. A review on the prediction of building energy consumption. Renew. Sustain. Energy Rev. 2012, 16, 3586–3592. [Google Scholar] [CrossRef]
  7. Li, X.; Wen, J. Review of building energy modeling for control and operation. Renew. Sustain. Energy Rev. 2014, 37, 517–537. [Google Scholar] [CrossRef]
  8. Kim, Y.M.; Ahn, K.U.; Park, C.S. Issues of Aplication of Machine Learning Models for Virtual an Real-Life Buildings. Sustainability 2016, 8, 543. [Google Scholar] [CrossRef]
  9. Dong, Q.; Xing, K.; Zhang, H. Artificial Neural Network for Assessment of Energy Consumption an Cost for Cross Laminated Timber Office Building in Severe Cold Regions. Sustainability 2018, 10, 84. [Google Scholar] [CrossRef]
  10. Chen, Y.; Norford, L.K.; Samuelson, H.W.; Malkawi, A. Optimal control of HVAC and window systems for natural ventilation through reinforcement learning. Energy Build. 2018, 169, 195–205. [Google Scholar] [CrossRef]
  11. Carlo, J.; Lamberts, R. Development of envelope efficiency labels for commercial buildings: Effect of different variables on electricity consumption. Energy Build. 2008, 40, 2002–2008. [Google Scholar] [CrossRef]
  12. Melo, A.P.; Versage, R.S.; Sawaya, G.; Lamberts, R. A novel surrogat model to support building energy labelling system: A new approach to assess cooling energy demand in commercial buildings. Energy Build. 2016, 131, 233–247. [Google Scholar] [CrossRef]
  13. Yan, D.; O’Brien, W.; Hong, T.; Feng, X.; Gunay, H.B.; Tahmasebi, F.; Mahdavi, A. Occupant behavior modeling for building performance simulation:Current state and future challenges. Energy Build. 2015, 107, 264–278. [Google Scholar] [CrossRef]
  14. Hong, T.; Taylor-Lange, S.C.; D’Oca, S.; Yan, D.; Corgnati, S.P. Advances in research an applications of energy-related occupant behavior in buildings. Energy Build. 2016, 116, 694–702. [Google Scholar] [CrossRef]
  15. Hong, T.; Chen, Y.; Belafi, Z.; D’Oca, S. Occupant behavior models: A critical review of implementation and representation approaches in building performance simulation programs. Build. Simul. 2018, 11, 1–14. [Google Scholar] [CrossRef]
  16. Huang, Y.J.; Ritschard, R.; Bull, J.; Chang, L. Climate Indicators for Estimating Residential Heating and Cooling Loads; Report LBL-21101; Lawrence Berkeley Laboratory: Berkeley, CA, USA, 1986. [Google Scholar]
  17. Sailor, D.J.; Muñoz, R. Sensitivity of electricity and natural gas consumption to climate in the USA—Methodology and results for eight states. Energy 1997, 22, 987–998. [Google Scholar] [CrossRef]
  18. Sailor, D.J. Relating residencial and commercial sector electricity loads to climate-evaluating state leel sensitivities and vulnerabilities. Energy 2001, 26, 645–657. [Google Scholar] [CrossRef]
  19. Krese, G.; Prek, M.; Butala, V. Incorporation of latent loads into the cooling degree days concept. Energy Build. 2011, 43, 1757–1764. [Google Scholar] [CrossRef]
  20. Shin, M.; Do, S.L. Prediction of cooling energy use in buildings using an enthalpy-based cooling degree days method in a hot and humid climate. Energy Build. 2016, 110, 57–70. [Google Scholar] [CrossRef]
  21. Bloomfield, C.; Bannister, P.; Australia, E. Energy and water performance benchmarking in the retail sector—NABERS shopping centres. In Proceedings of the 2010 American Council for an Energy Efficient Economy (ACEEE) Summer Study on Energy Efficiency in Buildings, Pacific Grove, CA, USA, 15–20 August 2010; pp. 1–13. [Google Scholar]
  22. Borgstein, E.H.; Lamberts, R. Developing energy consumption benchmarks for buildings: Bank branches in Brazil. Energy Build. 2014, 82, 82–91. [Google Scholar] [CrossRef]
  23. McQuinston, F.C.; Parker, J.D.; Spitler, J.D. Heating, Ventilation and Air Conditioning: Analysis and Design; John Wiley & Sons, Inc.: Hoboken, NJ, USA, 2005. [Google Scholar]
  24. Energy Star. Portfolio Manager Technical Reference: Climate and Weather. Available online: https://www.energystar.gov/sites/default/files/tools/Climate_and_Weather_August_2017_EN_508.pdf (accessed on 17 September 2017).
  25. Lin, Y.; Yang, W.; Gabriel, K.S. A study on the impact of household occupant’s behavior on energy comsuption using an integrated computer model. Front. Built Environ. 2015, 1, 1–16. [Google Scholar] [CrossRef]
  26. Lukomski, A.; Gabriel, K.; Lin, Y.; Pitman, D. Evaluation of building electricity consumption of residential dwellings in Oshawa. In Proceedings of the eSIM Conference, Quebec, QC, Canada, 21–22 May 2008; pp. 165–172. [Google Scholar]
  27. ASHRAE. Handbook 2013: Fundamentals, SI edition; American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.: Atlanta, GA, USA, 2013. [Google Scholar]
  28. Papakostas, K.; Kyriakis, N. Heating and cooling degree-hours for Athens and Thessaloniki, Greece. Renew. Energy 2005, 30, 1873–1880. [Google Scholar] [CrossRef]
  29. Dunn, G.; Knight, I. Small power equipment loads in UK office environments. Energy Build. 2005, 37, 87–91. [Google Scholar] [CrossRef]
  30. Korolija, I.; Marjanovic-Halburd, L.; Zhang, Y.; Hanby, V.I. UK office buildings archetypal model as methodological approach in development of regression models for predicting building energy consumption from heating and cooling demands. Energy Build. 2013, 60, 152–162. [Google Scholar] [CrossRef]
  31. Tian, W. A review of sensitivity analysis methods in building energy analysis. Renew. Sustain. Energy Rev. 2013, 20, 411–419. [Google Scholar] [CrossRef]
  32. R Core Team. R: A Language and Environment for Statistical Computing; R Foundantion for Statistical Computing: Viena, Austria, 2014. [Google Scholar]
  33. SIMLAB. V2.2. Simulation Environment for Uncertainty and Sensitivity Analysis. 2011. Available online: https://ec.europa.eu/jrc/en/samo/simlab (accessed on 5 October 2017).
  34. Saltelli, A.; Tarantola, S.; Campolongo, F.; Ratto, M. Sensitivity Analysis in Practice. A Guide to Assessing Scientific Models; John Wiley & Sons, Ltd.: Hoboken, NJ, USA, 2004. [Google Scholar]
  35. Glenn, I.D. Determining Sample Size (Tech. Rep. No. PEOD-6); University of Florida: Gainesville, FL, USA, 1992. [Google Scholar]
  36. Mckay, M.D.; Bechman, R.J.; Conover, W.J. A comparison of three methods for selecting values of input variables in the analysis of output from a computer code. Technometrics 1979, 21, 239–245. [Google Scholar]
  37. Stein, M. Large sample properties of simulations using Latin Hypercube sampling. Technometrics 1987, 29, 143–151. [Google Scholar] [CrossRef]
  38. Kuhn, M.; Johnson, K. Applied Predictive Modeling; Springer: New York, NY, USA, 2013. [Google Scholar]
  39. Box, G.E.P.; Cox, D.R. An Analysis of Transformations. J. R. Stat. Soc. 1964, 26, 211–252. [Google Scholar] [CrossRef]
  40. Panchal, G.; Ganatra, A.; Kosta, Y.P.; Panchal, D. Behaviour Analysis of Multilayer Perceptrons with Multiple Hidden Neurons and Hidden Layers. Int. J. Comput. Theory Eng. 2011, 3, 332–337. [Google Scholar] [CrossRef]
  41. Chou, J.; Bui, D. Modeling heating and cooling loads by artificial intelligence for energy-efficient building design. Energy Build. 2014, 82, 437–446. [Google Scholar] [CrossRef]
  42. Tso, G.K.F.; Yau, K.K.W. Predicting electricity energy consumption: A comparison of regression analysis, decision tree and neural networks. Energy 2007, 32, 1761–1768. [Google Scholar] [CrossRef]
  43. Freire, R.Z.; Oliveira, G.H.C.; Mendes, N. Development of regression equations for predicting energy and hygrothermal performance of buildings. Energy Build. 2008, 40, 810–820. [Google Scholar] [CrossRef]
  44. Lam, J.C.; Hui, S.C.M. Sensitivity Analysis of Energy Performance of Office Buildings. Build. Environ. 1996, 27–39. [Google Scholar] [CrossRef]
  45. Lam, J.C.; Hui, S.C.M.; Chan, A.L.S. Regression analysis of high-rise fully air-condicioned office buildings. Energy Build. 1997, 26, 189–197. [Google Scholar] [CrossRef]
  46. Versage, R.S. Metamodelo Para Avaliação do Desempenho Energético de Edificações Comerciais Condicionadas Artificialmente. Ph.D. Thesis, Federal University of Santa Catarina (UFSC), Florianópolis, Brazil, 2015. (In Portuguese). [Google Scholar]
Figure 1. Modeled office buildings: (a) Shell and core typical plan; (b) simulation model of the building model with its thermal zones.
Figure 1. Modeled office buildings: (a) Shell and core typical plan; (b) simulation model of the building model with its thermal zones.
Sustainability 10 04718 g001
Figure 2. Linear regression for prediction of annual cooling demand with the use of CDH (base temperature = 18 °C).
Figure 2. Linear regression for prediction of annual cooling demand with the use of CDH (base temperature = 18 °C).
Sustainability 10 04718 g002
Figure 3. Linear regression for prediction of annual cooling demand with the use of CEH (base enthalpy = 35 kJ/kg and base temperature = 18 °C).
Figure 3. Linear regression for prediction of annual cooling demand with the use of CEH (base enthalpy = 35 kJ/kg and base temperature = 18 °C).
Sustainability 10 04718 g003
Figure 4. Polynomial regression for prediction of annual cooling demand with the use of enthalpy-based cooling degree hours (CDHH) calculated from 407 Brazilian cities (base enthalpy = 35 kJ/kg).
Figure 4. Polynomial regression for prediction of annual cooling demand with the use of enthalpy-based cooling degree hours (CDHH) calculated from 407 Brazilian cities (base enthalpy = 35 kJ/kg).
Sustainability 10 04718 g004
Figure 5. Polynomial regression for prediction of annual cooling demand with the use of CEH calculated from 407 Brazilian cities (base enthalpy = 35 kJ/kg and base temperature = 18 °C).
Figure 5. Polynomial regression for prediction of annual cooling demand with the use of CEH calculated from 407 Brazilian cities (base enthalpy = 35 kJ/kg and base temperature = 18 °C).
Sustainability 10 04718 g005
Figure 6. Frequency distribution graph of the 407 cities in the 18 climate zones obtained from CEH values.
Figure 6. Frequency distribution graph of the 407 cities in the 18 climate zones obtained from CEH values.
Sustainability 10 04718 g006
Figure 7. Predicted versus simulated annual HVAC consumption—ANN32.
Figure 7. Predicted versus simulated annual HVAC consumption—ANN32.
Sustainability 10 04718 g007
Figure 8. Predicted versus simulated annual HVAC consumption for the unseen cases—ANN29_wDEM.
Figure 8. Predicted versus simulated annual HVAC consumption for the unseen cases—ANN29_wDEM.
Sustainability 10 04718 g008
Table 1. Characteristics of the model building and HVAC system.
Table 1. Characteristics of the model building and HVAC system.
VariableValue
Dimensions of the typical floor 65 × 18 m
Height between floors3 m
Number of floors15
Solar orientation of the building
WWR in the four facades0.5
Solar factor of glasses0.82
Thermal transmittance of glasses5.78 W/m2·K
Solar absorptance of external walls0.5
Thermal transmittance of external walls2.6 W/m2·K
Thermal capacity of external walls156 kJ/m2·K
Solar absorptance of roof0.3
Thermal transmittance of roof2.42 W/m2·K
Thermal capacity of roof253 kJ/m2·K
Thermal capacity of internal walls60 kJ/m2·K
Air infiltration0.5 air change per hour
Lighting power density12.5 W/m2
Equipment power density16.5 W/m2
Occupancy rate8.5 m2/person
Daily working hours of weekdays11 h
Setpoint24 °C
Economizer/Heat recoveryNone/None
Night cycleOff
Chilled water temperature resetOff
Ventilation typeConstant Volume
Supply fan delta pressure450 Pa
Chilled water pump configurationConstant Primary/Variable Secondary
Chilled water primary pump rated head179,352 Pa
Chilled water secondary pump rated head392,400 Pa
Outdoor air flow rate2.5 L/s·person and 0.3 L/s·m2 floor
Chiller COP3.0
Table 2. Results for cooling degree hours (CDH) and annual cooling demand for 20 Brazilian cities.
Table 2. Results for cooling degree hours (CDH) and annual cooling demand for 20 Brazilian cities.
CityCDHAnnual Cooling Demand (kWh/m2·year)
Curitiba11,40191.7
Sao Paulo18,729118.3
Santa Maria 26,677100.1
Brasilia29,493148.2
Florianopolis30,758118.0
Niteroi35,434133.7
Belo Horizonte35,528134.4
Foz do Iguaçu40,991140.9
Rio de Janeiro47,026155.2
Campo Grande50,181159.1
Governador Valadares53,655174.4
Rondonopolis66,656202.9
Recife67,898216.4
Macapa68,136227.6
Salvador68,881214.8
Cuiaba73,252214.3
Palmas77,271206.5
Boa Vista78,938228.5
Belem80,237242.8
Manaus81,288241.6
Table 3. Results of the coefficient of determination (R2) obtained with the use of different base temperatures in the CDH.
Table 3. Results of the coefficient of determination (R2) obtained with the use of different base temperatures in the CDH.
Base Temperature (°C)R2
150.9360
160.9391
170.9416
180.9428
190.9417
200.9379
210.9301
220.9158
Table 4. Results of R2 obtained with the use of different base enthalpies in the cooling enthalpy hours (CEH).
Table 4. Results of R2 obtained with the use of different base enthalpies in the cooling enthalpy hours (CEH).
Base Enthalpy (kJ/kg)R2
340.9647
350.9648
360.9646
370.9643
380.9637
390.9629
400.9619
410.9606
Table 5. The values of R2 obtained in the correlation between annual cooling demand and CDH, CDHH and CEH.
Table 5. The values of R2 obtained in the correlation between annual cooling demand and CDH, CDHH and CEH.
R2 R2
CDHCDHHCEH CDHCDHHCEH
Case 10.95740.97300.9854Case 80.90890.97120.9868
Case 20.93970.96980.9825Case 90.95710.97770.9870
Case 30.82990.92480.9478Case 100.90870.96760.9827
Case 40.92070.96670.9785Case 110.92850.97880.9881
Case 50.95420.94430.9672Case 120.93960.95990.9764
Case 60.93160.98360.9943Case 130.93580.98210.9934
Case 70.94310.96820.9798Case 140.91050.96790.9788
Case 150.90020.98720.9926Case 220.91200.98670.9957
Case 160.89020.98010.9909Case 230.76980.97370.9906
Case 170.93240.98100.9896Case 240.90520.98710.9934
Case 180.92310.98490.9920Case 250.97930.99940.9996
Case 190.94110.97330.9844Case 260.91650.96920.9851
Case 200.72160.98530.9934Case 270.89150.99160.9957
Case 210.84970.98190.9887Case 280.93870.99290.9986
Table 6. Variables and range of values used in the sensibility analysis.
Table 6. Variables and range of values used in the sensibility analysis.
VariableRange of Values
Width of base of building 10–50 m
Ratio between length and width1–6
Number of floors5, 10, 20, 30, 40 or 50
Solar orientation of the building0–135°
WWR0.15–0.95
Solar factor of glasses0.2–0.8
Thermal transmittance of glasses1.7, 2.7 or 5.8W/m2·K
Solar absorptance of external walls0.2–0.8
Thermal transmittance of external walls0.5–2.9 W/m2·K
Thermal capacity of external walls40–270 kJ/m2·K
Solar absorptance of roof0.2–0.8
Thermal transmittance of roof0.5–3.65 W/m2·K
Thermal capacity of roof30–250 kJ/m2·K
Thermal capacity of internal walls40–270 kJ/m2·K
Air infiltration0–0.75 air change per hour
Lighting power density7.5–17.5 W/m2
Occupancy rate3–15 m2/person
Daily working hours of weekdays8, 9, 10, 11, 12, 13, 14, 15 or 16 h
Weather18 weather files (climate zones)
Setpoint20–24 °C
Economizer/Heat recoveryDifferential Enthalpy/None, or
None/Enthalpy, or None/None
Night cycleOff or On
Chilled water temperature resetOff or On
Ventilation typeConstant Volume or Variable Volume
Supply fan delta pressure150–750 Pa
Chilled water pump configurationConstant Primary/Variable Secondary, or
Constant Primary/No Secondary or
Variable Primary/No Secondary
Chilled water pump rated head25–85 × 104 Pa
Condenser water pump rated head10–65 × 104 Pa
Outdoor air flow rateLevel 1, Level 2 or Level 3
Chiller10 different chillers (Appendix B)
Table 7. Variables and range of values used in the construction of the data.
Table 7. Variables and range of values used in the construction of the data.
VariableValues
Width of base of building 10, 20, 30 or 50 m
Ratio between length and width1.0, 2.5, 4.0 or 5.5
Number of floors5, 10, 30 or 50
Solar orientation of the building0, 45, 90 or 135°
WWR0.15, 0.35, 0.55, 0.75 or 0.95
Solar factor of glasses0.20, 0.35, 0.50, 0.65 or 0.80
Thermal transmittance of glasses1.7, 2.7 or 5.8 W/m2·K
Solar absorptance of external walls0.4
Thermal transmittance of external walls2.6 W/m2·K
Thermal capacity of external walls145 kJ/m2·K
Solar absorptance of roof0.5
Thermal transmittance of roof1.93 W/m2·K
Thermal capacity of roof106 kJ/m2·K
Thermal capacity of internal walls145 kJ/m2·K
Air infiltration0, 0.25, 0.50 or 0.75 air change per hour
Lighting power density7.5, 10.0, 12.5 or 15.0 W/m2
Occupancy rate3, 7, 11 or 15 m2/person
Daily working hours of weekdays8, 10, 12, 14 or 16 h
Weather18 weather files (climate zones)
Setpoint20, 22 or 24 °C
Economizer/Heat recoveryDifferential Enthalpy/None, or
None/Enthalpy, or None/None
Night cycleOff
Chilled water temperature resetOff
Ventilation typeConstant Volume or Variable Volume
Supply fan delta pressure150, 250, 350, 450, 550, 650 or 750 Pa
Chilled water pump configurationConstant Primary/Variable Secondary, or
Constant Primary/No Secondary or
Variable Primary/No Secondary
Chilled water pump rated head25, 35, 45, 55, 65, 75 or 85 × 104 Pa
Condenser water pump rated head10, 20, 30, 40, 50 or 60 × 104 Pa
Outdoor air flow rateLevel 1, Level 2 or Level 3
Chiller25 different chillers (Appendix C)
Number of chillers in parallel1, 2, 3 or 4
Table 8. Predictors and response variable.
Table 8. Predictors and response variable.
Predictor 1Ventilation type (0-VAC, 1-VAV),
Predictor 2Supply fan delta pressure (Pa)
Predictor 3Economizer (0-without, 1-with)
Predictor 4Heat recovery (0-without, 1-with)
Predictor 5Outdoor air flow rate (2.5-Level 1, 3.1-Level 2, 3.8-Level 3)
Predictor 6Chilled water pump rated head (Pa)
Predictor 7Condenser water pump rated head (Pa)
Predictor 8Secondary circuit in chilled water (0-without, 1-with)
Predictor 9Variable chilled water flow (0-without, 1-with)
Predictor 10Chiller COP at 100% capacity according AHRI 550/590
Predictor 11Chiller IPLV according AHRI 550/590
Predictor 12Number of chillers in parallel (1,2, 3 or 4)
Predictor 13Annual cooling demand per square meter of floor area (kWh/m2)
Predictor 14CEH climate indicator
Predictor 15Bin 1 of the cooling demand frequency histogram (frequency between 0% and 25%)
Predictor 16Bin 2 of the cooling demand frequency histogram (frequency between 25% and 50%)
Predictor 17Bin 3 of the cooling demand frequency histogram (frequency between 50% and 75%)
Predictor 18Bin 4 of the cooling demand frequency histogram (frequency between 75% and 100%)
Response VariableAnnual HVAC energy consumption per square meter of floor area (kWh/m2)
Table 9. Processing time and performance indicators of artificial neural networks (ANNs) trained with different sample sizes.
Table 9. Processing time and performance indicators of artificial neural networks (ANNs) trained with different sample sizes.
Sample SizeR2RMSENRMSEProcessing Time (s)
5%0.98236.4514130.075971619
10%0.98276.3745400.0750661353
15%0.98326.2773940.0739221785
20%0.98326.2843690.0740042742
25%0.98346.2513660.0736153206
30%0.98376.1963460.0729673647
Table 10. Processing time and performance indicators of ANNs with different hidden layer sizes.
Table 10. Processing time and performance indicators of ANNs with different hidden layer sizes.
Neurons in the Hidden LayerR2RMSENRMSEProcessing Time (s)SI
70.98056.7707850.0797329830.33
100.98206.5094690.07665413310.44
130.98326.2773940.07392217850.53
150.98406.1412240.07231822970.58
180.98466.0190040.07087931620.60
210.98515.9185510.06969642520.61
240.98595.7529180.06774556640.63
270.98695.5588900.06546165380.69
290.98645.6436630.06645977360.61
320.98815.2945930.06234888250.72
350.98695.5508540.06536692400.60
380.98835.2470430.06178810,9890.67
Table 11. Variables and range of values used in the construction of the unseen cases.
Table 11. Variables and range of values used in the construction of the unseen cases.
VariableValues
Width of base of building 20 or 40 m
Ratio between length and width1.75 or 4.75
Number of floors40
Solar orientation of the building22.5 or 112.5°
WWR0.25 or 0.65
Solar factor of glasses0.27 or 0.57
Thermal transmittance of glasses4.3 W/m2·K
Solar absorptance of external walls0.4
Thermal transmittance of external walls2.6 W/m2·K
Thermal capacity of external walls145 kJ/m2·K
Solar absorptance of roof0.5
Thermal transmittance of roof1.93 W/m2·K
Thermal capacity of roof106 kJ/m2·K
Thermal capacity of internal walls145 kJ/m2·K
Air infiltration0.37 air change per hour
Lighting power density8.75 or 13.75 W/m2
Occupancy rate5 or 13 m2/person
Daily working hours of weekdays9 or 13 h
Weather6 different weather files
Setpoint23 °C
Economizer/Heat recoveryDifferential Enthalpy/None, or
None/Enthalpy, or None/None
Night cycleOff
Chilled water temperature resetOff
Ventilation typeConstant Volume or Variable Volume
Supply fan delta pressure200 or 600 Pa
Chilled water pump configurationConstant Primary/Variable Secondary, or
Constant Primary/No Secondary or
Variable Primary/No Secondary
Chilled water pump rated head30 or 60 × 104 Pa
Condenser water pump rated head15 or 45 × 104 Pa
Outdoor air flow rateLevel 2
Chiller7 different chillers (Appendix D)
Number of chillers in parallel1, 2, 3 or 4
Table 12. Performance measures of ANNs to predict the annual HVAC consumption of the unseen cases.
Table 12. Performance measures of ANNs to predict the annual HVAC consumption of the unseen cases.
Neural NetworkR2RMSENRMSE
ANN320.97304.4714390.072966
ANN35_COP0.97764.1087310.067047
ANN29_wDEM0.97893.9089770.063788

Share and Cite

MDPI and ACS Style

Lopes, M.N.; Lamberts, R. Development of a Metamodel to Predict Cooling Energy Consumption of HVAC Systems in Office Buildings in Different Climates. Sustainability 2018, 10, 4718. https://doi.org/10.3390/su10124718

AMA Style

Lopes MN, Lamberts R. Development of a Metamodel to Predict Cooling Energy Consumption of HVAC Systems in Office Buildings in Different Climates. Sustainability. 2018; 10(12):4718. https://doi.org/10.3390/su10124718

Chicago/Turabian Style

Lopes, Mauricio Nath, and Roberto Lamberts. 2018. "Development of a Metamodel to Predict Cooling Energy Consumption of HVAC Systems in Office Buildings in Different Climates" Sustainability 10, no. 12: 4718. https://doi.org/10.3390/su10124718

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop